Process Industry Practices


Architectural

PIP ARC01016
Building Data Sheet

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES


In an effort to minimize the cost of process industry facilities, this Practice has
been prepared from the technical requirements in the existing standards of major
industrial users, contractors, or standards organizations. By harmonizing these
technical requirements into a single set of Practices, administrative, application, and
engineering costs to both the purchaser and the manufacturer should be reduced. While
this Practice is expected to incorporate the majority of requirements of most users,
individual applications may involve requirements that will be appended to and take
precedence over this Practice. Determinations concerning fitness for purpose and
particular matters or application of the Practice to particular project or engineering
situations should not be made solely on information contained in these materials. The
use of trade names from time to time should not be viewed as an expression of
preference but rather recognized as normal usage in the trade. Other brands having the
same specifications are equally correct and may be substituted for those named. All
Practices or guidelines are intended to be consistent with applicable laws and
regulations including OSHA requirements. To the extent these Practices or guidelines
should conflict with OSHA or other applicable laws or regulations, such laws or
regulations must be followed. Consult an appropriate professional before applying or
acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time by the responsible Function Team and
will be reviewed every 5 years. This Practice will be revised, reaffirmed, or withdrawn.
Information on whether this Practice has been revised may be found at www.pip.org.

Process Industry Practices (PIP), Construction Industry Institute, The


University of Texas at Austin, 3925 West Braker Lane (R4500), Austin,
Texas 78759. PIP member companies and subscribers may copy this Practice
for their internal use. Changes, overlays, addenda, or modifications of any
kind are not permitted within any PIP Practice without the express written
authorization of PIP.

PIP will not consider requests for interpretations (inquiries) for this Practice.
PRINTING HISTORY
June 2002
Issued
August 2002
Editorial Revision
Not printed with State funds

ASSOC. PIP:
ARC01015

DATA SHEET

ARC01016
PAGE 1 OF 10
August 2002

Building Data Sheet

Owners Name:
Project Title:
Project Number: ____________________
Project Site Location:

Name of Building:
Ref. No:
Date:

1. General
This Practice is intended to be used in conjunction with PIP ARC01015 - Architectural and Building Utilities Design
Criteria, PIP CVC01017 - Plant Site Data Sheets, and PIP STC01018 - Blast Resistant Building Design Criteria.
These data sheets contain architectural, HVAC, electrical, fire protection, plumbing, and communication information
that may be conveyed from the owner to the project design team or from the project design team leaders to the team
design members. This data may be provided by the owner or developed by the project design team and approved by
the owner.
Building Code: As Specified on PIP CVC01017.
Elevation:
Finished Grade: __________ ft (__________ m)
Floor Elevation (Ground Floor): __________ ft (__________ m)
Floor Elevation (___ Floor): __________ ft (__________ m)
Floor Elevation (___ Floor): __________ ft (__________ m)
Special Requirements:
Description
Yes
No
Blast Resistant Construction
Windows Permitted
Floor Drains Permitted
Furniture/Furnishings
Landscaping
Interior Design
Parking at Building
Signage/Graphics
Bridge Crane
Existing Colors or
Textures to Be Matched
Existing Siding/Roofing Profiles
to Be Matched
Designed for Future Expansion
Visual Access to Control Room
Number of Men ________________
Number of Women _____________
Number of Men per Shift ________________
Number of Women per Shift _____________
Number of Shifts ________________
General Comments:

See PIP STC01018 for design criteria.

# of cars ____ # of bikes ____


__________ tons (

) capacity

Room Types
(Description)

Air Lock

Ambulance Van Bay

Auditorium

Battery Room

Break Room(s)

Carpentry Area

Cashier

Chemical Laboratory

Change Room(s)

Coffee/Vending Room(s)

Communication Closet(s)

Communications
Equipment Room(s)
Communications
Computer Room(s)
Room
Requirements

Building Data Sheet


PAGE 2 OF 10
August 2002

Exposed Construction

ARC01016

Metal Liner Panels

DATA SHEET

Painted

Walls

Gypsum Board

Acoustical Tile

Plaster

Metal Liner Panels

Exposed Concrete

Wood Paneling

Fabric

Vinyl Wall Covering

Operable Steel Partition

Exposed Concrete

Boards

Ceramic Tile - Ft High

Plaster

Gypsum Board

Concrete Block (CMU)

