You are on page 1of 1

N

2BED UNIT

2BED UNIT
2BED UNIT

2BED UNIT

MAXIMUM DEMAND ( AT 0.8 DIVERSITY) = 549.176KWTOTAL CONNECTED LOAD=

686.467KW

REVISION

THREE STOREY TOWN HOUSE PROJECT


AT CANTONMENT, GHANA

600A TP
MCCB
N/A
100A
TP
MCCB
50 KA

LV PANEL- FORM 4

225A
TP
MCCB
50 KA

100A
TP
MCCB
50 KA

225A
TP
MCCB
50 KA
1600A TP&N+E
CU BUSBAR RATING

100A
TP
MCCB
50 KA

100A
TP
MCCB
50 KA

100A
TP
MCCB
50 KA

225A
TP
MCCB
50 KA

225A
TP
MCCB
50 KA

100A
TP
MCCB
50 KA

REF

55KA SCC FOR 3SECONDS

40A
TP
MCCB
35 KA

40A
TP
MCCB
35 KA

600A
TP
MCCB
25 KA

AMMETERS WITH
A
A
A
MAXIMUM DEMAND INDICATORS

TO L.V TRIP
Q1

TO H.V TRIP
VOLTMETER WITH
SELECTOR SWITCH

40A
TP
MCCB
35KA

REF

AMMETERS WITH A A A
MAXIMUM DEMAND INDICATORS

BATTERY &CHARGER UNIT

40A
SP
MCCB
35 KA

1600A TP & N+E CU BUSBAR RATING

FROM 30V DC SUPPLY

6A

40A
TP
MCCB
35 KA

--------

0-500V
V

6A

20A

1600A, TP,FULLY
DRAWOUT,SPRING CHARGED,
MOTORISED ACB WITH 30V DC SHUNT
TRIP WITH ADJUSTABLE OVER LOAD
AND SHORT CIRCUIT PROTECTION

S/S

6A

20A BUSBAR MOUNTED FUSE

1600A 4P FULLY
TO L.V TRIP
DRAWOUT,SPRING CHARGED,
MOTORISED ACB WITH 30V DC SHUNT
TRIP WITH ADJUSTABLE OVER LOAD
AND SHORT CIRCUIT PROTECTION

4P Electromechanical
interlock with ATS
Q2

20A

0-500V

2A

S/S

TO H.V TRIP

VOLTMETER WITH
SELECTOR SWITCH

200 kVAR @ MULTI-STEP


CAPACITOR BANK

1000KVA
TRANSFORMER
DRY TYPE

P.O. Box : 114535,Dubai ,U.A.E.


Tel. : +971 4 2662650, Fax : +971 4 2662680,
E-mail : blazemiddleeast@gmail.com
Website : www.blazeengineeringme.com

G
1000 KVA
EM-GENERATOR

SINGLE LINE DIAGRAM


LVP - VILLA

P002-EP-09