GENERAL MECHANICAL CONDITIONS

15.
16.

1.
2.
3.

4.
5.

6.
7.
8.

9.
10.
11.
12.

13.
14.
15.
16.

THE GENERAL AND SPECIAL CONDITIONS OF THE ARCHITECTURAL SPECIFICATIONS SHALL BE INCLUDED
AS PART OF THESE DOCUMENTS.
ALL MATERIALS SHALL BE NEW, UNUSED, AND THE BEST OF THEIR RESPECTIVE KINDS AND FREE FROM
DEFECTS.
THE CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE AIR DISTRIBUTION SYSTEM WITHIN THE
TENANT SPACE TO INCLUDE, BUT NOT LIMITED TO ALL DUCTWORK, HANGERS, INSULATION, VAPOR
BARRIER, SUPPLY DIFFUSERS, RETURN GRILLES, FLEXIBLE CONNECTIONS, AND CONTROL
INSTALLATION AS REQUIRED FOR A COMPLETE AND WORKING SYSTEM. THE CONTRACTOR SHALL PAY
ALL FEES, GIVE ALL NOTICES, FILE ALL NECESSARY DRAWINGS AND OBTAIN ALL PERMITS AND
CERTIFICATES OF APPROVAL REQUIRED IN CONNECTION WITH ALL WORK UNDER THIS CONTRACT. ALL
WORK SHALL BE FURNISHED AND INSTALLED IN FULL ACCORDANCE WITH ALL LAWS, ORDINANCES,
RULES AND REGULATIONS.
DRAWINGS ARE DIAGRAMMATIC ONLY, INTENDING TO SHOW GENERAL RUNS AND LOCATIONS OF THE
WORK AND ARE NOT INTENDED TO BE RIGID IN SPECIFIC DETAIL.
THE CONTRACTOR SHALL BE HELD TO HAVE EXAMINED THE SITE FOR HIS WORK BEFORE HAVING
SUBMITTED HIS PROPOSAL. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CONDITIONS FOUND
DURING THE COURSE OF THE CONTRACT.
THE CONTRACTOR SHALL VERIFY ALL MEASUREMENTS AT THE SITE AND BE RESPONSIBLE FOR THE
CORRECTNESS OF THE SAME.
THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF HIS WORK WITH LIGHTING PLANS,
REFLECTED CEILING PLANS, LANDLORD'S SPRINKLER PLANS AND ALL OTHER TRADES.
THE INSTALLATION OF ALL EQUIPMENT AND MATERIALS REQUIRING ACCESS SHALL BE MADE IN SUCH
MANNER AS TO MAKE THE EQUIPMENT AND MATERIALS READILY ACCESSIBLE FOR OPERATION,
MAINTENANCE AND REPAIRS.
STORAGE OF CONSTRUCTION EQUIPMENT AND MATERIALS SHALL BE ONLY IN SPACES AS DESIGNATED
BY THE ARCHITECT/OWNER.
CONSTRUCTION DEBRIS AND RUBBISH GENERATED BY THE CONTRACTOR SHALL BE REMOVED FROM
PREMISES AS OFTEN AS NECESSARY OR AS DIRECTED TO MAINTAIN A CLEAN AND WORKABLE AREA.
ALL WORK AND EQUIPMENT SHALL BE FULLY GUARANTEED FOR ONE (1) YEAR FROM THE DATE OF FINAL
PAYMENT AND ACCEPTANCE.
ALL WORK, INCLUDING INSIDE OF SUPPLY AIR DUCTS, AND EQUIPMENT WITHIN THE CONTRACT AREA
FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE CLEANED TO THE SATISFACTION OF THE
OWNER BEFORE TURNING SAME OVER TO THE OWNER.
CONNECT NEW WORK TO EXISTING IN A NEAT AND APPROVED MANNER.
INTERRUPTION OF HEATING, POWER AND AUXILIARY SYSTEMS WHERE AND IF REQUIRED SHALL BE
COORDINATED AND SHALL OCCUR ONLY DURING PREARRANGED ACCEPTABLE TIMES.
ALL DESIGN SHALL INCORPORATE CURRENT ASHRAE METHODS.
WHEN EXISTING DUCTWORK IS UTILIZED, SIZES SHALL BE AS SHOWN ON DWGS. AS MINIMUM
REQUIREMENT.

HVAC NOTES
1.
2.
3.
4.

5.
6.
7.

PROVIDE TESTING AND BALANCING FOR ALL AIR SYSTEMS. SUBMIT REPORTS TO ARCHITECT AND FINAL
INSPECTOR.
SUBMIT SHOP DRAWINGS TO ARCHITECT FOR APPROVAL OF MAJOR MECHANICAL EQUIPMENT PRIOR TO
ORDERING.
SEE ALL OTHER DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL WORK AND CLARIFICATIONS OR
WORK TO BE PERFORMED.
CONDENSATE FROM ROOFTOP EQUIPMENT SHALL DISCHARGE ONTO ROOF VERIFY WITH CITY CODE
OFFICIALS. IF OBJECTIONABLE, EXTEND CONDENSATE PIPE TO APPROVED FLOOR RECEPTOR, OR
EXTEND TO APPROVED EXTERIOR LOCATION. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF
DIFFUSERS, REGISTERS, GRILLES LOCATED IN THE CEILING GRID.
SEE ARCHITECTURAL ROOF PLAN AND DETAILS FOR LOCATION OF NEW ROOFTOP EQUIPMENT.
INSULATE LAST 5 FEET OF DUCT FROM TOILET ROOM EXHAUST DUCT WITH 1" THICK FIBERGLASS DUCT
WRAP. PROVIDE VAPOR BARRIER.
DUCTWORK LAYOUT SHOWN IS RECOMMENDED. ADJUST TO COMPLY WITH CITY CODE REQUIREMENTS
AND AS BUILT CONDITIONS.

