You are on page 1of 66

Installation and Operations Guide

VLD

Honeywell

LTBT-TM-VLDIOG Rev. 0002

Important safety information and installation


precautions
Read all instructions
Failure to follow all instructions may result in equipment damage or a hazardous condition. Read all instructions
carefully before installing equipment.

Local codes and practices


Always install equipment in accordance with the National Electric Code and in a manner acceptable to the local
authority having jurisdiction.

Electrostatic sensitivity
This product and its components may be susceptible to electrostatic discharge (ESD). Use appropriate ESD
grounding techniques while handling the product. When possible, always handle the product by its non-electrical
components.

High voltage safety test


Experienced electricians, at first contact, always assume that hazardous voltages may exist in any wiring
system. A safety check using a known, reliable voltage measurement or detection device should be made
immediately before starting work and when work resumes.

Lightning and high-voltage danger

Most electrical injuries involving low-voltage wiring result from sudden, unexpected high voltages on normally
low-voltage wiring. Low-voltage wiring can carry hazardous high voltages under unsafe conditions. Never install
or connect wiring or equipment during electrical storms. Improperly protected wiring can carry a fatal lightning
surge for many miles. All outdoor wiring must be equipped with properly grounded and listed signal circuit
protectors, which must be installed in compliance with local, applicable codes. Never install wiring or equipment
while standing in water.

Wiring and equipment separations


All wiring and controllers must be installed to minimize the possibility of accidental contact with other potentially
hazardous and disruptive power and lighting wiring. Never place 24VAC or communications wiring near other
bare power wires, lightning rods, antennas, transformers, or steam or hot water pipes. Never place wire in any
conduit, box, channel, duct or other enclosure containing power or lighting circuits of any type. Always provide
adequate separation of communications wiring and other electrical wiring according to code. Keep wiring and
controllers at least six feet from large inductive loads (power distribution panels, lighting ballasts, motors, etc.).
Failure to follow these guidelines can introduce electrical interference and cause the system to operate
erratically.

Warning
This equipment has been tested and found to comply with the limits for a class A digital device, pursuant to part
15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his own expense.
2009 Honeywell. All Rights Reserved.
6670 185th AVE NE
Redmond, WA 98052 USA
Phone: (425)869-8400 FAX: (425)869-8445
Web Site: www.alerton.com
All information in this document is provided as is without warranty of any kind. Honeywell reserves the right to
change any information herein without prior notice. No guarantees are given as to the accuracy of information.
Trademarks and trade names may be used in this document to refer to either the entities claiming the marks and
names or their products. Alerton, BACtalk, and their logos are registered trademarks and VisualLogic is a
trademark of Honeywell. Honeywell disclaims any proprietary interest in trademarks and trade names other than
its own.

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Contents

Contents
About VLD
About this document and related publications
VLD dimensions
Mounting guidelines
Installing the wallplate
Wiring the wallplate
Mounting the VLD
Adjusting the date and time
Setting the MAC address and device instance
Identifying terminals and terminating wire
Using terminal blocks
Power supply guidelines and requirements
VLD power ratings
Selecting a transformer
Power supply grounding and wiring
Backup Power
MS/TP LAN configuration
Operational overview
Screen elements
Common features
Setpoint mode
Occupancy mode
Hotel mode
Installer Setup (ISU) Mode
Field Service Mode
Appendix A: BACnet object and property reference
VLD objects
Object properties
Standard AVs and BVs
UI control AVs and BVs
Appendix B: Custom display configuration
Basic controls
Upper left controls
Upper right controls
Lower left controls
Lower right controls
Pre-defined display items
Key/BV-assignments
Custom screen supported characters
Appendix C: Ordered List of Control Points
Appendix D: Quick Reference

Honeywell

LTBT-TM-VLDIOG Rev. 0002

4
5
6
7
7
8
9
9
9
12
13
14
14
14
14
15
15
20
20
21
26
27
30
31
33
36
36
38
42
46
57
57
57
57
58
59
60
61
62
63
66

Installation and Operations Guide | VLD

About VLD
Alerton VisualLogic Display (VLD) is a communicating sensor/controller with
built-in humidity sensor and optional wireless capability. It combines the
functionality of a VisualLogic Controller (VLC) with a programmable user
interface display.
Electrical inputs and outputs wire directly to field equipment, and the control
sequence is programmable using Envision for BACtalks direct digital control
(DDC) language, VisualLogic. DDC is programmed and downloaded to the
controller using an Envision for BACtalk operator workstation.
Operational information and control data is available to other building
controllers and systems through the BACnet protocol (ANSI/ASHRAE
standard). This enables a VLD to share data and execute commands initiated
from other BACnet-compliant devices.

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | About this document and related publications

About this document and related publications


This document provides information about installing and wiring a VLD to
equipment, power, and communication channels. It also shows how to operate
the user interface.
I MP O R TA N T Always install equipment in accordance with the National
Electric Code and in a manner acceptable to the local authority having
jurisdiction (AHJ). No guidelines, instructions, installation practices, or other
information presented in this guide may be interpreted to supersede or modify
the local codes and practices of the AHJ.
Ta bl e 1

Other documentation related to BACtalk VLDs

Document (ID)

Contains

VLD Installation Instructions


(LTBT-TM-VLDINST)

Instructions for mounting and wiring the


backplate and for mounting the VLD on
the backplate. A printed copy ships with
each unit.

Data Sheet

Single-sheet summary of applications,


capabilities, and configuration.

(LTBT-VLD)
Wireless Occupancy Kit
Installation Instructions

Instructions for installing the optional


occupancy kit (AL-OC-KIT)

(LTBT-OC-INST)
Programmers Guide &
Reference for BACtalk
Systems
(LTBT-TM-PRGRMR)

Honeywell

Information and instructions for


programming DDC sequences for VLDs,
setting up I/Os in software, and
programming data displays to command
data.

LTBT-TM-VLDIOG Rev. 0002

Installation and Operations Guide | VLD

VLD dimensions
The VLD consists of a mounting plate and a circuit board with a plastic cover.
See the VLD Installation Instructions (LTBT-TM-VLDINST) for precise
dimensions.

Figure 1

VLD dimensions

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Mounting guidelines

Mounting guidelines
The VLD is designed to be wall-mounted indoors, with dimensions ideal for
mounting to a single-gang electrical box.
Mount in a clean, dry location away from windows, air ducts, and other places
where environmental factors may affect temperature and humidity readings. If
you mount the VLD on the interior of an outside wall, thoroughly insulate so
outside air behind the sensor doesnt affect the sensor reading.
To meet requirements of the Americans with Disabilities Act, mount no higher
than 48" from the floor and with a minimum clear floor space of 30" X 48" (760
X 1220 mm).
CAUTION Thoroughly read all instructions before mounting and wiring.

Always install equipment in accordance with applicable electric codes and the
instructions.

Installing the wallplate


The VLD can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6
mm x 50.8 mm) wiring box.
X To install the wallplate
1. Position and level the wallplate (for appearance only).
2. Use a pencil to mark the mounting holes.

Figure 2

Wallplate dimensions

3. Remove the wallplate from the wall and, if drywall, drill two 3/16-in.
holes in the wall, as marked. For firmer material such as plaster, drill
Honeywell

LTBT-TM-VLDIOG Rev. 0002

Installation and Operations Guide | VLD

two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes
until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring
opening.
5. Insert the mounting screws into the holes and tighten.

Wiring the wallplate


CAUTION Disconnect power before wiring. Failure to do so may result in

electrical shock or equipment damage.


X To wire the wallplate
1. Connect wires to the terminal block using Figure 3 as a guide. Note that
VLD does not have COM connections. All grounds are tied together.

Figure 3

VLD terminal assignments and pin numbers

2. Securely tighten each screw.


3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to prevent drafts from
affecting the VLD.
N o t e A jumper is pre-installed between pins 1 and 2 (24 VAC and

Relay 24 VAC). This supplies 24 VAC to BO 1, BO 3, and BO 4. It can


be removed if you want to power these inputs from a separate power
supply.

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Mounting guidelines

Mounting the VLD


To mount the VLD, align the terminal screw blocks with the pins on the back of
the VLD and push the VLD faceplate straight onto the wallplate.

Figure 4

VLD faceplate mounting

Adjusting the date and time


X To adjust the time
1. Press the CLOCK key.
2. Use the arrows to adjust the year, month, and day.
3. Press DONE.
4. Adjust the time and press DONE.

Setting the MAC address and device instance


The factory default MAC address is 0. Valid MAC addresses are 1-127. The
default device instance is 0009999. Valid device instances are 0-4194303.
Note The device instance can also be set using BACtalk operator workstation

software.
X To set the MAC address and device instance at the display
1. From the home screen, press the SYSTEM block area (block may not
be visible, see Figure 5).
Blank touch keys appear at the bottom of the screen.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

Installation and Operations Guide | VLD

2. Press and hold the two blank keys on either side of the center key for
approximately five seconds.

Figure 5

Entering ISU mode

The Installer Setup (ISU) screen appears. An ISU code is displayed in


the lower left. It is a four-digit code beginning with zero. The current
setting is displayed in the lower right.

Figure 6

ISU screen

3. Use the down arrow to advance to ISU code 800.


4. Use the up and down arrows to set ISU code 800 (MAC address) to a
value between 0 and 127.
5. Set ISU code 801 (first digit of device instance) to a value between 0
and 4.
N o t e The device instance is set by entering values in four separate
ISU codes. See example on page page 11.

10

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Mounting guidelines

6. Set ISU code 802 (second and third digits of device instance) to a value
between 00 and 99.
7. Set ISU code 803 (fourth and fifth digits of device instance) to a value
between 00 and 99.
8. Set ISU code 804 (sixth and seventh digits of device instance) to a value
between 0 and 99.
9. Press Done to exit Installer Setup.
For example, if you want to set the MAC address to 15 and the device
instance to 1876, you would use these settings:
ISU code 800=15
ISU code 801=0
ISU code 802=00
ISU code 803=18
ISU code 804=76

Honeywell

LTBT-TM-VLDIOG Rev. 0002

11

Installation and Operations Guide | VLD

Identifying terminals and terminating wire


The VLD label identifies wiring terminals by number and function. Terminals
are numbered from top to bottom, beginning with 1 on the upper right side of the
wallplate and continuing top-to-bottom on the right side of the controller. I/O
terminals carry an additional numeric identifier that corresponds to the software
I/O. Use this section to identify terminals on the VLD. See later sections for
more specific instructions, cautions, and recommendations.

Power supply terminals


Two terminals are used to connect the 24VAC power supply to the VLD.

Ground terminals
These terminals are used for terminating the grounded leg of the 24VAC circuit
and the return grounds of AIs, AOs, and BOs.

Universal inputs
Use these terminals (in conjunction with adjacent GND terminals) to connect
universal inputs. Input terminals accept a variety of signal types.

Binary outputs (BOs)


Use these terminals to connect BO loads (ON/OFF control). Terminate the BO
return ground to the panel/enclosure ground or a GND terminal on the VLD.

Analog outputs (AOs)


Use these terminals to connect AO-loads (modulating control). The AO-return
ground must terminate to the nearest GND terminal.

MS/TP LAN communications


Use terminals 11(MS/TP-) and 12 (MS/TP+) to connect the BACnet MS/TP
LAN to the VLD. Polarity must be maintained throughout the entire LAN. See
MS/TP LAN configuration on page 15 for more information.

12

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Identifying terminals and terminating wire

Using terminal blocks


The VLD uses header-style termination blocks to simplify field wiring of power,
communications, and I/Os. Terminal blocks accept wire gage from 1224AWG.
X To terminate wire to a VLD
1. Strip approximately 1/8 of the wire jacket from the end of the wire.
2. Use a small screwdriver (1/8 max) to turn the adjustment screw fully
counter-clockwise. The clamps in the wire slot separate as you turn the
screw.
3. When the clamps in the wire slot are fully open, insert the stripped end
of the wire into it (try to get the jacket flush with the terminal block). If
using stranded wire, be sure to insert all strands into the wire slot. If
terminating multiple wires, trim wires to same length and tightly twist
exposed wire together.
4. Hold the wire in place and turn the adjustment screw clockwise to
tighten it until the clamps in the wire slot secure the wire.
5. Tug gently on the wire to ensure it is secure.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

13

Installation and Operations Guide | VLD

Power supply guidelines and requirements


VLD uses 24VAC power from a UL Listed Class 2 24VAC transformer (not
provided). The VLD uses a half-wave rectifier to convert the AC power supply
to onboard power. This enables multiple VLDs with half-wave power supplies to
be powered from a single, grounded transformer.
CAUTION Half-wave devices and full-wave devices must not use the same AC

transformer. If a VLD will share its power supply with another device, make sure
that the other device utilizes a half-wave rectifier and that polarity of wiring is
maintained. Failure to do so can result in equipment damage.

