SINGLE LINE DIAGRAM FOR GENERATOR AND GEN. PROTECTION & METERING
TIRORA COAL FIRED POWER PLANT PROJECT (5 X 660 MW)

BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:TO GT & UT
22 KV
IPBD
TA9:400 / 5A 5P20 60VA TA10:400 / 5A 5P20 60VA TA11:400 / 5A 0.5 30VA

IPBD GPP - A GPP - B

TA8:25000 / 5A 5P40 60VA TA7:25000 / 5A 5P40 60VA TA6:25000 / 5A 0.2 100VA TA5:25000 / 5A 0.2 100VA

GPP - A GPP - B GTP & AVR AVR

GTP
DC ENB

PT / LA CABINET

+
ET

AVR

GEN
TA4:25000 / 5A 0.2S 100VA TA3:25000 / 5A 5P40 60VA TA2:25000 / 5A 5P40 60VA TA1:25000 / 5A 5P40 60VA

GPP A, GEMP GPP B - GFR

TA12:7500 / 5A 5P20 60VA TA13:7500 / 5A 5P20 60VA TA14:7500 / 5A 0.5 30VA

GPP - B GPP - A SPARE

GEMP GPP - B GPP - A TO GEN. & UT PROT. PANEL USING FOR OVERALL DIFFERENTIAL PROTECTION GPP A, GPP B - GFR GFR

GPP - A

GPP B, GTP & AVR

CABLE

AC ENB

GTP TO GEN. SHAFT 415 V MCC


TA0: 5 / 5A 0.5 30VA

GPP A GPP B

N.G.T.
EARTHING

BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:-

CT DETAILS FOR GENERATOR PROTECTION & METERING


SR.NO. 1 2 CT CODE TA0 TA1 CT DESCRIPTION 5 / 5A, 0.5, 30VA 25000 / 5A, 5P40, 60VA PANEL GENERATOR FAULT RECORDER TO GEN. & UT PROT. PANEL USING FOR RECORD USING FOR OVERALL DIFFERENTIAL PROTECTION GEN. DIFFERENTIAL (87G1 ) Id / I THERMAL OVERLOAD (49G1) I> m=3 USES QTY 1 3

STARTUP / SHUTDOWN (59G1) I>


3 TA2 25000 / 5A, 5P40, 60VA GENERATOR PROTECTION PANEL- A NEGATIVE PHASE SEQUENCE OVERCURRENT (46G1) I> m 3 VOLTAGE RESTRAINED OVERCURRENT (51VG1) U<, I> BACK-UP IMPEDANCE (21G1) Z< GEN. DIFFERENTIAL (87G2 ) Id / I THERMAL OVERLOAD (49G2) I> m=3 STARTUP / SHUTDOWN (59G2) I> 4 TA3 25000 / 5A, 5P40, 60VA GENERATOR PROTECTION PANEL- B NEGATIVE PHASE SEQUENCE OVERCURRENT (46G2) I> m 3 VOLTAGE RESTRAINED OVERCURRENT (51VG2) U<, I> BACK-UP IMPEDANCE (21G2) Z< 3 3

BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:-

CT DETAILS FOR GENERATOR PROTECTION & METERING


SR.NO. 5 6 CT CODE TA4 TA5 CT DESCRIPTION 25000 / 5A, 0.2S, 100VA 25000 / 5A, 0.2 100VA PANEL ENERGY METER PANEL EXCITATION CONTROL PANEL (AVR) GENERATOR TRANSDUCER PANEL & AVR USES USING FOR METERING (MAIN METER & BACKUP METER) USING FOR EXCITATION SYSTEM USING FOR CONVERT 4 - 20mA FOR DCS & EXCITATION SYSTEM GEN. DIFFERENTIAL (87G2 ) Id / I LOSS OF EXCITATION (40G2) < LOSS OF STEP (68/78 G2) dz/dt> 8 TA7 25000 / 5A, 5P40, 60VA GENERATOR PROTECTION PANEL- B QTY 3 3