17.

18.

19.

20.
21.
22.

GENERAL NOTES
1.

DUCT SIZES SHOWN ARE SHEET METAL DIMENSIONS. NOT DUCT LINER. REFER TO MECHANICAL
SPECIFICATIONS FOR DUCT INSULATION REQUIREMENTS.
2. PROVIDE SINGLE WALL TURNING VANES @ ALL ELBOWS AND TEES PER SMACNA STANDARDS.
3. DO NOT PROVIDE AIR EXTRACTORS OR SPLITTER DAMPERS WHICH PROTRUDE INTO RECTANGULAR
TRUNK DUCTS. PROVIDE ROUND SPIN-IN FITTINGS FOR ROUND BRANCH DUCTS.
4. ROUND BRANCH DUCTS ARE SAME SIZE AS DIFFUSER WHICH THEY SERVE.
5. CONTRACTOR SHALL FIELD VERIFY THE EXACT SIZE, LOCATION, AND CONDITION OF ALL EXISTING
EQUIPMENT, PIPING, DUCTWORK, ETC. TO BE REUSED, RETAINED OR CONNECTED.
6. CONTRACTOR SHALL COMPLY WITH ALL LANDLORD'S TENANT CRITERIA. COORDINATE AND SCHEDULE
ALL WORK WITH LANDLORD'S FIELD REPRESENTATIVE.
7. MAXIMUM FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 5'-0". REFER TO MECHANICAL SPECIFICATIONS
ON SHEET M-2.
8. CONTRACTOR SHALL PROCURE THE SERVICES OF A APPROVED NEBB OR AABC CERTIFIED AIR BALANCE
& TESTING AGENCY TO BALANCE, ADJUST & TEST EQUIPMENT. CONTRACTOR SHALL BE RESPONSIBLE
FOR SUBMITTING 3 COPIES OF BALANCE/TEST AGENCIES REPORT TO TENANT PROJECT MANAGER
AND/OR LANDLORD'S REPRESENTATIVE FOR REVIEW AND CITY INSPECTOR PRIOR TO FINAL
CERTIFICATE OF OCCUPANCY
9. BALANCING OF AIR DEVICES SHALL BE ACCOMPLISHED BY ADJUSTING BRANCH TAKEOFF DAMPER AT
MAIN TRUNK DUCT. DAMPERS IN THE NECKS OF AIR DEVICES SHALL BE USED FOR FINAL TRIM ONLY,
AND IN NO CASE FOR GREATER THAN 10% IF THE INDICATED VOLUME FOR THE INDIVIDUAL AIR DEVICE.
10. DO NOT ATTACH ANYTHING TO THE UNDERSIDE OF THE ROOF DECK. ALL LOADS AND BRACING MUST BE
ADEQUATELY SUPPORTED FROM THE BUILDING ROOF STRUCTURE.
11. GAS PIPING SHOWN IS FOR LOW PRESSURE GAS IN THE THE BUILDING. CONTRACTOR SHALL VERIFY
GAS PRESSURE PRIOR TO CONSTRUCTION. 2 PSIG MAY BE USED IF APPROVED BY AUTHORITIES. AND AS
APPROVED BY LITTLE CAESAR'S. PROVIDE PRESSURE REDUCING VALVES AT EACH APPLIANCE AND
VENT AS RECOMMENDED BY MFG. EXTEND NEW GAS LINE BACK TO EXISTING METER. VERIFY METER
SIZE WITH UTILITY COMPANY. CONNECT NEW GAS LINE TO EXISTING MANIFOLD.
12. ALL ROOF PENETRATIONS SHALL BE APPROVED BY LANDLORD AND DONE IN ACCORDANCE WITH ROOF
MANUFACTURERS RECOMMENDATIONS SO AS NOT TO VOID THE WARRANTY.

SENS.
MBH

EAT
DB/WB

AMBIENT
DB

ROWS

(S)EER

KW

STAGES

AGA
EFF(%)

CFM

TYPE

ESP IN
W.C.

MOTOR
(H.P.)

VOLTS

PHASE

MOCP

MCA

WEIGHT
(LBS.)

