You are on page 1of 70

BK THIEN UNG WELLHEAD PLATFORM PROJECT

DOCUMENT TITLE

HEAT LOAD CALCULATION FOR HVAC

TOTAL NO. OF PAGES

70

(INCLUDING FRONT SHEETS)

J.INT54021-15

VENDOR'S ORDER NO.


VENDOR'S OWN DOCUMENT NO

REV. NO

DATE

VENDOR'S APPROVAL
(NAME AND SIGNATURE)

TNG-VT-405-C22-0001

C
D
E

24.08.15
18.12.15
27.01.16

RONNARONG

Submitted For :
REVIEW

APPROVAL

INFO

FINAL DOCUMENTATION

REVIEW

BK THIEN UNG WELLHEAD PLATFORM

DOES NOT CONSTITUTE ACCEPTANCE OF

DESIGN DETAILS, CALCULATIONS, TEST METHODS OR

VENDOR NAME :

AAE-INT & VMPC

MATERIALS DEVELOPED OR SELECTED BY VENDOR NOR


DOES IT RELIEVE VENDOR FROM FULL COMPLIANCE
WITH CONTRACTUAL OR OTHER OBLIGATIONS.

PACKAGE
DESCRIPTION :

EPC HVAC PACKAGE

1. ACCEPTED
2. ACCEPTED, PROCEED WITH
WORK AND INCORPORATE
COMMENTS AND RE-SUBMIT
3. NOT ACCEPTED.
REVISE AND RE-SUBMIT.

4. FOR INFORMATION ONLY.


NO SIGNATURE REQUIRED.

NAME :

MODEL TYPE NOS. :

TAG NOS. :

PURCHASE ORDER NO:

0488/15/N-N2/HDDK-AAE

VDRL PRIME CODE :

C22

REQUISITION NO.

VDRLCAT.

SEQUENCE NO.:

Rev.

TNG-VT-405

C22

0001

DATE :
.
SIGNATURE :

Page 1 of 70

Document No.

Project Title:

TNG-VT-405-C22-0001

BK THIEN UNG WELLHEAD PLATFORM PROJECT

Reference No.
Sheet
2 of 70

Document Title:

HEAT LOAD CALCULATION FOR HVAC SYSTEM

Attachments:

Revision Record
E
D
C
B
A

27-Jan-16
18-Dec-15
24-Aug-15
12-Aug-15
29-Jul-15

Rev

Date

Issued for approval


Issued for approval
Issued for approval
Issued for approval
Issued for review
Description

Thong H.
Thong H.
Thong H.
Thong H.
Thong H.

T.N.Linh
T.N.Linh
T.N.Linh
T.N.Linh
T.N.Linh

RONNARONG
RONNARONG
RONNARONG
RONNARONG
RONNARONG

Prepared

Checked

Approved

Sub-Contractor:
AAE International Co., Ltd.
117/12 Moo1, T. Takeantea, A. Banglamung, Chonburi 20150, Thailand
Tel: +66 (0) 38172172 Fax: +66 (0) 38172103
www.aae-eng.com
Vien Dong Marine & Petrol Engineering Join Stock Company.
17 Hung Gia I Road, Tan Phong Ward, Distric 7, Ho Chi Minh City, Viet Nam.
Tel: +84 8 54103575, Fax: +84 8 54103576
www.sales@vmpc.com
Main Contractor:

VIETSOVPETRO

Client:

VIETSOVPETRO

Page 2 of 70

VENDOR DATA
TECHNICAL COMMENT SHEET

Project

BKTNG WELLHEAD PLATFORM

Vendors Name & Contract No.:


0488/15/N-N2/HDDK-AAE

Package Name :
EPC HVAC System

VSP CMS No.:


CMS-TNG-VT-405-C22-0001-Heat Load Calculation
For HVAC System

Rev.: E

Division CMS No.:

Rev.:

Document title :
Heat Load Calculation For HVAC System

VSP Code: 2

Document No. :
TNG-VT-405-C22-0001

Rev.: E

Approved by:
(Project manager)

Agreed by:
(NIPI)

Checked by:
(Discipline leader)

Prepared by:
(Discipline engineer)

Sign:

Sign:

Sign:

Sign:

Date:

Date:

Date:

Date:

1.

Section 5: Vendor to add the second criteria for Fresh air requirement
as: Total exhaust air (eg. Mechanical exhaust air plus pressurization
air/leakages)

*)
**)
Code
Code
Code
Code

1:
2:
3:
4:

Status *)

Description

Comment Status:
Criticality **)

Comment
No.

TECHNICAL COMMENTS

Div. Code:

BIDDERS RESPONSE

Schedule
impact

Cost
impact

No

No

By

HVT

O = Open; C = Closed; CI = Closed if implemented in document.


NC =Non Conformance (Response required); N=Note (Response required);
A=Advice (No Response required).
ACCEPTED.
ACCEPTED, PROCEED WITH WORK AND INCORPORATE COMMENTS AND RE-SUBMIT
NOT ACCEPTED. REVISE AND RE-SUBMIT.
FOR INFORMATION ONLY. NO SIGNATURE REQUIRED.

Page 3 of 70

Yes, right
Fresh air requirement as total exhaust air
(mechanical exhaust air plus pressurization
air/leakages) for pressure room >0Pa.

Page 1 of 5

VENDOR DATA
TECHNICAL COMMENT SHEET

Fresh air requirement as total exhaust air


(mechanical exhaust air except Infiltration air) for
pressure room <0Pa.
Vendor is going to re-calculation follow doc
no.BK.TNG-002-TS-ME-RPT-004_1_HVAC
Calculation Technical Building (Approval date: 05Dec-2014)

2.

Vendor to re-do heat load calculation as per input data indicated in BID
stage and mark-up @page 10/47

*)
**)
Code
Code
Code
Code

1:
2:
3:
4:

No

No

VHN

O = Open; C = Closed; CI = Closed if implemented in document.


NC =Non Conformance (Response required); N=Note (Response required);
A=Advice (No Response required).
ACCEPTED.
ACCEPTED, PROCEED WITH WORK AND INCORPORATE COMMENTS AND RE-SUBMIT
NOT ACCEPTED. REVISE AND RE-SUBMIT.
FOR INFORMATION ONLY. NO SIGNATURE REQUIRED.

Page 4 of 70

Page 2 of 5

VENDOR DATA
TECHNICAL COMMENT SHEET

VSP: Noted. Comment is closed

*)
**)
Code
Code
Code
Code

1:
2:
3:
4:

O = Open; C = Closed; CI = Closed if implemented in document.


NC =Non Conformance (Response required); N=Note (Response required);
A=Advice (No Response required).
ACCEPTED.
ACCEPTED, PROCEED WITH WORK AND INCORPORATE COMMENTS AND RE-SUBMIT
NOT ACCEPTED. REVISE AND RE-SUBMIT.
FOR INFORMATION ONLY. NO SIGNATURE REQUIRED.

Page 5 of 70

Page 3 of 5

VENDOR DATA
TECHNICAL COMMENT SHEET
We recheck our heat load calculation & As doc
no.BK.TNG-002-TS-ME-RPT-004_1_HVAC
Calculation Technical Building (Approval date: 05Dec-2014). We see the system no need duct
heater.
Vendor will re-submit with re-calculation heat load.

3.

For 50HH01A/B calcualation:


As per article 10: No heaters were added due to the assumption that at
least 50% of internal load are available at all times
As per heat dissipation load: total load is 4789W (from CCR) + 21718W
(From IER).
As per calculation, re-heat coil load is 5.6kW for zone 1 (CCR) and
19.2kW for zone 2 (IER)
Following the calculation, heaters must be required. But vendor confirm
No heaters were added
Vendor to clarify

VHN

4.

*)
**)
Code
Code
Code
Code

1:
2:
3:
4:

VHN

O = Open; C = Closed; CI = Closed if implemented in document.


NC =Non Conformance (Response required); N=Note (Response required);
A=Advice (No Response required).
ACCEPTED.
ACCEPTED, PROCEED WITH WORK AND INCORPORATE COMMENTS AND RE-SUBMIT
NOT ACCEPTED. REVISE AND RE-SUBMIT.
FOR INFORMATION ONLY. NO SIGNATURE REQUIRED.

Page 6 of 70

Yes

Yes

Yes

VSP 07-Jan-16:
- Vendor to provide heater calculation to
verify
- Vendor to show Space Input Data from
HAP
- Vendor to show System Input Data from
HAP
- Vendor to show Zone design load
summary from HAP
- Vendor to show Space design load
summary from HAP
- Vendor to show Winter design heating
from HAP
- Please provide native file from HAP to
check.
Note. Vendor confirm.
Same item 3. Pls review RevD for this calculation.

Similar comments for 50HH02A/B:


SWGR: 34460W
Battery room: 774W
Emergency SWGR: 311132W

Yes

VSP: VSP has sent updated heat dissipation for


Switchgear room, Main switchgear room,
Transformer room, Battery room and IE room but
Vendor did not incorporated. Vendor to clarify.
Refer to email dated 10- Nov-15 and 21-Dec-15
Note. Vendor confirm.

Page 4 of 5

VENDOR DATA
TECHNICAL COMMENT SHEET

5.

Similar comments for 50HH03A/B: No heat load dissipation

VHN

Same item 3.
There are 24W/m2 of lighting & 4 people in room
working. So, Internal heat load enough to heat
when the system run for dehumidified mode.
Pls review RevD for this calculation.

Yes

Yes

Yes

Yes

VSP: See comment in point 3


Note. Vendor confirm.
Note. Vendor revise & update.

6.

VSP has sent updated heat dissipation for Switchgear room, Main
switchgear room, Transformer room, Battery room and IE room but
Vendor ignored these comment. Vendor to clarify?

*)
**)
Code
Code
Code
Code

1:
2:
3:
4:

VHN

O = Open; C = Closed; CI = Closed if implemented in document.


NC =Non Conformance (Response required); N=Note (Response required);
A=Advice (No Response required).
ACCEPTED.
ACCEPTED, PROCEED WITH WORK AND INCORPORATE COMMENTS AND RE-SUBMIT
NOT ACCEPTED. REVISE AND RE-SUBMIT.
FOR INFORMATION ONLY. NO SIGNATURE REQUIRED.

Page 7 of 70

Page 5 of 5

INDEX
GENERAL ........................................................................................................................... 9

1.

1.1.

Background ................................................................................................................ 9

1.2.

Purpose of document ................................................................................................. 9

1.3.

Definitions and Abbreviations ................................................................................. 10

1.3.1.

Definitions ........................................................................................................... 10

1.3.2.

Abbreviations....................................................................................................... 10

1.4.

Reference Documents .............................................................................................. 11

1.4.1.

International Codes and Standards ..................................................................... 11

1.4.2.

Project Specifications and other Documents. .................................................... 12

2.

SUMMARY OF AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS ...... 13

3.

DESIGN BASIS ................................................................................................................ 14

4.

DESIGN CONDITION....................................................................................................... 15
4.1.

External Ambient Design Condition (All Year) ..................................................... 15

4.2.

Internal Design Condition....................................................................................... 15

5.

FRESH AIR VETILATION SYSTEM ................................................................................ 15

6.

U-VALUES (TRANSMISSION COEFFICIENT) ............................................................... 16

7.

ELECTRICAL AND INSTRUMENT HEAT DISSIPATION............................................... 18

8.