Figure 7

Internal VLD power wiring schematic, half-wave rectifier

VLD power ratings


The VLD minimum current draw is 24 VAC @50ma leading to ~1.2VA.
The minimum applies when the VLD supports no binary output (BO) loads. If
the VLD supports AOs, the minimum VA rating includes the draw of all
AO-loads energized at maximum rating. The maximum power draw is the
minimum VA rating plus the power draw when all BOs are energized at
maximum capacity.

Selecting a transformer
The safest way to size a transformer is to ensure that the maximum VA load
rating of the VLD is less than 85% of the Nameplate VA rating of the
transformer. Even if all outputs are not presently used, this ensures that each
VLD has sufficient power for future equipment additions.
I MP O R TA N T Transformer sizing should never exceed the maximum UL Class

2 rating.

Power supply grounding and wiring


When connecting power to the VLD, ensure that one leg of the VAC secondary
circuit connects to a known earth ground. Also ensure that the GND terminal on
the VLD connects to the same known earth ground.
Supplying a high-quality ground connection to a VLD and then properly
connecting the VLD to the ground is one of the most important things you can do
to ensure a trouble-free installation.
The 24VAC secondary leads are not interchangeable. Once a lead connects to
the GND terminal on the VLD, it is the grounded lead. Observe and maintain
polarity for subsequent connections. The GND terminal provides a reference
ground for the circuit board and communications wiring. Use 18 AWG cable for
best results.
14

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Power supply guidelines and requirements

WARN ING Ensure that all VLD power, communications, and I/O cabling are

grounded according to these instructions. Failure to follow these instructions


may result in VLD operational and communication failures or equipment
damage.

Power supply wire selection


If you are considering long power supply wiring runs, using the right wire size is
critical. If the wire is too small, the resistance may be too high, resulting in a low
voltage supply to the VLD. This is known as line loss. The wire size is based on
the length of the wire run and the current draw of the VLD. Use Figure 8 to
determine wire size; obtain additional information from the transformer
manufacturer.

Figure 8

VLD wiring recommendations

Backup Power
The VLD features a built-in supercapacitor that will run the on-board clock for
ten days in the event of power loss.

MS/TP LAN configuration


The VLD communicates on the site-wide BACnet system over a twisted-pair
MS/TP LAN, which uses the EIA485 signaling standard. VLDs are master
devices on the MS/TP LAN.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

15

Installation and Operations Guide | VLD

Each VLD employs a high-quality EIA485 transceiver and exerts unit load
on the MS/TP LAN.
Ta bl e 2

MS/TP LAN facts

Transmission speed

9.6, 19.2, 38.4, 76.8Kbps (configured at global


controller).

Layout

Bus.

Cabling

BACnet specifies the following. Shielded, twisted-pair


cabling with characteristic impedance between 100 and
130W. Distributed capacitance between conductors
must be less than 30 pF/foot (100 pF/m). Distributed
capacitance between conductor and shield must be less
than 60 pF/foot (200 pF/m). Foil or braided shield
acceptable.

Segment length

4000 ft. (1071 m.) per segment using recommended


wire.

Maximum devices
overall

Depends on classification of devices as master or slave.


Maximum number of master devices is 128. Maximum
number of slave devices or devices overall (mixed
master and slave) is 255. This includes VLDs, BACtalk
global controllers (all are considered masters) and any
other devices, regardless of their relative unit loads.

Maximum devices
per segment

Depends on relative unit load of devices (see


Terminating MS/TP LAN cabling on page 16).

Repeaters

Required when making runs longer than 4000 ft. Three


repeaters maximum between any two devices.

Terminating
resistors

Matched resistors required at each end of segment bus


wired across (+) and (). Use matched precision
resistors rated W 1% / 80 - 130 Ohms.

Shield grounding

Ground shield drain wire at single point earth (panel)


ground, not VLD ground. Tape off shield drain wire at
other end. Tie shield drain wire through at each VLD.

Terminating MS/TP LAN cabling


MS/TP terminations are located on the lower left of the VLD wallplate.
Maintain polarity of the MS/TP wire run throughout the MS/TP LAN.
Note Basic information about MS/TP terminations at the VLD are provided

here. See the BACtalk System Design Guide (LTBT-TM-SYSDSGN) for more
detailed information and limitations with respect to MS/TP LANs distance
requirements, unit loads, repeater architectures, etc.

MS/TP shield grounding


Proper shield grounding of the MS/TP cabling can help minimize the risk of
communications problems and damage to equipment because of transient
voltage spikes (for example, lightning strikes).

16

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Power supply guidelines and requirements

Follow these guidelines for grounding MS/TP cable shields:


Each MS/TP segment should have a single point of shield ground,
preferably as close to the middle of the cabling run as possible (see
Figure 9).
Do not ground the MS/TP shield using a VLD terminal.
Never ground both ends of a shield because differences in potential
between the grounds may induce current on the shield, causing
interference.
At connecting points of termination, tie the shield through with a wire
nut.
At ungrounded, exposed shield points (the end of a segment), tape back
the shield to the wire jacket or, for optimum transient shunting, use
100V gas discharge tubes or 120V MOVs between the shield and
ground. See Figure 9.

Figure 9

Honeywell

TMS/TP shield drain termination and tie through

LTBT-TM-VLDIOG Rev. 0002

17

Installation and Operations Guide | VLD

Terminating resistors
At the last device on each end of the MS/TP segment, matched terminating
resistors wired across Data + and Data are required for signal integrity (see
Figure 10).
Optimum segment performance typically requires tuning, a process by which
the value of the terminating resistors is selected based on the wave form of
signals on the segment. View wave forms using an industrial scope meter. The
goal is to have as square a wave form as possible with an amplitude greater than
200 mV. Resistors affect the wave form as follows:
When the resistance value decreases, the amplitude of the wave form
decreases and becomes more square.
When the resistance value increases, the amplitude of the wave form
increases and becomes less square.
Typically, precision resistors in the range 80-130 Ohms (+1%) yield acceptable
results. Ideally, the value of the terminating resistors should match the rated
characteristic impedance of the installed cable. For example, if the installed
MS/TP cable has a listed characteristic impedance of 100 Ohm, install 100 Ohm
matched precision resistors.
CAUTION Do not mismatch terminating resistors. Ensure that both resistors

on a segment have the same value.


Note In figure 2.6, White is Data - and Black is Data +.

Figure 10

Terminating resistor detail

Real-time operating code (ROC) file


VLD has downloadable software called real-time operating code (ROC file). The
ROC file is the brains of the device and handles the more complex functions of
the VLD (object support, DDC, I/O control, and so on). The ROC file can be
downloaded whenever a software upgrade is necessary. To upgrade the ROC file,
use BACtalk operator workstation software.

ROC file version


When servicing a VLD, communicating with Alerton customer support, or
reading documentation, you may need the firmware version of a VLD. VLD
firmware version information is available in software as the
application-software-version property of the VLD Device object.

18

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Power supply guidelines and requirements

To view the firmware version of a VLD, use BACtalk operator workstation


software to open a display template showing its Device Properties.

VLD
ROC
version

Figure 11

Honeywell

VLD device properties

LTBT-TM-VLDIOG Rev. 0002

19

Installation and Operations Guide | VLD

Operational overview
The VLD operates in one of three modes - Setpoint, Occupancy, or Hotel. While
in one of these modes, a user can enter one of two configuration modes - Installer
Setup or Field Service.
Setpoint mode - interface is similar to the Honeywell VisionPro. See page 26
for details.
Occupancy mode - interface is similar to the Alerton Microset. See page 27
for details.
Hotel mode - a subset of the functionality available in Occupancy mode.
Designed for hospitality applications. See page 30 for details.
Installer Setup utility - configuration mode similar to that of the VisionPro.
See page 31 for details.
Field Service utility - configuration mode similar to the Alerton Microset. See
page 33 for details.
Note All VLD operating logic executes in DDC. Data displays can directly
reference data points in the VLD.

In addition to the standard operating mode screens, a custom screen can be


managed by DDC for additional user feedback or control selection. See Custom
screen on page 25.
These operating modes pertain to user interaction via the touchscreen and
display only. Actual control behavior is determined by the DDC loaded into the
unit. Physical control is separated from the user input controls so that, in case of
conflicting inputs, DDC controls the system. The job engineer is free to choose
the extent of control that will be allowed to users. VLD uses typical Alerton
Microset conventions, which are supported fully in Occupancy mode and to
some extent in Setpoint mode. Because of this, DDC written for VLC/Microset
applications requires few modifications to run properly in a VLD.

Screen elements
The user interface is presented in different screens, which are made up of blocks,
keys, and displays. The elements that appear on a given screen are determined by
the purpose of the screen and by configuration settings. Custom screens can be
created to meet specific needs.
Blocks include the SYSTEM block and the FAN block. Both blocks are on the
left side of the screen. You can set the blocks to be visible or not visible to users.
In addition, the items that appear in the SYSTEM block can be configured as
visible and not visible. Figure 12 shows the blocks.
Keys are areas of the touch screen programmed to respond to touch. Keys have
labels or icons that indicate their functions. Keys are visible only when relevant
the current display screen. Figure 12 shows examples of keys.
Displays provide the user with information about current conditions and
settings. They respond to keys. For example, the inside air temperature
DISPLAY will increment when the up arrow KEY is pressed. Figure 13 shows
examples of displays.
20

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Operational overview

Figure 12 and Figure 13 show the basic features of the user interface.

Figure 12

VLD user interface - blocks and keys (Setpoint mode with heat (one setpoint))

Figure 13

VLD user interface - displays

Common features
This section describes features common to all operating modes (Setpoint,
Occupancy, and Hotel).

SYSTEM block
The SYSTEM block can be used to provide information to the user about the
current control state. The information displayed is controlled by DDC using AVs
and BVs. The user can also be allowed to use this block to select a control state.
User selections are not implemented or displayed unless DDC is programmed to
act on them. See discussion of AV-110 and AV-111.
The SYSTEM block, when made visible, allows a user to select one of five
system functions - EMHEAT, HEAT, OFF, COOL, and AUTO. To select a
function the user presses the SYSTEM block. All of the enabled choices (each of
the five can be configured to appear or not) are shown in the block with the

Honeywell

LTBT-TM-VLDIOG Rev. 0002

21

Installation and Operations Guide | VLD

current function flashing. The user presses the SYSTEM block to cycle through
the choices and presses DONE to save and exit.

SYSTEM block

To enable function selection to affect the screen, set the VLD to Setpoint mode
and use DDC to transfer AV-111 to AV-110.
Note EMHEAT is selectable by the user but has no separate indication on

AV-111 or AV-110. BV-125 provides the indication to the screen when AV-110
indicates 2 (heat) that EMHEAT is to be displayed. When AV-111 is transferred
to AV-110 via DDC, EMHEAT will be shown if enabled. If DDC is controlling
the SYSTEM block via AV-110 independent of AV-111, set BV-125 to Active
and AV-110 to 2 (heat) in order to show EMHEAT in the SYSTEM block.

FAN block
The FAN block can be used to provide information to the user about the current
control state. The information displayed is controlled by DDC using AVs and
BVs. The user can also be allowed to use this block to select a control state. User
selections are not implemented or displayed unless DDC is programmed to act
on them.
Fan control can be enabled (BV-80=1) to allow users control of the fan. When
enabled, the user presses the FAN block to select a fan setting. All enabled
options are displayed and the current setting blinks. Press the FAN block to cycle
through the options. Press DONE to save and the selection.

FAN block

22

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Operational overview

The fan setting can be displayed in one of three formats (selected by AV-137).
AV-137 value

Available settings

OFF
LO
MEd
HI

OFF
1
2
3

0%
33%
66%
100%

DDC can be programmed to display the current fan setting without allowing the
user to change it.