MANUFACTURER

MODEL

ESIGN

RTU 1

SALES/OFFICE

46.5

42.7

80/63

110

10.0

6.0

80

1600

FC

0.5"

208

30.0

26.0

520

CARRIER

50TFQ005--511

RTU 2

LOBBY/ PREP

79.0

72.0

80/63

115

10.5

81

2400

FC

0.5"

208

50.0

36.5

877

TRANE

YSC072A3ELA

2,3,4,5,6,7

REMARKS:
1, EXISTING TO REMAIN- CONTRACTOR TO CLEAN / INSPECT FOR PROPER WORKING ORDER.
2. NEW FACTORY 14" STANDARD ROOF CURBS FOR ALL RTUS.
3. EXTEND GAS PIPING TO ALL RTUS AS REQUIRED. CONTRACTOR TO COORDINATE INSTALLATION OF GAS METER WITH GAS UTILITY COMPANY.
4. ALL RTUS TO BE FURNISHED WITH FACTORY INSTALLED HACR CIRCUIT BREAKER, DISCONNECT AND 120V GFCI SERVICE OUTLET. ELECTRICAL CONTRACTOR TO MAKE FIELD CONNECTIONS TO ALL UNITS.
5. ALL RTUS SHALL BE FURNISHED WITH FACTORY INSTALLED SMOKE DETECTORS; ONE IN SUPPLY AND ONE IN RETURN DUCT.
ST

ER

6. FURNISH AND INSTALL FACTORY SEVEN DAY PROGRAMMABLE THERMOSTATS FOR EACH RTU.
G

7. ALL RTUS SHALL BE INSTALLED WITH FULL SIZE SUPPLY AND RETURN DROPS.

CFM

MANUFACTURER
& MODEL NO.

MUA
1

AAON

1100

#RQ-005

0.75

MOTOR

FAN
RPM

VOLTAGE

HP

RPM

WEIGHT
(LBS.)

856

120V. 1

3/4

1750

250

PROVIDED
COOLING

CALCULATED
COOLING
SENS.
MBH

LATENT
MBH

TOTAL
MBH

SENS.
MBH

TOTAL
MBH

MBH

MBH

116.8

12.1

28.9
(10 tons)

120

125

25.3

25.6

AREA SERVED

6/11/12
Si g
ne d

RI

Z ON

.
A U. S

A.

REMARKS
EXP. DATE: 07-30-2013

ROOF

HVAC LOAD CALCULATIONS

(PER 2006 IECC 503)


CALCULATED PROVIDED
HEAT
HEAT

C A T
F I
E

te

MAKE-UP AIR FAN


UNIT NO.

E D ARC
H

TYPE 1 HOOD

NEW UNIT, INTERLOCK WITH EF-2. SEE M-4

DIFFUSER AND GRILLE SCHEDULE


PATTERN

MAT'L.

FINISH

BORDER

TITUS/TMS

ADJ.

STEEL

26

RADIAL OPPOSED BLADE DAMPER

LAY-IN T-BAR

12x12 CEILING

TITUS 300RL

ADJ.

STEEL

26

OPPOSED BLADE DAMPER

LAY-IN T-BAR

CEILING

TITUS

STEEL

26

LAY-IN T-BAR
WITH FILTERS

MARK

APPLICATION

MFR. / MODEL

S-1

24x24 CEILING

S-2
R-1

HVAC LOAD BASED UPON PROPOSED TENENT REQUIREMENTS.


TENENT TO BE LITTLE CAESAR'S
-

ACCESSORIES

REMARKS

DEVICES SHALL BE TITUS OR APPROVED EQUAL. SEE SPECIFICATIONS.


FLEXIBLE OR RIGID RUNOUT DUCT SIZE SHALL BE SAME SIZE AS DIFFUSER NECK
UNLESS OTHERWISE SPECIFICALLY SHOWN ON DRAWINGS.
MAXIMUM NC FOR ANY DEVICE WITH SPECIFIED CFM AND WIDE-OPEN DAMPER
SHALL BE NO GREATER THAN NC25.
CEILING MODULE SHALL BE 24X24 UNLESS OTHERWISE NOTED.
AIR PATTERN SHALL BE 4-WAY UNLESS SHOWN OTHERWISE ON DRAWINGS.
DUCT MOUNTED AIR DEVICES SHALL BE INSTALLED AS SHOWN ON DETAIL.