HVAC LOAD CALCULATION ......................................................................................... 22


8.1.

Summary of space & system input data & output data. ...................................... 22

8.2.

Design weather parameters and maximum solar heat gains. ............................. 24

8.3.

Heat load analysis. .................................................................................................. 24

9.
10.

PRELIMINARY DATA FOR EQUIPMENT SIZING .......................................................... 24


CONCLUSION .............................................................................................................. 25
ATTACHMENT A: DESIGN WEATHER PARAMETERS AND MAXIMUM SOLAR HEAT
GAINS .............................................................................................................................. 26
ATTACHMENT B: SPACE INPUT DATA ......................................................................... 28
ATTACHMENT C: AIR HANDLING UNIT 50HH01A/B ..................................................... 36
ATTACHMENT D: AIR HANDLING UNIT 50HH02A/B ..................................................... 47
ATTACHMENT E: AIR HANDLING UNIT 50HH03A/B ..................................................... 60
ATTACHMENT F: AIR HANDLING UNIT 50HC01A/B ..................................................... 70

Page 8 of 70

1. GENERAL
1.1. Background
Thien Ung field is located in the middle part of Block 04-3 in the Nam Con Son Basin, offshore
the Socialist Republic of Vietnam, approximately 15 km of Dai Hung field, and approximately
270 km southeast of Vung Tau. The Block 04-3 covers an area of approximately 2600 km2. The
Thien Ung field is including its 2 structural parts. Thien Ung structure discovery was made in
2004 with the 04- 3-TU-1X well. Two subsequent appraisal wells (04.3-TU-2X and 04.3-TU-3X),
drilled and tested respectively, delineated the field.
Location of Thien Ung field is shown in Figure 1.1 below.

Figure 1.1: Thien Ung Reservoir Location


1.2. Purpose of document
This document is to define the required capacity for the HVAC systems. It will be use as a basis
for equipment sizing, duct sizing as well as electrical and other utilities consumption requirement.
This calculation utilizes the Carrier E-20 HAP software which heat load analysis is based on
the ASHRAE transfer function method for load calculations and detailed 8760 hour-by-hour
simulation techniques for the energy analysis.

Page 9 of 70

1.3. Definitions and Abbreviations


1.3.1. Definitions
PROJECT

HVAC PACKAGE FOR THIEN UNG WELLHEAD PLATFORM

COMPANY

The party which initiates the project and ultimately pays for its design
and construction and owns the facilities. Here the COMPANY is
Vietsovpetro
(Referred to as VSP)

CONTRACTOR

The party which carries out all or part of the design,


engineering,
procurement, construction and commissioning of the project.

VENDOR

The party on which the order or contract for supply of the


equipment/ package or services is placed.

SHALL

Indicates a mandatory requirement.

SHOULD

Indicates a recommendation.

1.3.2. Abbreviations
AMB
BK-TNG
CLTD
DB
DE
FA
GSH
GTH
L/S
OA
PVE
RA
RH
RLH
RSH
SA
SC
SCL
VSP
WB

Ambient
Thien Ung Wellhead Platform
Cooling Load Temperature Defferece
Dry Buld
Detail Engineering
Fresh Air
Grand Sensible Heat
Grand Total Heat
Liters per second
Outside Air
Relative
Return Air
Relative Humidity
Room Latent Heat
Room Sensible Heat
Supply Air
Shading Coefficient
Solar Cooling Load
Vietsovpetro
Wet Bulb

Page 10 of 70

1.4. Reference Documents


1.4.1. International Codes and Standards
The HVAC systems calculation, equipment selection and operation are to be in accordance
with the codes and standards listed below and shall include any other document referenced.
The latest editions, as of the purchase order date, of the referenced Codes, Standards,
Specifications and Regulations are considered part of this calculation.
ADFD

ASHRAE Duct Fitting Database Program version 5.0- Consult


Duct Design chapter in the ASHREA Fundamentals
Handbook.

API RP 505

Recommended Practice for Classification of Location for


Electrical Installations at Petroleum Facilities.

ASHRAE

ASHRAE Handbook Fundamentals.

ASHRAE

Ventilation Standards.

Standard 62
EN 50272-2

Safety requirements for secondary batteries and battery


installations Stationary batteries.

ISO 15138:2007

Petroleum and natural gas industries "Offshore production


installations. Heating, Ventilation and Air-conditioning".

NFPA 105

Standard for Smoke Door Assemblies and Other Opening


Protectives.

NFPA 496

Purged and pressurized enclosures for electrical equipment.

SMACNA

Sheet Metal and Air conditioning Contractors National Engineers.

Page 11 of 70

1.4.2. Project Specifications and other Documents.


BK.TNG-001-TS-PR-GEN-001

Process and Utilities Design Basis

BK.TNG-002-GEN-SA-RPT-0001

Project Safety plan

BK.TNG-002-GEN -SA-RPT-0002

HSE Design Basis

BK.TNG-002-GEN-SA-PHL-001

Hazardous Area Classification Philosophy

BK.TNG-002-TS-IN-SP-0003

Specification for Fire and Gas System (FGS)

BK.TNG-002-TS-IN-RPT-0001

Instrument Design Basis.

BK.TNG-002-TS-EL-RPT-0001

Electrical Design Basis.

BK.TNG-002-TS-PI-DW-0101

Equipment Arrangement Plan Upper Deck.

BK.TNG-002-TS-PI-DW-0102

Equipment Arrangement Plan Main Deck.

BK.TNG-002-TS-PI-DW-0103

Equipment Arrangement Plan Mezz. Deck.

BK.TNG-002-TS-PI-DW-0104

Equipment Arrangement Plan Cellar Deck.

BK.TNG-002-TS-PI-DW-0105

Equipment Arrangement Plan Sump Deck.


Equipment Arrangement Plan Elevation View

BK.TNG-002-TS-PI-DW-0106

Looking North.
Equipment Arrangement Plan Elevation View

BK.TNG-002-TS-PI-DW-0107

Looking West.

BK.TNG-002-TS-ME-RPT-0003

BK.TNG-002-TS-ME-DW-0004
BK.TNG-002-TS-ME-DW-0001

HVAC Design Philosophy and Design Basis Technical building.


HVAC Overall Duct and Instrumentation
Diagram - Technical building.
HVAC Equipment Layout - Technical Building.

Page 12 of 70

2. SUMMARY OF AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS


Air cooled
chiller

Total load
(kW)

Entering Water
Temperature (oC)

Leaving Water
Temperature (oC)

Water flow rate


(l/s)

50HC01A/B

351.0

12.8

7.2

17.5

Chilled water pump

Water flow rate (l/s)

Pressure (bar)

50P01A/B

17.5

3.0

Room

Total
load
(kW)

Sensible
load (kW)

Air flow
rate (l/s)

Ex. Static
Pressure
(Pa)

Central control room


Instrument equipment room

84.2

47.6

2893

900

50HH02A/B

Switchgear room Battery


room Emergency
Switchgear room

249.0

130.2

6424

1300

50HH03A/B

Instrument / Electrical
Workshop

17.8

5.9

490

300

Air Handling
units

50HH01A/B

Fan

Room / System

Air flow
rate (l/s)

Fan type

External Static
Pressure (Pa)

50HF01A/B

Purging fan AHU 50HH01A/B

2893

Exhaust fan

200

50HF02A/B

Purging fan FCU 50HH03A/B

490

Exhaust fan

100

50HF03A/B

Mechanical workshop

861

Exhaust fan

200

50HF04A/B

Transformer room

6113

Exhaust fan

250

50HF05A/B

Purging fan AHU 50HH02A/B

5867

Exhaust fan

700

50HF06A/B

Battery room

678

Exhaust fan

150

Page 13 of 70

3. DESIGN BASIS
A minimum of 800 l/s of fresh air are introduced into the system to provide pressurization. These
amounts are generally sufficient to cater for leakages and also providing fresh air for the
personnel. Except for Battery room where the amount of fresh air will have to replace the air
exhausted out where 100% fresh air will be supplied.
A minimum of 50% electrical loads are assumed to be working at all time. No heater will
be provided if the heating requirement is less than 50% of internal loads.
An additional safety factor of 10 % (sensible) and 10 % (latent) heat gain shall be provided in
this calculation.
Values used for solar heat gain are based on peak hour periods.
Internal loads used are assumed to occur or coincided at the peak load condition. Sensible and
latent heat gain for peoples shall be included in this heat load calculation.
Bypass factor (BF) used for the cooling coil is 0.10 and is industry standard for typical comfort
application.
Winter design heating calculation was done to give the required heater capacity during
the minimum temperature condition. The calculation will provide the heater size when there is
no space load on the system. The given heater size will maintain design temperature and
humidity range.
Part load condition may also be calculated from Air System Design Load Summary Table.
The heat gain estimation from lighting is considered in this calculation. Lighting power densities
is 20W/m2.

Page 14 of 70

4. DESIGN CONDITION
4.1. External Ambient Design Condition (All Year)
Dry bulb (oC)

Wet bulb (oC)

Relative humidity (%)

Maximum condition

39

38.7

98

Minimum condition

21

16.2

62

Description

4.2. Internal Design Condition


Internal design conditions shall be as follows:
Room

Temperature Relative humidity


RH (%)
DB (oC)

Room pressure
(Pa)

Central Control room

24 2

35-75

+50

Instrument equipment room

24 2

35-75

+50

Emergency Switchgear room

24 2

35-75

+50

Switchgear room

24 2

35-75

+50

Max. 24

NC

Slightly negative

Instrument / Electrical workshop

24 2

35-75

+25

Transformer room

AMB+5

NC

Slightly negative

NC

NC

Slightly negative

Battery room

Mechanical workshop
NC = Not controlled
5. FRESH AIR VETILATION SYSTEM

Fresh air requirement for HVAC system shall be the greater value of the following two criteria:
Total fresh air required per standard (The fresh air supply shall be 8.5 liters per second per
occupant for manned areas).
Fresh air requirement as total exhaust air (mechanical exhaust air plus leakages) for pressure
room >0Pa.
Fresh air requirement as total exhaust air (mechanical exhaust air except infiltration air) for
pressure room <0Pa.
The air change rate for Battery room (BR) shall meet the larger value of the following two criteria:
Room air changes per hour as per API RP 505 standard (12 ACH). Minimum expelled air due
to the gas emission from battery, based on EN 50272-2 standard.
Transformer Room (TR) and Mechanical Workshop shall be forced ventilated, exhaust system
are required to ventilate the spaces in order to dissipate heat and expel foul air.