TA6

25000 / 5A, 0.2 100VA

REVERSE POWER (32G2) _P


GENERATOR BACK - ENERGIZATION (50 / 27 G2) I> U> LOW FORWARD POWER (37 G2) P< GEN. DIFFERENTIAL (87G1 ) Id / I LOSS OF EXCITATION (40G1) < LOSS OF STEP (68/78 G1) dz/dt>

TA8

25000 / 5A, 5P40, 60VA

GENERATOR PROTECTION PANEL- A

REVERSE POWER (32G1) _P GENERATOR BACK - ENERGIZATION (50 / 27 G1) I> U> LOW FORWARD POWER (37 G1) P<

BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:-

CT DETAILS FOR GENERATOR PROTECTION & METERING


SR.NO. CT CODE CT DESCRIPTION PANEL USES EXCITATION TRANSFORMER INSTANTANEOUS OVERCURRENT (50SET1) Is> EXCITATION TRANSFORMER OVERCURRENT (51ET1) I> EXCITATION TRANSFORMER INSTANTANEOUS OVERCURRENT (50SET2) Is> EXCITATION TRANSFORMER OVERCURRENT (51ET2) I> GENERATOR FAULT RECORDER USING FOR RECORD 3 QTY

10

TA9

400 / 5A, 5P20, 60 VA

GENERATOR PROTECTION PANEL- A

GENERATOR PROTECTION PANEL- B 11 TA10 400 / 5A, 5P20, 60 VA

12

TA11

400 / 5A, 0.2, 30 VA

GENERATOR TRANSDUCER PANEL & AVR


GENERATOR PROTECTION PANEL- B GENERATOR PROTECTION PANEL- A

USING FOR CONVERT 4 - 20mA FOR DCS & EXCITATION SYSTEM EXCITATION TRANSFORMER THERMAL OVERLOAD (49ET2) 3I> EXCITATION TRANSFORMER THERMAL OVERLOAD (49ET1) 3I> SPARE

13

TA12

7500 / 5A, 5P20, 60 VA 7500 / 5A, 5P20, 60 VA 7500 / 5A, 0.5, 30 VA

14 15

TA13 TA14

3 3

BTG - ELECTRICAL
DETAILS OF GENERATOR :-

PURCHASER

SICHUAN MECHANICAL EQUIPMENT IMPORT EXPORT CO. LTD. (SCMEC) SHANGHAI ELECTRIC POWER GENERATION CO. LTD. GENERATOR PLANT SOUTHWEST ELECTRIC POWER DESIGN INSTITUTE (SWEPDI)

BARGAINOR
DESIGN UNIT

BTG - ELECTRICAL
DETAILS OF GENERATOR :DESCRIPTION SPECS AND MODE GENERATOR MODEL RATED CAPACITY SN MVA QFSN-660-2 776 UNIT DESIGN VALUE

RATED POWER PN
RATED POWER FACTOR COSN RATED VOLTAGE UN RATED CURRENT IN RATED FREQUENCY FN RATED ROTATION SPEED NN RATED EXCITATION VOLTAGE UFN RATED EXCITATION CURRENT IFN/ NOLOAD EXCITATION CURRENT IFOZ STATOR WINDING CONNECTION MODE COOLING MODE VENTILATION MODE EXCITATION MODE

MW

660
0.85 (LAG)

KV A HZ RPM V A

22 20377 50 3000 494 4690/1497 YY WATER, H2, H2 TAKE GAS FROM THE AIR GAP STATIC EXCITATION 7

BTG - ELECTRICAL
DETAILS OF GENERATOR :DESCRIPTION PARAMETER PROPERTY DC RESISTANCE FOR EACH PHASE OF THE STATOR 75 DC RESISTANCE FOR WINDING OF THE ROTOR 75 GROUND CAPACITANCE FOR EACH PHASE OF THE STATOR A B C SELF INDUCTANCE OF THE ROTOR WINDING DIRECT AXIS SYNCHRO REACTANCE XD HORIZONTAL AXIS SYNCHRO REACTANCE XQ DIRECT AXIS TRANSIENT VALUE) X'DU REACTANCE (NON-SATURATED F F F H % % % % 0.229 0.229 0.229 0.762 226 220 31.3 27.5 W W 1.44710 0.1004
-3