Acoustical Wall Panel

Painted

Bulletin Boards

Bases

Chalk/Marker Boards

Wood

Carpet

Floors

Vinyl Cover Base


Ceramic

Carpet

Chemical Resistant

Seamless Monolithic

Access Flooring System

Vinyl Composition Tile

Ceramic Tile

Sealer on Concrete

Hardened Concrete Finish

Exposed Concrete

Notes (See Section 8)

Size of Rooms

Number of Rooms

ASSOC. PIP:
ARC01015

2. Architectural

2.1 Room Size and Room Finish Schedule


Ceilings

Room Types
(Description)

Communications Entrance
Room(s)
Computer Room(s)

Conference Room(s)

Control Room(s)

Copy/Fax Room(s)

Covered Parking

Dining Room(s)

Electrical/Telephone/Radio
Room(s)
Electrical Repair Area

Elevator and Equip. Room

Emergency Shower

Fire Suppression Equip.

Fire Truck Bay

Generator Room
Room
Requirements

Building Data Sheet


PAGE 3 OF 10
August 2002

Exposed Construction

ARC01016

Metal Liner Panels

DATA SHEET

Painted

Walls

Gypsum Board

Acoustical Tile

Plaster

Metal Liner Panels

Exposed Concrete

Wood Paneling

Fabric

Vinyl Wall Covering

Operable Steel Partition

Exposed Concrete

Boards

Ceramic Tile - Ft High

Plaster

Gypsum Board

Concrete Block (CMU)

Acoustical Wall Panel

Painted

Bulletin Boards

Bases

Chalk/Marker Boards

Wood

Carpet

Floors

Ceramic Tile

Vinyl Cover Base

Carpet

Chemical Resistant

Seamless Monolithic

Access Flooring System

Vinyl Composition Tile

Ceramic Tile

Sealer on Concrete

Hardened Concrete Finish

Exposed Concrete

Notes (See Section 8)

Size of Rooms

Number of Rooms

ASSOC. PIP:
ARC01015

Ceilings

Room Types
(Description)

Health Services

I/O Room

Instrumentation I/O Room

Instrument Repair Area

Janitors Room

Kitchen(s)

Laboratory

Ladies Locker/Shower

Ladies Restroom

Library/Reading Area(s)

Lobby/Reception

Lounge

Maintenance Pit

MCC/Switch Gear Room

Mechanical Room(s)

Medical Room

Men's Locker/Shower

Men's Restroom

Office(s)
Room
Requirements

Building Data Sheet


PAGE 4 OF 10
August 2002

Exposed Construction

ARC01016

Metal Liner Panels

DATA SHEET

Painted

Walls

Gypsum Board

Acoustical Tile

Plaster

Metal Liner Panels

Exposed Concrete

Wood Paneling

Fabric

Vinyl Wall Covering

Operable Steel Partition

Exposed Concrete

Boards

Ceramic Tile - Ft High

Plaster

Gypsum Board

Concrete Block (CMU)

Acoustical Wall Panel

Painted

Bulletin Boards

Bases

Chalk/Marker Boards

Wood

Carpet

Floors

Ceramic Tile

Vinyl Cover Base

Carpet

Chemical Resistant

Seamless Monolithic

Access Flooring System

Vinyl Composition Tile

Ceramic Tile

Sealer on Concrete

Hardened Concrete Finish

Exposed Concrete

Notes (See Section 8)

Size of Rooms

Number of Rooms

ASSOC. PIP:
ARC01015

Ceilings

Room Types
(Description)

Open Landscaped Area

Prayer Room

Radio Area

Receiving Area

Record/File Room(s)

Recovery Room

Refueling Area

Reproduction

Safety Equipment Room

Sandblasting Area

Security Office

Shop(s)

Storage Room(s)

Testing Area

Training Room(s)

Travel Services

Unloading Area (Covered)

Unloading Area (Open)


Room
Requirements

Building Data Sheet


PAGE 5 OF 10
August 2002

Exposed Construction

ARC01016

Metal Liner Panels

DATA SHEET

Painted

Walls

Gypsum Board

Acoustical Tile

Plaster

Metal Liner Panels

Exposed Concrete

Wood Paneling

Fabric

Vinyl Wall Covering

Operable Steel Partition

Exposed Concrete

Boards

Ceramic Tile - Ft High

Plaster

Gypsum Board

Concrete Block (CMU)

