You are on page 1of 1

INERTIA BASE LOAD CALCULATION

For primary pumps Operating Weight of the Pump Size of Inertia Base Density of RCC Weight of RCC Weight of inertia base (Approx.) Steel Wight (10% of RCC Weight) Total Weight With Safety Factor ( 25%) Load Acting Points Point Load Spring Selection Load Design Summary 358 1650 * 900* 200 2450 705.6 100 70.56 1234.16 1542.7 4 385.675 390 Kg mm Kg /M3 Kg Kg Kg Kg Kg Nos Kg Kg

1650mm * 900mm* 200mm inertia base with 4 point load each point having 390 kg vibration spring isolators

For Secondary Pumps Operating Weight of the Pump Size of Inertia Base Density of RCC Weight of RCC Weight of inertia base (Approx.) Steel Wight (10% of RCC Weight) Total Weight With Safety Factor ( 25%) Load Acting Points Point Load Spring Selection Load Design Summary 736 2050 * 1100* 250 2450 1360.975 200 136.0975 2433.0725 3041.340625 4 760.3351563 765 Kg mm Kg /M3 Kg Kg Kg Kg Kg Nos Kg Kg

2050mm * 1100mm* 250mm inertia base with 4 point load each point having 765 kg vibration spring isolators

You might also like