UNIT

DESIGN VALUE

DIRECT AXIS TRANSIENT REACTANCE (SATURATED VALUE)X'D

HORIZONTAL AXIS TRANSIENT REACTANCE (NON-SATURATED VALUE) X'QU


HORIZONTAL AXIS TRANSIENT REACTANCE (SATURATED VALUE)X'Q

%
%

46
40.5 8

BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION PARAMETER PROPERTY DIRECT AXIS SUPER-TRANSIENT REACTANCE (NON-SATURATED VALUE) X"DU DIRECT AXIS VALUE)X"D SUPER-TRANSIENT REACTANCE (SATURATED (NON-

UNIT

DESIGN VALUE

% % %

23.2 21.4 22.8

HORIZONTAL AXIS SUPER-TRANSIENT SATURATED VALUE) X"QU

REACTANCE

HORIZONTAL AXIS SUPER-TRANSIENT REACTANCE (SATURATED VALUE) X"Q


NEGATIVE SEQUENCE REACTANCE (NON-SATURATED VALUE) X2U NEGATIVE SEQUENCE REACTANCE (SATURATED VALUE) X2 ZERO SEQUENCE REACTANCE (NON-SATURATED VALUE) XOU ZERO SEQUENCE REACTANCE (SATURATED VALUE)X0 DIRECT AXIS OPEN CIRCUIT TRANSIENT TIME CONSTANT T'DO HORIZONTAL AXIS OPEN CIRCUIT TRANSIENT TIME CONSTANT T'QO DIRECT AXIS SHORT CIRCUIT TRANSIENT TIME CONSTANT T'D

%
% % % % S S S

20.9
23 21.2 10.7 10.2 8.73 0.97 1.065

BTG - ELECTRICAL
DETAILS OF GENERATOR :DESCRIPTION PARAMETER PROPERTY HORIZONTAL AXIS SHORT CIRCUIT TRANSIENT TIME CONSTANT T'Q DIRECT AXIS OPEN CONSTANT T"DO CIRCUIT TRANSIENT TIME S S S S S S T-M2 0.179 0.045 0.068 0.035 0.035 3 41 0.518 % S 8 8 UNIT DESIGN VALUE

HORIZONTAL AXIS OPEN CIRCUIT TRANSIENT TIME CONSTANT T"QO DIRECT AXIS SHORT CIRCUIT SUPER TRANSIENT TIME CONSTANT T"D HORIZONTAL AXIS SHORT CIRCUIT TRANSIENT TIME CONSTANT T"Q DE-EXCITATION TIME CONSTANT TDM FLYWHEEL MOMENT GD2 SHORT CIRCUIT RATIO SCR STEADY STATUS NEGATIVE SEQUENCE CURRENT I2 TRANSIENT STATUS CURRENTI22T NEGATIVE SEQUENCE SUPER

10

BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION

UNIT

DESIGN VALUE

PARAMETER PROPERTY
ALLOWABLE FREQUENCY DEVIATION % ALLOWABLE STATOR VOLTAGE DEVIATION DE-EXCITATION ASYNCHRONOUS RUN CAPABILITY DE-EXCITATION ASYNCHRONOUS RUNTIME LEADING PHASE RUN CAPABILITY LEADING PHASE RUNTIME (H FOR RUN HOUR) THF TELEPHONE HARMONIC FACTOR KU VOLTAGE WAVEFORM SINUS DISTORTION RATE KU THREE PHASE SHORT CIRCUIT STEADY STATUS CURRENT TRANSIENT STATUS SHORT CIRCUIT CURRENT EFFECTIVE (AC COMPONENT) PHASE-NEUTRAL POINT PHASE-PHASE THREE PHASE % % % 584 407 416 % MW MIN MW H % % % 162 SEE 4.2.13.4 660 0.95PF (ADVANCE) LONG TERM CONTINUOUS RUN +3 -5 5

11

BTG - ELECTRICAL
DETAILS OF GENERATOR :DESCRIPTION UNIT DESIGN VALUE

PARAMETER PROPERTY
SUB-TRANSIENT STATUS SHORT CIRCUIT EFFECTIVE VALUE (AC COMPONENT) PHASE-NEUTRAL POINT PHASE-PHASE THREE PHASE THREE PHASE SHORT CIRCUIT MAXIMUM CURRENT VALUE (INCLUDING DC COMPONENT PEAK VALUE) PHASE-PHASE SHORT CIRCUIT MAXIMUM ELECTROMAGNETIC TORSION ROTOR AXIAL VOLTAGE BEARING INSULATION RESISTANCE NORMAL/MINIMUM VALUE MAXIMUM ALLOWABLE OVER-SPEED OUT OF STEP POWER GENERATOR STATUS RUN CAPABILITY PEAK ADJUSTMENT CAPABILITY GENERATOR SERVICE LIFE NOISE YEAR DB CURRENT % % % % T.M V MW % MW S ALLOWING 10000TIMES MACHINE START/STOP. 30 90 120 1260 633 453 520 1200 2130

12

BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION VIBRATION VALUE CRITICAL SPEED (FIRST ORDER) CRITICAL SPEED (SECOND ORDER) CRITICAL SPEED BEARING VIBRATION VALUE VERTICAL HORIZONTAL BEARING VIBRATION VALUE IN CASE OF OVER-SPEED VERTICAL HORIZONTAL BEARING VIBRATION VALUE IN CASE OF RATED ROTATION SPEED VERTICAL HORIZONTAL CRITICAL SPEED AXIS VIBRATION VALUE VERTICAL

UNIT

DESIGN VALUE

R/MIN R/MIN

690 1935

MM MM

MM MM

MM MM

MM 13

BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION VIBRATION VALUE HORIZONTAL

UNIT

DESIGN VALUE

MM

AXIS VIBRATION VALUE IN CASE OF OVER-SPEED


VERTICAL HORIZONTAL AXIS VIBRATION VALUE IN CASE OF RATED ROTATION SPEED VERTICAL HORIZONTAL FV STATOR WINDING TERMINAL VIBRATION FREQUENCY MM MM HZ 0.11.0 UN NO-LOAD OR 1.0 I N SHORT CIRCUIT. MM MM

STATOR WINDING TERMINAL VIBRATION AMPLITUDE VALUE MM AXIAL TORSIONAL FREQUENCY HZ

14

BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION

UNIT

DESIGN VALUE

LOSS AND EFFICIENCY ( UNDER RATED CONDITIONS) STATOR WINDING COPPER LOSS QCU1 STATOR IRON LOSS QFE EXCITATION LOSS QCU2 SHORT CIRCUIT QKD ADDITIONAL LOSS KW KW AND 1055 1607 KW KW KW 1803 637 2208

MECHANICAL LOSS QM EXCITATION MACHINE EQUIPMENT LOSS TOTAL LOSS Q FULL LOAD EFFICIENCY

KW
KW % 7310 98.9

15

BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION INSULATION GRADE AND TEMPERATURE STATOR WINDING INSULATION GRADE WINDING OUTLET WATER TEMPERATURE STATOR WINDING THA WORK CONDITIONS UNDER

UNIT

DESIGN VALUE

F 74

WINDING OUTLET WATER TEMPERATURE UNDER STATOR WINDING T-MCR WORK CONDITIONS WINDING OUTLET WATER TEMPERATURE UNDER STATOR WINDING VWO WORK CONDITIONS INTERLAYER TEMPERATURE UNDER STATOR WINDING THA WORK CONDITIONS INTERLAYER TEMPERATURE UNDER STATOR WINDING T-MCR WORK CONDITIONS INTERLAYER TEMPERATURE UNDER STATOR WINDING VWO WORK CONDITIONS STATOR IRON CORE INSULATION GRADE

79

F 16

BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION INSULATION GRADE AND TEMPERATURE

UNIT

DESIGN VALUE

HOTTEST POINT TEMPERATURE UNDER STATOR IRON CORE THA WORK CONDITIONS
HOTTEST POINT TEMPERATURE UNDER STATOR IRON CORE T-MCR WORK CONDITIONS TEMPERATURE UNDER STATOR TERMINAL STRUCTURE PART THA WORK CONDITIONS TEMPERATURE UNDER STATOR TERMINAL STRUCTURE PART T-MCR WORK CONDITIONS TEMPERATURE UNDER STATOR TERMINAL STRUCTURE PART VWO WORK CONDITIONS ROTOR WINDING INSULATION GRADE TEMPERATURE UNDER ROTOR WINDING THA WORK CONDITIONS (RESISTANCE METHOD) TEMPERATURE UNDER ROTOR WINDING T-MCR WORK CONDITIONS (RESISTANCE METHOD)

88

F 17 92

BTG - ELECTRICAL
DETAILS OF EXCITATION TRANSFORMER :-

DESCRIPTION EXCITAION TRANSFORMER TYPE MODEL CAPACITY MANUFACTURER RATED VOLTAGE RATED VOLTAGE PRIMARY PRIMARY

UNIT

DESIGN VALUE

SINGLE PHASE DRY TYPE 32950 JINPAN/SHUNTE

KVA

KV V

22

1060 FREQUENCY PHASE NO. CONNECTION GROUP CATEGORY TERMINAL LEAD-OUT AND GROUNDING MODE INSULATION GRADE F 18 HZ 50 3 /-11

BTG - ELECTRICAL
DETAILS OF EXCITATION TRANSFORMER :-

DESCRIPTION EXCITAION TRANSFORMER INSULATION WITHSTAND VOLTAGE IMPACT VOLTAGE HIGH SIDE LOW SIDE HIGH SIDE LOW SIDE PROTECTION GRADE COOLING MODE LOSS

UNIT

DESIGN VALUE

KV KV 125

KV 50 IP23 AN/AF

COPPER LOSS
IRON LOSS LOSS ADDITIONAL LOSS LOSS TOTAL LOSS EFFICIENCY

KW
KW KW KW

26
14 9 49 99.8 19

BTG - ELECTRICAL
DETAILS OF EXCITATION TRANSFORMER :-

DESCRIPTION EXCITAION TRANSFORMER VOLTAGE REGULATION IMPEDANCE VOLTAGE POSITIVE SEQUENCE IMPEDANCE ZERO SEQUENCE IMPEDANCE HIGH VOLTAGE WINDING RESISTANCE EXCITATION CURRENT NOISE LEVEL OVERLOAD CAPACITY OVERLOAD CAPACITY TRANSFORMER TEMPERATURE SIGNAL

UNIT A DBA KVA 5 8 8 7.2 30.1138 0.9 70

DESIGN VALUE

1.1 LONG TERM I SECTION OVER TEMPERATURE ALARM II SECTION OVER TEMPERATURE TRIPPING

TRANSFORMER MAXIMUM ALLOWABLE TEMPERATURE RISE EXTERNAL SIZE (LWH) MM

100K 340015202950

TRANSPORT SIZE (LWH)


