Professional Documents
Culture Documents
29-Nov-14
Location Path
UNIT-3
Relay Name
7UM62
Serial Number
Manufacturer
SIEMENS
Nominal Ratings:
fn
Model
50.000 Hz
110.00 V (Ph-Ph)
5.000 A
Vn
In
VTR
15750 : 110
Station Name
KORBA
7UM62X
2000.000% In
1000.00% Vn
A-B-C
10000 : 5
Test Name
Test Type
Ramp
INTERTURN PICKUP
Tested Date
29-11-2014
Tested By
Evaluation
Op
Test Configuration
Test Module
Amplitude-Current-Stepped-Auto-Double - Ramp
Values are
Secondary
Source Configuration
Source
Pre-fault
Amplitude
Action
Ph Ang [deg]
Amplitude
Ph Ang [deg]
Frequency(Hz)
IA
0.100 A
0.00
1.000 A
0.00
50.000
IB
0.100 A
-120.00
1.000 A
-120.00
50.000
IC
0.100 A
120.00
1.000 A
120.00
50.000
I1
0.100 A
0.00
Action
0.00
50.000
I2
0.000 A
-120.00
0.000 A
0.00
50.000
I3
0.000 A
120.00
0.000 A
0.00
50.000
Doble
Page 1 of 3
29-Nov-14
Ramp Details
Trigger
LN1 0->1
Delay
0.0000 s
Pre-fault Duration
0.0000 s
Offset Current
Duration
0.0000 s
0.900 A
1.0000 s
0.020 A
Delta Current #1
Delta Time #1
1.1000
Ramp 1 Limit
1.100 A
Wait
0.0000 s
Delta Current #2
-0.020 A
Delta Time #2
1.1000 s
Ramp 2 Limit
0.900 A
Ramp Result
Test Objective
Expected
[A]
Actual
-tol [A]
+tol [A]
Error[A]
Eval
[A]
Ramp1
1.000
1.000
1.000
1.000
0.000
Pass
Ramp2
0.990
0.940
1.000
1.000
-0.050
Pass
1.010
1.064
0.054
Op
Test Notebook
Originator Comments
Doble
Page 2 of 3
29-Nov-14
Test Name
INTERTRN TIME
Test Type
Ssimul
TIME
Tested Date
29-11-2014
Tested By
Evaluation
Pass
State No
State1Name
Name
Source Name
Amplitude
Ph Ang [deg]
Frequency (Hz)
IA
1.00 A
0.00
50.0000
IB
1.00 A
-120.00
50.0000
IC
1.00 A
120.00
50.0000
I1
1.1000 A
0.00
50.0000
I2
0.0000 A
-120.00
50.0000
I3
0.0000 A
120.00
50.0000
1.5000 s
State Duration
Trigger
0->1
Trigger Condition
LN1
Measurement
Timer Name
Timer
Start State
1-State1Name
Stop Signal
LN1, 0->1
t Exp
[s]
1.0000
Doble
t Act
[s]
1.2142
+ tol
[%]
25.000
- tol
[%]
t Err
25.000
21.420
Eval
[%]
Pass