English and metric units


You can set the VLD to display English or metric units based on the selection in
the DDC header file or you can toggle that status in software. The English or
metric setting at the VLD is referred to as the native units mode.
BV69 can be set ON to reverse native units mode for the VLD display. Thus, if
the VLD is set to English, and BV-69 is ON, the VLD displays units in
appropriate metric equivalents. This enables the system to display units at the
VLD according to occupant preference without a programmer having to write
separate DDC sequences around each unit of measure.

Humidity display
If your system includes a humidifier, dehumidifier, or outside humidity sensor,
the inside humidity can be displayed below and to the right of the temperature.
Outside humidity can also be displayed on the MORE screen. To enable outside
humidity display, set BV-101 to 1. If both humidity and OAT are enabled on the
main screen, they will be displayed alternately every few seconds.

Outside air temperature (OAT) display


The outside air temperature can be displayed when the user presses MORE from
the main screen. It can also be displayed on the main screen. If both OAT and
humidity are enabled on the main screen, they will be displayed alternately every
few seconds. For OAT read at another unit to display at the VLD, the OAT value
must be written in DDC to the Present Value of AV-103.

Schedule display and editing


If enabled in DDC, a user can view or edit the internal VLD schedule. To deny a
user read permission, set BV-114 to 1. To deny schedule editing permission, set
BV-141 to 1.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

23

Installation and Operations Guide | VLD

LCD backlight operation


BV-79 controls backlight operation. If BV-79 is OFF, the backlight turns ON
when any key is pressed and stays on for 20 seconds after there is no key activity.
If BV-79 is ON, the backlight is ON continuously.

Clock operation
The VLD real-time clock provides time and date for displaying the date and
time, implementing daylight savings settings, and implementing schedules. If
AC power is lost, a supercapacitor will power the clock for ten days. If the date
and time are lost, the VLD will display the set time and date screens when
powered up.
Note The real-time clock is separate from the CPU time keeping utility. It only

affects the items listed in this section.


Daylight savings (DLS) settings can be controlled by VLD or by BACtalk
operator workstation software. If Installer Setup (ISU) parameter 330 is set to
non-zero, VLD will control DLS settings. If ISU 330 is zero, DLS is controlled
by BACtalk operator workstation software.
The clock accepts time syncs from BACtalk operator workstation software. If
configured in DDC, the date and time can also be set manually using the display.
To deny a user permission to set the clock, set BV-116 to 1.
The last time command, whether from the user screen or BACnet, takes
precedence.
X To adjust the real-time clock
1. Press CLOCK.
2. Use the arrow keys to select a year, month, and day.
3. Press DONE.
4. Select a time.
5. Press DONE.

MORE key navigation


The MORE key allows a programmer to make additional screens available to
users. Enabling the display of one or more of these screens causes the MORE
key to appear on the main screen. The screens that can be made available are:
Outside air temperature
Inside/outside humidity
Custom screen (See Custom screen on page 25)
Humidifier control
Dehumidifier control
Filter
Dehumidifier pad
UV lamp

24

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Operational overview

When the user presses MORE, the first enabled screen appears. Pressing
MORE again displays the next, and so on.

Touchscreen cleaning
If the display screen needs to be cleaned, the user presses SCREEN. The display
will lock for 30 seconds allowing the user to wipe the screen without pressing
any keys. When the display reads 0, press SCREEN to continue cleaning or
DONE to quit. Use a non-abrasive glass cleaner.

Filter, humidifier pad, and UV lamp notifications


Notifications can be set to inform the user that a filter, humidifier pad, or UV
lamp needs to be changed. Notifications can be triggered by an elapsed run time
or by DDC writing to an associated BV. When a notification is ON, a display
alternately flashes the word CHANGE and the name of the item.

Notifications set by timer


Notifications can be set up using the touchscreen in Installer Setup mode (see
Installer Setup (ISU) Mode on page 31).
ISU Code

Description

Allowed Values

500

Filter change
reminder

0 reminder not used


1 10 days
2 30 days
3 60 days
4 90 days
5 120 days
6 365 days

AV-124

510

Humidity pad
change reminder
AV-125

520

UV lamp change
reminder

0 reminder not used


1 90 days
2 180 days
3 365 days
0 reminder not used
1 365 days

AV-126

Notifications set by DDC


Theses notifications can also be forced ON by setting the associated BV to 1.
BV-111 forces the CHANGE FILTER notification.
BV-112 forces the CHANGE UV LAMP notification.
BV-113 forces the CHANGE HUMIDIFIER PAD notification.

Custom screen
You can create a custom screen that displays numbers and text and provides user
touchscreen feedback for DDC to monitor. The custom screen is configured
using the of points listed in Appendix B: Custom display configuration on
page 57.
A user reaches the custom screen by pressing MORE twice from the main
screen.
Honeywell

LTBT-TM-VLDIOG Rev. 0002

25

Installation and Operations Guide | VLD

The VLD screen has digit fields in the upper left, upper right, lower right, and
lower left areas of the screen. Arrows can be displayed next to the upper right,
lower right, and lower left blocks. When any of these three blocks is enabled,
numeric, and editable, VLD will automatically display the arrows and will
process user adjustments to the displayed value. These adjustments are limited
by assigned maximum and minimum values. Each time the user presses an
arrow, the associated value will increment or decrement. The amount of each
increment or decrement can be configured.
If a block is enabled and numeric but not flagged as editable, the arrow keys will
be disabled.
Custom screens support DDC interaction by providing key push feedback in
BVs. A DDC application can take input from a custom screen by watching the
appropriate BVs and taking any desired action. If a block is not flagged as
numeric, the adjustment arrows can still be manually turned on and DDC can
respond to user key pushes to make any desired adjustments.

Setpoint mode
This section describes the functionality unique to Setpoint mode. See also
Common features on page 21.
Setpoint mode is similar to the Honeywell VisionPro interface. It is typically
used for residential applications. The screens in Setpoint mode mimic the
VisionPro, but physical control performed by the VLD depends on the DDC
uploaded to it. A job engineer may program DDC that mimics VisionPro
behavior, or may program other behavior.
The internal schedules contain Wake/Leave/Return/Sleep periods, each with a
definable start time and assignable heating and cooling setpoints. The user is
allowed to temporarily or permanently override the scheduled setpoints.
Note The internal schedule used by this interface is not visible remotely using

BACnet.

When HEAT (AV-110=2) or COOL (AV-110=1) are selected in the SYSTEM


block, only one setpoint is displayed on the main screen. If OFF (AV-110=0) is
selected, no setpoint is displayed.

26

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Operational overview

Schedule configuration in Setpoint mode


VLD can be configured to follow an internal schedule by setting ISU parameter
160 or BV-133.
Schedule Usage

ISU Parameter 160

BV-133

No internal schedule

7-day internal schedule

If the internal schedule is OFF, the user can adjust the setpoint (within setpoint
limits).
Schedules are stored in flash memory so they persist through power cycles.
In setpoint mode, each schedule period consists of a start time, a heating
setpoint, and a cooling setpoint. The maximum number of periods per day is
configured using ISU parameter 540 (AV-129). A value of 2 specifies two
periods per day - Wake and Sleep. A value of 4 specifies 4 periods per day Wake, Leave, Return, and Sleep. The scheduler selects the last valid period start
before the present time as the period to use. Setpoint mode schedules are not
accessible via BACnet. The only way to view, edit and save a schedule is from
the unit LCD screen.

Schedule setpoint overrides in Setpoint mode


An override is created by one of three methods:
Temporary - press an arrow next to a setpoint. The words Hold Temperature
Until appear above the time display, which shows the default ending time (the
beginning of the next schedule transition). Use the arrows to adjust the ending
time. Wait a few seconds. The arrows next to the ending time disappear and the
override takes effect.
Permanent - press HOLD. The words Permanent Hold appear below the
time display and the override takes effect.
Vacation - while in Permanent Hold, press HOLD. The words Hold
Temperature Until appear above the time display. Use the arrows to select the
number of days (1-365) you want the override to last. Wait a few seconds. The
arrows next to the ending time disappear and the override takes effect.
Pressing CANCEL returns the VLD to the current schedule.
The Setpoint mode override status (AV-113 and MV-13), hold until time
(AV 130), and number of vacation days left (AV-130) can be adjusted remotely
using BACnet or by DDC.
A users ability to set Permanent or Vacation holds can be disallowed by setting
BV-115 and BV-130, respectively.

Occupancy mode
This section describes the functionality unique to Occupancy mode. See also
Common features on page 21.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

27

Installation and Operations Guide | VLD

Occupancy mode (AV-123=0) is similar to the Alerton VLC/Microset interface.


In occupancy mode, the VLD can operate in the Occupied or the Unoccupied
state. In addition, an optional after-hours override can temporarily over-ride the
Unoccupied state.
Occupancy mode emulates the user interface and behavior of the Alerton
VLC/Microset setup. It is typically used in office and commercial buildings. The
internal schedule determines the times that the space will be considered occupied
or unoccupied. While occupied, the unit controls to a user-adjustable setpoint.
While unoccupied, the unit controls to unoccupied setpoints determined by the
building engineer. The internal schedule is visible using BACnet and can be
saved and downloaded from the operator workstation. The user is allowed to
override occupied setpoints in a manner similar to the Alerton VLC/Microset
setup.
The internal schedule can be disabled to allow a BACnet global controller to
control the VLD.

Occupied state
In the Occupied state (BV-67=1), the LCD displays the occupant-selected space
temperature setpoint (AV-90). The unit controls to occupied heating and cooling
setpoints (derived by subtracting and adding heating and cooling offsets from/to
the space temperature setpoint.).
The occupant can adjust the setpoint using the arrows (within minimum and
maximum setpoint limits).

28

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Operational overview

Unoccupied state
In the Unoccupied state (BV-67=OFF), the LCD displays the word OFF and the
VLD controls to unoccupied setpoints.

The OFF display will alternate with the time display (if enabled) every few
seconds. The Unoccupied setpoints can be displayed on the Unoccupied screen
by setting BV-105 to ON.

After-hours override
After-hours override enables a user to override a scheduled unoccupied status.
Pressing an arrow next to the OFF display will start an after-hours override.

In override, VLD calculates current setpoints (AV-99 and AV-100) using


occupied setpoint logic. The user can change the timer in half-hour increments
and adjust the setpoint and fan speed (if enabled).
The after-hours timer (AV-98) automatically counts down whenever it is set to a
non-zero value.
To disable this feature, set the after-hours timer limit (AV-97) to zero.

Schedule configuration in Occupancy mode


VLD can be configured to follow an internal schedule by setting ISU parameter
160 or BV-133. If the internal schedule is OFF, VLD follows the schedule sent

Honeywell

LTBT-TM-VLDIOG Rev. 0002

29

Installation and Operations Guide | VLD

by a BACnet global controller. Schedules are stored in flash memory so they


persist through power cycles.
Schedule Usage

ISU Parameter 160

BV-133

No internal schedule

7-day internal schedule

In occupancy mode the internal schedule is formatted as a BACnet schedule


object with one weekly schedule (7days, 4 commands per day). The maximum
number of periods per day is always 4. Each command consists of a start time
and an occupancy command (0=OFF, 1=ON). For a list of supported BACnet
properties associated with the schedule object, see Schedule object properties
on page 41.
To enable the internal schedule, set ISU parameter 160 (BV-133) to 4. Once
enabled, the schedule will write occupancy status to BV-40, priority 16. The
internal schedule can be overridden by sending schedule commands from a
global controller to BV-40, priority 9, or by the operator using BV-40, priority 8.
(This assumes that unit DDC transfers BV-40 to BV-64 as the occupancy
indicator.)
To select the number of program periods per day for the internal schedule, set
ISU parameter 540 (AV-129) to 2 or 4.
To edit the internal schedule in Envision for BACtalk, use the Raw Schedule
Editor (Tools>Advanced>Schedules). Note that you cannot use the Envision for
BACtalk Schedule Wizard to edit the VLD internal schedule.
To edit the internal schedule at the VLD display screen, press SCHED and then
press EDIT.

Setpoint adjustment in Occupancy mode


Within limits, a user can adjust a setpoint by pressing the arrows next to a
setpoint display. The maximum and minimum temperatures the user can select
are defined by AV-91 (Setpoint High Limit) and AV-92 (Setpoint Low Limit).

