PART 2. SAFETY RULES FOR OVERHEAD LINES

235B 1b(l)

m
Table 235-2
Horizontal Clearances Between Line Conductors
Smaller Than A WG No.2 at Supports, Based on Sags
(See also Rule 235Blb.)
Sag (mm)
Voltage
between
conductors
(kV)

915

1220

1830

2440

3050

4570

6095

But
not
less
than 1

300

Horizontal clearance (mm)

2.4

375

520

730

890

1025

1300

1525

4.16

390

535

745

905

1040

1315

1540

300

12.47

450

595

805

965

1100

1375

1605

345

13.2

455

605

810

970

1105

1385

1610

350

13.8

460

605

815

975

1110

1385

1615

355

14.4

465

610

820

980

1115

1390

1620

365

24.94

545

695

900

1060

1195

1475

1700

470

34.5

620

765

975

1135

1270

1545

1775

570

46

705

855

1060

1220

1355

1635

1860

685

Clearance determined by Table 235-1, Rule 235B 1a.

NOTE: Clearance = 7.6 (kV) + 20.4

Js - 610, where S is the sag in millimeters.


in
Table 235-2
Horizontal Clearances Between Line Conductors
Smaller Than A WG No.2 at Supports, Based on Sags
(See also Rule 235Blb.)
Sag (in)

Voltage
between
conductors
(kV)

36

48

72

96

120

180

240

But
not
less
than l

Horizontal clearance (in)


2.4

14.7

20.5

28.7

35.0

40.3

51.2

60.1

12.0

4.16

15.3

21.1

29.3

35.6

40.9

51.8

60.7

12.0

12.47

17.7

23.5

31.7

38.0

43.3

54.2

63.1

13.5

13.2

18.0

23.8

32.0

38.3

43.6

54.5

63.4

13.8

13.8

18.1

23.9

32.1

38.4

43.7

54.6

63.5

14.0

14.4

18.3

24.1

32.3

38.6

43.9

54.8

63.7

14.3

24.94

21.5

27.3

35.5

41.8

47.1

58.0

66.9

18.5

34.5

24.4

30.2

38.4

44.7

50.0

60.9

69.8

22.4

46

27.8

33.6

41.8

48.1

53.4

64.3

73.2

26.9

1 Clearance

determined by Table 235-1, Rule 235B 1a.

NOTE: Clearance =0.3 (kV) + 4.04

Js - 24, where S is the sag in inches.