Page 15 of 70

6. U-VALUES (TRANSMISSION COEFFICIENT)


The following U-Values calculation shall be used in this calculation document.
Wall detail - W1 (A60 Rated wall)
Wall Details
Outside Surface Color .......................................... Dark
Absorptivity .......................................................... 0.900
Overall U-Value ................................................... 0.384 W/(m-K)
Wall Layers Details (Inside to Outside)
Layers
Inside surface resistance
Wall panel
Air space
Insulation
Crimped plate
Outside surface resistance
Totals

Thickness
mm
0.000
25.000
139.000
60.000
6.000
0.000
230.000

Density
kg/m
0.0
30.0
1.2
160.0
7830.0
0.0
-

Specific Ht.
kJ / (kg - K)
0.00
0.92
0.00
0.84
0.50
0.00

R-Value
(m-K)/W
0.12064
0.62500
0.15000
1.66670
0.00010
0.04410
2.60654

Weight
kg/m
0.0
0.8
0.2
9.6
47.0
0.0
57.5

Specific Ht.
kJ / (kg - K)
0.00
0.84
0.50
0.00

R-Value
(m-K)/W
0.12064
1.66670
0.00010
0.04410
1.83154

Weight
kg/m
0.0
9.6
47.0
0.0
56.6

Specific Ht.
kJ / (kg - K)
0.00
0.84
0.50
0.00

R-Value
(m-K)/W
0.12060
1.66670
0.00010
0.12060
1.90800

Weight
kg/m
0.0
9.6
47.0
0.0
56.6

Wall detail - W2 (A60 wall)


Wall Details
Outside Surface Color .......................................... Dark
Absorptivity .......................................................... 0.900
Overall U-Value ................................................... 0.546 W/(m-K)
Wall Layers Details (Inside to Outside)
Layers
Inside surface resistance
Insulation
Crimped plate
Outside surface resistance
Totals

Thickness
mm
0.000
60.000
6.000
0.000
66.000

Density
kg/m
0.0
160.0
7830.0
0.0
-

Wall detail - W3 (A60 - Partition wall)


Wall Details
Outside Surface Color .......................................... Dark
Absorptivity .......................................................... 0.900
Overall U-Value ................................................... 0.524 W/(m-K)
Wall Layers Details (Inside to Outside)
Layers
Inside surface resistance
Insulation
Crimped plate
Outside surface resistance
Totals

Thickness
mm
0.000
60.000
6.000
0.000
66.000

Density
kg/m
0.0
160.0
7830.0
0.0
-

Page 16 of 70

Floor detail - F1 (Floor without ceiling)


Roof Details
Outside Surface Color .......................................... Dark
Absorptivity .......................................................... 0.900
Overall U-Value ................................................... 0.524 W/(m-K)
Roof Layers Details (Inside to Outside)
Layers
Inside surface resistance
Crimped plate
Insulation
Outside surface resistance
Totals

Thickness
mm
0.000
10.000
60.000
0.000
70.000

Density
kg/m
0.0
7830.0
160.0
0.0
-

Specific Ht.
kJ / (kg - K)
0.00
0.50
0.84
0.00

R-Value
(m-K)/W
0.12064
0.00020
1.66670
0.12064
1.90818

Weight
kg/m
0.0
78.3
9.6
0.0
87.9

Specific Ht.
kJ / (kg - K)
0.00
0.50
0.00
0.50
0.84
0.00

R-Value
(m-K)/W
0.12064
0.00010
0.28680
0.00020
1.66670
0.12060
2.19504

Weight
kg/m
0.0
47.0
0.7
78.3
96.0
0.0
222.0

Specific Ht.
kJ / (kg - K)
0.00
0.50
0.00
0.50
0.84
0.00
0.92
0.00

R-Value
(m-K)/W
0.12064
0.00010
0.30680
0.00020
1.66670
0.38000
0.06250
0.12060
2.65754

Weight
kg/m
0.0
47.0
0.9
78.3
9.6
1.1
6.4
0.0
143.2

Floor detail - F2 (Raise floor)


Roof Details
Outside Surface Color .......................................... Dark
Absorptivity .......................................................... 0.900
Overall U-Value ................................................... 0.456 W/(m-K)
Roof Layers Details (Inside to Outside)
Layers
Inside surface resistance
Raise floor
Air space
Crimped plate
Insulation
Outside surface resistance
Totals

Thickness
mm
0.000
6.000
624.000
10.000
60.000
0.000
700.000

Density
kg/m
0.0
7830.0
1.2
7830.0
1600.0
0.0
-

Floor detail - F3
Roof Details
Outside Surface Color .......................................... Dark
Absorptivity .......................................................... 0.900
Overall U-Value ................................................... 0.376 W/(m-K)
Roof Layers Details (Inside to Outside)
Layers
Inside surface resistance
Raise floor
Air space
Crimped plate
Insulation
Air space
Ceiling panel
Outside surface resistance
Totals

Thickness
mm
0.000
6.000
724.000
10.000
60.000
900.000
10.000
0.000
1710.000

Density
kg/m
0.0
7830.0
1.2
7830.0
160.0
1.2
640.0
0.0
-

Page 17 of 70

7. ELECTRICAL AND INSTRUMENT HEAT DISSIPATION


Item

1
2
3
4

1
2
3
4
5
6
7
8
9
10

1
2
3
4

HEAT DISSIPATION IS UPDATED FOR BATERRY ROOM ONLY. KINDLY SEE


ATTACHMENT FOR :
- TRANFORMER ROOM
- EMERGENCY SWITCHGEAR ROOM
- MAIN SWITCHGEAR ROOM

Equipment
Transformer room
6.0/0.42kV Transformer 2.0MVA
6.0/0.42kV Transformer 2.0MVA
6.0/0.42kV Transformer 2.0MVA
6.0/0.42kV Transformer 2.0MVA
Subtotal
Battery room
230V AC UPS Battery Bank A
230V AC UPS Battery Bank B
Battery for Navaid system
120V DC Battery for GTG A
120V DC Battery for GTG B
Battery for Gas compressor
Battery Isolating Switch for 230V AC UPS Battery Bank A
Battery Isolating Switch for 230V AC UPS Battery Bank B
Battery Isolating Switch for DH compressor
Battery information:
- Number of cells
- Battery type
Subtotal
Emergency Switchgear room
LV Switchboard/MCC
400/230V AC UPS A/B
UPS DB
DC Starter Panel (GTG A)

Heat
Sum of heat
Diversity
Quantity dissipation
dissipation Remarks
factor
per unit (W)
(W)
Note 1
1
38,500
0.5
8,500
1
38,500
0.5
8,500
1
38,500
0.5
8,500
1
38,500
0.5
8,500
34,000
Note 1
1
292
1
292
1
292
1
292
1
12
1
11.5
1
2
1
2
1
2
1
2
1
12
1
11.5
1
66
1
66
1
66
1
66
1
31
1
31
364 cells
Lead Acid VRLA cells

Page 18 of 70

774
Note 1
1
1
1
1

5796
11693
1,100
22

0.8
1
1
1

4637
11693
1100
22

5
6
7
8
9
10
11
12
13
14
15
17
18
20
21
22
23
24
25

1
2
3
4
5
6

DC Starter Panel (GTG B)


120VDC Battery Charger (GTG A)
120VDC Battery Charger (GTG B)
VFD Panel (GTG A)
VFD Panel (GTG B)
Line Reactor (Input) for VFD Panel GTG A
Line Reactor (Input) for VFD Panel GTG B
400/230V Emergency Lighting & Small Power Transformer
400/230V Emergency Lighting & Small Power Transformer
Emergency Lighting & Small Power Distribution Board
Navaid Control Panel and Distribution Board
Aeronautical Obstruction Light Control Panel
Unit Control Panel for Emergency Diesel Generator
Charger for Gas Compressor
HVAC Control Panel
HVAC Emergency Panel
Fuel Gas Pre-Heater Control Panel
Fuel Gas Super Heater Control Panel
HP flare KO drum heater control panel
Subtotal
Main Switchgear room
6.6kV switchboard
400V LV Switchgear/MCC 01
400V LV Switchgear/MCC 02
Daihung MCC
ECS control cabinet
MOV Distribution Board [HOLD]

Page 19 of 70

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

22
198
198
10
10
4
4
2,530
2,530
1,100
853
994
891.5
197.5
1,865
1,425
711
711
84

1
1
1
1
1
1
1
1
1
1
1
1
1
1
0.8
0.8
1
1
1

22
198
198
10
10
4
4
2530
2530
1100
853
994
892
198
1492
1140
711
711
84
31,132
Note 1

1
1
1
1
1
1

7,026
4,983
6,666
4,983
2,130
1,100

0.8
0.8
0.8
0.8
0.8
1

5,621
3,986
5,333
3,986
1,704
1,100

Heat Tracing Distribution Board

1,100

1,100

Wet Gas Heater Control Panel

1,374

1,374

10

Condensate Water Heater Control Panel

714

714

11

TEG Reboiler Heater control panel

1,374

1,374

12

Closed drain vessel heater control panel

76

76

13

400/230V Normal Lighting & Heat Tracing Transforme

2,530

2,530

14

400/230V Normal Lighting & Heat Tracing Transforme

2,530

2,530

15

HVAC Normal Panel

2,415

0.8

1,932

Subtotal

34,460

Instrument equipment room


1

Network Cabinet

1,540

1,540

DCS System Cabinet

815

815

1110

DCS Mashalling Panels

815

1,630

340

FGS System Cabinet

900

1,800

1110

FGS Mashalling Panels

900

2,700

340

ESD System Cabinet

980

1,960

1100

ESD Mashalling Panels


Centralised Machine Monitoring System
Workstation
Sand Detection System

980

2,940

340

370

370

1100

1,100

10

Export Gas Metering System Cabinet

1,750

1,750

11

Export Condensate Metering System Cabinet

1,750

1,750

12

DH Gas Metering System Cabinet

700

700

13

FM 200 System

1,120

1,120

14

PAGA System B Cabinet

2,478

2,478

15

Gas Turbine Generator UCP#1

560

560

16

Gas Turbine Generator UCP#2

560

560

17

Export Gas Compressor UCP (Future)

560

560

18

Misc. Load 1

770

770

19

Misc. Load 2

210

8
9

Subtotal

210
25,313 21718

Page 20 of 70

1
2
3
4
5
6
7
8
9
10

Central Control room


Operator Workstation
Engineering Workstation for DCS
Engineering Workstation for ESD/FGS
SOE Server / Workstation
DTCS Server
AMS Server / Workstation
FGS mimic panel
Printer
OPS Console for ESD
OPS Console for FGS
Subtotal

5
1
1
1
1
1
1
4
1
1

350
350
350
350
350
350
350
137
200
200

1
1
1
1
1
1
1
1
1
1

Notes:
1) For detail of heat dissipation values, refer to Electrical equipment list BK.TNG-002-TS-EL-SCH-001

Page 21 of 70

1,750
350
350
350
350
350
350
137
200
200
4,798

8. HVAC LOAD CALCULATION


8.1. Summary of space & system input data & output data.
ROOM BOOK DATA SHEET

ea
ACH
AC
MV

Project: Thien Ung Wellhead Platform


Rev: E
Date: 22-Jan-16

- Each
- Air change per hour
- Air conditioner
- Mechanical ventilation

- Input data
- Output data

Input Datasheet

Room Noise

Room Pressure

35-75

<65

50

Instrument equipment room

AC

11.5

6.9

3.3

3.3

242

35-75

<65

Emergency room

AC

12.5

7.7

5.1

3.8

242

35-75

Main switchgear room

AC

12.5

13.7

5.1

3.8

242

35-75

Battery room

3.7

5.1

3.8

Max.24

ACMV 12.5

Roof

Floor

4.2

0.35

83

1.8

79

1.8

<65

50

31132

24

8.5

12

2.1

11

4.2

0.35

106

1.8

<65

50

34460

24

8.5

12

2.1

11

4.2

0.35

152

1.8

171

<65

(-)

774

24

12

2.1

11

4.2

0.35

123

1.8

46

<65

25

Instrument Electric workshop

AC

4.7

9.2

4.3

4.3

242

1000

24

Transformer room

MV

12.5

6.0

3.5

3.5

<85

34000

24

Mechanical workshop

MV

4.7

9.2

4.3

4.3

<85

24

No.