Hotel mode
Hotel mode is a subset of the functionality available in Occupancy mode. It is
intended for use in hospitality installations.
Hotel mode emulates the user interface and behavior of the Alerton
VLC/Microset setup.

Hotel mode states


In Hotel mode, the VLD operates in one of three states - Rented, Standby, or
Vacant.

Rented
In the Rented state (BV-64=1), a user can change the setpoint and display units
(Fahrenheit/Celsius). User access to fan controls is optionally selected by the
building system operator. In addition, the unit can be programmed to display
inside and outside air temperatures, time, and day of week.
30

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Operational overview

In the Rented state, the MORE key is programmed to toggle the display between
Fahrenheit and Celsius units. The MORE key is blank to accommodate an F/C
decal, which is supplied with the VLD and can be affixed over the MORE key.

Standby
The Standby state (BV-131=1) occurs when a room is rented but DDC senses
that the room is unoccupied. This state is typically used to relax setpoints while
nobody is in the room. In Standby, the display shows only the inside air
temperature. When motion is detected, the display reverts to the Rented state.
The VLD requires infrared sensors, door switches, and additional DDC to detect
room occupancy.
DDC can indicate this state to the VLD user interface by setting BV 131 to
Active.
A user should never see the screen in a Standby state. If they do, occupancy
detection is not working properly. If a user does see this screen, pressing any key
returns the unit to rented mode for two minutes.

Vacant
When a room is vacant (BV-64=0), the VLD displays only the inside air
temperature and the word OFF.
In the Vacant state, DDC will usually control to unoccupied setpoints. A
housekeeping override is provided to allow reverting to Rented setpoints for up
to 99 minutes. During a housekeeping override, the number of minutes
remaining in the override are displayed instead of time of day. The override can
be cancelled by adjusting the override minutes to 0. During housekeeping
override the user has the same control over setpoint as in the Rented state.
Vacant mode allows technicians to access the Field service and Installer setup
screens using the standard access procedures. Note that a PIN security option can
be enabled to restrict access to these screens. The SCREEN key is displayed and
allows cleaning of the screen in while in Vacant mode.

Installer Setup (ISU) Mode


Installer setup mode provides access to functions specific to installation of a
VLD. Some VLD configuration parameters can be altered from the ISU
(Installer Setup) screens. The ISU parameters are identified by the same numbers
used in Honeywells VisionPro and the meaning of the values of the ISU
parameters can be cryptic. The ISU parameters can also be accessed via BACnet.
Installer Setup capability closely emulates that of the Honeywell VisionPro. The
codes use the same numbering, but new codes have been added for the MAC
address and device instance.
You can require a PIN to access ISU mode by setting AV-133 to a non-zero,
four-digit number.
X To access the ISU screens
1. From the home screen, press the SYSTEM block.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

31

Installation and Operations Guide | VLD

2. Five blank touch keys appear on the bottom of the screen between the
Done and Cancel keys. Press and hold the two blank keys on either side
of the center key for approximately five seconds.
3. If a PIN code is required, use the top arrows to select the first two digits
of the code and the bottom arrows to select the third and fourth digits of
the code, and then press DONE.
The ISU screen appears.
4. Use the arrows to select parameters and values.
5. Press DONE when finished.
Table 3 provides a list of ISU parameters
Ta bl e 3

ISU parameters

ISU
Parameter
Code

Description

Allowed Values

120

Year, first 2 digits

19-21

130

Year, second 2
digits

00-99 (00-54 if ISU 200=21)

140

Month

1-12

150

Day

1-31

160

Schedule format
BV-133

0 not programmable (BV-133=0) 4 7


day programmable (BV-133=1)

280

Backlight control
BV-79

0 on for 20 seconds after keypress


1 low always on, bright after keypress

320

Swap
English/Metric
BV-69

1 show opposite units to specified in


DDC header

330

Daylight saving

0 off; no automatic adjustments


1 pre 2007 scheme
2 2007 and later scheme

AV-127
500

Filter change
reminder
AV-124

510

Hum pad change


reminder
AV-125

520

UV lamp change
reminder

0 reminder not used


1 10 days
2 30 days
3 60 days
4 90 days
5 120 days
6 365 days
0 reminder not used
1 90 days
2 180 days
3 365 days
0 reminder not used
1 365 days

AV-126

32

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Operational overview

Ta bl e 3

ISU parameters

ISU
Parameter
Code

Description

Allowed Values

540

Program periods

2 Wake/Sleep
4 Wake/Leave/Return/Sleep

AV-129
640

Clock format
BV-83

670

Keypad lock
AV-128

12 12 hour (BV-83=0)
24 24 hour (BV-83=1)
0 no lock
1 access temperature settings only
2 fully locked

700

Sensed room
temperature offset
(AV-138)

-4 to +4 degrees F

701

Sensed room
humidity offset
(AV-139)

-5% TO +5%
Humidity cannot be adjusted above 100%
or below 0%.

702

Sensed outside air


temperature offset
(AV-140)

-4 to +4 degrees F

703

Sensed outside
humidity offset
(AV-141)

-5% TO +5%
Humidity cannot be adjusted above 100%
or below 0%.

800

MS/TP MAC

0-127

801

BACnet Device
Instance - first digit

0-4

802

BACnet Device
00-99
Instance second and
third digits

803

BACnet Device
Instance forth and
fifth digits

804

BACnet Device
Instance sixth and
seventh digits

00-99

Field Service Mode


Field service mode enables technicians to query and command key operating
variables in the VLD while at the VLD touchscreen. A technician presses a
particular key sequence at the VLD to enter field service mode. In field service
mode a technician uses the left arrows to scroll through data codes and the right
arrows to change the value associated with a code.
Field Service capability closely emulates that of the VLC/Microset combination.
The standard codes are the same and the user can create customized codes in the
same manner. Dealers who have created customized FS codes can also use those
codes on the VLD.
Honeywell

LTBT-TM-VLDIOG Rev. 0002

33

Installation and Operations Guide | VLD

The lower left of the LCD shows the two-digit data code and the main area
displays the data value. A pre-defined list of data codes is available (see Table 4
on page 34). You can add customized codes to this list and assign data points to
them in the DDC header. See the Programmers Guide and Reference for
BACtalk Systems (LTBT-TM-PRGRMR) for more information.
Note Fixed codes appear with a colon before them. This enables a technician to

distinguish them quickly from custom codes.


The data range in field service mode is 199.9 to 99.9.
You can deny users access to field service mode by setting BV-68 to ON. You
can also require a PIN code in order to enter Field Service mode by setting
AV-132 to the desired PIN number.
Field service mode ends automatically if there is no key activity for five minutes.
X To set field service codes
1. Press SYSTEM.
2. Press and hold the center bottom key (blank) for about five seconds.
3. If a PIN code is required, use the top arrows to select the first two digits
of the code and the bottom arrows to select the third and fourth digits of
the code, and then press DONE.
The field service screen appears.
4. Press the left up or down arrows until the desired code appears.
Field service codes appear in the order shown in Table 4 . After fixed
codes are exhausted, custom codes (if enabled) display in the order
entered in DDC.
5. Press the right up or down arrows to adjust the value associated with the
code.
6. Press the left up or down arrows to accept the change and scroll to a
different code.
7. Press DONE to exit Field Service mode.
Ta bl e 4

34

Field service mode fixed codes.

Code

Data
point

Meaning

:UC

AV-95

Unoccupied cooling setpoint

:UH

AV-96

Unoccupied heating setpoint

:CO

AV-93

Cooling offset

:HO

AV-94

Heating offset

:HS

AV-100

Occupied heating setpoint

:CS

AV-99

Occupied cooling setpoint

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Operational overview

Ta bl e 4

Field service mode fixed codes.

Code

Data
point

Meaning

:AL

AV-97

Override limit

:HI

AV-91

Setpoint high limit

:LO

AV-92

Setpoint low limit

:SP

AV-90

Occupant-selected space temperature


setpoint

Checking MS/TP communication


You can check MS/TP communication from the display. The VLD will indicate
if MS/TP packets and headers have been seen, the baud rate, and the MAC
address.
X To check MS/TP communication
1. Enter Field Service mode.
2. Ensure the UC code is displayed.
3. Press the blank key normally labeled MORE (bottom row, second from
right).
4. Press the down arrow.
The MS/TP communication screen appears.

Baud rate

Headers seen

Requests seen
MAC address

5. Press DONE twice to exit.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

35

Installation and Operations Guide | VLD

Appendix A: BACnet object and property reference


This section shows the BACnet objects available in the VLD. The tables that
follow list individual points and give details about the properties of each object
listed.

VLD objects
Object
(instance range)

Remarks

AI-(0-2)

Analog input objects associated with physical,


universal input terminals on VLDs. AIs are identified
as AI-nn, where nn is the input terminal number.

AO-(0-7)

Analog output objects associated with physical output


terminals. AOs are identified as AO-nn, where nn is
the output terminal number.

AV-(90107)

RESERVED AVs for Alerton legacy Microset


behavior.

AV-(0-89)

General use AVs.

AV-(108-136)

Screen control and feedback

AV-(210-233

Custom screen control and feedback

BI (0-2)

Binary input objects associated with physical,


universal input terminals on VLD. BIs are identified
as BI-nn, where nn is the input terminal number.

BO (0-5)

Binary output objects associated with physical output


terminals on VLD. BOs are identified as BO-nn,
where nn is the output terminal number.

BV-(0-63)

General use BVs. BV-40 supports the priority-array


property.
BV-40 is typically used by Alerton DDC applications
to receive scheduled occupancy commands from a
global controller. The priority array allows a BACnet
user to override the occupancy command. When in
Occupancy mode with an internal schedule enabled,
internal schedule commands are written to BV-40
priority 16, therefore DDC applications that use
BV-40 can easily use either internal or external
scheduling.

36

BV-(90-147)

Screen control and feedback

BV-(200-202)

AI-current mode select

BV-(210-299)

Custom screen control and feedback

BV-(300-301)

AO-current mode detection feedback

BV-(400-402)

AI-pullup enables

MV-(0-23)

Multistate values used only for values that will not be


modified by DDC.

Device

Provides general information about a device


LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

Object
(instance range)

Remarks

File (254)

Provides information about the ROC file.

File (0)

Provides information about the current DDC file.

File (2048)

Provides information about the DDC trap file.

Program 254

Firmware program. Entry into boot loader requires


writing password to property
ALERBP_DOWNLOAD_PASSWORD with 1's
complement of the first 10 characters of the firmware
revision.

Program 0

DDC program
The Instance_Of property contains the DDC
rep/job/application/display information
The Reason_For_halt, Description_Of_Halt, and
related properties display any DDC errors.

Honeywell

File 1

DDC trap file

File 240

Legacy method of setting device instance. Has


special security feature

File 254

File object used to do firmware download. Has


special semantics.

File 260

AI-Linearization data. Only writable by halting


associated program object.

File 261

AI-and AO-Calibration data. Only writable by halting


associated program object

Program 260

Allows access to AI-linearization data when halted.


Halting requires writing password to property
ALERBP_DOWNLOAD_PASSWORD with 1's
complement of the first 10 characters of the firmware
revision.

Program 261

Allows access to calibration data when halted.


Halting requires writing password to property
ALERBP_DOWNLOAD_PASSWORD with 1's
complement of the first 10 characters of the firmware
revision.

Schedule 0

Internal schedule used only in Occupancy mode and


only if enabled by BV-133

LTBT-TM-VLDIOG Rev. 0002

37

Installation and Operations Guide | VLD

Object properties
Device object properties
Property

Access Notes

Object Identifier

R/W

Object Name

R/W

Object Type

System Status

OPERATIONAL

Vendor Name

Alerton

Vendor Identifier

18

Model Name

VLD-XXXXXX

Firmware Revision

(comes from boot loader) initially RL 5.00 (build x)

Application Software Version

5.00 (build y) or similar

Location

R/W

Description

R/W

Protocol Version

Protocol Revision

Protocol Services Supported

atomicReadFile, atomicWriteFile, readProperty,


readPropertyMultiple, writeProperty, writePropertyMultiple,
deviceCommunicationsControl, reinitializeDevice, i-Am,
unconfirmedPrivateTransfer, timeSynchronization, who-Has,
who-Is, utcTimeSynchronization

Protocol Object Types


Supported

analog-input, analog-output, analog-value, binary-input,


binary-output, binary-value, device, file, program, schedule

Object List

Too large to return in a single request, so returns segmentation


not supported. Individual array entries can be read.