Acoustical Wall Panel

Painted

Bulletin Boards

Bases

Chalk/Marker Boards

Wood

Carpet

Floors

Ceramic Tile

Vinyl Cover Base

Carpet

Chemical Resistant

Seamless Monolithic

Access Flooring System

Vinyl Composition Tile

Ceramic Tile

Sealer on Concrete

Hardened Concrete Finish

Exposed Concrete

Notes (See Section 8)

Size of Rooms

Number of Rooms

ASSOC. PIP:
ARC01015

Ceilings

Room Types
(Description)

Vehicle Maintenance

Vending Area

VIP Waiting Room

Waiting Room

Welding Pipe

Fitting Machine Shop

X-Ray Room

Others:

.
Room
Requirements

ARC01016

Building Data Sheet


PAGE 6 OF 10
August 2002

Exposed Construction

DATA SHEET

Metal Liner Panels

Painted

Walls

Gypsum Board

Acoustical Tile

Plaster

Metal Liner Panels

Exposed Concrete

Wood Paneling

Fabric

Vinyl Wall Covering

Operable Steel Partition

Exposed Concrete

Boards

Ceramic Tile - Ft High

Plaster

Gypsum Board

Concrete Block (CMU)

Acoustical Wall Panel

Painted

Bulletin Boards

Bases

Chalk/Marker Boards

Wood

Carpet

Floors

Ceramic Tile

Vinyl Cover Base

Carpet

Chemical Resistant

Seamless Monolithic

Access Flooring System

Vinyl Composition Tile

Ceramic Tile

Sealer on Concrete

Hardened Concrete Finish

Exposed Concrete

Notes (See Section 8)

Size of Rooms

Number of Rooms

ASSOC. PIP:
ARC01015

Ceilings

ASSOC. PIP:
ARC01015

DATA SHEET
Building Data Sheet

2.2 Materials and Construction:


Primary Structure
Steel Frame
Reinforced Concrete Frame
Pre-Engineered System
Load-Bearing Reinf. Masonry (CMU)
Load-Bearing Precast Concrete Walls
Load-Bearing Cast-in-Place Walls
Blast Resistant
Other ________________________

Exterior Walls
Concrete Masonry Units (CMU)
Brick Veneer
Tilt-up/Precast Concrete
Cast-in-place Concrete
Metal Panels
Light Gage Steel Framing
Wood Sheathing
Stucco
Store Front System
Painted
Insulated
Other ________________

Elevated Levels
Single-Ply Membrane
Built-up
Uninsulated Metal Panel
Insulated Metal Panel
Fiberglass/Plastic
Bare Concrete
Sealed/Coated Concrete
Other _______________________

Doors
INT.
EXT.

Roof Systems
Single-Ply Membrane
Built-up Asphalt Roof
Uninsulated Metal Panel
Insulated Metal Panel
Fiberglass/Plastic
Bare Concrete
Sealed/Coated Concrete
Other ________________

Windows
Steel Frame
Aluminum Frame
Safety Glass (Type: _______________)
Insulating Glass
Fixed
Operable
Tinted Glass
Other ________________
Other ________________

Roof Structures
Metal Form Deck
Composite Metal Deck/Concrete Slab
Wood Formed Concrete Slab
Metal Deck Only
Precast Concrete
Composite (Type: ________________)
Standing Seam Roof System
Other ________________

Louvers
Operable
Fixed
Birdscreen
Steel
Aluminum
Blast Resistant
Other ________________

Standard Steel
Pressed Steel Frame
Wood
Aluminum and Glass
Fiberglass
Painted
Galvanized
Laminated
Roll-up
Canopy
Other ________________