EXHAUST FAN SCHEDULE

MECHANICAL GENERAL NOTES


1. PROVIDE MATERIALS AND EQUIPMENT AND EXECUTE THE WORK, INCLUDING ALL TESTING AND
INSPECTIONS, IN COMPLIANCE WITH THE APPLICABLE PROVISIONS OF FEDERAL, STATE AND LOCAL
GOVERNMENT LAWS, ORDINANCES, REFERENCED CODES AND STANDARDS CURRENT AS OF THE ISSUE
DATE OF THESE DRAWINGS INCLUDING THE GOVERNING LAWS, ORDINANCES, CODES AND STANDARDS
CONSTITUTE MINIMUM REQUIREMENTS. ALL MORE STRINGENT REQUIREMENTS OF THE CONTRACT
DOCUMENTS SHALL MODIFY, SUPPLEMENT AND SUPERSEDE APPLICABLE PORTIONS OF GOVERNING LAWS,
ORDINANCES, CODES AND STANDARDS.
2. CONTRACTOR SHALL PRESENT CERTIFICATE TO THE OWNER THAT ALL APPLICABLE BUILDING PERMITS
HAVE BEEN SECURED PRIOR TO STARTING ANY WORK, AND PROVIDE THE OWNER WITH ALL REQUIRED
CERTIFICATES OF FINAL APPROVAL FROM THE GOVERNING JURISDICTIONS AT COMPLETION OF THE WORK.
PROVIDE ALL SHOP DRAWINGS AS REQUIRED IN FOLLOWING SECTIONS.
3. MAKE ALL CONNECTIONS TO EXISTING SYSTEMS DURING DESIGNATED PERIODS UPON APPROVAL OF THE
OWNER AND AT NO INCREASE IN CONTRACT SUM.
4. EXISTING FACILITIES:
A. DO NOT INTERRUPT EXISTING UTILITIES UTILIZED BY THE OWNER, EXCEPT AS SPECIFIED OR WHEN
APPROVED IN WRITING AND THEN ONLY AFTER TEMPORARY UTILITY SERVICES HAVE BEEN APPROVED
AND PROVIDED. INTERRUPTIONS MUST BE SCHEDULED TO SUIT THE OWNER'S REQUIREMENTS.
B. VERIFY ALL EXISTING WORK, WHERE EXISTING CONNECTIONS ARE PARTIAL, PROVIDE ALL NECESSARY
MATERIALS, LABOR AND EQUIPMENT REQUIRED TO MODIFY EXISTING WORK. IN ADDITION, MAINTAIN
INTEGRITY OF THE EXISTING SYSTEMS. RECTIFY ANY CONTAMINATION, DEGRADATION OF CLEANLINESS
OR DAMAGE TO THE EXISTING SYSTEMS TO THE SATISFACTION OF THE OWNER. PROVIDE ALL WORK SO
REQUIRED AT NO INCREASE IN THE CONTRACTOR'S ORIGINAL PROPOSAL.
5. COORDINATE EXACT LOCATION OF CONSTRUCTION TO PRECLUDE ANY INTERFERENCES BETWEEN PIPING,
WIRING, LIGHTING FIXTURES, DUCTWORK, BUILDING EQUIPMENT, PROCESS EQUIPMENT AND OTHER
CONSTRUCTION.
6. PROVIDE LABOR, INCLUDING FIELD ERECTION AND SUPERVISION, MATERIALS, EQUIPMENT AND
ANCILLARIES, AND COORDINATE, PROCURE, FABRICATE, DELIVER, ERECT OR INSTALL, INTERFACE WITH
EXISTING WORK, START, DEBUG AND TEST ALL SYSTEMS AS NECESSARY TO PROVIDE THE OWNER WITH A
COMPLETE, OPERATING FACILITY IN CONFORMANCE WITH THE CONSTRUCTION BID DOCUMENTS.
7. ALL CUTTING AND PATCHING THAT MAY BE NECESSARY FOR THE INSTALLATION OF THE MECHANICAL
CONTRACTOR'S WORK SHALL BE PERFORMED AND REPAIRED BY THE TRADE WHOM NORMALLY PERFORMS
THAT WORK AND PAID FOR BY THE MECHANICAL CONTRACTOR. NO CUTTING OF THE BUILDING
STRUCTURAL SYSTEM SHALL BE PERFORMED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT BEING
PREVIOUSLY OBTAINED.
8. THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING HIS BID TO FAMILIARIZE
HIMSELF WITH THE ACTUAL PROJECT CONDITIONS AND TO CHECK FOR ANY INTERFERENCES BETWEEN HIS
WORK AND THAT OF THE OTHER TRADES, AND/OR ANY APPARENT VIOLATIONS OF LOCAL OR STATE
CODES, LAWS, ORDINANCES AND REGULATIONS. SHOULD ANY VIOLATIONS OR INTERFERENCES APPEAR
AND DEPARTURE FROM THE DESIGN INTENT OF THE CONTRACT DOCUMENTS IS REQUIRED, THE
CONTRACTOR SHALL NOTIFY THE ARCHITECT AND/OR OWNER. FAILURE TO PROVIDE THE ARCHITECT
AND/OR OWNER WITH THE AFOREMENTIONED NOTIFICATION SHALL RESULT IN THE CONTRACTOR BEING
HELD RESPONSIBLE TO COMPLETE ALL WORK TO MEET THE INTENT OF THE CONTRACT DOCUMENTS WITH
NO ADDITIONAL EXPENSES BEING INCURRED BY THE OWNER.
9. AIR BALANCE TEST AND REPORT BY INDEPENDENT AIR BALANCE CONTRACTOR WILL BE REQUIRED FOR
ALL DIFFUSERS, GRILLES AND EXHAUST HOODS PRIOR TO FINAL APPROVAL OF WORK.

ENTERPRISES, INC.

TAG
NUMBER

AREA SERVED QNT

MANUFACTURER/ ACTUAL
MODEL#
CFM

TOTAL STATIC
FAN ELECTRICAL
PRESSURE
DRIVE TYPE NOTES
AMPS
V/P
(IN WC)

EF
1

BATHROOM

BROAN
#671

100

120/1

N/A

EF
2

PIZZA OVEN

ACCUREX
XRUB-141-VG

1600

208/1

N/A

EF
3

DELIVERY /
TRASH DOOR

COOK
AIR CURTAIN

3234

115/1

N/A

NOTES
1.
2.
3.

EXHAUST FAN CONTROLLED BY BATHROOM LIGHT SWITCH (V.I.F.)


NEW UPBLAST EXHAUST FAN, INTERLOCK WITH MAU-1, UL LISTED FOR GREASE APPLICATION.
USE COOK OR EQUIVALENT - FOLLOW ALL MANUFACTURERS INSTALLATION INSTRUCTIONS.