Max APDU Length Accepted

480

Segmentation Supported

no-segmentation

Local Time

R/W

Default = 00:00:00

Local Date

R/W

Default = Jan 1, 1900"

UTC Offset

R/W

Default = 0

Daylight Savings Status

R/W or
R

Read-only if ISU parameter 330 is set to one of the auto-adjust


options.

APDU Timeout

R/W

Default = 6000, limited to 100..60000

Number of APDU Retries

R/W

Default = 3, limited to 0..16

Max Master

127

Max Info Frames

RW

Default = 3, limited to 1..60

Device Address Binding

Empty List

38

Not writable in VLD

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

AI-object properties
Property

Access

Notes

Object Identifier

Object Name

Object Type

Present Value

R/W

Value handled as described in the sequence of operation

Description

R/W

Read only if configured in DDC header via Visual Logic

Status Flags

All false

Event State

NORMAL

Out Of Service

FALSE

Units

Value set in DDC file via Visual Logic except where noted
otherwise in the sequence of operation

AI nnn

AO-object properties
Property

Access Notes

Object Identifier

Object Name

Object Type

Present Value

R/W

Limit 0.0 .. 102.4

Description

R/W

Read only if configured in DDC header via Visual Logic

Status Flags

Usually no flags set. The out-of-service bit shall be set whenever the point
is configured as such via Visual Logic.

Event State

normal

Out Of Service

Value configured in DDC file via Visual Logic. See below.

Units

Value configured in DDC file via Visual Logic

Priority Array

R/W

Limit 0.0 .. 102.4

Relinquish Default

Value configured in DDC file via Visual Logic

AO-nn

AV-object properties
Property

Access Notes

Object Identifier

Object Name

Object Type

Present Value

R/W

As described below

Description

R/W

Read only if configured in DDC header via Visual Logic

Honeywell

AV-nnn except where noted otherwise

LTBT-TM-VLDIOG Rev. 0002

39

Installation and Operations Guide | VLD

Property

Access Notes

Status Flags

No flags set

Event State

Normal

Out Of Service

FALSE

Units

As described below

BI object properties
Property

Access Notes

Object Identifier

Object Name

BI nnn

Object Type

BINARY INPUT

Present Value

As described in the sequence of operation

Description

R/W

Read only if configured in DDC header via VisualLogic

Status Flags

All false

Event State

NORMAL

Out Of Service

FALSE

Polarity

NORMAL

BO object properties
Property

Access Default location and value

Object Identifier

Object Name

BO nn

Object Type

BINARY OUTPUT

Present Value

R/W

See sequence of operation below

Description

R/W

Read only if configured in DDC header via Visual Logic

Status Flags

Usually no flags set. The out-of-service bit shall be set whenever the
point is configured as such via Visual Logic.

Event State

normal

Out Of Service

Selectable in DDC header

Polarity

NORMAL

Priority Array

R/W

RAM

Relinquish Default

Selectable in DDC header

40

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

BV-object properties
Property

Access Notes

Object Identifier

Object Name

Object Type

Present Value

R/W

As described below

Description

R/W

Read only if configured in DDC header via Visual Logic

Status Flags

No flags set

Event State

NORMAL

Out Of Service

FALSE

Priority Array

R/W

BV-40 only

Relinquish Default

R/W

BV-40 only

BV-nnn for most BVs, except where otherwise noted

MV-object properties
Property

Access Notes

Out of Service

False

Event State

Normal

Status Flag

NO flags set

Object Name

MV-nnn except where otherwise noted

Description

R.W

State Text

As described below

Present Value

As described below

Number of States

Object ID

Schedule object properties


Property

Access Notes

Object Identifier

R/O

SCHEDULE 0

Object Name

R/O

Schedule 0

Object Type

R/O

SCHEDULE

Present_Value

R/O

Description

R/O

Main Schedule

Effective_Period

R/O

ANYTIME (always in effect)

Weekly_Schedule

R/W

7 days, 4 events per day maximum

Schedule_Default

R/W

Inactive (enum 0)

List_Of_Object_Property_References R/O

Honeywell

Empty

LTBT-TM-VLDIOG Rev. 0002

41

Installation and Operations Guide | VLD

Property

Access Notes

Priority_For_Writing

R/O

16

Status_Flags

R/O

All bits clear

Reliability

R/O

NO FAULT DETECTED

Out_Of_Service

R/O

FALSE

Standard AVs and BVs


This section lists the logical points in the VLD. Points with access type of R/O are computed
by the VLD and provided as inputs to the user application. Points with access type R/W are
written by the user application or via BACnet in order to provide information to the VLD.

Legacy (Microset) AVs


The following AVs function in a fashion substantially similar to the same AVs in a Microset.
Point

Object_Name

Units

Access Notes

AV-90

Setpoint (SP)

Deg F/C

R/W

AV-91

Setpoint High Limit

Deg F/C

R/W

AV-92

Setpoint Low Limit

Deg F/C

R/W

AV-93

Cooling SP Offset

Deg F/C

R/W

AV93 + AV94 represents the deadband


surrounding the setpoint AV-90

AV-94

Heating SP Offset

Deg F/C

R/W

AV93 + AV94 represents the deadband


surrounding the setpoint AV-90

AV-95

Unoccupied Cooling SP

Deg F/C

R/W

Cooling setpoint in unoccupied mode

AV-96

Unoccupied Heating SP

Deg F/C

R/W

Heating setpoint in unoccupied mode

AV-97

After Hours Timer Limit

Hours

R/W

Maximum value of AV98

AV-98

After Hours Timer

Hours

R/W

Current after hours timer

This is the user-specified setpoint in


occupancy mode

Set to 0.0 if not in occupancy mode or


if not in tenant override mode.
Value reverts to 0.0 in case of power
failure.
AV-99

Current Cooling SP

Deg F/C

R/O

Occupancy mode:
BV67 ON:
AV108 + AV106
BV67 OFF:
AV108

Setpoint mode:
AV108 + AV106

42

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

Point

Object_Name

Units

Access Notes

AV-100

Current Heating SP

Deg F/C

R/O

Occupancy mode:
BV67 ON:
AV109 - AV106
BV67 OFF:
AV109

Setpoint mode:
AV109 - AV106
AV-101

Displayed Room
Temperature

Deg F/C

R/W

Temperature displayed on the screen.


Sensed Room Temperature (AV-104)
adjusted by Room Temperature Offset
(AV-138).

AV-102

Displayed Room
Humidity

%RH

R/O

Space humidity displayed on the


screen. Sensed Room Humidity
(AV-105) adjusted by Room Humidity
Offset (AV-139).

AV-103

Displayed Outside Air


Temperature

Deg F/C

R/W

Outside air temperature to display on


screen. Sensed Outside Air
Temperature plus Outside Air
Temperature Offset (AV-140). For
proper screen display, units should
match native units in DDC header.

AV-104

Sensed Room
Temperature

Deg F/C

R/O

Room temperature reading from


on-board sensors. Usually transferred
to AV-101.

AV-105

Sensed Room Humidity

%RH

R/O

Room humidity reading from on-board


sensor. Usually transferred to AV-102.

AV-106

Demand Offset

Deg F/C

R/W

See AV-99 and AV-100. Can be used


by DDC to relax setpoints when energy
use is heavy.

AV-107

Displayed Outside
Humidity

%RH

R/W

Outside humidity to display on screen.


Sensed humidity plus Outside
Humidity Offset (AV-141).

AV-108

SP Mode Cooling SP

Deg F/C

R/O

Occupancy mode:
Updated from the legacy Microset
setpoints as follows:
BV67 ON:
AV90 + AV93
BV67 OFF:
AV95
Setpoint mode:
Storage for the current UI cooling
setpoint. Gets updated from the
schedule in Following Schedule
mode.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

43

Installation and Operations Guide | VLD

Point

Object_Name

Units

Access Notes

AV-109

SP Mode Heating SP

Deg F/C

R/O

Occupancy mode:
Get updated from the legacy microset
setpoints as follows:
BV67 ON:
AV90 - AV94
BV67 OFF:
AV96
Setpoint mode:
Storage for the current UI heating
setpoint. Gets updated from the
schedule in Following Schedule
mode.

Legacy (Microset) BVs


The following BVs function substantially the same as corresponding BVs in a Microset.
Point

Object Name

Access

Description

BV-64

Time Schedule Output

R/W

Occupancy mode:
ON: Places unit into occupied mode
OFF: Places unit into unoccupied (or tenant
override) mode
Setpoint mode: ignored

BV-65

User ON/OFF in
Occupied Mode

n/a

Replaced by BV-142 Master OFF

BV-66

After Hours Timer Status

R/O

ON: occupancy mode and after-hours is in progress.


OFF: occupied or if in setpoint mode

BV-67

Occupied / Unoccupied
Status

R/0

Occupancy Mode:
ON: Selects occupied setpoints in AV99 and
AV100
OFF: Selects unoccupied setpoints in AV99 and
AV100.
Setpoint Mode:
Ignored

BV-68

Field Service Lockout

R/W

OFF: Field service mode is allowed


ON: Field service mode is not accessible

BV-69

Swap English / Metric

R/W

ON: Causes the display to operate in English/Metric


mode opposite from what is specified in BV71.
OFF: English/Metric mode is specified by BV71

BV-71

BV-72

44

English (OFF) / Metric


(ON)

R/O

Fan Low Speed

R/O

ON: The DDC header specifies Metric


OFF: The DDC header specifies English
Fan stage 1

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

Point

Object Name

Access

Description

BV-73

Fan Medium Speed

R/O

Fan stage 2

BV-74

Fan High Speed

R/O

Fan stage 3

BV-77

Heating ICON

R/W

ON: Display heat on when in the Displaying


Home state

BV-78

Cooling ICON

R/W

ON: Display cool on when in the Displaying


Home state

BV-79

Backlight ON

R/W

ON: Backlight always on dimly when not


interacting with user
OFF: Backlight turns completely off when not
interacting with user
Backlight always comes on full during user
interaction

BV-80

Enable Fan Speed Control R/W

ON: Allow the FAN control to be visible to the


end user
OFF: FAN control is always hidden

BV-81

Select Hotel Mode

R/W

ON: Select Hotel mode

BV-82

Enable Time Display

R/W

ON: Display current time on standard backdrop

BV-83

24Hr Time Format

R/W

ON: Use 24Hr time format

BV-84

Enable Space Humidity

R/W

ON: Display space humidity

Honeywell

LTBT-TM-VLDIOG Rev. 0002

45

Installation and Operations Guide | VLD

Mode select BVs


Point

Object Name

Access

Description

BV-200

AIn Current Mode

R/W

ON: Configures the corresponding AI-in current


mode

...

OFF: Configures the corresponding AI-in voltage


mode

BV-202
BV-300

AOn Current Mode

R/O

Read-only. Active indicates AO0..AO1 has


detected current mode (load is 550 Ohms or less).
Inactive indicates voltage mode (load is 1K Ohm
or higher).

AIn Pullup

R/W

Enables the pullup on AI0..A3. Gets set to default


value from DDC header at beginning of first pass of
DDC, allowing DDC to override the default.

...
BV-301
BV-400
...
BV-402

An Active setting of one of these pullup BVs


overrides the setting of the corresponding
AI-current mode BV-(see above).

UI control AVs and BVs


The following AVs, BVs, and MVs control the VLD user interface.

General control AVs


Point

Object Name

Access

Description

AV-110

SP Mode Setpoint Model

R/W

Setpoint Mode:
Chooses the setpoint model, and also selects the
layout of the Generic Backdrop display
0.0: use OFF Format (no setpoints shown)
1.0: use 1-setpoint format (cooling)
2.0: use 1-setpoint format (heating)
3.0: use 2-setpoint format
Occupancy Mode:
Ignored

AV-111

SYSTEM Setpoint Model

R/W

Provides a compatible output from the SYSTEM


control that can be transferred into the setpoint
model AV-110 (above) to reproduce default
VisionPro behavior. The values produced by the
SYSTEM control are limited by the configuration
AVs, BVs, and MVs.
0.0: OFF selected
1.0: COOL selected
2.0: HEAT/EM HEAT selected
3.0: AUTO selected

AV-123

Occupancy Mode Select

R/W

Sets system to Occupancy mode.

