You are on page 1of 2

UL 12-12

12V 12AH
General

UL12 -12

Physical Specification
Part Number:

UL12-12

Length:

151 2 mm ( 5.95 inches )

Width:

98

2 mm ( 3.85 inches )

Container Height:

95

2 mm ( 3.74 inches )

Total Height (with terminal): 101 2 mm ( 3.98 inches )


Approx 3.60 kg (7.94lbs)

Approx Weight:

Specifications

Terminal Type
Container Material
Rated Capacity

Nominal Voltage

12V

Nominal Capacity (20HR)

12AH

Standard Terminal

F1

Optional Terminal

F2

Standard Option

ABS

Flame Retardant Option (FR)

ABS (UL94:VO)

12.0 AH/0.60A

(20hr,1.80V/cell, 25C / 77F)

11.2 AH/1.12A

(10hr,1.80V/cell, 25C / 77F)

10.2 AH/2.04A

(5hr,1.75V/cell, 25C / 77F)

9.2 AH/3.06A

(3hr,1.75V/cell, 25C / 77F)

7.54AH/7.54A

(1hr,1.60V/cell, 25C / 77F)

Max Discharge Current

180A (5s)

Internal Resistance

Approx 14m

Discharge Characteristics

Operating Temp. Range

Discharge: -15 ~ 50C (5 ~ 122F)


Charge:

0 ~ 40C (5 ~ 104F)

Storage: -15 ~ 40C (5 ~ 104F)


Nominal Operating Temp. Range

25 3C (77 5F)

Cycle Use

Inital Charging Current less than 3.6A.Voltage


14.4V ~ 15.0V at 25C (77F) Temp. Coefficient -30mV/C
No limit on Initial Charging Current Voltage

Standby Use

13.5V ~ 13.8V at 25C (77F) Temp. Coefficient -20mV/C


Capacity affected by Temperature

40C (104F)

103%

25C (77F)

100%

0C (32F)

86%

Design Floating Life at 20C

5 Years

Self Discharge

Ultracell batteries may be stored for up to 6 months at 25C(77F) and then a refresh charge is
required. For higher temperatures the time interval will be shorter.

Dimensions
F1 Terminal
95 1
101 1

78 1
98 1

4. 75( 0. 187)
3. 2( 0. 126)
6. 35( 0. 25)
0. 8( 0. 031)

151 1

Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk

www.ultracell.co.uk

ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE

ISO9001

Constant Current Discharge (Amperes) at 25 C (77 F )


0

F.V/Time

5min

10min

15min

20min

30min

45min

1h

2h

3h

4h

5h

6h

8h

10h

20h

1.85V/cell

22.9

17.5

14.5

12.6

9.72

7.16

6.03

3.57

2.79

2.27

1.85

1.61

1.30

1.08

0.594

1.80V/cell

30.7

22.4

17.6

14.9

11.5

8.33

6.76

3.90

3.00

2.42

1.99

1.72

1.37

1.12

0.600

1.75V/cell

34.6

24.6

19.2

16.0

11.9

8.64

7.07

4.04

3.06

2.48

2.04

1.77

1.40

1.15

0.606

1.70V/cell

38.1

26.9

20.5

16.8

12.4

8.99

7.29

4.14

3.15

2.54

2.09

1.81

1.42

1.17

0.617

1.65V/cell

42.0

29.0

21.8

17.8

13.1

9.21

7.46

4.20

3.28

2.63

2.15

1.85

1.44

1.19

0.625

1.60V/cell

46.3

31.5

23.3

19.0

13.8

9.60

7.54

4.38

3.38

2.71

2.22

1.89

1.45

1.21

0.629

Constant Power Discharge (Watts) at 25 0C (77 0F )