Person

12
8.5
15

Effective Air
Leakage Area

Leakage Area

11

Effective Air
Leakage Area

2.1

Leakage Area

1.8

Effective Air
Leakage Area

53

Door Area

1.8

No.

68

Effective Air
Leakage Area

0.35

Door Area

4.2

Effective Air
Leakage Area

10%

Air Change

m2 cm2/m2 m2 cm2/m2 m2 cm2/m2 m2

11

Equipment
Heatload

m2 cm2/m2 ea
2.1

50

2
W/m2 L/s ACH cm /ea ea
24
8.5
12
1
25313 24
8.5
12
1

4798

35-75

Wall

Leakage air Safety Factor

Humidity

Pa

3.3

Double Door

Leakage Area

Room
Temperature

dBA

3.3

o
C
242

4.6

Light Heatload

Person No.

11.5

Ceiling Height

AC

Height

Central control room

Room Name

Width

Length
m

1.8

96

1.1

1.8

171

1.1

1.8

46

1.1

12

2.1

11

4.2

0.35

120

1.8

43

1.8

43

1.1

2.1

11

4.2

0.35

130

1.8

75

1.8

75

1.1

12

2.1

11

4.2

0.35

120

1.8

43

1.8

43

1.1

North West

South West
m

38.0
38.0
47.5
47.5
47.5
20.2
43.8
20.2

15.2
22.8
29.3
52.1
14.1
39.6
21.0
39.6

Page 22 of 70

cm

177.3
329.3
256.6
727.3
267.8
243.7
373.5
255.7

Fresh Air Flow


Requirement

15.2
22.8
29.3
52.1
14.1
39.6
21.0
39.6

Total Exhaust Air


Flow

Mechanical
Exhaust Air Flow

38.0
38.0
47.5
47.5
47.5
20.2
43.8
20.2

Infiltraintion

m3

174.6
261.9
365.8
650.8
175.8
185.9
262.5
185.9

1.1
1.1

12

Exfiltraintion
/Leakages

m2

52.9
79.4
96.3
171.3
46.3
43.2
75.0
43.2

South East

Central control room


Instrument equipment room
Emergency room
Main switchgear room
Battery room
Instrument Electric workshop
Transformer room
Mechanical workshop

North East

1
2
3
4
5
6
7
8

Room Cubic

Room Name

Room Area

No.

55

Output Datasheet
Wall Area

Total Building Air


Leakage Area

No.

Single Door

Ventilation

System

Room Dimension (m)

L/s

L/s

L/s

L/s

L/s

115.7
214.9
167.4
345.2
112.5
-

55.3
-

600
6,018
775

116
215
167
345
545
112
6,100
775

Remarks

116
215
167
345
545 100% FA
112
6,100 Ambient + 5oC
775 100% FA

Note:
1. Total outdoor air required shall be based on fresh air required for human.
Reference from ASHRAE standard 62.1-2010 "Ventilation for Acceptable Indoor Air Quality",
Table 6.1: Minimum Ventilation Rates in Breathing Zone.
2. Leakage area required shall be based on area of door, wall, floor and roof.
- 2001 ASHRAE Handbook - HVAC Fundamentais, Chapter 26 - Ventilation and Infiltration.
- 2007 ASHRAE Handbook - HVAC Applications, Chapter 52 - Fire and Smoke Management.
3. Required ventilation air shall be based on either directly exhaust air plus exfiltration air or outdoor air required based on ASHRAE
standard 62.1-2010 requirement, whichever is higher.
4. Conditioned supply air shall be selected based on minimum required air change per hour per room or calculated airflow based on
heat load requirements, whichever is higher.
5. Ventilation for Battery room based on below equation (EN 50272-2):
Flow rates (m3/h) = 0.05 m3/Ah * n * Igas (mA/Ah) * Crt (Ah) *10-3
n = 364 cells- number of cells
Igas = 8 mA/Ah - Current producing gas
Crt = 1200 Ah - Rated capacity
6. Number of Air Change per Hour is selected based on Ashrae Application 2007
7. Abbreviations:
AC - AIR CONDITIONED
MV - MECHANICAL VENTILATION
ACH - AIR CHANGE PER HOUR
OA - OUTDOOR AIR
8. Formula for calculating flow rate based on number of Air Change per Hour:
Flow rates (L/s) = Room volume (m3) * ACH/3.6
9. Formula for calculating flow rate based on sensible heat gains from equipment loads
Flow rates (L/s) = Sensible load (W) / {Specific heat (kJ/kg.K) * Density (kg/m3) * Delta T (K)}
Specific heat = 1.007 kJ/kg.K at 41.5 deg. C
Density = 1.122 kg/m3 at 41.5 deg. C and 98% RH
Delta T = 5(K), Design room max. 44 deg. C (Ventilation only).

Page 23 of 70

8.2. Design weather parameters and maximum solar heat gains.


For design weather parameters and maximum solar heat gains see ATTACHMENT A
8.3. Heat load analysis.
For Air Handling Unit 50HH01A/B, see ATTACHMENT B
For Air Handling Unit 50HH02A/B, see ATTACHMENT C
For Air Handling Unit 50HH03A/B, see ATTACHMENT D
For Chiller Plant 50HC01A/B, see ATTACHMENT E
9. PRELIMINARY DATA FOR EQUIPMENT SIZING
On-coil temp.
AHUs/FCUs DB/WB (oC)

Off-coil Temp.
DB/WB (oC)

Total load
(kW)

Sensible
load
(kW)

Chilled
water
(l/s)

50HH01A/B

25.6 / 20.4

12.6 / 12.2

81.5

45.3

4.5

50HH02A/B

26.2 / 20.9

9.4 / 9.2

249.3

130.4

12.0

50HH03A/B

27.2 / 25.5

16.2 / 16.1

6.4

1.0

18.4

Update the new heat load from 21718kW up to 25313kW of Instrument Equipment Room.
Following VSP request.
On-coil temp.
AHUs/FCUs DB/WB (oC)

Off-coil Temp.
DB/WB (oC)

Total load
(kW)

Sensible
load
(kW)

Chilled
water
(l/s)

50HH01A/B

25.7/20.2

12.0/11.6

84.2

47.6

4.5

50HH02A/B

26.3 / 21

9.5 / 9.3

249.0

130.2

12.0

50HH03A/B

27.0 / 25.9

5.9

1.0

17.3 / 17.3

17.8

Chiller Sizing
Cooling Capacity (min)

350 kW 351.0 kW

Chilled Water Flow rate (min)

17.5 l/s

Entering/Leaving Water Temperature

12.8 C / 7.2 C

Page 24 of 70

10. CONCLUSION
Equipment shall be sized to maximum ambient condition of 39 C and minimum ambient of
21 C. No heaters were added due to the assumption that at least 50% of internal load are
available at all times. The result shows that the amount of re-heat requirement for
humidity/temperature control are less than the available internal heat load.

Page 25 of 70

ATTACHMENT A: DESIGN WEATHER PARAMETERS AND


MAXIMUM SOLAR HEAT GAINS

Page 26 of 70

Design Parameters:
City Name .......................................................................................... BK.TNG Platform
Location ............................................................................................................. Vietnam
Latitude .................................................................................................................... 10.8
Longitude .............................................................................................................. -108.0
Elevation .................................................................................................................. 14.2
Summer Design Dry-Bulb ......................................................................................... 39.0
Summer Coincident Wet-Bulb .................................................................................. 38.7
Summer Daily Range ................................................................................................. 8.2
Winter Design Dry-Bulb ............................................................................................ 21.0
Winter Design Wet-Bulb ........................................................................................... 16.2
Atmospheric Clearness Number ............................................................................... 1.00
Average Ground Reflectance ................................................................................... 0.20
Soil Conductivity ..................................................................................................... 1.385
Local Time Zone (GMT +/- N hours) ......................................................................... -7.0
Consider Daylight Savings Time ................................................................................ No
Simulation Weather Data ................................................................................. noneN/A
Current Data is ........................................................................................ User Modified
Design Cooling Months .............................................................. January to December

Deg.
Deg.
m
C
C
K
C
C

W/(m-K)
hours

Design Day Maximum Solar Heat Gains


(The MSHG values are expressed in W/m )
Month
January
February
March
April
May
June
July
August
September
October
November
December
Month
January
February
March
April
May
June
July
August
September
October
November
December

N
99.2
105.9
114.1
126.5
201.4
249.4
209.7
134.5
118.4
108.9
100.8
96.1
SSW
665.3
544.9
371.8
188.6
125.9
125.7
128.6
182.3
368.3
531.5
652.3
699.0

NNE
99.2
105.9
201.1
350.4
440.7
471.5
439.2
346.4
193.1
108.9
100.8
96.1
SW
776.4
715.3
601.2
444.4
325.9
274.9
311.9
424.5
573.6
681.9
760.4
779.5

NE
215.3
344.0
472.6
563.3
609.0
614.6
597.3
543.0
455.5
334.9
208.7
165.3
WSW
793.7
783.5
729.3
625.3
540.3
498.5
522.0
599.9
702.0
755.0
771.0
782.3

ENE
473.7
572.3
654.6
685.9
686.2
670.8
665.7
654.9
634.1
575.2
489.4
445.1
W
687.9
730.8
746.7
710.3
665.5
637.5
645.8
684.0
724.1
720.7
683.4
666.0

Mult. = User-defined solar multiplier factor.

Page 27 of 70

E
686.5
735.5
737.2
703.5
659.3
627.2
636.5
668.5
716.0
718.6
676.7
647.6
WNW
473.9
577.3
650.2
687.9
692.1
682.7
675.0
666.3
635.7
575.2
489.2
443.8

ESE
793.3
786.1
723.2
613.5
533.1
489.7
514.1
589.0
688.1
750.9
764.5
780.2
NW
214.9
346.4
464.9
562.4
615.0
626.3
604.4
549.9
450.1
332.2
201.3
159.3

SE
777.0
715.1
599.6
434.1
320.7
270.5
306.4
418.8
572.1
684.6
764.9
792.2
NNW
99.2
105.9
200.9
343.2
445.6
477.6
443.6
344.2
184.6
108.9
100.8
96.1

SSE
665.2
546.3
375.0
191.9
126.0
125.8
128.6
184.5
368.7
530.6
648.9
698.6
HOR
831.6
902.0
933.5
911.1
879.0
856.6
860.8
886.9
908.2
890.7
833.2
800.6

S
552.8
395.4
209.7
125.1
124.9
122.6
126.9
130.6
212.9
388.0
548.0
604.6
Mult
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

ATTACHMENT B: SPACE INPUT DATA

Page 28 of 70

Lack input data for:


- Transformer room
- ME workshop

Battery
1. General Details:
Floor Area ............................................................. 46.3
Avg. Ceiling Height .................................................. 3.8
Building Weight ................................................... 341.8
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 ................................................. 100
OA Requirement 2 .................................................. 0.0
Space Usage Defaults ASHRAE Standard 62.1-2007

m
m
kg/m

As per point 3.1of "


1014-BKTNG-ME-RPT-0004_Rev 0 - HVAC
Calculations-Technical building": Lighting density
is 20W/m^2

% of supply air
L/s

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................. Recessed (Unvented)
Wattage ............................................................... 24.00 W/m
Ballast Multiplier .................................................... 1.00
Schedule ........................................................ Lighting

2.4. People:
Occupancy .............................................................. 0.0 Person
Activity Level ........................................ Medium Work
Sensible ................................................................. 86.5 W/person
Latent .................................................................. 133.3 W/person
Schedule ............................................................. None
2.5. Miscellaneous Loads:
Sensible ...................................................................... 0 W
Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

2.2. Task Lighting:


Wattage ................................................................. 0.00 W/m
Schedule ............................................................. None

2.3. Electrical Equipment:


Wattage ............................................................... 774.0 Watts
Schedule ................................................ Equipment E

Kindly update data

3. Walls, Windows, Doors:


Exp.