AV-124

Filter Change Reminder

R/W

Enables the filter change reminder.

AV-125

Humidity Pad Change


Reminder

R/W

Enables the humidity pad change reminder.

46

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

Point

Object Name

Access

Description

AV-126

UV Lamp Change
Reminder

R/W

Enables the UV lamp change reminder.

AV-127

Daylight Savings

R/W

Sets Daylight savings to Off, pre-2007 scheme, or


post-2007 scheme.

AV-128

Keypad Lock

R/W

Locks the keypad.

AV-132

Field Service Mode


Security PIN

R/W

Allows access to Field Service mode only by


authorized users.

AV-133

ISU Mode Security PIN

R/W

Allows access to ISU mode only by authorized


users.

AV-137

Fan Setting Display


Format

R/W

Selects the format in which fan settings are shown


on the display.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

47

Installation and Operations Guide | VLD

General control BVs


Point

Object Name

Access

BV-80

Enable Fan Speed Control R/W

Description

ON: Allow the FAN control to be visible to the


end user
OFF: FAN control is always hidden

BV-84

Enable Space Humidity

R/W

ON: Display space humidity as appropriate


OFF: Never display the space humidity

BV-100

Enable OSA Temp

R/W

ON: Display the OSA temp as appropriate


OFF: Never display the OSA temp

BV-101

Enable OSA Humidity

R/W

ON: Display outside humidity as appropriate


OFF: Never display outside humidity

BV-102

Enable System Control

R/W

ON: Allow the SYSTEM control to be visible


OFF: The SYSTEM control is always hidden

BV-103

Hide Fan and System

R/W

ON: Hide the FAN and SYSTEM controls in


unoccupied mode (regardless of other display
settings)
OFF: Show them if allowed

BV-104

Enable DOW

R/W

ON: Allow day of week to be shown is possible


OFF: Never show the day of week

BV-105

Show Unocc Setpoints

R/W

ON: Display the unoccupied heating/cooling


setpoints in unoccupied mode
OFF: Don't display them

48

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

General control MVs


Point

Object Name

Access

Description

MV-0

Time Mode

Provides feedback about the device's time handling


capability: Normal clock operation will result in a
present value of 3.
1: Time Of Day Unknown Mode
2: Time Of Day Available Mode
3: Date/Time Available Mode

MV-1

Schedule Model

Provides feedback about the device's schedule


model
1: Setpoint (VisionPro-style)
2: Occupancy (Microset-style)

MV-2

Keypad Lock

Provides feedback about the keypad access level:


1: full access
2: setpoints only
3: locked

MV-3

DLS Mode

Provides feedback about the mode of Daylight


Saving operation
1: OFF
2: Auto (pre-2007)
3: Auto (2007 and later)

MV-4

SP Increment

Amount of change in setpoint per arrow press


1: 1 deg F / 0.5 deg C (default)

MV-5

Schedule Increment

Amount of change in schedule times per arrow


press
1: 1 min (default)

Optional screen segment control BVs


In Setpoint Mode, the setpoint layout is controlled by AV-110, see above.
Point

Object_Name

Access

Description

BV-77

Heating ICON

R/W

ON: Display heat on icon

BV-78

Cooling ICON

R/W

ON: Display cool on icon

BV-106

Show Wait

R/W

ON: Display Wait

BV-107

Show Aux heat on

R/W

ON: Display Aux heat on

BV-108

Show Recovery

R/W

ON: Display Recovery

BV-109

Show FROST

R/W

ON: Display FROST

BV-110

Show DEHUMIDIFIER

R/W

ON: Display DEHUMIDIFIER

BV-111

Force CHANGE FILTER

R/W

ON: Force CHANGE FILTER to be displayed


(can also be automatically displayed due to filter
timer)

Honeywell

LTBT-TM-VLDIOG Rev. 0002

49

Installation and Operations Guide | VLD

Point

Object_Name

Access

Description

BV-112

Force CHANGE UV
LAMP

R/W

ON: Force CHANGE UV LAMP to be


displayed (can also automatically be displayed
due to UV lamp timer)

BV-113

Force CHANGE
HUMIDIFIER PAD

R/W

ON: Force CHANGE HUMIDIFIER PAD to be


displayed (can also be displayed due to humidifier
pad timer)

BV-114

Disable SCHED key

R/W

OFF: Allow SCHED key to be used to access


standard scheduling UI (if appropriate)
ON: The SCHED key is always invisible

BV-115

Disable Permanent HOLD R/W


key

OFF: Allow HOLD key to be used to access the


Permanent Hold UI
ON: the HOLD key is invisible or used for
Vacation HOLD, if enabled.

BV-130

Disable Vacation HOLD


key

R/W

OFF: Allow HOLD key to be used to access the


standard Vacation Hold UI (if appropriate)
ON: the HOLD key is invisible.

BV-116

Disable CLOCK key

R/W

OFF: Allow CLOCK key to be used to set clock


(if appropriate)
ON: the CLOCK key is always invisible

BV-131

Hotel Standby Mode

R/W

Set Active by DDC to indicate to the display that


DDC is controlling to standby mode. Useful for
visual indication if DDC mistakenly thinks the
room is unoccupied.

BV-142

Master OFF

R/W

OFF: no effect
ON: Override occupied status in Occupancy
Mode. Home screen shows OFF without
override arrows and user setpoint is not displayed.
Used to implement user ON/OFF or fan control
ON/OFF.
Replaces the legacy BV65.

SYSTEM control BVs


The following points control the behavior of the SYSTEM control (if enabled).
BVs 122-125 indicate the last user-selected SYSTEM state. Only one of these BVs can be ON at
any given time when set using the user interface. DDC can set these BVs and can set more than
one ON. If the system control is OFF, all these BVs shall be OFF.

50

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

If a user sets the SYSTEM control to OFF, then all of the these BVs are set to off unless
overwritten by DDC.
Point

Object Name

Access

Description

BV-117

Allow System OFF

R/W

ON: Allow the OFF state

BV-118

Allow System HEAT

R/W

ON: Allow the HEAT state

BV-119

Allow System COOL

R/W

ON: Allow the COOL state

BV-120

Allow System AUTO

R/W

ON: Allow the AUTO state

BV-121

Allow System EM HEAT

R/W

ON: Allow the EM HEAT state

BV-122

System HEAT Mode

R/O

ON: HEAT mode is selected

BV-123

System COOL Mode

R/O

ON: COOL mode is selected

BV-124

System AUTO Mode

R/O

ON: AUTO mode is selected

BV-125

System EM HEAT Mode

R/O

ON: EM HEAT mode is selected

SYSTEM control MV
Point

Object Name

Access

Description

MV-6

User SYSTEM selection

Current selected mode


1: OFF
2: HEAT
3: COOL
4: AUTO
5: EM HEAT

FAN control BVs


The following points configure the behavior of the FAN control. A maximum of one of these
BVs can be on at any given time.
If the fan control is not visible to the user, then the R/O values read consistently with an OFF
setting.
Point

Object Name

Access

Description

BV-126

Enable fan OFF select

R/W

ON: Allow the OFF state

BV-127

Enable fan stage1 select

R/W

ON: Allow the Stage 1" state

BV-128

Enable fan stage2 select

R/W

ON: Allow the Stage 2" state

BV-129

Enable fan stage3 select

R/W

ON: Allow the Stage 3" state

BV-72

Fan stage 1

BV-73

Fan stage 2

BV-74

Fan stage 3

Honeywell

LTBT-TM-VLDIOG Rev. 0002

51

Installation and Operations Guide | VLD

FAN control MVs


If the fan control is not visible to the user, the R/O values read consistently with an OFF setting.
Point

Object Name

Access

Description

MV-7

Fan status

Fan stage. Text shown depends on stage


configuration (see above).
1: OFF or 00 or F0
2: ON, 33, 50, LO, or F1
3: ON, 50, 66, or F2
4: ON, 99, HI, or F3

MV-8

Fan OFF text

R/W

OFF state display configuration


1: OF
2: 00
3: F0

MV-9

Fan stage 1 text

R/W

Stage 1 display configuration


1: On
2: 33
3: 50
4: LO
5: F1

MV-10

Fan stage 2 text

R/W

Stage 2 display configuration


1: On
2: 50
3: 66
4: HI
5: F2

MV-11

Fan stage 3 text

R/W

Stage 3 display configuration


1: On
2: 99
3: HI
4: F3

52

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

Schedule control BVs


Point

Object Name

Access

Description

BV-114

Deny schedule viewing

R/W

If set, the user is not allowed to view schedules.

BV-133

Enable internal schedule

R/W

ON: Internal 7-day scheduling is enabled (subject to


other factors). The BACnet schedule object is
visible via BACnet
OFF: Disables use of internal scheduling
mechanism. The BACnet schedule object is
invisible. All UI components related to schedule
editing are disabled.
This is ISU parameter 160.
BV-133=0 shown as ISU 160=0.
BV-133=1 shown as ISU 160=4.

BV-141

Disable schedule edit

R/W

ON: Inhibits screen EDIT key. Internal schedules


may be viewed but not edited.

AV-129

Weekday periods ISU


value

R/W

2: Two schedule periods per day


4: Four schedule periods per day

Units

Access

Description

R/W

While in setpoint mode, indicates the


setpoint override state. This point can be
written in DDC to cancel the override
status

Schedule control AVs


Point

Object Name

AV-113

SP Override Mode AV

1.0: scheduled
2.0: temporary
3.0: permanent
4.0: vacation
5.0: initial
AV-130

Hold until time

Minutes

R/W

While in setpoint mode, indicates the


minute of the day (0-1440) at which a
temporary or vacation override is to
expire.

AV-131

Vacation days remaining

Days

R/W

While in setpoint mode, indicates the


number of days remaining in a vacation
override.

Honeywell

LTBT-TM-VLDIOG Rev. 0002

53

Installation and Operations Guide | VLD

Schedule control MVs


Point

Object Name

Access

Description

MV-12

Schedule Format

This point is a human-friendly version of AV-129,


ISU parameter 540 (see above)
1: 2 commands per day
2: 4 commands per day

MV-13

SP Override Mode

While in setpoint mode, indicates the setpoint


override state. This point is a human-friendly version
of AV-113 (see above)
1: scheduled
2: temporary
3: permanent
4: vacation

Filter timer control BVs


Point

Object Name

Access

Description

BV-134

Filter Enable

R/W

ON: Enable filter timer and automatic change filter


warning
OFF: detail display shall be skipped, change filter
warning shall not be activated automatically

BV-135

Filter ON

R/W

ON: Accumulator ON
OFF: Accumulator OFF

Filter timer control AVs


Point

Object_Name

Units

Access

Notes

AV-114

Filter Runtime

Hours

R/W

Current filter runtime hours. Can be


reset via DDC or by pressing the reset
key on the details display

AV-115

Filter Runtime Limit

Hours

Filter runtime limit

UV lamp timer control BVs


Point

Object_Name

Access

Description

BV-136

UV Lamp Enable

R/W

ON: Enable UV Lamp timer and automatic UV


Lamp warning
OFF: detail display shall be skipped, UV Lamp
warning shall not be activated automatically

BV-137

54

UV Lamp ON

R/W

ON: Accumulator ON
OFF: Accumulator OFF

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix A: BACnet object and property reference

UV lamp timer control AVs


Point

Object_Name

Units

Access

Notes

AV-116

UV Lamp Runtime

Hours

R/W

Current UV Lamp runtime hours.


Can be reset via DDC or by pressing
the reset key on the details display

AV-117

UV Lamp Runtime Limit

Hours

UV Lamp runtime limit

Humidifier pad timer control BVs


Point

Object_Name

Access

Description

BV-138

Humidifier Pad Enable

R/W

ON: Enable Humidifier Pad timer and automatic


Humidifier Pad warning
OFF: detail display shall be skipped, Humidifier
Pad warning shall not be activated automatically

BV-139

Humidifier Pad ON

R/W

ON: Accumulator ON
OFF: Accumulator OFF

Humidifier pad timer control AVs


Point

Object_Name

Units

Access

Notes

AV-118

Humidifier Pad Runtime

Hours

R/W

Current Humidifier Pad runtime


hours. Can be reset via DDC or by
pressing the reset key on the details
display

AV-119

Humidifier Pad Runtime


Limit

Hours

Humidifier Pad runtime limit

Dehumidifier and humidifier BVs


Point

Access

Description

BV-140

R/W

ON: Enable dehumidifier setpoint on detail screen (also requires humidity to be


enabled or you cannot get to the detail screen)
OFF: Dehumidifier setpoint not shown on detail screens

BV-143

R/W

ON: Enable humidifier setpoint on detail screens (also requires humidity to be


enabled or you cannot get to the detail screen)
OFF: Humidifier setpoint not shown on humidity detail screen

BV-144

R/W

ON: Enable AUTO/OFF user selection on humidifier detail screen


OFF: AUTO/OFF option not shown on humidifier detail screen

BV-145

R/W

User humidifier AUTO/OFF selection. ON=AUTO.

