Table 235-2
Horizontal Clearances Between Line Conductors
Smaller Than A WG No.2 at Supports, Based on Sags
(See also Rule 235Blb.)
Sag (mm)
Voltage
between
conductors
(kV)
915
1220
1830
2440
3050
4570
6095
But
not
less
than 1
300
2.4
375
520
730
890
1025
1300
1525
4.16
390
535
745
905
1040
1315
1540
300
12.47
450
595
805
965
1100
1375
1605
345
13.2
455
605
810
970
1105
1385
1610
350
13.8
460
605
815
975
1110
1385
1615
355
14.4
465
610
820
980
1115
1390
1620
365
24.94
545
695
900
1060
1195
1475
1700
470
34.5
620
765
975
1135
1270
1545
1775
570
46
705
855
1060
1220
1355
1635
1860
685
Voltage
between
conductors
(kV)
36
48
72
96
120
180
240
But
not
less
than l
14.7
20.5
28.7
35.0
40.3
51.2
60.1
12.0
4.16
15.3
21.1
29.3
35.6
40.9
51.8
60.7
12.0
12.47
17.7
23.5
31.7
38.0
43.3
54.2
63.1
13.5
13.2
18.0
23.8
32.0
38.3
43.6
54.5
63.4
13.8
13.8
18.1
23.9
32.1
38.4
43.7
54.6
63.5
14.0
14.4
18.3
24.1
32.3
38.6
43.9
54.8
63.7
14.3
24.94
21.5
27.3
35.5
41.8
47.1
58.0
66.9
18.5
34.5
24.4
30.2
38.4
44.7
50.0
60.9
69.8
22.4
46
27.8
33.6
41.8
48.1
53.4
64.3
73.2
26.9
1 Clearance
117