Quick Start Micrologix 1200/1500 and Modbus Communications

Quick Start Modbus Channel Configuration for Micrologix 1100/1200/1500


Step 1 : Select channel configuration Step 2 : Select Channel 0 tab Step 3 : Choose Modbus RTU Slave driver and assign driver characteristics.

Step 4 : Enter Modbus data table file number for required Modbus function

Quick Start Micrologix 1200/1500 and Modbus Communications

Step 5 : Enter data table size and type for each required file.

The data table file will be created automatically.

Quick Start Micrologix 1200/1500 and Modbus Communications

Use the Following Table to assign memory mapping. Example: To access word 5 of the holding register (data file N104:5 above) you would read 40006.

Note: Status file information are currently required to be copied to integer or binary files for mapping.