Wall Gross Area (m)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

NE

47.5

SE

14.1

3.1. Construction Types for Exposure NE


Wall Type ........................ Wall detail - W1 (A60 Rated wall)
Door Type .......................................................... Single door
3.2. Construction Types for Exposure SE
Wall Type ................................... Wall detail - W2 (A60 wall)
Door Type ........................................................... Doubl door

Kindly check wall at NW (H60)

4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details:
Partition Type ........................................ Wall Partition
Area ....................................................................... 14.2
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9
Ambient at Space Max Temp ................................ 35.0
Uncondit. Space Min Temp ................................... 23.9
Ambient at Space Min Temp ................................. 21.0

7.2. 2nd Partition Details:


(No partition data).
m
W/(m-K)
C
C
C
C

partition is in 3 sides: NE,


SE, NW (H60). Kindly
check and revise

Page 29 of 70

2nd partition is available wirh


46.3 m^2 (ceiling ). Kindly
check and revise

Central Control Room


1. General Details:
Floor Area ............................................................. 52.9
Avg. Ceiling Height .................................................. 3.3
Building Weight ................................................... 341.8
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 8.5
OA Requirement 2 ................................................ 0.00
Space Usage Defaults ASHRAE Standard 62.1-2007

m
m
kg/m

L/s/person
L/(s-m)

As per point 3.1of "


1014-BKTNG-ME-RPT-0004_Rev 0 - HVAC
Calculations-Technical building": Lighting density
is 20W/m^2

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................. Recessed (Unvented)
Wattage ............................................................... 24.00 W/m
Ballast Multiplier .................................................... 1.00
Schedule ........................................................ Lighting

2.4. People:
Occupancy .............................................................. 4.0 People
Activity Level ..................................... Sedentary Work
Sensible ................................................................. 82.1 W/person
Latent .................................................................... 79.1 W/person
Schedule .......................................................... People

2.2. Task Lighting:


Wattage ................................................................. 0.00 W/m
Schedule ............................................................. None

2.5. Miscellaneous Loads:


Sensible ...................................................................... 0 W
Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

2.3. Electrical Equipment:


Wattage ............................................................. 4798.0 Watts
Schedule ................................................ Equipment E

Kindly update data


3. Walls, Windows, Doors:
Exp.

Wall Gross Area (m)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

NE

38.0

SE

15.2

3.1. Construction Types for Exposure NE


Wall Type ........................ Wall detail - W1 (A60 Rated wall)
Door Type ........................................................... Doubl door

Shall be SW

- Double door at NE
- Single door at SW

3.2. Construction Types for Exposure SE


Wall Type ................................... Wall detail - W2 (A60 wall)
Door Type .......................................................... Single door
4. Roofs, Skylights:
(No Roof or Skylight data).

Kindly check wall at NW (H60)

5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................. 52.9
Total Floor U-Value ............................................. 0.524
Unconditioned Space Max Temp. ......................... 23.9
Ambient at Space Max Temp. ............................... 35.0
Unconditioned Space Min Temp. .......................... 23.9
Ambient at Space Min Temp. ................................ 21.0
7. Partitions:
7.1. 1st Partition Details:
Partition Type ........................................ Wall Partition
Area ....................................................................... 15.2
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9
Ambient at Space Max Temp ................................ 35.0
Uncondit. Space Min Temp ................................... 23.9
Ambient at Space Min Temp ................................. 21.0

m
W/(m-K)
C
C
C
C

m
W/(m-K)
C
C
C
C

Floor partition
7.2. 2nd Partition Details:
Partition Type ................................... Ceiling Partition
Area ....................................................................... 46.2
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9
Ambient at Space Max Temp ................................ 35.0
Uncondit. Space Min Temp ................................... 23.9
Ambient at Space Min Temp ................................. 12.8

partition is in 3 sides: NE,


SW, NW (H60). Kindly
check and revise

Page 30 of 70

m
W/(m-K)
C
C
C
C

Emergency Switchgear
1. General Details:
Floor Area ............................................................. 96.3
Avg. Ceiling Height .................................................. 3.8
Building Weight ................................................... 341.8
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 8.5
OA Requirement 2 ................................................ 0.00
Space Usage Defaults ASHRAE Standard 62.1-2007

m
m
kg/m

L/s/person
L/(s-m)

As per point 3.1of "


1014-BKTNG-ME-RPT-0004_Rev 0 - HVAC
Calculations-Technical building": Lighting density
is 20W/m^2

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................. Recessed (Unvented)
Wattage ............................................................... 24.00 W/m
Ballast Multiplier .................................................... 1.00
Schedule ........................................................ Lighting

2.4. People:
Occupancy .............................................................. 2.0 People
Activity Level ..................................... Sedentary Work
Sensible ................................................................. 82.1 W/person
Latent .................................................................... 79.1 W/person
Schedule .......................................................... People

2.2. Task Lighting:


Wattage ................................................................. 0.00 W/m
Schedule ............................................................. None

2.5. Miscellaneous Loads:


Sensible ...................................................................... 0 W
Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

2.3. Electrical Equipment:


Wattage ........................................................... 31132.0 Watts
Schedule ................................................ Equipment E

Kindly update data

3. Walls, Windows, Doors:


Exp.

Wall Gross Area (m)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

SE

29.3

3.1. Construction Types for Exposure SE


Wall Type ................................... Wall detail - W2 (A60 wall)
Door Type ........................................................... Doubl door

Kindly check wall at NW (H60)

4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ....................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details:
Partition Type ........................................ Wall Partition
Area ....................................................................... 29.3
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9
Ambient at Space Max Temp ................................ 35.0
Uncondit. Space Min Temp ................................... 23.9
Ambient at Space Min Temp ................................. 21.0

7.2. 2nd Partition Details:


(No partition data).
m
W/(m-K)
C
C
C
C

partition is in 2 sides: SE,


NW (H60). Kindly check
and revise

Page 31 of 70

2nd partition is available wirh


96.3 m^2 (ceiling ). Kindly
check and revise

Instrument Equipment R.
1. General Details:
Floor Area ............................................................. 79.4
Avg. Ceiling Height .................................................. 3.3
Building Weight ................................................... 341.8
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 8.5
OA Requirement 2 ................................................ 0.00
Space Usage Defaults ASHRAE Standard 62.1-2007

m
m
kg/m

L/s/person
L/(s-m)

As per point 3.1of "


1014-BKTNG-ME-RPT-0004_Rev 0 - HVAC
Calculations-Technical building": Lighting density
is 20W/m^2

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................. Recessed (Unvented)
Wattage ............................................................... 24.00 W/m
Ballast Multiplier .................................................... 1.00
Schedule ........................................................ Lighting

2.4. People:
Occupancy .............................................................. 4.0 People
Activity Level ..................................... Sedentary Work
Sensible ................................................................. 82.1 W/person
Latent .................................................................... 79.1 W/person
Schedule .......................................................... People

2.2. Task Lighting:


Wattage ................................................................. 0.00 W/m
Schedule ............................................................. None

2.5. Miscellaneous Loads:


Sensible ...................................................................... 0 W
Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

2.3. Electrical Equipment:


Wattage ........................................................... 25313.0 Watts
Schedule ................................................ Equipment E
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (m)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

SE

22.8

3.1. Construction Types for Exposure SE


Wall Type ........................ Wall detail - W1 (A60 Rated wall)
Door Type ........................................................... Doubl door

Kindly check wall at NW (H60)

4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................. 79.4
Total Floor U-Value ............................................. 0.524
Unconditioned Space Max Temp. ......................... 23.9
Ambient at Space Max Temp. ............................... 35.0
Unconditioned Space Min Temp. .......................... 23.9
Ambient at Space Min Temp. ................................ 21.0
7. Partitions:
7.1. 1st Partition Details:
Partition Type ........................................ Wall Partition
Area ....................................................................... 60.8
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9
Ambient at Space Max Temp ................................ 35.0
Uncondit. Space Min Temp ................................... 23.9
Ambient at Space Min Temp ................................. 21.0

m
W/(m-K)
C
C
C
C

7.2. 2nd Partition Details:


(No partition data).
m
W/(m-K)
C
C
C
C

partition is in 2 sides: SE,


NW (H60). Kindly check
and revise

Page 32 of 70

2nd partition is available wirh


79.4 m^2 (Floor ). Kindly
check and revise

Intrument Electric Work.


1. General Details:
Floor Area ............................................................. 43.2
Avg. Ceiling Height .................................................. 4.3
Building Weight ................................................... 341.8
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 8.5
OA Requirement 2 ................................................ 0.00
Space Usage Defaults ASHRAE Standard 62.1-2007

m
m
kg/m

L/s/person
L/(s-m)

As per point 3.1of "


1014-BKTNG-ME-RPT-0004_Rev 0 - HVAC
Calculations-Technical building": Lighting density
is 20W/m^2

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................. Recessed (Unvented)
Wattage ............................................................... 24.00 W/m
Ballast Multiplier .................................................... 1.00
Schedule ........................................................ Lighting

2.4. People:
Occupancy .............................................................. 4.0 People
Activity Level ................................................. Athletics
Sensible ............................................................... 208.1 W/person
Latent .................................................................. 319.4 W/person
Schedule .......................................................... People

2.2. Task Lighting:


Wattage ................................................................. 0.00 W/m
Schedule ................................................ Equipment E

2.5. Miscellaneous Loads:


Sensible ...................................................................... 0 W
Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

2.3. Electrical Equipment:


Wattage ............................................................. 1000.0 Watts
Schedule ................................................ Equipment E

Kindly update data


- SE: Single door
- SW : Double door

3. Walls, Windows, Doors:


Exp.

Wall Gross Area (m)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

SW

20.2

3.1. Construction Types for Exposure SW


Wall Type ........................ Wall detail - W1 (A60 Rated wall)
Door Type ........................................................... Doubl door
4. Roofs, Skylights:
(No Roof or Skylight data).

