You are on page 1of 15

Beban Pendinginan

Tica C. Nisa Sustia Agustini Prim Arista M. Nizar Aditya A. Syukron

(2409100037) (2409100047) (2409100059) (2409100061) (2409100063)

METODE CLTD/CLF
Konduksi pada Dinding Luar, Jendela dan Pintu Dr CLTDcorr (CLTD LM ) K (78 Tr) (T0 85) 2

LM K Tr To Dr

: Faktor koreksi lintang dan bulan : Faktor koreksi warna permukaan luar dinding : Suhu ruangan (F) : Suhu rancangan luar (F) : daily rate / suhu rata-rata harian (F)

Beban Akibat Lampu

Q P 3.41 CLF f
Q : laju kalor (Btu/h) P : Daya input (watt) CLF : cooling load factor fs : factor ballast

Konduksi Atap dan Lantai

Q A U T
Q : laju heat loss (Btu/h) U : koefisien transmisi kalor bahan (Btu/ h.F.ft2) A : luas permukaan bahan (ft2) T : Perbedaan suhu dalam dan luar ruangan (F)
Beban akibat Penghuni

Qs N sensHG CLF
Qs : laju kalor (Btu/h) sensHG : laju kalor sensible per orang CLF : Cooling Load Factor

Beban akibat Peralatan

Q A U T
Q : Laju heat loss (Btu/h) U : Koefisien transmisi kalor bahan (Btu/ h.F.ft2) A : Luas permukaan bahan (ft2) T : Perbedaan suhu dalam dan luar ruangan (F)
Radiasi Matahari melalui Jendela

Q A SC SHGF CLF
Q SC SHGF CLF : laju aliran kalor radiasi pada kaca (Btu/h) : Shading Coefficient : Solar Heat Gain Maximum (Btu/h.ft2) : Cooling Load Factor

Denah ruangan
2,1 m
S kasur T B

box

2,7 m

meja rak buku

Koefisien transmisi kalor bahan dan nilai cltd

Data pendukung
To : Tdb = 104 oF, Twb = 95 oF Tr : Tdb = 91.4 oF, Twb = 82.4 oF T = To Tr = 313 306 = 7 K Tkeseharian = 98,6 F Dr = 21,6 oF P = 5 watt Sens HG = 315 Btu Jumlah orang = 3 orang

Perhitungan CLTD
Nilai Cooling Load Temperature Different (CLTD) dari berbagai sisi adalah : Sisi Utara CLTD corrected = [10 + (91.4 82.4) + (104 ((104 82.4)/2) 98,6] = 13,6 oF = 262,7 K Sisi Timur CLTD corrected = [19 + (91.4 82.4) + (104 ((104 82.4)/2) 98,6] = 22,6oF = 267,7 K Sisi Selatan CLTD corrected = [14 + (91.4 82.4) + (104 ((104 82.4)/2) 98,6] = 17,6 oF = 265 K Sisi Barat CLTD corrected = [19 + (91.4 82.4) + (104 ((104 82.4)/2) 98,6] = 22,6 oF = 267,7 K

SISI UTARA

SISI TIMUR

SISI BARAT
Q dinding kosong selatan = Adinding x Udinding x T = (2,7 x 2.75) x 8,35 x 7 = 433,9 Watt

SISI SELATAN
Q dinding kosong selatan = Adinding x Udinding x T = (2,1 x 2,75) x 8,35 x 7 = 337,5 Watt

Konduksi Atap dan Lantai


Qatap = Aatap x Uasbes x CLTDtimur = 5.67 x 27 x 267,7 = 40982,2 Watt Qlantai = Alantai x Ukeramik x T = 5,67 x 113,6 x 7 = 4508,7 Watt Qtotal = Qatap + Qlantai = 45490,984 Watt

Beban Akibat Penghuni


Qs = Jumlah orang x sensHG x CLF = 3 x 315 Btu x 1 = 945 Btu/h

Beban Akibat LAMPU


Q = 1 x P x 3,41 x CLF x fs = 1 x 5 x 3,41 (-1) x 1 = -17,5 Btu/h

Beban TOTAL

KESIMPULAN
Total keseluruhan nilai Q adalah : 305522,684 Watt = 290,24 btu/hr = 0,25 PK Untuk PK di pasaran = 0,03 Dari hasil perhitungan cooling load yang telah dilakukan secara manual dengan metode CLTF/CLF, didapatkan nilai Qtotal sebesar 305522,684 Watt. Dengan Qtotal tersebut, jika dikonversi kedalam bentuk satuan PK maka dihasilkan nilai 0,25 PK. Jadi, untuk kamar kos E29 sebenarnya membutuhkan membutuhkan AC dengan nilai 0,25 PK. Namun jika di pasaran nilai 0,25 PK itu sebenarnya adalah 0,03 PK dan untuk AC nilai tersebut tidak ada. Jadi, kamar E29 tidak begitu membutuhkan AC untuk pendinginan.