AIR BALANCE SCHEDULE


UNIT TYPE

MAKE/MODEL

SUPPLY

O.S.A.

% O.S.A.

RETURN

EXHAUST

PRESSURE

6 TON HVAC UNIT

TRANE
YSC072

2400

480

20

1920

480

4 TON HVAC UNIT

CARRIER
50TFQ005

1600

320

20

1280

320

AAON
RQ-005

1100

1100

100

1100

ACCUREX
XRUD-141-VG

NON-TEMPERED MAKE-UP AIR


FAN
GAS CONVEYOR OVEN
EXHAUST FAN
RESTROOM EXHAUST FAN

-1600

-1600

-70

-70

-1670

230

BROAN #671

TOTAL

5100

1900

3200

O.S.A. CALCULATIONS
OCCUPANT LOAD
PER 1000 SQ.FT.

TOTAL SQ.FT.

TOTAL
OCCUPANTS

OUTDOOR
AIR-CFM/PER

O.S.A.
REQUIRED

REMARKS

LOBBY

30

240

7.20

15

108

PREP AREA

20

576

11.52

15

173

BACKROOM

20

215

4.30

15

65

1 WC (58SQ.FT)

75

75

REQUIRED

PROVIDED

420

500

ROOM

TOILET
ROOMS

REMARKS:
1. TOTAL SQUARE FOOTAGE BASED ON NET FLOOR AREA PER IMC TABLE 403.3
(FOOTNOTE A AND IMC CHAPTER 2 DEFINITIONS.

8345 W. GLENDALE AVENUE - #103


GLENDALE, ARIZONA 85305

10.

TOTAL
MBH

.
N O

9.

REMARKS

TONS

7.
8.

RCHITECTURE

ELECTRICAL DATA

RE

6.

AREA SERVED

SUPPLY FAN

CT

5.

5.

TAG

ELECTRIC HEATING

TE

4.

4.

COOLING CAPACITY

Da

3.

3.

