Professional Documents
Culture Documents
Standar USA
Jumlah/ Diameter
kawat (mm2)
Arus 80%
rating cable
kabel trefoil di
udara
Tegangan jatuh
kabel trefoil di
udara
mm2
AWG
mm2
Amp
Amp
Volt
KABEL TEMBAGA INTI 3 atau 4 atau 5 utk 3 phase ( contoh NYY 3c35 atau
NYFGBY 4c35 atau NYM 5c4.0 mm2 )
1.5
# 14
1/1.38
18
14
38.9
2.5
# 12
1/1.78
25
20
32.0
# 10
1/2.25
34
27
27.2
#8
1/2.76
44
35
23.9
10
#6
1/3.57
60
48
19.2
16
#4
7/1.70
80
64
16.0
25
#2
7/2.14
105
84
13.4
35
#1
7/2.52
130
104
12.0
2/0
19/1.78
215
172
15.0
70
3/0
19/2.14
270
216
13.2
95
4/0
19/2.52
335
268
12.1
120
250*
37/2.03
390
312
11.5
150
300*
37/2.25
445
356
11.0
185
400*
37/2.50
510
408
10.6
240
500*
61/2.25
606
485
10.7
300
600*
61/2.52
701
561
10.9
400
750*
61/2.85
820
656
11.5
500
1000*
61/3.20
936
749
12.0