Kindly check wall at SE, NW (H60)

5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................. 43.2
Total Floor U-Value ............................................. 0.524
Unconditioned Space Max Temp. ......................... 23.9
Ambient at Space Max Temp. ............................... 35.0
Unconditioned Space Min Temp. .......................... 23.9
Ambient at Space Min Temp. ................................ 21.0
7. Partitions:
7.1. 1st Partition Details:
Partition Type ........................................ Wall Partition
Area ....................................................................... 99.4
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9
Ambient at Space Max Temp ................................ 35.0
Uncondit. Space Min Temp ................................... 23.9
Ambient at Space Min Temp ................................. 21.0

m
W/(m-K)
C
C
C
C

m
W/(m-K)
C
C
C
C

Floor partition

7.2. 2nd Partition Details:


Partition Type ................................... Ceiling Partition
Area ....................................................................... 86.4
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9
Ambient at Space Max Temp ................................ 35.0
Uncondit. Space Min Temp ................................... 23.9
Ambient at Space Min Temp ................................. 21.0

partition is in 2 sides: SE,


SW, NW (H60). Kindly
check and revise

Page 33 of 70

m
W/(m-K)
C
C
C
C

Main Switchgear
1. General Details:
Floor Area ........................................................... 171.3
Avg. Ceiling Height .................................................. 3.8
Building Weight ................................................... 341.8
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................. 8.5
OA Requirement 2 ................................................ 0.00
Space Usage Defaults ASHRAE Standard 62.1-2007

m
m
kg/m

L/s/person
L/(s-m)

As per point 3.1of "


1014-BKTNG-ME-RPT-0004_Rev 0 - HVAC
Calculations-Technical building": Lighting density
is 20W/m^2

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................. Recessed (Unvented)
Wattage ............................................................... 24.00 W/m
Ballast Multiplier .................................................... 1.00
Schedule ........................................................ Lighting

2.4. People:
Occupancy .............................................................. 2.0 People
Activity Level ..................................... Sedentary Work
Sensible ................................................................. 82.1 W/person
Latent .................................................................... 79.1 W/person
Schedule .......................................................... People

2.2. Task Lighting:


Wattage ................................................................. 0.00 W/m
Schedule ............................................................. None

2.5. Miscellaneous Loads:


Sensible ...................................................................... 0 W
Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

2.3. Electrical Equipment:


Wattage ........................................................... 34460.0 Watts
Schedule ................................................ Equipment E

Kindly update data


3. Walls, Windows, Doors:
Exp.

Wall Gross Area (m)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

SE

52.1

3.1. Construction Types for Exposure SE


Wall Type ................................... Wall detail - W2 (A60 wall)
Door Type ........................................................... Doubl door

Kindly check wall at NW (H60)

4. Roofs, Skylights:
Exp.

Roof Gross Area (m)

Roof Slope (deg.)

Skylight Qty.

171.3

4.1. Construction Types for Exposure H


Roof Type ............. Floor detail - F1 (Floor without ceiling)
5. Infiltration:
Design Cooling ...................................................... 0.00 L/s
Design Heating ...................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ........................................................... 171.3
Total Floor U-Value ............................................. 0.376
Unconditioned Space Max Temp. ......................... 25.0
Ambient at Space Max Temp. ............................... 35.0
Unconditioned Space Min Temp. .......................... 23.9
Ambient at Space Min Temp. ................................ 21.0

m
W/(m-K)
C
C
C
C

7. Partitions:
7.1. 1st Partition Details:
Partition Type ........................................ Wall Partition
Area ....................................................................... 99.6
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9
Ambient at Space Max Temp ................................ 35.0
Uncondit. Space Min Temp ................................... 23.9
Ambient at Space Min Temp ................................. 21.0
7.2. 2nd Partition Details:
Partition Type .................................... Ceiling Partition
Area ....................................................................... 80.0
U-Value ............................................................... 0.524
Uncondit. Space Max Temp .................................. 23.9

m
W/(m-K)
C
C
C
C

m
W/(m-K)
C

Page 34 of 70

partition is in 2 sides: SE,


NW (H60). Kindly check
and revise

ATTACHMENT C: AIR HANDLING UNIT 50HH01A/B

Page 35 of 70

Air System Information


Number of zones ............................................................ 2
Floor Area ................................................................ 132.3 m
Location .................................. Thien Ung field, Vietnam

Air System Name ....................................... 50HH01AB


Equipment Class ........................................... CW AHU
Air System Type ............................................. CAV/RH

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 84.2
Sensible coil load .................................................. 47.6
Coil L/s at Aug 1500 ............................................. 2893
Max block L/s ....................................................... 2893
Sum of peak zone L/s .......................................... 2893
Sensible heat ratio .............................................. 0.566
m/kW ...................................................................... 1.6
W/m .................................................................... 636.2
Water flow @ 5.6 K rise ....................................... 3.63

Load occurs at .................................................. Aug 1500


OA DB / WB .................................................... 39.0 / 38.7
Entering DB / WB ............................................ 25.7 / 20.2
Leaving DB / WB ............................................. 12.0 / 11.6
Coil ADP .................................................................... 10.5
Bypass Factor ......................................................... 0.100
Resulting RH ................................................................ 46
Design supply temp. .................................................. 13.0
Zone T-stat Check ................................................... 2 of 2
Max zone temperature deviation ................................. 0.0

kW
kW
L/s
L/s
L/s

L/s

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s ...................................................... 2893 L/s
Standard L/s ......................................................... 2888 L/s
Actual max L/(s-m) ............................................. 21.87 L/(s-m)

Fan motor BHP .......................................................... 4.38 BHP


Fan motor kW ............................................................ 3.47 kW
Fan static .................................................................... 900 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................... 331 L/s
L/(s-m) .................................................................. 2.50 L/(s-m)

L/s/person ................................................................ 41.38 L/s/person

Page 36 of 70

Air System Information


Air System Name ....................................... 50HH01AB
Equipment Class ........................................... CW AHU
Air System Type ............................................. CAV/RH

Number of zones ............................................................ 2


Floor Area ................................................................ 132.3 m
Location .................................. Thien Ung field, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1
Zone 2

Maximum
Cooling
Sensible
(kW)
7.7
30.6

Design
Air
Flow
(L/s)
583
2310

Minimum
Air
Flow
(L/s)
583
2310

Time
of
Peak
Load
Jul 1000
Nov 1000

Maximum
Heating
Load
(kW)
0.0
0.0

Reheat
Coil
Load
(kW)
2.8
11.1

Reheat
Coil
Water
L/s
@ 11.1 K
-

Zone
Htg
Coil
Load
(kW)
0.0
0.0

Zone
Htg
Water
L/s
@ 11.1 K
0.00
0.00

Mixing
Box Fan
Airflow
(L/s)
0
0

Zone
Floor
Area
(m)
52.9
79.4

Zone Terminal Sizing Data

Zone Name
Zone 1
Zone 2

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
Central Control Room
Zone 2
Instrument Equipment R.

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

7.7

Jul 1000

583

0.0

52.9

11.03

30.6

Nov 1000

2310

0.0

79.4

29.09

Page 37 of 70

Zone
L/(s-m)
11.03
29.09

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate, Corrected for Exhaust Air ........................ 331 L/s
Design Ventilation Airflow Rate ..................................................................... 68 L/s

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
Central Control Room
Zone 2
Instrument Equipment R.
Totals (incl. Space Multipliers)

Mult.

Floor
Area
(m)

Maximum
Occupants

Maximum
Supply Air
(L/s)

Required
Outdoor Air
(L/s/person)

Required
Outdoor Air
(L/(s-m))

52.9

4.0

583.3

8.50

0.00

0.0

0.0

34.0

79.4

4.0

2309.7
2893.0

8.50

0.00

0.0

0.0

34.0
68.0

Page 38 of 70

Required
Required
Outdoor Air Outdoor Air
(L/s) (% of supply)

Uncorrected
Outdoor Air
(L/s)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
Terminal Reheat Coils
>> Total Conditioning
Key:

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 39.0 C / 38.7 C
HEATING OA DB / WB 21.0 C / 16.2 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
67 m
526
67 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
9 m
235
9 m
0
132 m
-8
132 m
0
76 m
-4
76 m
0
46 m
-3
46 m
0
3175 W
3175
0
0
0W
0
0
0
30111 W
30110
0
0
8
657
633
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
3469
63
0%
0
0
38156
696
0
0
38137
696
-120
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
2562 L/s
0
2562 L/s
0
331 L/s
6015
35851
331 L/s
-1867
-1056
2893 L/s
3472
2893 L/s
-3472
0
0
0%
0
0%
0
47623
36547
-5459
-1056
47623
36544
-16877
-1056
0
0
0
11419
47623
36544
-5459
-1056
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 39 of 70

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Zone 2

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1000
HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 C / 34.1 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 17.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
48 m
518
48 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
5 m
119
5 m
0
53 m
-3
53 m
0
15 m
-1
15 m
0
46 m
-3
46 m
0
1270 W
1270
0
0
0W
0
0
0
4798 W
4798
0
0
4
328
316
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
703
32
0%
0
0
7728
348
0
0

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Nov 1000
HEATING DATA AT DES HTG
COOLING OA DB / WB 30.5 C / 30.2 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 17.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
19 m
215
19 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
4 m
63
4 m
0
79 m
-5
79 m
0
61 m
-3
61 m
0
0 m
0
0 m
0
1906 W
1905
0
0
0W
0
0
0
25313 W
25312
0
0
4
328
316
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
2782
32
0%
0
0
30597
348
0
0

Page 40 of 70

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

NE EXPOSURE
WALL
DOOR
DOOR GLASS
SE EXPOSURE
WALL
DOOR
DOOR GLASS

COMPONENT LOADS FOR SPACE '' Central Control Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1000
HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 C / 34.1 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 17.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
48 m
518
48 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
5 m
119
5 m
0
53 m
-3
53 m
0
15 m
-1
15 m
0
46 m
-3
46 m
0
1270 W
1270
0
0
0W
0
0
0
4798 W
4798
0
0
4
328
316
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
703
32
0%
0
0
7728
348
0
0

ENVELOPE LOADS FOR SPACE '' Central Control Room '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)

HEATING
TRANS
(W)

34
4
0

0.384
1.703
0.524

0.880

376
60
1

20

0
0
0

13
2
0

0.546
1.703
0.524

0.880

142
29
1

0
0
0

Page 41 of 70

TABLE 2.1.A.

COMPONENT LOADS FOR SPACE '' Instrument Equipment R. '' IN ZONE '' Zone 2 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Nov 1000
HEATING DATA AT DES HTG
COOLING OA DB / WB 30.5 C / 30.2 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 17.0 C
Sensible
Latent
Sensible
Latent
SPACE LOADS
Details
(W)
(W)
Details
(W)
(W)
Window & Skylight Solar Loads
0 m
0
0 m
Wall Transmission
19 m
215
19 m
0
Roof Transmission
0 m
0
0 m
0
Window Transmission
0 m
0
0 m
0
Skylight Transmission
0 m
0
0 m
0
Door Loads
4 m
63
4 m
0
Floor Transmission
79 m
-5
79 m
0
Partitions
61 m
-3
61 m
0
Ceiling
0 m
0
0 m
0
Overhead Lighting
1906 W
1905
0
0
Task Lighting
0W
0
0
0
Electric Equipment
25313 W
25312
0
0
People
4
328
316
0
0
0
Infiltration
0
0
0
0
Miscellaneous
0
0
0
0
Safety Factor
10% / 10%
2782
32
0%
0
0
>> Total Zone Loads
30597
348
0
0

TABLE 2.1.B.

