Table of Contents.......................................................................................................... 1
SF0010PE - Secondary Framing ......................................................................... 2
SF0020PE - Z Section Properties ...................................................................... 3
SF0030PE - C Section Properties ..................................................................... 4
SF0040PE - S Section Properties ..................................................................... 5
AG0001 - Z Roof Purlins ................................................................................... 6
SF0050PE - Z Wall Girts (Inset/Flush) ............................................................... 7
SF0060PE - Z Wall Girts (Bypass Bolted Clips) ................................................ 8
SF0065PE - Z Wall Girts (Bypass Welded Clips)............................................... 9
SF0070PE Open-Web Welded Joists .............................................................. 10
SF0071PE -Open-Web All Bolted Joists ............................................................ 11
SF0072PE Open Web Bolted Joist Detail Continued ...................................... 12
ClearBay CFR: ................................................................................................. 13
SF0080PE - Cold-Formed Box Beams .............................................................. 14
SF0090PE - Standard Purlin Spacing (Gable Building)...................................... 15
SF0100PE - Standard Purlin Spacing (Single Slope Building) ........................... 16
SF0110PE - Standard Girt Spacing ................................................................... 17
4.3.1
4.3.2
B
(in.)
2.500
2.500
2.500
2.500
2.500
2.500
2.500
DESIGN t
(in.)
0.0540
0.0600
0.0670
0.0750
0.0890
0.0990
0.1050
DESIGN t Wt.
(plf)
2.65
2.94
3.29
3.68
4.36
4.85
5.15
GROSS lx
(in^4)
7.52
8.34
9.30
10.38
12.27
13.60
14.40
Sx
(in ^3)
1.60
1.89
2.13
2.46
3.07
3.40
3.60
Ma
(in-kip)
52.85
62.52
70.26
81.15
101.02
112.03
118.60
10 Z 120
10.00
10.00
10.00
10.00
10.00
10.00
10.00
2.500
2.500
2.500
2.500
2.500
2.500
2.500
0.0600
0.0670
0.0750
0.0890
0.0990
0.1050
0.1200
3.35
3.74
4.19
4.97
5.53
5.86
6.70
14.15
15.78
17.63
20.86
23.15
24.52
27.93
2.36
2.77
3.35
4.17
4.63
4.90
5.58
77.50
91.35
110.48
137.40
152.50
161.52
183.97
12 Z 075
12 Z 089
12 Z 099
12 Z 105
12 Z 120
12.00
12.00
12.00
12.00
12.00
3.500
3.500
3.500
3.500
3.500
0.0750
0.0890
0.0990
0.1050
0.1200
5.21
6.18
6.87
7.29
8.33
32.68
38.69
42.96
45.52
51.88
4.04
5.35
6.25
6.70
8.04
133.33
176.20
205.70
220.80
265.07
SECTION
8 Z 054
8 Z 060
8 Z 067
8 Z 075
8 Z 089
8 Z 099
8 Z 105
10 Z 060
10 Z 067
10 Z 075
10 Z 089
10 Z 099
10 Z 105
LAST REVISION
DATE:
11/26/2013
BY: HJP CHK: KMC
4.3.3
8 C 060
8 C 067
8 C 075
8 C 089
8 C 099
8 C 105
D
(in.)
8.00
8.00
8.00
8.00
8.00
8.00
B
(in.)
2.750
2.750
2.750
2.750
2.750
2.750
DESIGN t
(in.)
0.0600
0.0670
0.0750
0.0890
0.0990
0.1050
DESIGN t Wt.
(plf)
2.95
3.29
3.68
4.37
4.86
5.15
GROSS lx
(in^4)
8.39
9.35
10.44
12.33
13.67
14.47
Sx
(in ^3)
1.75
2.03
2.31
2.92
3.32
3.55
Ma
(in-kip)
57.92
66.94
76.18
96.29
109.27
117.11
10 C 060
10 C 067
10 C 075
10 C 089
10 C 099
10 C 105
10.00
10.00
10.00
10.00
10.00
10.00
2.750
2.750
2.750
2.750
2.750
2.750
0.0600
0.0670
0.0750
0.0890
0.0990
0.1050
3.35
3.75
4.19
4.97
5.53
5.87
14.21
15.85
17.71
20.94
23.23
24.61
2.16
2.60
3.14
3.98
4.51
4.83
71.65
85.59
103.39
131.06
148.66
159.38
SECTION
LAST REVISION
DATE:
11/26/2013
BY: HJP CHK: KMC
4.3.4
8 S 075
8 S 089
8 S 099
8 S 105
8 S 120
D
(in.)
8.00
8.00
8.00
8.00
8.00
B
(in.)