F.V/Time

5min

10min

15min

20min

30min

45min

1h

2h

3h

4h

5h

6h

8h

10h

20h

1.85V/cell

41.8

32.4

27.1

23.7

18.5

13.8

11.6

6.93

5.44

4.44

3.63

3.16

2.56

2.14

1.18

1.80V/cell

55.5

40.9

32.3

27.6

21.5

15.9

13.0

7.51

5.82

4.71

3.88

3.37

2.71

2.21

1.19

1.75V/cell

61.2

44.3

34.9

29.4

22.2

16.3

13.5

7.76

5.91

4.80

3.97

3.46

2.75

2.26

1.20

1.70V/cell

65.6

47.1

36.7

30.7

22.9

16.9

13.9

7.94

6.06

4.92

4.06

3.52

2.78

2.31

1.22

1.65V/cell

71.3

50.4

38.7

32.3

24.0

17.2

14.1

8.01

6.29

5.07

4.16

3.59

2.82

2.35

1.23

1.60V/cell

76.8

53.5

40.8

34.1

25.2

17.8

14.2

8.31

6.45

5.21

4.28

3.65

2.84

2.37

1.24

Float Charging Characteristics

Discharge Characteristics

Terminal Voltage(V)

12V
6V
4V
2V
Battery Battery Battery Battery
V
V
V
V

13.0

6.5

4.33

2.16

12.0

6.0

4.00

2.00

11.0

5.5

3.66

1.84

10.0

5.0

3.33

1.68

9.0

4.5

3.00

1.52

8.0

4.0

2.67

1.36

Charge Charging Charging


Volume Current Voltage

Temperature:25 0 C(77 0 F)

%
120
110

0.4C

0.207C

100

0.093C 0.05C

90
80

50

0.20
0.15

0.10

40
30

3C
2

6 8 10

20
10
0

2C
60

40

20

6 8 10

20

15.0

7.5

14.0

7.0

13.0

6.5

12.0

6.0

11.0

5.5

1.83

Charging Current
0

Life expectancy(year)

Capacity %

0
-20

-10

.0 C A

10

3. 0C A

20

30

40

2
1
0.5

50

20
68

Capcity(%)

Remaining Capacity (%)

80
50%
DOD

30%
DOD
Ambient Termperature:
25oC (77oF)

400

600

800

1000

1200

Number of Cycles

Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk

www.ultracell.co.uk

50
122

100C

80

250C

60

C
F

A
B

300C

400C

40

20
0

200

40
104

100

100

0
0

30
86

Self Discharge Characteristics

120

20

40

Charging voltage :
2.25V/cell

Testing condition
Discharging:current 0.17C (FV 1.7V/cell);
Charging:current 0.25C max, voltage 2.45V/cell;
Charging volume:125% of discharged capacity.

40

36

Battery temperature

Cycle Life in Relation to Depth of Discharge

100%
DOD

32

28

24

Temperature(0C)

60

20

16

1 .0 C A

12

6
5
4

0 .2 C A

20

2.00

10

A
0 .0 5 C
A
0 .1 C

40

2.17

After 50% Discharge

Effect of Temperature on Long Term Float Life

120

60

2.33

Charge Voltage
(Constant 2.25v/cell)

Charging Time (Hours)

Temperature Effects in Relation to Battery Capacity

80

2.50

Charged Volume

Discharge Time

100

(V)

After 100% Discharge


0.05

Min

Charging
Voltage

temperature250C

0.25

70
60

0.628C

1C

0.10CA-2.25V/cell

(V)

(V)

(XCA)

10

Storage Time (Months)

12

No supplementary required
(Carryout supplementary charge before use if 100% capacity is required.)

Supplementary charge required before use. Optional charging way as below:


1. Charged for above 3 days at limited current 0.25CA and constant voltage 2.25V/cell.
2. Charged for above 20 hours at limited current 0.25CA and constant voltage 2.25Vcell.
3. Charged for 8 ~ 10 hours at limited current 0.05 CA.

Supplementary charge may often fail to recover the capacity.


The battery should never be left standing till this is reached.

ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE