VIGAS CONTINUAS DE CIMENTACION EJE FD-FA

1. Colocar dimensiones de la viga continua


30.0 cm
3 3/4 '' As Positivo 5.04 cm
80.0 cm
2 1/2" Para evitar el pandeo del estribo
8.40 cm
40.0 cm
As Negativo 11.04 cm
9 1/2 '' 190.0 cm
11.04 cm
2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.
REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 min = 0.0024
fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.40 cm
b = 190.00 cm b = 30.00 cm barra = 3/4 ''
h = 120.00 cm h = 120.00 cm As = 2.850 cm
barra = 1/2 '' barra = 1/2 '' Tomamos 3 3/4 ''
estribo = 3/8 '' estribo = 3/8 '' ACERO MAXIMO
recub. = 2.50 cm recub. = 7.50 cm max = 0.0163
d = 115.91 cm d = 110.91 cm As max = 56.57 cm
M = 22.03 Tn-m M = 44.48 Tn-m barra = 3/4 ''
a = 0.624 cm a = 8.659 cm As = 2.850 cm
As = 5.04 cm As = 11.04 cm Tomamos 20 3/4 ''
3. Aceros Negativos y Positivos Finales
ACERO POSITIVO ACERO NEGATIVO
As Positivo 8.40 cm As Negativo 11.04 cm 0.43
barra = 3/4 '' barra = 1/2 ''
As = 2.850 cm As = 1.267 cm
Tomamos 3 3/4 '' Tomamos 9 1/2 ''
DISEO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION
Verificar As min y As max
Cumple con As min y As max
ACERO LONGITUDINAL
sadm Suelo = 15.000 Tn/m REFUERZO NEGATIVO
s diseo = 22.500 Tn/m f`c = 210.00 Kg/cm2
Tomando B = 1.00 m 3/8 '' @ 0.27 fy = 4200.00 Kg/cm2
Mom. Neg = 7.20 Tn-m b = 100.00 cm
30.0 cm h = 40.00 cm
barra = 1/2 ''
80.0 cm 1/2 '' @ 0.2 estribo = 3/8 ''
recub. = 7.50 cm
80.0 cm d = 30.91 cm
M = 7.20 Tn-m
40.0 cm a = 1.486 cm
As = 6.31 cm
190.0 cm barra = 1/2 ''
As = 1.267 cm
22.50 Tn/m @ = 20.00
Vu = 25.000 Tn A cara de columna .Vc = Vud =
Wu = 1.49 Tn/m 38.344 Tn > 24.541 Tn Ok
recub. = 7.50 cm
barra = 1/2 ''
estribo = 3/8 ''
b = 190.00 cm
d = 30.91 cm
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocar refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.218 m
estribo = 3/8 ''
La separacion de los estribos debe ser:
S d/4 = 27.73 cm S = 27.00 cm 3/8 '' @ 0.27
S 30.00 cm
REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO
La separacion de los estribos debe ser:
S = 55.00 cm 3/8 '' @ 0.55
DISEO DE REFUERZO TRANSVERSAL
VERIFICACION POR CORTANTE
ACERO TRANSVERSAL
VIGAS CONTINUAS DE CIMENTACION EJE F10-F6
1. Colocar dimensiones de la viga continua
30.0 cm
4 3/4 '' As Positivo 9.20 cm
80.0 cm
2 1/2" Para evitar el pandeo del estribo
9.20 cm
40.0 cm
As Negativo 14.93 cm
8 5/8 '' 180.0 cm
14.93 cm
2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.
REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 min = 0.0024
fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.40 cm
b = 180.00 cm b = 30.00 cm barra = 3/4 ''
h = 120.00 cm h = 120.00 cm As = 2.850 cm
barra = 1/2 '' barra = 1/2 '' Tomamos 3 3/4 ''
estribo = 3/8 '' estribo = 3/8 '' ACERO MAXIMO
recub. = 2.50 cm recub. = 7.50 cm max = 0.0163
d = 115.91 cm d = 110.91 cm As max = 56.57 cm
M = 40.08 Tn-m M = 59.29 Tn-m barra = 3/4 ''
a = 1.202 cm a = 11.710 cm As = 2.850 cm
As = 9.20 cm As = 14.93 cm Tomamos 20 3/4 ''
3. Aceros Negativos y Positivos Finales
ACERO POSITIVO ACERO NEGATIVO
As Positivo 9.20 cm As Negativo 14.93 cm 0.43
barra = 3/4 '' barra = 5/8 ''
As = 2.850 cm As = 1.979 cm
Tomamos 4 3/4 '' Tomamos 8 5/8 ''
DISEO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION
ACERO LONGITUDINAL
Cumple con As min y As max
Cumple con As min y As max
sadm Suelo = 15.000 Tn/m REFUERZO NEGATIVO
s diseo = 22.500 Tn/m f`c = 210.00 Kg/cm2
Tomando B = 1.00 m 3/8 '' @ 0.27 fy = 4200.00 Kg/cm2
Mom. Neg = 6.33 Tn-m b = 100.00 cm
30.0 cm h = 40.00 cm
barra = 1/2 ''
80.0 cm 1/2 '' @ 0.225 estribo = 3/8 ''
recub. = 7.50 cm
75.0 cm d = 30.91 cm
M = 6.33 Tn-m
40.0 cm a = 1.302 cm
As = 5.53 cm
180.0 cm barra = 1/2 ''
As = 1.267 cm
22.50 Tn/m @ = 22.50
Vu = 25.000 Tn A cara de columna .Vc = Vud =
Wu = 1.49 Tn/m 36.325 Tn > 24.541 Tn Ok
recub. = 7.50 cm
barra = 1/2 ''
estribo = 3/8 ''
b = 180.00 cm
d = 30.91 cm
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocar refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.218 m
estribo = 3/8 ''
La separacion de los estribos debe ser:
S d/4 = 27.73 cm S = 27.00 cm 3/8 '' @ 0.27
S 30.00 cm
REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO
La separacion de los estribos debe ser:
S = 55.00 cm 3/8 '' @ 0.55
DISEO DE REFUERZO TRANSVERSAL
ACERO TRANSVERSAL
VERIFICACION POR CORTANTE
VIGAS CONTINUAS DE CIMENTACION EJE FB-FC
1. Colocar dimensiones de la viga continua
30.0 cm
3 3/4 '' As Positivo 5.01 cm
80.0 cm
2 1/2" Para evitar el pandeo del estribo
8.40 cm
40.0 cm
As Negativo 11.52 cm
10 1/2 '' 180.0 cm
11.52 cm
2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.
REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 min = 0.0024
fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.40 cm
b = 180.00 cm b = 30.00 cm barra = 3/4 ''
h = 120.00 cm h = 120.00 cm As = 2.850 cm
barra = 1/2 '' barra = 1/2 '' Tomamos 3 3/4 ''
estribo = 3/8 '' estribo = 3/8 '' ACERO MAXIMO
recub. = 2.50 cm recub. = 7.50 cm max = 0.0163
d = 115.91 cm d = 110.91 cm As max = 56.57 cm
M = 21.90 Tn-m M = 46.33 Tn-m barra = 3/4 ''
a = 0.655 cm a = 9.035 cm As = 2.850 cm
As = 5.01 cm As = 11.52 cm Tomamos 20 3/4 ''
3. Aceros Negativos y Positivos Finales
ACERO POSITIVO ACERO NEGATIVO
As Positivo 8.40 cm As Negativo 11.52 cm 0.43
barra = 3/4 '' barra = 1/2 ''
As = 2.850 cm As = 1.267 cm
Tomamos 3 3/4 '' Tomamos 10 1/2 ''
DISEO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION - CONECTADAS
ACERO LONGITUDINAL
Verificar As min y As max
Cumple con As min y As max
sadm Suelo = 15.000 Tn/m REFUERZO NEGATIVO
s diseo = 22.500 Tn/m f`c = 210.00 Kg/cm2
Tomando B = 1.00 m 3/8 '' @ 0.27 fy = 4200.00 Kg/cm2
Mom. Neg = 6.33 Tn-m b = 100.00 cm
30.0 cm h = 40.00 cm
barra = 1/2 ''
80.0 cm 1/2 '' @ 0.225 estribo = 3/8 ''
recub. = 7.50 cm
75.0 cm d = 30.91 cm
M = 6.33 Tn-m
40.0 cm a = 1.302 cm
As = 5.53 cm
180.0 cm barra = 1/2 ''
As = 1.267 cm
22.50 Tn/m @ = 22.50
Vu = 25.000 Tn A cara de columna .Vc = Vud =
Wu = 1.49 Tn/m 36.325 Tn > 24.541 Tn Ok
recub. = 7.50 cm
barra = 1/2 ''
estribo = 3/8 ''
b = 180.00 cm
d = 30.91 cm
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocar refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.218 m
estribo = 3/8 ''
La separacion de los estribos debe ser:
S d/4 = 27.73 cm S = 27.00 cm 3/8 '' @ 0.27
S 30.00 cm
REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO
La separacion de los estribos debe ser:
S = 55.00 cm 3/8 '' @ 0.55
DISEO DE REFUERZO TRANSVERSAL
ACERO TRANSVERSAL
VERIFICACION POR CORTANTE