SE EXPOSURE
WALL
DOOR
DOOR GLASS

ENVELOPE LOADS FOR SPACE '' Instrument Equipment R. '' IN ZONE '' Zone 2 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)
19
4
0

0.384
1.703
0.524

Page 42 of 70

0.880

215
37
0

26

HEATING
TRANS
(W)
0
0
0

August DESIGN COOLING DAY, 1500


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Zone Direct Exhaust
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
39.0
25.7
12.0
12.0
13.0
13.0
23.9
23.9
23.9

Specific
Humidity
(kg/kg)
0.04526
0.01267
0.00838
0.00838
0.00838
0.00838
0.00846
0.00846
0.00846

Airflow
(L/s)
331
2893
2893
2893
2893
2893
2893
331
2562

CO2 Level
(ppm)
400
623
623
623
623
623
652
652
652

Sensible
Heat
(W)
6015
47623
0
3472
38137
0

Latent
Heat
(W)
35851
36544
696
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.6 W/(L/s)
Site Altitude = 14.2 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1
Zone 2

Zone
Sensible
Load
(W)
7614
30542

T-stat
Mode
Deadband
Deadband

Zone
Cond
(W)
7601
30536

Page 43 of 70

Zone
Temp
(C)
23.8
24.0

Zone
Airflow
(L/s)
583
2310

CO2
Level
(ppm)
680
644

Terminal
Heating
Coil
(W)
0
0

Zone
Heating
Unit
(W)
0
0

WINTER DESIGN HEATING


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Zone Direct Exhaust
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
21.0
16.9
12.0
12.0
13.0
13.0
16.3
16.3
16.3

Specific
Humidity
(kg/kg)
0.00953
0.00857
0.00845
0.00845
0.00845
0.00845
0.00845
0.00845
0.00845

Airflow
(L/s)
331
2893
2893
2893
2893
2893
2893
331
2562

CO2 Level
(ppm)
400
473
473
473
473
473
482
482
482

Sensible
Heat
(W)
1867
16877
0
3472
120
0

Latent
Heat
(W)
1056
1056
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.6 W/(L/s)
Site Altitude = 14.2 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1
Zone 2

Zone
Sensible
Load
(W)
0
0

T-stat
Mode
Heating
Heating

Zone
Cond
(W)
60
60

Page 44 of 70

Zone
Temp
(C)
16.3
16.3

Zone
Airflow
(L/s)
583
2310

CO2
Level
(ppm)
482
482

Terminal
Heating
Coil
(W)
2274
9145

Zone
Heating
Unit
(W)
0
0

Location: Thien Ung field, Vietnam


Altitude: 14.2 m.
Data for: August DESIGN COOLING DAY, 1500
1. Mixed
Outdoor
Air
2.
Air
3.
Cooling
Coil Outlet
4. Central
SupplyAir
Fan
Outlet
5.
Room

0.050
1

0.045
0.040
Specific Humidity ( kg/kg )

0.035
0.030
0.025

0.020
0.015

0.010

3 4

0.005
0.000
0

10

15

20
25
Temperature ( C )

Page 45 of 70

30

35

40

ATTACHMENT D: AIR HANDLING UNIT 50HH02A/B

Page 46 of 70

Air System Information


Air System Name ....................................... 50HH02AB
Equipment Class ........................................... CW AHU
Air System Type ............................................. CAV/RH

Number of zones ............................................................ 3


Floor Area ................................................................ 313.9 m
Location .................................. Thien Ung field, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ...................................................... 249.0
Sensible coil load ................................................ 130.2
Coil L/s at Aug 1500 ............................................. 6424
Max block L/s ....................................................... 6424
Sum of peak zone L/s .......................................... 6424
Sensible heat ratio .............................................. 0.523
m/kW ...................................................................... 1.3
W/m .................................................................... 793.2
Water flow @ 5.6 K rise ..................................... 10.73

Load occurs at .................................................. Aug 1500


OA DB / WB .................................................... 39.0 / 38.7
Entering DB / WB ............................................ 26.3 / 21.0
Leaving DB / WB ................................................. 9.5 / 9.3
Coil ADP ...................................................................... 7.6
Bypass Factor ......................................................... 0.100
Resulting RH ................................................................ 39
Design supply temp. .................................................. 11.4
Zone T-stat Check ................................................... 3 of 3
Max zone temperature deviation ................................. 0.0

kW
kW
L/s
L/s
L/s

L/s

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s ...................................................... 6424 L/s
Standard L/s ......................................................... 6414 L/s
Actual max L/(s-m) ............................................. 20.47 L/(s-m)

Fan motor BHP ........................................................ 18.90 BHP


Fan motor kW .......................................................... 14.99 kW
Fan static .................................................................. 1750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 1057 L/s
L/(s-m) .................................................................. 3.37 L/(s-m)

L/s/person .............................................................. 264.25 L/s/person

Page 47 of 70

Air System Information


Air System Name ....................................... 50HH02AB
Equipment Class ........................................... CW AHU
Air System Type ............................................. CAV/RH

Number of zones ............................................................ 3


Floor Area ................................................................ 313.9 m
Location .................................. Thien Ung field, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1
Zone 2
Zone 3

Maximum
Cooling
Sensible
(kW)
37.5
51.8
2.9

Design
Air
Flow
(L/s)
2469
3411
545

Minimum
Air
Flow
(L/s)
2469
3411
545

Time
of
Peak
Load
Nov 1000
Mar 1400
Jul 1000

Maximum
Heating
Load
(kW)
0.0
0.0
0.0

Reheat
Coil
Load
(kW)
13.7
18.9
0.0

Reheat
Coil
Water
L/s
@ 11.1 K
-

Zone
Htg
Coil
Load
(kW)
0.0
0.0
0.0

Zone
Htg
Water
L/s
@ 11.1 K
0.00
0.00
0.00

Mixing
Box Fan
Airflow
(L/s)
0
0
0

Zone
Floor
Area
(m)
96.3
171.3
46.3

Zone Terminal Sizing Data

Zone Name
Zone 1
Zone 2
Zone 3

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
Emergency Switchgear
Zone 2
Main Switchgear
Zone 3
Battery

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

37.5

Nov 1000

2469

0.0

96.3

25.64

51.8

Mar 1400

3411

0.0

171.3

19.91

2.9

Jul 1000

545

0.0

46.3

11.77

Page 48 of 70

Zone
L/(s-m)
25.64
19.91
11.77

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate, Corrected for Exhaust Air ...................... 1057 L/s
Design Ventilation Airflow Rate ................................................................... 579 L/s

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
Emergency Switchgear
Zone 2
Main Switchgear
Zone 3
Battery
Totals (incl. Space Multipliers)

Mult.

Floor
Area
(m)

Maximum
Occupants

Maximum
Supply Air
(L/s)

Required
Outdoor Air
(L/s/person)

Required
Outdoor Air
(L/(s-m))

96.3

2.0

2468.8

8.50

0.00

0.0

0.0

17.0

171.3

2.0

3410.5

8.50

0.00

0.0

0.0

17.0

46.3

0.0

545.0
6424.3

0.00

0.00

0.0

100.0

545.0
579.0

Page 49 of 70

Required
Required
Outdoor Air Outdoor Air
(L/s) (% of supply)

Uncorrected
Outdoor Air
(L/s)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
Terminal Reheat Coils
>> Total Conditioning
Key:

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 39.0 C / 38.7 C
HEATING OA DB / WB 21.0 C / 16.2 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
130 m
1193
130 m
0
171 m
7273
171 m
0
0 m
0
0 m
0
0 m
0
0 m
0
13 m
326
13 m
0
171 m
62
171 m
0
143 m
-8
143 m
0
80 m
-5
80 m
0
7534 W
7533
0
0
0W
0
0
0
66366 W
66363
0
0
4
328
316
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
8307
32
0%
0
0
91372
348
0
0
90726
348
-397
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
5367 L/s
0
5367 L/s
0
1057 L/s
24530
118408
1057 L/s
-9647
-7754
6424 L/s
14991
6424 L/s
-14991
0
0
0%
0
0%
0
130247
118756
-25034
-7754
130247
118755
-52442
-7754
0
0
0
27407
130247
118755
-25034
-7754
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 50 of 70

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Zone 2

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Nov 1000
HEATING DATA AT DES HTG
COOLING OA DB / WB 30.5 C / 30.2 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 16.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
26 m
414
26 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
4 m
63
4 m
0
0 m
0
0 m
0
29 m
-2
29 m
0
0 m
0
0 m
0
2311 W
2311
0
0
0W
0
0
0
31132 W
31131
0
0
2
164
158
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
3408
16
0%
0
0
37489
174
0
0

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Mar 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 36.0 C / 35.7 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 16.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
49 m
434
49 m
0
171 m
7789
171 m
0
0 m
0
0 m
0
0 m
0
0 m
0
4 m
77
4 m
0
171 m
58
171 m
0
100 m
-6
100 m
0
80 m
-5
80 m
0
4111 W
4111
0
0
0W
0
0
0
34460 W
34458
0
0
2
164
158
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
4708
16
0%
0
0
51789
174
0
0

Page 51 of 70

Zone 3

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1000
HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 C / 34.1 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 16.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
56 m
610
56 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
5 m
119
5 m
0
0 m
0
0 m
0
14 m
-1
14 m
0
0 m
0
0 m
0
1111 W
1111
0
0
0W
0
0
0
774 W
774
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
261
0
0%
0
0
2875
0
0
0

Page 52 of 70

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

SE EXPOSURE
WALL
DOOR
DOOR GLASS

COMPONENT LOADS FOR SPACE '' Emergency Switchgear '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Nov 1000
HEATING DATA AT DES HTG
COOLING OA DB / WB 30.5 C / 30.2 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 16.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
26 m
414
26 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
4 m
63
4 m
0
0 m
0
0 m
0
29 m
-2
29 m
0
0 m
0
0 m
0
2311 W
2311
0
0
0W
0
0
0
31132 W
31131
0
0
2
164
158
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
3408
16
0%
0
0
37489
174
0
0

ENVELOPE LOADS FOR SPACE '' Emergency Switchgear '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)
26
4
0

0.546
1.703
0.524

Page 53 of 70

0.880

414
37
0

26

HEATING
TRANS
(W)
0
0
0

TABLE 2.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 2.1.B.

SE EXPOSURE
WALL
DOOR
DOOR GLASS
H EXPOSURE
ROOF

COMPONENT LOADS FOR SPACE '' Main Switchgear '' IN ZONE '' Zone 2 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Mar 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 36.0 C / 35.7 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 16.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
49 m
434
49 m
0
171 m
7789
171 m
0
0 m
0
0 m
0
0 m
0
0 m
0
4 m
77
4 m
0
171 m
58
171 m
0
100 m
-6
100 m
0
80 m
-5
80 m
0
4111 W
4111
0
0
0W
0
0
0
34460 W
34458
0
0
2
164
158
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
4708
16
0%
0
0
51789
174
0
0

ENVELOPE LOADS FOR SPACE '' Main Switchgear '' IN ZONE '' Zone 2 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)

HEATING
TRANS
(W)

49
4
0

0.546
1.703
0.524

0.880

434
63
1

14

0
0
0

171

0.524

7789

Page 54 of 70

TABLE 3.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

COMPONENT LOADS FOR SPACE '' Battery '' IN ZONE '' Zone 3 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1000
HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 C / 34.1 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 16.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
56 m
610
56 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
5 m
119
5 m
0
0 m
0
0 m
0
14 m
-1
14 m
0
0 m
0
0 m
0
1111 W
1111
0
0
0W
0
0
0
774 W
774
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
261
0
0%
0
0
2875
0
0
0

TABLE 3.1.B.