EXISTING HVAC UNITS, MAKE-UP AIR UNITS, DUCTWORK, SHALL REMAIN UNLESS OTHERWISE NOTED.
SHEETMETAL DUCTWORK CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF
"SMACNA" STANDARDS, NFPA 90A AND 96, AND THE LATEST EDITION OF THE ASHRAE GUIDE AND DATA
BOOKS. ALL DUCTWORK SIZES INDICATED ON THE PLANS ARE THE INTERNAL DIMENSIONS AND
DUCTWORK SIZES SHALL BE INCREASED ACCORDING SHOULD DUCTWORK BE INTERNALLY LINED WITH
INSULATION. ALL DUCTWORK SHALL BE SEALED AIR TIGHT AND SHALL NOT ALLOW MORE THAN 10% AIR
LEAKAGE THROUGHOUT THE ENTIRE SYSTEM.
ALL DUCTWORK SHALL BE CONCEALED. EXPOSING OF ANY DUCTWORK MUST HAVE PRIOR APPROVAL OF
THE ARCHITECT.
KITCHEN EXHAUST DUCTWORK SHALL BE MINIMUM 16 GAUGE WELDED BLACK STEEL OR STAINLESS
STEEL WHERE VISIBLE. PROVIDE ACCESS DOORS IN THE VERTICAL FACE OF THE HORIZONTAL RUN
EVERY 10'-0"
AND AT ALL CHANGES IN DIRECTION. VENTILATION SYSTEMS SHALL CONFORM TO
NFPA-96 REQUIREMENTS AND RECOMMENDATIONS.
THE CONTRACTOR HAS THE OPTION OF REVISING DUCTWORK SIZES TO OTHERS OF EQUIVALENT
CROSS-SECTIONAL AREA SHOULD SPACE PERMIT.
PROVIDE VOLUME DAMPERS IN THE DUCT SYSTEMS WHERE SHOWN ON PLANS AND WHERE REQUIRED
TO INSURE PROPER SYSTEM BALANCING. SPIN-IN FITTINGS WITH MANUAL VOLUMN DAMPERS MAY BE
USED.
PROVIDE FLEXIBLE DUCT CONNECTORS ON ALL DUCT CONNECTIONS TO AIR HANDLING EQUIPMENT.
THE CONTRACTOR SHALL SUBMIT TO THE ARCHITECT A COMPLETE AIR BALANCE REPORT OF ALL AIR
HANDLING SYSTEMS. THE REPORT SHALL INCLUDE FAN RPM, TOTAL STATIC PRESSURE, MOTOR RATED
AMPACITY, TEMPERATURES, AIR QUANTITIES AT ALL DIFFUSERS AND GRILLES, A MOTOR OPERATING
AMPACITY, ENTERING AND DISCHARGE AIR RECOMMENDATIONS TO CORRECT ANY DEFICIENCIES. THE
AIR BALANCE DIAGRAM OF THE AIR HANDLING SYSTEM INSTALLED, AND REPORT SHALL BE PERFORMED
BY AN INDEPENDENT N.E.B.B. CERTIFIED AIR BALANCE CONTRACTOR.
DUCTWORK INSULATION:
A. ALL SUPPLY DUCTWORK INSIDE OF THE BUILDING, IN NON-CONDITIONED SPACES, SHALL BE
INSULATED WITH DUCT WRAP OF 1" MINIMUM THICKNESS AND 1 1/2" DENSITY, WITH VAPOR BARRIER
WITH R-VALUES PER 2005 T-24 REQUIREMENTS. JOINTS SHALL BE STAPLED AND TAPED. AS AN
ALTERNATE, THE CONTRACTOR MAY LINE THE DUCTS WITH 1" THICK, 1 1/2# DENSITY FIBERGLASS
DUCT LINER.
B. ALL DUCTWORK EXPOSED OUTSIDE OF THE BUILDING SHALL BE COVERED WITH 1 1/2" THICK, 3#
DENSITY, FIBERGLASS BOARD WITH F.S.K. FACING WITH R-VALUES PER 2005 T-24 REQUIREMENTS. ALL
JOINTS SHALL BE TAPED. WEATHERPROOF DUCTS WITH WEATHERPROOF MASTIC BOTH UNDER AND
OVER ONE LAYER OF FIRE RETARDANT GLASS CLOTH WITH 2" OVERLAP ON ALL SEAMS.
WEATHERPROOF COATING SHALL BE 1/8" THICK.
C. DUCTWORK INSULATION SHALL HAVE A FLAME SPREAD/SMOKE DENSITY RATING NOT EXCEEDING 25/50
PER NFPA PAMPHLET 90A.
VIBRATION ABSORBING SUPPORTS SHALL BE INSTALLED AS REQUIRED ON ALL EQUIPMENT TO PREVENT
TRANSMISSION OF VIBRATION AND NOISE TO THE STRUCTURE. PROVIDE VIBRATION ISOLATION PER
A.S.H.R.A.E. STANDARDS.
ALL MECHANICAL EQUIPMENT LOCATED ON THE ROOF SHALL BE PROPERLY SUPPORTED WITH
PRE-FABRICATED CURBS, EQUIPMENT RAILS, OR OTHER MEANS AS APPROVED BY THE ARCHITECT.
SMOKE DETECTORS AND/OR HEAT DETECTORS (SYSTEMS 2000 CFM & OVER):
A. WHERE REQUIRED BY LOCAL CODE, FURNISH AND INSTALL IN THE MAIN SUPPLY AIR DUCT OF EACH
AIR HANDLING UNIT, A SELF-CONTAINED, IONIZATION-TYPE DUCT SMOKE DETECTOR DESIGNED TO
MOUNT TO A DUCT USING SAMPLING TUBES ACROSS THE DUCT TO SENSE THE AIR. UNIT SHALL BE