WEIGHT

MM
T

410026002950
19.6 20

BTG - ELECTRICAL
DETAILS OF EXCITATION POWER CABINET :-

DESCRIPTION EXCITATION POWER CABINET TYPE THYRISTOR POWER ELEMENT RATED VOLTAGE RATED CURRENT REVERSE PEAK VOLTAGE RATED CURRENT COOLING MODE ELEMENT NO. SERIES CONNECTIONS FOR EACH CABINET AND EACH BRIDGE ARM PARALLEL CONNECTION BRANCH NO. FOR EACH CABINET AND EACH BRIDGE ARM RECTIFICATION CABINET NOISE BLOWER FAN AVERAGE NO-FAULT TIME POWER CABINET NO. CURRENT SHARING FACTOR Voltage sharing factor

UNIT

DESIGN VALUE

V A V A 2075 4200 1700 FORCE WIND COOLING PCS PCS DB H 1 6 65DB 45000 5 0.95 21

BTG - ELECTRICAL
DETAILS OF EXCITATION POWER CABINET :-

DESCRIPTION MAGNETIC FIELD BREAKER RATED VOLTAGE RATED CURRENT RATED CURRENT BREAKING CURRENT CONTROL VOLTAGE (DC) MAX. ARC VOLTAGEABOVE 2000V MANUFACTURER MODEL

UNIT

DESIGN VALUE

V A A VD.C V

2000 6000 75000 220 2800 ABB HPB60M-82S

22

BTG - ELECTRICAL
DETAILS OF EXCITATION POWER CABINET :-

DESCRIPTION AVR PROPRTY VOLTAGE REGULATION MANUAL REGULATION SCOPE STATIC DIFFERENCE RATE TRANSITION STATUS RESOLUTION SINGLE TIME RECORD LENGTH TOTAL RECORD LENGTH RISE TIME CONTROL PERIOD SAMPLING MODE PHASE FREQUENCY MARGIN AMPLITUDE FREQUENCY MARGIN CONTROL RULE MANUFACTURER

UNIT MS S S S MS AC DB 40 6DB PID 1000 0.04

DESIGN VALUE 30%110% UG0 10%IF0110% IFN 1

23

BTG - ELECTRICAL
DETAILS OF EXCITATION POWER CABINET :-

DESCRIPTION EXCITATION INITIATING CIRCUIT PARAMETER EXCITATION INITIATING VOLTAGE EXCITATION INITIATING CURRENT EXCITATION INITIATING POWER WASTE ROTOR OVER VOLTAGE PROTECTION OVER VOLTAGE NON LINEAR RESISTANCE CAPACITY OVER VOLTAGE PROTECTION ACTION VOLTAGE VALUE