NE EXPOSURE
WALL
DOOR
DOOR GLASS
SE EXPOSURE
WALL
DOOR
DOOR GLASS

ENVELOPE LOADS FOR SPACE '' Battery '' IN ZONE '' Zone 3 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)

HEATING
TRANS
(W)

46
2
0

0.384
1.703
0.524

0.880

499
29
1

20

0
0
0

11
4
0

0.546
1.703
0.524

0.880

111
60
1

0
0
0

Page 55 of 70

August DESIGN COOLING DAY, 1500


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Zone Direct Exhaust
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
39.0
26.3
9.5
9.5
11.4
11.4
23.8
23.8
23.8

Specific
Humidity
(kg/kg)
0.04526
0.01346
0.00718
0.00718
0.00718
0.00718
0.00720
0.00720
0.00720

Airflow
(L/s)
1057
6424
6424
6424
6424
6424
6424
1057
5367

CO2 Level
(ppm)
400
466
466
466
466
466
479
479
479

Sensible
Heat
(W)
24530
130247
0
14991
90726
0

Latent
Heat
(W)
118408
118755
348
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.6 W/(L/s)
Site Altitude = 14.2 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1
Zone 2
Zone 3

Zone
Sensible
Load
(W)
37351
51303
2718

T-stat
Mode
Deadband
Deadband
Deadband

Zone
Cond
(W)
37340
50380
3006

Page 56 of 70

Zone
Temp
(C)
23.9
23.7
16.0

Zone
Airflow
(L/s)
2469
3411
545

CO2
Level
(ppm)
480
478
474

Terminal
Heating
Coil
(W)
0
0
0

Zone
Heating
Unit
(W)
0
0
0

WINTER DESIGN HEATING


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Zone Direct Exhaust
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
21.0
16.2
9.5
9.5
11.4
11.4
15.3
15.3
15.3

Specific
Humidity
(kg/kg)
0.00953
0.00745
0.00704
0.00704
0.00704
0.00704
0.00704
0.00704
0.00704

Airflow
(L/s)
1057
6424
6424
6424
6424
6424
6424
1057
5367

CO2 Level
(ppm)
400
446
446
446
446
446
455
455
455

Sensible
Heat
(W)
9647
52442
0
14991
397
0

Latent
Heat
(W)
7754
7754
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.6 W/(L/s)
Site Altitude = 14.2 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1
Zone 2
Zone 3

Zone
Sensible
Load
(W)
0
0
0

T-stat
Mode
Heating
Heating
Deadband

Zone
Cond
(W)
25
196
175

Page 57 of 70

Zone
Temp
(C)
15.3
15.3
11.7

Zone
Airflow
(L/s)
2469
3411
545

CO2
Level
(ppm)
455
455
455

Terminal
Heating
Coil
(W)
11566
15841
0

Zone
Heating
Unit
(W)
0
0
0

Location: Thien Ung field, Vietnam


Altitude: 14.2 m.
Data for: August DESIGN COOLING DAY, 1500
1. Mixed
Outdoor
Air
2.
Air
3.
Cooling
Coil Outlet
4. Central
SupplyAir
Fan
Outlet
5.
Room

0.050
1

0.045
0.040
Specific Humidity ( kg/kg )

0.035
0.030
0.025
0.020
0.015

2
3

0.010

0.005
0.000
0

10

15

20
25
Temperature ( C )

Page 58 of 70

30

35

40

ATTACHMENT E: AIR HANDLING UNIT 50HH03A/B

Page 59 of 70

Air System Information


Air System Name ....................................... 50HH03AB
Equipment Class ........................................... CW AHU
Air System Type ............................................. CAV/RH

Number of zones ............................................................ 1


Floor Area .................................................................. 43.2 m
Location .................................. Thien Ung field, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 17.8
Sensible coil load .................................................... 5.9
Coil L/s at Aug 1500 ............................................... 490
Max block L/s ......................................................... 490
Sum of peak zone L/s ............................................ 490
Sensible heat ratio .............................................. 0.331
m/kW ...................................................................... 2.4
W/m .................................................................... 412.4
Water flow @ 5.6 K rise ....................................... 0.77

Load occurs at .................................................. Aug 1500


OA DB / WB .................................................... 39.0 / 38.7
Entering DB / WB ............................................ 27.3 / 25.9
Leaving DB / WB ............................................. 17.3 / 17.3
Coil ADP .................................................................... 16.2
Bypass Factor ......................................................... 0.100
Resulting RH ................................................................ 72
Design supply temp. .................................................. 18.1
Zone T-stat Check ................................................... 1 of 1
Max zone temperature deviation ................................. 0.0

kW
kW
L/s
L/s
L/s

L/s

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s ........................................................ 490 L/s
Standard L/s ........................................................... 489 L/s
Actual max L/(s-m) ............................................. 11.34 L/(s-m)

Fan motor BHP .......................................................... 0.58 BHP


Fan motor kW ............................................................ 0.46 kW
Fan static .................................................................... 700 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................... 112 L/s
L/(s-m) .................................................................. 2.59 L/(s-m)

L/s/person ................................................................ 28.00 L/s/person

Page 60 of 70

Air System Information


Air System Name ....................................... 50HH03AB
Equipment Class ........................................... CW AHU
Air System Type ............................................. CAV/RH

Number of zones ............................................................ 1


Floor Area .................................................................. 43.2 m
Location .................................. Thien Ung field, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
3.5

Design
Air
Flow
(L/s)
490

Minimum
Air
Flow
(L/s)
490

Time
of
Peak
Load
Oct 1600

Maximum
Heating
Load
(kW)
0.0

Zone
Floor
Area
(m)
43.2

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
Intrument Electric Work.

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

3.5

Oct 1600

490

0.0

43.2

11.34

Page 61 of 70

Zone
L/(s-m)
11.34

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate, Corrected for Exhaust Air ........................ 112 L/s
Design Ventilation Airflow Rate ..................................................................... 34 L/s

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
Intrument Electric Work.
Totals (incl. Space Multipliers)

Mult.

Floor
Area
(m)

Maximum
Occupants

43.2

4.0

Maximum
Supply Air
(L/s)

Required
Outdoor Air
(L/s/person)

Required
Outdoor Air
(L/(s-m))

490.0
490.0

8.50

0.00

Page 62 of 70

Required
Required
Outdoor Air Outdoor Air
(L/s) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(L/s)
34.0
34.0

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
Terminal Reheat Coils
>> Total Conditioning
Key:

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 39.0 C / 38.7 C
HEATING OA DB / WB 21.0 C / 16.2 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
17 m
163
17 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
4 m
96
4 m
0
43 m
-3
43 m
0
99 m
-6
99 m
0
86 m
-5
86 m
0
1037 W
1037
0
0
0W
0
0
0
1000 W
1000
0
0
4
832
1278
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
312
128
0%
0
0
3427
1405
0
0
3403
1405
120
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
378 L/s
0
378 L/s
0
112 L/s
2042
10508
112 L/s
-418
0
490 L/s
457
490 L/s
-457
0
0
0%
0
0%
0
5903
11914
-755
0
5903
11914
-755
0
0
0
0
0
5903
11914
-755
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 63 of 70

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Oct 1600
HEATING DATA AT DES HTG
COOLING OA DB / WB 36.5 C / 36.3 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 17.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
17 m
215
17 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
4 m
92
4 m
0
43 m
-3
43 m
0
99 m
-6
99 m
0
86 m
-5
86 m
0
1037 W
1037
0
0
0W
0
0
0
1000 W
1000
0
0
4
832
1278
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
316
128
0%
0
0
3479
1405
0
0

Page 64 of 70

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.1.B.

SW EXPOSURE
WALL
DOOR
DOOR GLASS

COMPONENT LOADS FOR SPACE '' Intrument Electric Work. '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Oct 1600
HEATING DATA AT DES HTG
COOLING OA DB / WB 36.5 C / 36.3 C
HEATING OA DB / WB 21.0 C / 16.2 C
OCCUPIED T-STAT 24.0 C
OCCUPIED T-STAT 17.0 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
0 m
0
0 m
17 m
215
17 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
4 m
92
4 m
0
43 m
-3
43 m
0
99 m
-6
99 m
0
86 m
-5
86 m
0
1037 W
1037
0
0
0W
0
0
0
1000 W
1000
0
0
4
832
1278
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
316
128
0%
0
0
3479
1405
0
0

ENVELOPE LOADS FOR SPACE '' Intrument Electric Work. '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)
17
4
0

0.384
1.703
0.524

Page 65 of 70

0.880

215
67
1

24

HEATING
TRANS
(W)
0
0
0

August DESIGN COOLING DAY, 1500


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Zone Direct Exhaust
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
39.0
27.3
17.3
17.3
18.1
18.1
23.9
23.9
23.9

Specific
Humidity
(kg/kg)
0.04526
0.02067
0.01241
0.01241
0.01241
0.01241
0.01338
0.01338
0.01338

Airflow
(L/s)
112
490
490
490
490
490
490
112
378

CO2 Level
(ppm)
400
996
996
996
996
996
1172
1172
1172

Sensible
Heat
(W)
2042
5903
0
457
3403
0

Latent
Heat
(W)
10508
11914
1405
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.6 W/(L/s)
Site Altitude = 14.2 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Zone
Sensible
Load
(W)
3427

T-stat
Mode
Deadband

Zone
Cond
(W)
3403

Page 66 of 70

Zone
Temp
(C)
23.9

Zone
Airflow
(L/s)
490

CO2
Level
(ppm)
1172

Terminal
Heating
Coil
(W)
0

Zone
Heating
Unit
(W)
0

WINTER DESIGN HEATING


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Zone Direct Exhaust
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
21.0
18.6
17.3
17.3
18.1
18.1
17.9
17.9
17.9

Specific
Humidity
(kg/kg)
0.00953
0.00953
0.00953
0.00953
0.00953
0.00953
0.00953
0.00953
0.00953

Airflow
(L/s)
112
490
490
490
490
490
490
112
378

CO2 Level
(ppm)
400
430
430
430
430
430
439
439
439

Sensible
Heat
(W)
418
755
0
457
-120
0

Latent
Heat
(W)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.6 W/(L/s)
Site Altitude = 14.2 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Zone
Sensible
Load
(W)
0

T-stat
Mode
Deadband

Zone
Cond
(W)
-120

Page 67 of 70

Zone
Temp
(C)
17.9

Zone
Airflow
(L/s)
490

CO2
Level
(ppm)
439

Terminal
Heating
Coil
(W)
0

Zone
Heating
Unit
(W)
0

Location: Thien Ung field, Vietnam


Altitude: 14.2 m.
Data for: August DESIGN COOLING DAY, 1500
1. Mixed
Outdoor
Air
2.
Air
3.
Cooling
Coil Outlet
4. Central
SupplyAir
Fan
Outlet
5.
Room

0.050
1

0.045
0.040
Specific Humidity ( kg/kg )

0.035

0.030
0.025
2

0.020
34

0.015

0.010
0.005
0.000
0

10

15

20
25
Temperature ( C )

Page 68 of 70

30

35

40

ATTACHMENT F: AIR HANDLING UNIT 50HC01A/B

Page 69 of 70

1. Plant Information:
Plant Name ..................................................................................... 50HC01AB
Plant Type .................................................................... Generic Chilled Water
Design Weather ...................................................... Thien Ung field, Vietnam

2. Cooling Plant Sizing Data:


Maximum Plant Load ............................................................................... 351.0 kW
Load occurs at .................................................................................. Aug 1500
m/kW ........................................................................................................... 1.4 m/kW
Floor area served by plant ....................................................................... 489.4 m

3. Coincident Cooling Loads for Aug 1500

System
Cooling
Coil Load
Air System Name

Mult.

( kW )

50HH01AB

84.2

50HH02AB

249.0

50HH03AB

17.8

Page 70 of 70