acumulare pentru
prepararea apei calde de
consum - Boilere
Conf.dr.ing. Daniela Teodorescu
Facultatea de Instalatii
Curs 17
Qa
Qs
RGIMES DE FONCTIONNEMENT
Qs Qc Qa
rgime d'accumulation
rgime de rcupration-accumulation
rgime de rcupration
Qc Qs Qa
0 Qc Qc
max horaire
Q c t deviendra Q c
Qs Qa
ou
max
et Qa 0
Qs Qc
rgime d'accumulation-rcupration
Qs Qc Qa
Calculul boilerelor
Qs Qc Qa
PRPARATION EN ACCUMULATION
PURE Mthode 2 RO
PRPARATION EN ACCUMULATION
PURE Mthode 2 RO
Qac
cac ,max ac ,min
ac ,max 55 60o C
ac ,min 40 45o C
se determina qc = f(E)
Se considera perioada de varf de
consum (app 10 15 min)
Se determina Vb = 10 min x qc
unde
Eacc = energia necesara prepararii acm, pe durata unei zile, in
kWh
Vmax zi, acm = volumul de acm consumat in ziua maxima, se
considera la temp de preparare 60 grd C, in litri
1,16/1000 = coeficient de transformare
10 = temperatura apei reci
In care
Tec = temperatura apei in rezervorul de acumulare
10 = temperatura apei reci
a = coeficient de eficacitate sau randamentul
boilerului
In care
Pdis = pierderi de caldura pe reteaua de distributie + circulatie
0,9 = coeficient de majorare a pierderilor prin acumulare (prin
mantaua boilerului)
Se considera, in general, o putere minima instalata de 10 12 W/l
acumulat.