3.625
3.625
3.625
3.625
3.625
DESIGN t
(in.)
0.0750
0.0890
0.0990
0.1050
0.1200
DESIGN t Wt.
(plf)
4.19
4.97
5.53
5.87
6.71
GROSS lx
(in^4)
12.68
14.98
16.61
17.58
19.98
Sx
(in ^3)
2.59
3.17
3.59
3.87
4.67
Ma
(in-kip)
85.36
104.38
118.34
127.52
153.89
12 S 075
12 S 089
12 S 099
12 S 105
12 S 120
12.00
12.00
12.00
12.00
12.00
3.625
3.625
3.625
3.625
3.625
0.0750
0.0890
0.0990
0.1050
0.1250
5.21
6.18
6.88
7.30
8.34
32.60
38.57
42.82
45.36
51.67
4.05
5.38
6.28
6.75
8.08
133.43
177.14
206.76
222.21
266.20
SECTION
LAST REVISION
DATE:
11/26/2013
BY: HJP CHK: KMC
4.3.5
NOTES:
1) ALL PURLIN CONNECTIONS UTILIZE DIAMETER BOLTS.
2) Z PURLINS HAVE SYMMETRICAL FLANGES FOR EASE OF ERECTION.
3) Z PURLINS ARE ECONOMICAL FOR SPANS UP TO AND INCLUDING 40
FEET.
LAST REVISION
DATE:
08/06/04
BY: KMC CHK: RJF
4.3.6
LAST REVISION
DATE:
02/09/01
BY: CDM CHK: RJF
4.3.7
LAST REVISION
DATE:
08/06/04
BY: KMC CHK: RJF
4.3.8
LAST REVISION
DATE:
08/06/04
BY: KMC CHK: RJF
4.3.9
LAST REVISION
DATE:
06/11/09
BY: AES CHK:
4.3.10
LAST REVISION
DATE:
06/11/09
BY: AES CHK:
4.3.11
LAST REVISION
DATE:
06/06/13
BY: AES CHK: EGB
4.3.12
CLEARBAY CFR:
What jobs are ClearBay CFR? All jobs with a standard CFR panel system (non-composite)
over roof joist.
What jobs are NOT ClearBay CFR? Jobs with Deck, VR16 II, Classic Roof, Etc.
The ClearBay CFR system was created to standardize bridging rows to speed up the
Estimating process and simplify the system.
** = The pre-determined bridging (30-60 bays) may not be the most economical choice for
some of these reasons, BUT they are still considered ClearBay because they will still utilize
reduced bridging.
These jobs can be either All Bolted, Bolted With Some Welding Reqd, or Welded.
These joists will be detailed the same as our typical roof joist system. The reduced bridging will
be specified by Vulcraft. No other considerations need to be taken into account. You will utilize
the ClearBay ordering spreadsheet.
Note: If you mark a job as non-ClearBay, Vulcraft will not design the joists utilizing the standard
bridging rows. This may cost Nucor extra money. Please verify if you are unsure if its ClearBay or
not.
LAST REVISION
DATE: 8/29/12
BY: MWD CHK:
4.3.13
LAST REVISION
DATE: 10/23/09
BY: AES CHK:
4.3.14
PURLIN SPACE
< 1/2:12
MIN. = 1-10
MAX = 3-10
1/2:12
MIN. = 1-10
MAX = 5-6
NOTE: THESE SPACINGS ARE TO BE USED FOR BOTH NUCOR CFR AND
NUCOR CLASSIC ROOF SYSTEMS.
WITH NUCOR CFR ROOF (UL CLASS 90, UL 580, CONSTRUCTION NO. 590).
- MAXIMUM PURLIN SPACING IS 5-0 W/ PURLINS.
- MAXIMUM PURLIN SPACING IS 5-6 W/ JOISTS.
LAST REVISION
DATE:
10/11/11
BY: RT CHK: EGB
4.3.15
PURLIN SPACE
< 1/2:12
MIN. = 1-10
MAX = 3-10
1/2:12
MIN. = 1-10
MAX = 5-6
NOTE: THESE SPACINGS ARE TO BE USED FOR BOTH NUCOR CFR AND
NUCOR CLASSIC ROOF SYSTEMS.
WITH NUCOR CFR ROOF (UL CLASS 90, UL 580, CONSTRUCTION NO. 590).
- MAXIMUM PURLIN SPACING IS 5-0 W/ PURLINS.
- MAXIMUM PURLIN SPACING IS 5-6 W/ JOISTS.
LAST REVISION
DATE:
10/11/11
BY: RT CHK: EGB
4.3.16
LAST REVISION
DATE:
02/09/01
BY: CDM CHK: RJF
4.3.17