PROJECT: NEW DOHA INTERNATIONAL AIRPORT-CP20 CONSULTANT: BECHTEL CONTRACTOR: HOW UNITED SERVICES W.L.L.

FAULT DIAGNOSTIC IN MDB PANELS. S. No. 1 Recommended corrective Remarks action Phase indication lamps are not glowing. Check the incoming supply side upstream power is available by using voltmeter & voltmeter selector switch. No supply at outgoing Sections. Check the Incoming supply If it is trip, Please sort-out the cause of ACB is OFF/TRIP. the trip & reset the TRIP flag button in ACB and switch ON. Metering circuits & indication lamps are not working Replace with proper rated fuse & Check the control fuses. properly. check. Ammeters are not showing readings. 1. Check CT short links. 2. Check CT termination. Incomer breaker is continuously tripping. Check the connected load and cable condition. Outgoing breaker is not closing/opening. Fault

3 4 5 6

1. Check the control fuse of the particular breaker. 2. Check the command signal from BMS points.

Page1of2

7 ATS operation is not performing in manual/Auto modes.

1. Check the control fuse of the ATS circuits. 2. Check the time settings on the timers. 3. Check the selector switch position. 4. Check the Phase failure relay control fuses. 5. Check the ON/OFF push buttons conditions. 6. Check the breaker accessories like motor operator, closing coil & opening coils conditions. 7. Check the electrical inter lock circuits related to this MDB panel.

Still problem exist, contact authorized service provider.