E1 B all all 42 42 42 50 N all all B all all S all all N all all V all all S all all V all all E2 N all all SUPPLY SIDE EMAX E3 S H all all all all E4 H all all E6 H all all V all all 42 42 42 42 42 55 42 50 42 65 42 50
Breaker
X1
E1
E2
42 65 42 50 42 65 65
42 65 42 50 42 65 75
42 65 42 50 42 65 75
42 65 42 50 42 65 85
E3
42 65 42 50 42 65 75 65 75 75 75
42 65 42 50 42 65 85 65 75 100 100
42 65 42 50 42 65 85 65 75 100 100
E4
E6
Version B N B N B N S N S H V S H V H V
Iu all all all all all all all all all all all all all all all all
415Vac Breaker version Iu In In all all all all all all all all all all all all all all all all
Notes: Iu and In of Emax of supply side must be higher than Iu and In of load side Emax to obtain selectivity, protection thresholds must be set as follows:Emax on supply side- S =ON, t2 =max, I=OFF - Emax on load side - S=OFF, I=ON