BV-146

R/W

ON: Enable AUTO/OFF user selection on dehumidifier detail screen


OFF: AUTO/OFF option not shown on dehumidifier detail screen

BV-147

Honeywell

R/W

User dehumidifier AUTO/OFF selection. ON=AUTO.

LTBT-TM-VLDIOG Rev. 0002

55

Installation and Operations Guide | VLD

Dehumidifier and humidifier AVs


Point

Object_Name

Units

Access

Notes

AV-120

Dehumidifier Setpoint

% RH

R/W

Current dehumidifier setpoint

AV-121

Dehumidifier SP Max

% RH

R/W

Dehumidifier max. limit

AV-122

Dehumidifier SP Min

% RH

R/W

Dehumidifier min. limit

AV-134

Humidifier Setpoint

% RH

R/W

Current humidifier setpoint

AV-135

Humidifier SP Max

% RH

R/W

Humidifier max. limit

AV-136

Humidifier SP Min

% RH

R/W

Humidifier min. limit

Temperature and Humidity Offset AVs


Point

Object_Name

Units

Access

Notes

AV-138

Sensed Temperature
Offset

Deg F/C

R/W

Limited to +/- 4 degrees F.

AV-139

Sensed Humidity Offset

%RH

R/W

Limited to +/- 5%.

AV-140

Sensed Outside Air


Temperature Offset

Deg F/C

R/W

Limited to +/- 4 degrees F. Added to


Sensed Outside Air Temperature
(AV-103) to produce Displayed
Outside Air Temperature (AV-13.

AV-141

Sensed Outside Air


Humidity Offset

%RH

R/W

Added to AV-107 to generate OA


humidity on the details screens. Limited
to +/- 5%.

56

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix B: Custom display configuration

Appendix B: Custom display configuration


Basic controls
This table shows the points that enable, disable, and reset the custom display.
Point

Object_Name

Access

Description

BV-210

Custom 1
Enable

R/W

ON: Enable Custom Details Screen 1


OFF: Custom Detail 1 Screen will be skipped, all related parameters
are ignored

BV-211

Reset

R/W

RESET key visible

Upper left controls


This table shows the points associated with the controls that appear in the upper left corner of the
display.
Point

Object_Name

Access

Description

BV-212

ULHC enable

R/W

ON: Enable value


OFF: Value is blank

MV-20

ULHC mode

R/W

Item display mode:


1: Numeric value (range 0 to 99.5, resolution 0.5)
2: Alphanumeric value

BV-213

ULHC decimal

R/W

ON: Show decimal point and 10th's place in numeric mode

BV-214

ULHC lead
zero

R/W

ON: Display leading zeros

AV-210

UHLH number

R/W

Current numeric value

AV-211

ULHC left
character

R/W

10's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

AV-212

ULHC right
character

R/W

1's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

Upper right controls


This table shows the points associated with the controls that appear in the upper right corner of
the display
Point

Object_Name

Access

Description

BV-215

URHC enable

R/W

ON: Enable value


OFF: Value is blank

MV-21

URHC mode

R/W

Item display mode:


1: Numeric value (range 0.0 to 99.5, resolution 0.5)
2: Alphanumeric value

BV-216

URHC decimal

R/W

ON: Show decimal point and 10th's place

BV-217

URHC lead
zero

R/W

ON: Display leading zeros

Honeywell

LTBT-TM-VLDIOG Rev. 0002

57

Installation and Operations Guide | VLD

Point

Object_Name

Access

Description

BV-218

URHC edit

R/W

ON: value is editable (only works for numeric value)


OFF: value is not editable

AV-216

URHC
minimum

R/W

Minimum allowable numeric value

AV-217

URHC
maximum

R/W

Maximum allowable numeric value

AV-218

URHC delta

R/W

Up/down increment

AV-213

URHC number

R/W

Current numeric value

AV-214

URHC 10 char

R/W

10's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

AV-215

URHC 1 char

R/W

1's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

BV-262

URHC Adj
Arrows

R/W

Up/Down Arrows (upper right)

Lower left controls


This table shows the points associated with the controls that appear in the lower left corner of the
display
Point

Object_Name

Access

Description

BV-219

LLHC enable

R/W

ON: Enable value


OFF: Value is blank

MV-22

LLHC mode

R/W

Item display mode:


1: Numeric value (range -999 to 9999, integers only)
2: Alphanumeric value
3: HH:MM mode (numeric value in minutes since midnight 23:59
max)
4: MM:SS mode (numeric value is in seconds, 99:59 max)

BV-220

LLHC lead
zero

R/W

ON: Display leading zeroes in numeric mode

BV-221

LLHC edit

R/W

ON: value is editable (ignored for alphanumeric)


OFF: value is not editable

AV-222

LLHC
minimum

R/W

Minimum allowable numeric value (ignored for alphanumeric)

AV-223

LLHC
maximum

R/W

Maximum allowable numeric value (ignored for alphanumeric)

AV-224

LLHC delta

R/W

Up/down increment (ignored for alphanumeric)

AV-219

LLHC number

R/W

Current numeric value (ignored for alphanumeric)

AV-225

LLHC 1000
char

R/W

1000's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

58

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix B: Custom display configuration

Point

Object_Name

Access

Description

AV-226

LLHC 100 char R/W

100's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

AV-220

LLHC 10 char

R/W

10's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

AV-221

LLHC 1 char

R/W

1's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

BV-266

LLHC Adj
Arrows

R/W

Up/Down Arrows (lower left)

Lower right controls


This table shows the points associated with the controls that appear in the lower right corner of
the display
Point

Object_Name

Access

Description

BV-222

LRHC enable

R/W

ON: Enable value


OFF: Value is blank

MV-23

LRHC mode

R/W

Item display mode:


1: Numeric value (range -99.5 to 199.5, resolution 0.5)
2: Alphanumeric value

BV-223

LRHC decimal

R/W

ON: Show decimal point and 10th's place in numeric mode

BV-224

LRHC lead
zero

R/W

ON: Display leading zeroes in numeric mode

BV-225

LRHC edit

R/W

ON: value is editable (numeric mode only)


OFF: value is not editable

AV-230

LRHC
minimum

R/W

Minimum allowable numeric value

AV-231

LRHC
maximum

R/W

Maximum allowable numeric value

AV-232

LRHC delta

R/W

Up/down increment

AV-227

LRHC number

R/W

Current numeric value

AV-228

LRHC 10 char

R/W

10's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

AV-229

LRHC 1 char

R/W

1's place alphanumeric character for alphanumeric mode. See


Custom screen supported characters on page 62.

BV-226

LRHC leading
1

R/W

Show leading 1 (lower right, ignored in numeric mode)

BV-276

LRHC Adj
Arrows

R/W

Up/Down Arrows (lower right)

Honeywell

LTBT-TM-VLDIOG Rev. 0002

59

Installation and Operations Guide | VLD

Pre-defined display items


This table shows the points associated with pre-defined display items.
Point

Object_Name

Access

Description

BV-228

Mon text

R/W

MON

BV-229

Tue text

R/W

TUE

BV-230

Wed text

R/W

WED

BV-231

Thu text

R/W

THU

BV-232

Fri text

R/W

FRI

BV-233

Sat text

R/W

SAT

BV-234

Sun text

R/W

SUN

BV-235

Mon check

R/W

MON check mark

BV-236

Tue check

R/W

TUE check mark

BV-237

Wed check

R/W

WED check mark

BV-238

Thu check

R/W

THU check mark

BV-239

Fri check

R/W

FRI check mark

BV-240

Sat check

R/W

SAT check mark

BV-241

Sun check

R/W

SUN check mark

BV-227

Day boxes

R/W

Boxed around days of week

BV-242

Ok to pick

R/W

OK TO PICK MULTIPLE DAYS

BV-243

Screen locked

R/W

Not used

BV-244

Change

R/W

CHANGE

BV-245

Filter

R/W

FILTER

BV-246

UV Lamp

R/W

UV LAMP

BV-247

Hum Pad

R/W

HUMIDIFIER PAD

BV-250

Inside

R/W

Inside (upper-left)

BV-251

ULHC %
Humidity

R/W

% and Humidity (upper-left)

BV-253

Set to

R/W

Set To (upper-right)

BV-254

Aux

R/W

Aux (upper-right)

BV-255

Heat On

R/W

Heat On (upper-right)

BV-256

Wait

R/W

Wait (upper-right)

BV-257

Cool On

R/W

Cool On (upper-right)

BV-258

Heat Adjust

R/W

HEAT (upper-right, between UP and DN)

BV-259

Frost

R/W

FROST (upper-right)

BV-260

Follow

R/W

Following Schedule

BV-269

Hold Until

R/W

Hold Temperature Until

BV-268

Permanent

R/W

Permanent Hold

60

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix B: Custom display configuration

Point

Object_Name

Access

Description

BV-264

Am

R/W

AM

BV-263

Pm

R/W

PM

BV-265

Days

R/W

DAYS (lower-left)

BV-261

Recovery

R/W

Recovery

BV-270

Cancel Period

R/W

Cancel Period (lower left)

BV-272

DE

R/W

DE (lower right, couples with BV-273 to make


DEHUMIDIFIER)

BV-273

HUMIDIFIER

R/W

HUMIDIFIER (lower right)

BV-279

Cool Adj

R/W

COOL (lower-right, between UP and DN)

BV-271

Outside

R/W

Outside (lower-right)

BV-274

LRHC
Humidity

R/W

Humidity (lower-right)

BV-275

Minutes

R/W

Minutes (lower-right)

BV-280

Vent

R/W

VENT (lower-right)

BV-278

LLRC minus

R/W

- (lower-right, ignored in numeric mode)

BV-277

LLRC %

R/W

% (lower-right)

Key/BV-assignments
This table lists the points assigned to keys in custom screens. When a key is pressed, the
associated BV-responds as dictated by DDC.
Point

Object_Name

Access

Description

BV-294

RESET key

R/O

Responds to the RESET key on this detail display. If the reset


key is disabled, this reads OFF.

BV-281

Mon key

R/O

Responds to the MON key at the top of the display

BV-282

Tue key

R/O

Responds to the TUE key at the top of the display

BV-283

Wed key

R/O

Responds to the WED key at the top of the display

BV-284

Thu key

R/O

Responds to the THU key at the top of the display

BV-285

Fri key

R/O

Responds to the FRI key at the top of the display

BV-286

Sat key

R/O

Responds to the SAT key at the top of the display

BV-287

Sun key

R/O

Responds to the SUN key at the top of the display

BV-297

FAN key

R/O

Responds to the FAN control area

BV-298

SYSTEM key

R/O

Responds to the SYSTEM control area

BV-288

URHC up key

R/O

Responds to the upper-right UP control (even in numeric


mode)

BV-289

URHC dn key

R/O

Responds to the upper-right DN control (even in numeric


mode)

Honeywell

LTBT-TM-VLDIOG Rev. 0002

61

Installation and Operations Guide | VLD

Point

Object_Name

Access

Description

BV-290

LRHC up key

R/O

Responds to the lower-right UP control (even in numeric


mode)

BV-291

LRHC dn key

R/O

Responds to the lower-right DN control (even in numeric


mode)

BV-292

LLHC up key

R/O

Responds to the lower-left UP control (even in numeric or


HH:MM/MM:SS mode)

BV-293

LLHC dn key

R/O

Responds to the lower-left DN control (even in numeric or


HH:MM/MM:SS mode)

BV-295

CANCEL
PERIOD key

R/O

Responds to the CANCEL PERIOD key.