UNIT

DESIGN VALUE

V/AC A KVA

415 150 65

MJ

5 4UFN~6 UFN

24

BTG - ELECTRICAL

DETAILS OF NGT CABINET :-

QUANTITY TYPE & SPECIFICATION UNIT UNIT # 1 UNIT # 2 UNIT # 3 TOTAL

SINGLE PHASE ISOLATOR: 22KV / 400A NGT: 22/0.22KV, 50KVA

RESISTANCE: 0.4, 50KW CT OF NGT SECONDARY WIRING: 500/5A, 5P20

SET

CT OF NGT PRIMARY WIRING: 5/5A, 0.5 25

BTG - ELECTRICAL

DETAILS OF PT / LA CABINET :-

QUANTITY TYPE & SPECIFICATION UNIT UNIT # 1 UNIT # 2 UNIT # 3 TOTAL

RN4 - 22, 0.5A Y5W1 - 24 / 61.6

SET

22/3, 0.11/3, 0.11/3, 0.11/3 KV 0.2/3P/3P, 60VA SEMI-INSULATING

22/3, 0.11/3, 0.11/3, 0.11/3 KV 0.2/3P/3P, 60VA SEMI-INSULATING

22/3, 0.11/3, 0.11/3, 0.11/3 KV 0.2/3P/3P, 60VA FULL-INSULATING

26

BTG - ELECTRICAL
DETAILS OF GENERATOR PROTECTION:SR.NO.
1 2 3 4 A) B) 5 6 7 8

GENERATOR PROTECTION
GENERATOR DIFFERENTIAL PROTECTION VOLTAGE RESTRAINED OVER CURRENT PROTECTION GENERATOR BACK-UP IMPEDANCE STATOR EARTH FAULT 95% & 100% PROTECTION GENERATOR STATOR 95% EARTHING PROTECTION GENERATOR STATOR 100 EARTHING PROTECTION STATOR INTER-TURN FAULT PROTECTION ASYMMETRIC NEGATIVE PHASE SEQUENCE OVER CURRENT PROTECTION SYMMETRICAL THERMAL OVERLOAD PROTECTION OVER/UNDER VOLTAGE PROTECTION

PROTECTION CODE
87G 51VG 21G 64G1, 64G2 64G1 (ZERO SEQUENCE VOLTAGE THEORY) 64G2 (THIRD-HARMONIC THEORY) 95G 46G 49G 59/27G

9
10

OVER/UNDER FREQUENCY PROTECTION


LOSS OF EXCITATION PROTECTION

81G
40G

27

BTG - ELECTRICAL
DETAILS OF GENERATOR PROTECTION:-

SR.NO 11 12 13 14 15 16 17 18 19 20

GENERATOR PROTECTION REVERSE POWER PROTECTION LOW FORWARD POWER PROTECTION GENERATOR OUT OF STEP PROTECTION OVER EXCITATION PROTECTION GENERATOR BACK-ENERGIZATION PROTECTION GENERATOR ROTOR EARTH FAULT PROTECTION STARTUP/SHUTDOWN PROTECTION GENERATOR COOLING WATER-LOSS PROTECTION HEAT ENGINEERING PROTECTION ET INSTANTANEOUS OVERCURRENT PROTECTION

PROTECTION CODE 32G 37G 78G 61G 51BEG 64F164F2 59G 30G 30T 50SET 28

BTG - ELECTRICAL
DETAILS OF GENERATOR PROTECTION:-

SR.NO

GENERATOR PROTECTION

PROTECTION CODE

21

ET OVERCURRENT PROTECTION

51ET

22

ET EXCITATION WINDING THERMAL OVERLOAD PROTECTION

49ET

23 24 25 26 27

ET WINDING TEMPERATURE PROTECTION CT, VT SUPERVISION PROTECTION UNIT EMERGENCE TRIPPING INTERFACE EXCITATION SYSTEM FAULT TRIPPING INTERFACE 400KV BREAKER OUR OF ORDER TRIPPING INTERFACE

ET26W 9760

29

BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:TO GT & UT
22 KV
IPBD
TA9:400 / 5A 5P20 60VA TA10:400 / 5A 5P20 60VA TA11:400 / 5A 0.5 30VA

IPBD GPP - A GPP - B

TA8:25000 / 5A 5P40 60VA TA7:25000 / 5A 5P40 60VA TA6:25000 / 5A 0.2 100VA TA5:25000 / 5A 0.2 100VA

GPP - A GPP - B GTP & AVR AVR

GTP
DC ENB

PT / LA CABINET

+
ET
1060V

AVR

GEN
TA4:25000 / 5A 0.2S 100VA TA3:25000 / 5A 5P40 60VA TA2:25000 / 5A 5P40 60VA TA1:25000 / 5A 5P40 60VA

GPP A, GEMP GPP B - GFR

TA12:7500 / 5A 5P20 60VA TA13:7500 / 5A 5P20 60VA TA14:7500 / 5A 0.5 30VA

GPP - B GPP - A SPARE

GEMP GPP - B GPP - A TO GEN. & UT PROT. PANEL USING FOR OVERALL DIFFERENTIAL PROTECTION GPP A, GPP B - GFR GFR

GPP - A

GPP B, GTP & AVR

CABLE

AC ENB

GTP TO GEN. SHAFT 415 V MCC


TA0: 5 / 5A 0.5 30VA

GPP A GPP B

N.G.T.
EARTHING

30

BTG - ELECTRICAL

31

VOTE OF THANKS

32