MANUALLY RESET AND SHALL HAVE A SET OF CONTACTS FOR FAN SHUT-DOWN. SMOKE DETECTORS
SHALL BE IN ACCORDANCE WITH THE LATEST ADOPTED EDITIONS OF NFPA 90A AND INTERNATIONAL
MECHANICAL CODE OF THE LOCAL AUTHORITY HAVING JURISDICTION.
B. WHERE REQUIRED BY LOCAL CODE, FURNISH AND INSTALL IN THE MAIN RETURN AIR DUCT OF EACH
AIR HANDLING UNIT, A MANUALLY RESET HEAT DETECTOR. HEAT DETECTORS SHALL BE WIRED (BY
MECHANICAL TRADES) TO SHUT DOWN THE AIR HANDLING UNITS SUPPLY FANS UPON SENSING
ADVERSE CONDITIONS IN THE AIR HANDLING SYSTEMS. HEAT DETECTORS SHALL BE IN ACCORDANCE
WITH THE ADOPTED EDITIONS OF NFPA 90A AND THE INTERNATIONAL MECHANICAL CODE OF THE
AUTHORITY HAVING JURISDICTION.
C. SMOKE DETECTORS SHALL BE INTEC CONTROLS MODEL SM-501 OR EQUAL WITH SAMPLING TUBES
AND AUXILIARY CONTACTS FOR FAN SHUT-DOWN. SMOKE DETECTORS SHALL BE CONNECTED TO THE
BUILDING FIRE ALARM SYSTEM, IF ONE IS IN PLACE.
HEATING, VENTILATING, AND AIR CONDITIONING SYSTEMS ARE DESIGNED ON THE FOLLOWING
CONDITIONS:
WINTER: INSIDE TEMP. 72 DEGREES F.,
OUTSIDE TEMP. 0 DEGREES F. AND 15 MPH WIND.
SUMMER: INSIDE TEMP. 78 DEGREES F. D.B. AND 50% R.H.
OUTSIDE TEMP. 90 DEGREES F. D.B. AND 75 DEGREES F., W.B.
SHEETMETAL RUN-OUTS AND FLEX DUCT CONNECTIONS TO AIR DISTRIBUTION DEVICES SHALL BE THE
SAME SIZE AS THE DEVICE NECK, UNLESS OTHERWISE NOTED.
DUCTS CONNECTING TO HVAC EQUIPMENT SHALL BE THE SAME SIZE AS EQUIPMENT DUCT
CONNECTIONS, UNLESS OTHERWISE NOTED.
ALL FLUES THROUGH ROOF SHALL BE CODE APPROVED TYPE "B" GAS VENTS SIMILAR TO METAL-FAB
STYLE "M" OR AS APPROVED BY THE ARCHITECT, COMPLETE WITH ROOF FLASHING, STORM COLLAR AND
WEATHERPROOF CAP. PRESSURIZED FLUES THROUGH THE ROOF SHALL BE U.L. LISTED GAS VENT
SIMILAR TO METALBESTOS MODEL PS. INSTALLATION PER MANUFACTURER'S REQUIREMENTS.
AIR DISTRIBUTION DEVICE LOCATIONS INDICATED ON THE PLANS ARE APPROXIMATE. THE CONTRACTOR
SHALL VERIFY EXACT LOCATIONS OF ALL AIR DISTRIBUTION DEVICES WITH ARCHITECTURAL PLANS
AND/OR ELECTRICAL PLANS PRIOR TO INSTALLATION. LIGHT FIXTURES AND SPRINKLER HEAD LOCATIONS
SHALL TAKE PRECEDENCE OVER AIR DISTRIBUTION DEVICES, UNLESS OTHERWISE NOTED.
THE CONTRACTOR SHALL SUBMIT EQUIPMENT SHOP DRAWINGS TO THE ARCHITECT FOR APPROVAL
PRIOR TO INSTALLATION OF ANY OF THE FOLLOWING:
A. HVAC UNITS
B. ROOF AND/OR CEILING EXHAUST FANS
C. AIR DISTRIBUTION DEVICES APPROVAL OF SHOP DRAWING DOES NOT RELIEVE THE CONTRACTOR OF
HIS RESPONSIBILITY TO CONFORM TO THE DESIGN INTENT OF THE BID DOCUMENTS. APPROVAL OF
SHOP DRAWINGS IS INTENDED TO BE FOR GENERAL CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS ONLY. ANY EQUIPMENT THAT IS INSTALLED THAT WILL INVOLVE THE WORK OF OTHER
TRADES SHALL BE COORDINATED WITH THOSE TRADES. REFER TO OTHER TRADES BID DOCUMENTS.
A MAXIMUM OF 85% OF THE REQUIRED VENTILATION AIR SHALL BE RECIRCULATED WHEN THE SYSTEM IS
ALSO EQUIPPED WITH EFFECTIVE ABSORPTION OR FILTERING EQUIPMENT SO THAT THE CONDITION OF
THE AIR SUPPLIED TO THE ROOM OR SPACE IS WITHIN THE QUALITY LIMITS REQUIRED BY CODE.
REFER TO SCHEDULE SHEET FOR NEW EQUIPMENT MANUFACTURER AND MODEL NO. NOT HERE
SPECIFIED.
ALL EXISTING EQUIPMENT SHALL BE UP TO GOOD WORKING ORDER TO GUARANTEE A COMPLETE
WORKING SYSTEM INCLUDING REPAIRS, ACID WASH, FILTERS ETC.
THERMOSTATS TO BE TRANE #BAYSENS019A (OR EQUAL) AT 48" AFF. 23. DIFFUSERS TO BE TITUS,
RETURN AIR GRILLS TO BE EGGCRATE WITH ROUND NECK SUPPLY. (KITCHEN TO BE FILTERED)