ARC01016
PAGE 7 OF 10
August 2002

ASSOC. PIP:
ARC01015

DATA SHEET
Building Data Sheet

ARC01016
PAGE 8 OF 10
August 2002

3. Heating, Ventilation, and Air Conditioning (HVAC)


(Refer to PIP CVC01017 for outside design temperatures.)
No
Electric
Steam
Hot Water
Gas
Other ___________
Heating:
No
Blow Through
Draw Through
Gravity
Ventilation:
No
Air Conditioning:
Chilled Water
DX
_________________
Cooling Medium:
Packaged
Split
_________________
System:
Water Cooled
Air Cooled
Condenser:
Air Handler
Condenser
Corrosion Resistant Coil Coating:
Stand by Capacity ________ %
Multi Zone
Single Zone
Other ______________
Air Distribution System:
Pneumatic
Electronic
Thermostat Control:
Standard
Explosion Proof
Motor:
Yes
No
Dust Filter:
Yes
No
Wall Louvers:
Yes
No
Sand Filter:
Yes
No
Air Intake Stack:
Yes
No
Chemical Filter:
Equipment Heat Loads:
Btu/hr (kW)
Electrical Equipment:
Btu/hr (kW)
DCS Equipment:
Btu/hr (kW)
Btu/hr (kW)
Thermostat Setting Temperatures and % Relative Humidities and Pressures (Deviation or Addendum from
PIP ARC01015):
______________ Room __________ deg F (C) _________ % RH
_________ inches of water (Pa)
______________ Room __________ deg F (C) _________ % RH
_________ inches of water (Pa)
______________ Room __________ deg F (C) _________ % RH
_________ inches of water (Pa)
___________________ __________ deg F (C) _________ % RH
_________ inches of water (Pa)
___________________ __________ deg F (C) _________ % RH
_________ inches of water (Pa)
___________________ __________ deg F (C) _________ % RH
_________ inches of water (Pa)
Special Ventilation System Requirements:
Yes
No
For Whole Building:
Partial Area ____________________________________________________
Yes
No
Fresh Air Makeup Controlled:
Automatic
Manual
Air Intake Shutdown Capability:
No
Pressure: _________________ inches of water (Pa)
Building Pressurization:
Yes
No
Gas Detection Alarm:
Yes
No
Building Purging:

4. Electrical
Power Source for Building ____________________________
Incandescent Lamp
Fluorescent Lamp
Interior Electrical Light:
Special Grounding __________________________________
Interior Wiring __________________________________
Exterior Wiring __________________________________
Yes
No
Exterior Lighting:
Other Requirements _________________________________

5. Communication
Communication Standards Bodies:
USA TIA/EIA, BICSI, NFPA, IEEE
Other
Communication Requirements:
Telephone
Closed Circuit TV
Other

Yes

No

Yes
Yes

No
No

Others __________________

ASSOC. PIP:
ARC01015

DATA SHEET

ARC01016
PAGE 9 OF 10
August 2002

Building Data Sheet


6. Building Fire Protection and Safety
Description
Yes
Fire Detection/Alarm:
Smoke Detector
Heat Detector
Fire Alarm Box
Audible/Visual Alarm
Fire Alarm Panel
Sprinkler System
Pressure Switch
Fixed Fire Suppression
Discharge
Fixed Fire Suppression
Discharge
Automatic Sprinkler
Actuation

No

Description
Yes
No
Fire Suppression:
Hose Cabinets
Sprinkler System
Clean Agent Fire-Extinguishing
System
Portable Fire Extinguisher
17-lb (7.7-kg) ABC (Ammonium
Phosphate) Extinguisher
15-lb (6.9-kg) CO2 Extinguisher
100-lb (45.3-kg) CO2 Wheeled
Extinguisher
Building Hydrant (Standpipes):
Class I
Class II
Class III
Miscellaneous:
Emergency Lighting
Sprinkler Flow Switch

Safety:
Gas Detection System
Breathing Air System
Combustible Gas
Detectors
Toxic Gas Sensors
Oxygen Analysis

7. Plumbing
7.1 Plumbing Codes
State Plumbing Code (year: _______)
Local/County/Municipal Plumbing Code (year: _______)
(Or Adopted Plumbing Code ________, year: _______, date: _______)
(In the absence of any locally adopted plumbing code, building plumbing system will be designed in accordance
with) the latest edition of the International Plumbing Code (IPC).
7.2 Plumbing Systems
Description
Domestic Water
Cold Water
Hot Water
Storm Drain
Cooling Tower
Supply
Return

Yes

No

7.3 Plumbing Fixtures and Specialties


Description
Yes
No
Water Closet
Urinal
Lavatory
Kitchen Sink
Service Sink
Lab Sink
Floor Drain

Description
Fire Water
Natural Gas
Sanitary Sewer
Instrument Air
Steam
Condensate Return
Oily Water Sewer

Yes

No

Description
Emergency Shower
Emergency Eye Wash
Electrical Water Cooler
Hose Bib
Shower Stall
Dishwasher
Rough-in (for Ice Maker)

Yes

No

ASSOC. PIP:
ARC01015

DATA SHEET
Building Data Sheet

(Section 7.3, continued)

Garbage Disposal
Water Heater
Grease Interceptors
Oil Interceptor
8.0 Notes

Vacuum Pump
Backflow Preventor
Pressure Regulator
Drinking Fountain

ARC01016
PAGE 10 OF 10
August 2002