F6TesT

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Location Path

UNIT-3

Relay Under Test General Parameters

Relay Name

7UM62

Serial Number
Manufacturer

SIEMENS

Nominal Ratings:

fn

Model

50.000 Hz
110.00 V (Ph-Ph)
5.000 A

Vn
In
VTR

15750 : 110

Station Name

KORBA

7UM62X

Max Test Current

2000.000% In
1000.00% Vn

Max Test Voltage

A-B-C

Phase Names and Rotation


CTR

10000 : 5

Protected Object Parameters

Protected Object Name

UNIT-5 GENERATOR MAIN-1

Protected Object Parameters


Test and Test Definition Information

Test Plan Name

GT OVER FLUX

Test Name

PICKUP

Test Type

Ramp

Test Definition Name

24GT PICKUP

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Op

Test Definition Description


Test Configuration

Test Module

Amplitude-Voltage-Stepped-Auto-Single - Ramp

Values are

Secondary

Source Configuration
Source

Pre-fault
Amplitude

Action
Ph Ang [deg]

Amplitude

Ph Ang [deg]

Frequency(Hz)

VA

63.51 V

0.00

Action

0.00

50.000

VB

63.51 V

-120.00

Action

-120.00

50.000

VC

63.51 V

120.00

Action

120.00

50.000

Doble

Page 1 of 5

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Ramp Details

Trigger

LN1 0->1

Delay

0.0000 s

Pre-fault Duration

0.0000 s

Offset Voltage

Duration

0.0000 s

75.00 V

Offset Voltage Duration

1.0000 s
0.10 V

Delta Voltage
Delta Time

0.5000

Voltage Limit

78.00 V

Ramp Result
Test Objective

Expected
[V]

Ramp1

Actual

-tol [V]

+tol [V]

Error[V]

Eval

[V]

76.20

76.50

0.30

Op

Test and Test Definition Information

Test Plan Name

GT OVER FLUX

Test Name

TIME

Test Type

Ssimul

Test Definition Name

24GT ALARM

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Pass

Test Definition Description

Doble

Page 2 of 5

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test Configuration

State No

V/HZ ALARM

Name

Source Name

Amplitude

Ph Ang [deg]

Frequency (Hz)

VA

76.50 V

0.00

50.0000

VB

76.50 V

-120.00

50.0000

VC

76.50 V

120.00

50.0000

15.0000 s

State Duration

0->1

Trigger Condition

LN1

Trigger
Measurement
Timer Name

Timer

Start State

1-V/HZ ALARM

Stop Signal

t Exp
[s]

LN1, 0->1

t Act
[s]

10.0000

+ tol
[%]

10.2495

10.000

- tol
[%]

10.000

t Err

Eval

[%]

2.495

Pass

Test and Test Definition Information

Test Plan Name

GT OVER FLUX

Test Name

TIME

Test Type

Ssimul

Test Definition Name

24GT=135%

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Pass

Test Definition Description


Test Configuration

State No
Source Name

Amplitude

Ph Ang [deg]

Frequency (Hz)

VA

85.72 V

0.00

50.0000

VB

85.72 V

-120.00

50.0000

VC

85.72 V

120.00

50.0000

25.0000 s

State Duration
Trigger

135%

Name

LN1

Trigger Condition

Doble

0->1

Page 3 of 5

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Measurement
Timer Name

Timer

Start State

1-135%

Stop Signal

t Exp
[s]

LN1, 0->1

t Act
[s]

20.0000

+ tol
[%]

21.6242

10.000

- tol
[%]

10.000

t Err

Eval

[%]

8.121

Pass

Test and Test Definition Information

Test Plan Name

GT OVER FLUX

Test Name

TIME

Test Type

Ssimul

Test Definition Name

24GT=130%

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Pass

Test Definition Description


Test Configuration

State No

130%

Name

Source Name

Amplitude

Ph Ang [deg]

Frequency (Hz)

VA

82.55 V

0.00

50.0000

VB

82.55 V

-120.00

50.0000

VC

82.55 V

120.00

50.0000

40.0000 s

State Duration

0->1

Trigger Condition

LN1

Trigger
Measurement
Timer Name

Timer

Start State

1-130%

Stop Signal

LN1, 0->1

t Exp
[s]

35.0000

t Act
[s]

37.6987

+ tol
[%]

10.000

- tol
[%]

10.000

t Err

Eval

[%]

7.711

Pass

Test and Test Definition Information

Test Plan Name

GT OVER FLUX

Test Name

TIME

Test Type

Ssimul

Test Definition Name

24GT=125%

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Pass

Test Definition Description

Doble

Page 4 of 5

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test Configuration

State No

125%

Name

Source Name

Amplitude

Ph Ang [deg]

Frequency (Hz)

VA

79.50 V

0.00

50.0000

VB

79.50 V

-120.00

50.0000

VC

79.50 V

120.00

50.0000

70.0000 s

State Duration
Trigger

0->1

Trigger Condition

LN1

Measurement
Timer Name

Timer

Start State

1-125%

Stop Signal

LN1, 0->1

t Exp
[s]

60.0000

Doble

t Act
[s]

63.3699

+ tol
[%]

10.000

- tol
[%]

10.000

t Err

Eval

[%]

5.617

Pass

Page 5 of 5