C E
R

2.

AIR BALANCING
A. CONTRACTOR SHALL PROCURE THE SERVICES OF AN INDEPENDENT NEBB OR AABC CERTIFIED AIR
BALANCE AND TESTING AGENCY TO BALANCE, ADJUST & TEST EQUIPMENT. CONTRACTOR SHALL BE
RESPONSIBLE FOR SUBMITTING 3 COPIES OF BALANCE/TEST AGENCIES REPORT TO P.S.S. PROJECT
MANAGER AND LANDLORD OPERATIONS DIRECTOR FOR REVIEW. MIN. OUTDOOR C.F.M. AND INDOOR
FAN C.F.M. SHALL BE PROVIDED AS SHOWN ON RTU SCHEDULE.
DUCTWORK
A. INSTALL ALL DUCTWORK IN COMPLETE CONFORMANCE WITH RECOMMENDED CONSTRUCTION
STANDARDS FOR RECTANGULAR AND ROUND SHEET METAL AND FLEXIBLE DUCTS IN ACCORDANCE
WITH SMACNA DUCT CONSTRUCTION STANDARDS AND ALL OTHER AUTHORITIES HAVING
JURISDICTION. FLEXIBLE DUCT SHALL NOT EXCEED 5'-0" IN LENGTH. MINIMUM SHEETMETAL
THICKNESS SHALL BE 26 GA.
B. ALL DUCT JOINTS LONGITUDINAL AND TRANSVERSE ARE TO BE SEALED USING 181A OR 181B LISTED
TAPES AND MASTICS. MECHANICAL FASTENERS MUST BE USED TO FASTEN DUCTS.
C. STRAP HANGERS SHALL NOT BE LESS THAN 1" BY 1/8" THICK ON SIX (6) FOOT CENTERS AND
ATTACHED TO SIDE OF DUCT WITH SHEET METAL SCREWS. INSULATED FLEXIBLE DUCT MAY BE USED
FOR LOW PRESSURE RUNOUTS TO INDIVIDUAL DIFFUSERS IN LENGTHS NOT TO EXCEED FIVE (5) FEET
FOR EACH DIFFUSER. SEAL ALL SHEETMETAL SCREW PENETRATIONS.
D. ALL RECTANGULAR AND ROUND SUPPLY DUCTWORK SHALL BE INTERNALLY INSULATED WITH A
MINIMUM THICKNESS THAT CONFORMS TO THE STANDARD CODE AND SHALL IN NO CASE BE LESS
THAN 2" AND SHALL HAVE A CONTINUOUS VAPOR BARRIER JACKET W/ALL JOINTS TAPED AND SEALED.
FRESH AIR DUCT SHALL HAVE 2" INTERNAL DUCT LINER FROM POINT OF OUTSIDE AIR CONNECTION
TO POINT OF CONNECTION AT PLENUM BOX OR MIXING BOX. ALL EXPOSED SPIRAL DUCT SHALL HAVE
SPIRACOUSTIC INTERNAL DUCT LINER, OR TOUGHGARD ULTRA ROUND BY CERTAINTEED.
E. PROVIDE FLEXIBLE CONNECTION BETWEEN ALL FAN POWERED EQUIPMENT AND CONNECTING
DUCTWORK.
F. ALL INSULATION, JOINING MATERIALS, SEALER, ETC. SHALL HAVE A U.L. FLAME SPREAD
CLASSIFICATION OF NO MORE THAN 25 AND A SMOKE DEVELOPMENT RATING NOT MORE THAN 50.
AIR DEVICES
A. SUPPLY DIFFUSERS: (TITUS AS STANDARD) SHALL BE FURNISHED WITH BAKED WHITE ENAMEL
FINISH, AND SHALL BE SELECTED FOR NECK VELOCITIES NOT EXCEEDING 800 FPM AND NOISE LEVEL
OF NC-35 OR LESS.
B. SUPPLY DIFFUSERS SHALL BE ROUND NECK, STEEL, MODEL TMS, SIZED USING CRITERIA INDICATED
ABOVE FOR LAY-IN CEILING GRID TYPE CONSTRUCTION OR DRYWALL CEILING AS INDICATED ON
DWG. DIFFUSERS SHALL BE COMPLETE WITH ADJUSTABLE AIR PATTERNS AND VOLUME CONTROL
DAMPERS.
C. RETURNS SHALL BE 22 INCH SQUARE NECK ALUM. MODEL 50F AND/OR AS NOTED ON PLANS AND AIR
DEVICE SCHEDULE. FACE VELOCITY OF RETURN REGISTERS SHALL NOT EXCEED 500 FPM. VOLUME
CONTROL DAMPER NOT REQUIRED FOR RETURN INSTALLATION EXCEPT WHERE NOTED.
D. COORDINATE LOCATION OF AIR DEVICES WITH LIGHTS, SPRINKLERS, SPEAKER, SMOKE DETECTORS,
ETC.
EQUIPMENT
A. REFER TO MECHANICAL PLANS FOR SPECIFICATIONS OF HVAC EQUIPMENT.
B. ALL NEW EQUIPMENT SHALL BE EQUIVALENT TO THE SPECIFIED ITEM. ANY ACCOMMODATIONS FOR
ALTERNATE MANUFACTURERS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
C. NEW PLATFORM EQUIPMENT SHALL HAVE VIBRATION ISOLATION MOST SUITABLE FOR THE
APPLICATION.
D. ALL EQUIPMENT SHALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS.
E. COORDINATE UNIT LOCATION WITH LANDLORD AND SITE CONDITIONS.
F. GAS PIPING SHALL BE SCHEDULE 40 (ASTM-A120) BLACK STEEL WITH 300 lb. MALLEABLE IRON BANDED
SCREWED OR WELD PATTERN FITTINGS AS APPLICABLE.
G. ALL PIPING AND FITTINGS LOCATED OUTDOORS AND ABOVE GRADE SHALL BE CLEANED FREE OF
RUST AND PAINTED. ALL FITTINGS TO BE MADE WITH PIPE JOINT COMPOUND. TEFLON TAPE NOT
ALLOWED.
H. ROOF CURBS BY CONTRACTOR.
CONTROLS
A. PROVIDE CONTROLS AS SPECIFIED. SPECIAL CONTROL METHODS WILL BE ADDRESSED ON AN
INDIVIDUAL BASIS.
B. THE CONTRACTOR SHALL PROVIDE ALL 24V WIRING INCLUDING CONNECTIONS, CHECK, TEST AND
START-UP.
C. CONTRACTOR SHALL SUPPLY AND PROGRAM CONTROLS TO SATISFY THE ENERGY CODE REQUIRED
BY THE LOACAL ENERGY CODE. A 5F DEADBAND SHALL BE PROGRAMMED WITH CAPABILITY OF 55F
HEATING AND 85 COOLING SETBACK TMEPERATURES. CONTROLS SHALL ALSO HAVE AN ACCESIBLE
2 HOUR OCCUPANT OVERRIDE.

1.
2.

LITTLE CAESAR

1.

ROOFTOP HVAC UNIT (RTU) SCHEDULE

HVAC GENERAL NOTES

MECHANICAL SPECIFICATIONS

MECHANICAL NOTES
AND SCHEDULES
GREASE DUCT VELOCITY CALCULATIONS

A12179
11 . JUNE . 2012

MAIN DUCT (HOOD 1)


REQUIRED AIR FLOW:
DUCT SIZE:
DUCT VELOCITY:

AS NOTED

1380 CFM
10" X 12" = 120 IN = 0.83 FT
1380 CFM / 0.83 FT =
1662.65 FEET PER MINUTE

JA
CC

M-2