SECTION-3 DISCRIMINATION TABLE


E1 B all all 42 42 42 50 N all all B all all S all all N all all V all all S all all V all all E2 N all all SUPPLY SIDE EMAX E3 S H all all all all E4 H all all E6 H all all V all all 42 42 42 42 42 55 42 50 42 65 42 50

COORDINATION TABLE FOR EMAX CIRCUIT BREAKERS

Breaker

X1

E1

E2

LOAD SIDE EMAX

42 65 42 50 42 65 65

42 65 42 50 42 65 75

42 65 42 50 42 65 75

42 65 42 50 42 65 85

E3

42 65 42 50 42 65 75 65 75 75 75

42 65 42 50 42 65 85 65 75 100 100

42 65 42 50 42 65 85 65 75 100 100

E4

42 65 42 50 42 65 85 65 75 100 100 75 100 100

42 65 42 50 42 65 85 65 75 100 100 75 100 100

E6

Version B N B N B N S N S H V S H V H V

Iu all all all all all all all all all all all all all all all all

415Vac Breaker version Iu In In all all all all all all all all all all all all all all all all

Notes: Iu and In of Emax of supply side must be higher than Iu and In of load side Emax to obtain selectivity, protection thresholds must be set as follows:Emax on supply side- S =ON, t2 =max, I=OFF - Emax on load side - S=OFF, I=ON