Custom screen supported characters


This table shows the characters supported in VLD custom screens.
0: 0

10: A

20: L

30: h

1: 1

11: b

21: n

31: o

2: 2

12: C

22: O

32: u

3: 3

13: d

23: P

33: -(dash)

4: 4

14: E

24: r

34: _ (underscore)

5: 5 or S

15: F

25: S

35: (blank)

6: 6

16: g

26: t

7: 7

17: H

27: U

8: 8

18: I

28: y

9: 9

19: j

29: c

62

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix C: Ordered List of Control Points

Appendix C: Ordered List of Control Points


Point

Object Name

Point

Object Name

AV-100
AV-102
AV-104
AV-106
AV-108
AV-110
AV-113
AV-115
AV-117
AV-119
AV-121
AV-123
AV-125
AV-127
AV-129
AV-131
AV-133
AV-135
AV-137
AV-139
AV-141
AV-211
AV-213
AV-215
AV-217
AV-219
AV-221
AV-223
AV-225
AV-227
AV-229
AV-231
AV-90
AV-92
AV-94
AV-96
AV-98
BV-100
BV-102
BV-104
BV-106
BV-108
BV-110
BV-112
BV-114
BV-115
BV-117

Current Heating SP
Displayed Room Humidity
Sensed Room Temperature
Demand Offset
SP Mode Cooling SP
SP Mode Setpoint Model
SP Override Mode AV
Filter Runtime Limit
UV Lamp Runtime Limit
Humidifier Pad Runtime Limit
Dehumidifier SP Max
Set system to Occupancy mode
Humidity Pad Change Reminder
Daylight savings
Weekday periods ISU value
Vacation days remaining
ISU mode security PIN
Humidifier SP Max
Fan Setting Display Format
Sensed Humidity Offset
Sensed Outside Air Humidity Offset
ULHC left character
URHC number
URHC 1 char
URHC maximum
LLHC number
LLHC 1 char
LLHC maximum
LLHC 1000 char
LRHC number
LRHC 1 char
LRHC maximum
Setpoint (SP)
Setpoint Low Limit
Heating SP Offset
Unoccupied Heating SP
After Hours Timer
Enable OSA Temp
Enable System Control
Enable DOW
Show Wait
Show Recovery
Show DEHUMIDIFIER
Force CHANGE UV LAMP
Disable SCHED key
Disable Permanent HOLD key
Allow System OFF

AV-101
AV-103
AV-105
AV-107
AV-109
AV-111
AV-114
AV-116
AV-118
AV-120
AV-122
AV-124
AV-126
AV-128
AV-130
AV-132
AV-134
AV-136
AV-138
AV-140
AV-210
AV-212
AV-214
AV-216
AV-218
AV-220
AV-222
AV-224
AV-226
AV-228
AV-230
AV-232
AV-91
AV-93
AV-95
AV-97
AV-99
BV-101
BV-103
BV-105
BV-107
BV-109
BV-111
BV-113
BV-114
BV-116
BV-118

Displayed Room Temperature


Displayed Outside Air Temperature
Sensed Room Humidity
Displayed Outside Humidity
SP Mode Heating SP
SYSTEM Setpoint Model
Filter Runtime
UV Lamp Runtime
Humidifier Pad Runtime
Dehumidifier Setpoint
Dehumidifier SP Min
Filter Change Reminder
UV Lamp Change Reminder
Keypad lock
Hold until time
Field Service mode security PIN
Humidifier Setpoint
Humidifier SP Min
Sensed Temperature Offset
Sensed Outside Air Temperature Offset
UHLH number
ULHC right character
URHC 10 char
URHC minimum
URHC delta
LLHC 10 char
LLHC minimum
LLHC delta
LLHC 100 char
LRHC 10 char
LRHC minimum
LRHC delta
Setpoint High Limit
Cooling SP Offset
Unoccupied Cooling SP
After Hours Timer Limit
Current Cooling SP
Enable OSA Humidity
Hide Fan and System
Show Unocc Setpoints
Show Aux heat on
Show FROST
Force CHANGE FILTER
Force CHANGE HUMIDIFIER PAD
Deny schedule viewing
Disable CLOCK key
Allow System HEAT

Honeywell

LTBT-TM-VLDIOG Rev. 0002

63

Installation and Operations Guide | VLD

Point

Object Name

Point

Object Name

BV-119
BV-121
BV-123
BV-125
BV-131
BV-134
BV-136
BV-138
BV-140
BV-142
BV-144

Allow System COOL


Allow System EM HEAT
System COOL Mode
System EM HEAT Mode
Hotel Standby Mode
Filter Enable
UV Lamp Enable
Humidifier Pad Enable
Enable dehumidifier setpoint on detail screen
Master OFF
Enable AUTO/OFF user selection on
humidifier detail screen
Enable AUTO/OFF user selection on
dehumidifier detail screen
AIn Current Mode

BV-120
BV-122
BV-124
BV-130
BV-133
BV-135
BV-137
BV-139
BV-141
BV-143
BV-145

Allow System AUTO


System HEAT Mode
System AUTO Mode
Disable Vacation HOLD key
Enable internal schedule
Filter ON
UV Lamp ON
Humidifier Pad ON
Disable schedule edit
Enable humidifier setpoint on detail screens
User humidifier AUTO/OFF selection

BV-147

User dehumidifier AUTO/OFF selection

BV-210

Custom 1 Enable

Reset
ULHC decimal
URHC enable
URHC lead zero
LLHC enable
LLHC edit
LRHC decimal
LRHC edit
Day boxes
Tue text
Thu text
Sat text
Mon check
Wed check
Fri check
Sun check
Screen locked
Filter
Hum Pad
ULHC % Humidity
Aux
Wait
Heat Adjust
Follow
URHC Adj Arrows
Am
LLHC Adj Arrows
Hold Until
Outside
HUMIDIFIER
Minutes
LLRC %

BV-212
BV-214
BV-216
BV-218
BV-220
BV-222
BV-224
BV-226
BV-228
BV-230
BV-232
BV-234
BV-236
BV-238
BV-240
BV-242
BV-244
BV-246
BV-250
BV-253
BV-255
BV-257
BV-259
BV-261
BV-263
BV-265
BV-268
BV-270
BV-272
BV-274
BV-276
BV-278

ULHC enable
ULHC lead zero
URHC decimal
URHC edit
LLHC lead zero
LRHC enable
LRHC lead zero
LRHC leading 1
Mon text
Wed text
Fri text
Sun text
Tue check
Thu check
Sat check
Ok to pick
Change
UV Lamp
Inside
Set to
Heat On
Cool On
Frost
Recovery
Pm
Days
Permanent
Cancel Period
DE
LRHC Humidity
LRHC Adj Arrows
LLRC minus

BV-146
BV-200
BV-202
BV-211
BV-213
BV-215
BV-217
BV-219
BV-221
BV-223
BV-225
BV-227
BV-229
BV-231
BV-233
BV-235
BV-237
BV-239
BV-241
BV-243
BV-245
BV-247
BV-251
BV-254
BV-256
BV-258
BV-260
BV-262
BV-264
BV-266
BV-269
BV-271
BV-273
BV-275
BV-277

64

LTBT-TM-VLDIOG Rev. 0002

Honeywell

Installation and Operations Guide | Appendix C: Ordered List of Control Points

Point

Object Name

Point

Object Name

BV-279
BV-281
BV-283
BV-285
BV-287
BV-289
BV-291
BV-293
BV-295
BV-298

Cool Adj
Mon key
Wed key
Fri key
Sun key
URHC dn key
LRHC dn key
LLHC dn key
CANCEL PERIOD key
SYSTEM key

Vent
Tue key
Thu key
Sat key
URHC up key
LRHC up key
LLHC up key
RESET key
FAN key
AOn Current Mode

BV-400
BV-402
BV-65
BV-67
BV-69
BV-72
BV-74
BV-78
BV-80
BV-82
BV-84
MV-1
MV-11
MV-13
MV-20
MV-22
MV-3
MV-5
MV-7
MV-9

AIn Pullup

BV-280
BV-282
BV-284
BV-286
BV-288
BV-290
BV-292
BV-294
BV-297
BV-300
BV-301
BV-64

BV-66
BV-68
BV-71
BV-73
BV-77
BV-79
BV-81
BV-83
MV-0
MV-10
MV-12
MV-2
MV-21
MV-23
MV-4
MV-6
MV-8

After Hours Timer Status


Field Service Lockout
English (OFF) / Metric (ON)
Fan stage 2
Heating ICON
Backlight ON
Select Hotel Mode
24Hr Time Format
Time Mode
Fan stage 2 text
Schedule Format
Keypad Lock
URHC mode
LRHC mode
SP Increment
User SYSTEM selection
Fan OFF text

User ON/OFF in Occupied Mode


Occupied / Unoccupied Status
Swap English / Metric
Fan stage 1
Fan stage 3
Cooling ICON
Enable Fan Speed Control
Enable Time Display
Enable Space Humidity
Schedule Model
Fan stage 3 text
SP Override Mode
ULHC mode
LLHC mode
DLS Mode
Schedule Increment
Fan status
Fan stage 1 text

Honeywell

Time Schedule Output

LTBT-TM-VLDIOG Rev. 0002

65

Installation and Operations Guide | VLD

Appendix D: Quick Reference

Field Service Codes


(Press SYSTEM block and hold down bottom middle key.)
:UC

Unoccupied cooling setpoint (AV-95)

:UH

Unoccupied heating setpoint (AV-96)

:CO

Cooling offset (AV-93)

:HO

Heating offset (AV-94)

:HS

Occupied heating setpoint (AV-100)

:CS

Occupied cooling setpoint (AV-99)

:AL

Override limit (AV-97)

:HI

Setpoint high limit (AV-91)

Function

Description

Days of
Week

Shows the current day of the week.


In Schedule Setup mode, shows all
days; check marks appear beside
selected days.

Maintenance
needed
messages

Flashes when it is time to change a


filter, UV lamp, or humidifier pad.

FAN block

Displays the current fan setting and


allows users to select a setting.

Inside
condition

Displays the current inside


temperature and/or humidity.

Setpoint

Displays the current setpoint

Heating
adjustment

Pressing the arrows adjusts the


heating setpoint.

SYSTEM
block

Displays the current system setting


and allows users to select a setting.

Schedule
block

Displays schedule holds and allows


users to change schedules.

Outside
condition

Displays the current outside


temperature and/or humidity.

10 Cooling
adjustment

11 SCHED
EDIT

:LO

Setpoint low limit (AV-92)

:SP

Occupant-selected space temperature setpoint (AV-90)

12 HOLD

Installer Setup Codes


(Press SYSTEM block and hold down keys on either side of
bottom middle key.)

66

120

Year, first 2 digits

130

Year, second 2 digits

140

Month

150

Day

160

Schedule format (BV-133)

280

Backlight control (BV-79)

320

Swap English/Metric (BV-69)

330

Daylight saving (AV-127)

500

Filter change reminder (AV-124)

510

Hum pad change reminder (AV-125)

520

UV lamp change reminder (AV-126)

540

Program periods (AV-129)

640

Clock format (BV-83)

670

Keypad lock (AV-128)

700

Sensed temperature offset (AV-138)

701

Sensed humidity offset (AV-139)

WAKE

13 CLOCK
LEAVE

14 SCREEN
RETURN

15 MORE
SLEEP

702

Sensed outside air temperature offset (AV-140)

703

Sensed outside air humidity offset (AV-141)

800

MS/TP MAC address

801

BACnet Device Instance first digit

802

BACnet Device Instance second and third digits

803

BACnet Device Instance fourth and fifth digits

804

BACnet Device Instance sixth and seventh digits

LTBT-TM-VLDIOG Rev. 0002

Pressing the arrows adjusts the


cooling setpoint.
Displays the current schedule.
In schedule mode, displays the Edit
Schedule screen.
Allows users to place the system on
Permanent or Vacation hold.
In Edit Schedule mode, flashing bar
indicates that WAKE is the active
schedule period.
Allows users to change the system
date and time.
When editing a schedule, flashing
bar indicates that LEAVE is the
active schedule period.
Locks the screen for cleaning.
In Edit Schedule mode, flashing bar
indicates that RETURN is the active
schedule period.
Displays additional screens.
In Edit Schedule mode, flashing bar
indicates that SLEEP is the active
schedule period.

Honeywell

You might also like