You are on page 1of 3

F6TesT

Test Result Details

29-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Location Path

UNIT-3

Relay Under Test General Parameters

Relay Name

7UM62

Serial Number
Manufacturer

SIEMENS

Nominal Ratings:

fn

Model

50.000 Hz
110.00 V (Ph-Ph)
5.000 A

Vn
In
VTR

15750 : 110

Station Name

KORBA

7UM62X

Max Test Current

2000.000% In
1000.00% Vn

Max Test Voltage

A-B-C

Phase Names and Rotation


CTR

10000 : 5

Protected Object Parameters

Protected Object Name

UNIT-5 GENERATOR MAIN-1

Protected Object Parameters


Test and Test Definition Information

Test Plan Name

INTER TURN PROTECTION

Test Name

INTERTURN PICKUP AND DROP OFF

Test Type

Ramp

Test Definition Name

INTERTURN PICKUP

Tested Date

29-11-2014

Tested By

NTPC KORBA GRP ST-1

Test Definition Description

Setting: Interturn protection


CTR = 3000/5 A
213 CT ratio Pri/Sec Iee2 = 600
214 Grounded terminal CT Iee2 = Q8
5102 IEE> Pickup = 1000ma
5103 T IEE> Delay = 1 sec

Evaluation

Op

Test Configuration

Test Module

Amplitude-Current-Stepped-Auto-Double - Ramp

Values are

Secondary

Source Configuration
Source

Pre-fault
Amplitude

Action
Ph Ang [deg]

Amplitude

Ph Ang [deg]

Frequency(Hz)

IA

0.100 A

0.00

1.000 A

0.00

50.000

IB

0.100 A

-120.00

1.000 A

-120.00

50.000

IC

0.100 A

120.00

1.000 A

120.00

50.000

I1

0.100 A

0.00

Action

0.00

50.000

I2

0.000 A

-120.00

0.000 A

0.00

50.000

I3

0.000 A

120.00

0.000 A

0.00

50.000

Doble

Page 1 of 3

Test Result Details

29-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Ramp Details

Trigger

LN1 0->1

Delay

0.0000 s

Pre-fault Duration

0.0000 s

Offset Current

Duration

0.0000 s

0.900 A

Offset Current Duration

1.0000 s
0.020 A

Delta Current #1
Delta Time #1

1.1000

Ramp 1 Limit

1.100 A

Wait

0.0000 s

Delta Current #2

-0.020 A

Delta Time #2

1.1000 s

Ramp 2 Limit

0.900 A

Ramp Result
Test Objective

Expected
[A]

Actual

-tol [A]

+tol [A]

Error[A]

Eval

[A]

Ramp1

1.000

1.000

1.000

1.000

0.000

Pass

Ramp2

0.990

0.940

1.000

1.000

-0.050

Pass

1.010

1.064

0.054

Op

Test Notebook
Originator Comments

Neutral side current should be injected

Doble

Page 2 of 3

Test Result Details

29-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test and Test Definition Information

Test Plan Name

INTER TURN PROTECTION

Test Name

INTERTRN TIME

Test Type

Ssimul

Test Definition Name

TIME

Tested Date

29-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Pass

Test Definition Description


Test Configuration

State No

State1Name

Name

Source Name

Amplitude

Ph Ang [deg]

Frequency (Hz)

IA

1.00 A

0.00

50.0000

IB

1.00 A

-120.00

50.0000

IC

1.00 A

120.00

50.0000

I1

1.1000 A

0.00

50.0000

I2

0.0000 A

-120.00

50.0000

I3

0.0000 A

120.00

50.0000

1.5000 s

State Duration
Trigger

0->1

Trigger Condition

LN1

Measurement
Timer Name

Timer

Start State

1-State1Name

Stop Signal

LN1, 0->1

t Exp
[s]

1.0000

Doble

t Act
[s]

1.2142

+ tol
[%]

25.000

- tol
[%]

t Err

25.000

21.420

Eval

[%]

Pass

Page 3 of 3

You might also like