DESIGN CALCULATION

SHEET

Project No.

Date

Sheet No.

Computed by

of
Subject

Checked by

Approved by

Design calculation sheet


Project no.:
Subject

Date:

Sheet no.: 25 of 25

Computed by:
Checked by:
Approved by:

Design calculation sheet


Project no:
Subject:

SN07010/2

Date:

7/3/07

Sheet no.:

of

Computed by:

Chilled Water Secondary Pumps

Checked by:

Serving terminal

Approved by:

S.A.

91.7 l/s
1453 gpm

3 Pumps acting; flow per pump=

Pump Head
A- Pipe Losses
Dia

Length

Eq.leng

Flow

Fr. losses

Losses

in

ft

ft

GPM

L/s

ft/100ft

ft

18
18

100

328.08

426.51

332.00

0.82

294.7

0.7

3.50
27.98

275

0.65

7.70

18
Sub-Total-1

1016

3331.148 3997.377

5261
4670

278

911.4754 1184.918

4358

39.18 ft

B- Accessories Losses
Dia

AHU

Pump

Item

Qty.

Equ. L

Flow

Fr. losses

Losses

ft.

gpm

ft/100ft

ft

in.

Gate Valve

12

13

1453

0.82

0.21

Globe valve

12

320

1453

2.62

Check Valve

12

120

1453

0.82
0.82

Gate Valve

284.00

0.00

2-way control valve 5

9.9

284.00

0.00

Balancing valve

140

284.00

0.00

Strainer

80

284.00

0.00

Coil

0.98

284.00

3.82 ft

Sub-Total-2

Sum

43.00

ft

Friction Losses

13.11

Static head

sub total=

13.1

Total with 10% safety=

14.4

Design calculation sheet


Project no:
Subject:

SN07010/2

Date:

3/24/07

Sheet no.:

of

Computed by:

Chilled Water Secondary Pumps

Checked by:

Serving terminal

Approved by:

S.A.

106.2 l/s
1683 gpm

3 Pumps acting; flow per pump=

3 acting + 1 St. By

Pump Head
A- Pipe Losses
Dia

Length

Eq.leng

Flow

Fr. losses

Losses

in

ft

ft

GPM

L/s

ft/100ft

ft

20
20

100

328.08

426.51

5261
5304

332.00

0.55

334.7

0.51

2.35
18.98

5049
1683

318.6

0.8

106

0.63

18
12
Sub-Total-1

946

3101.639 3721.9672

494

1619.672 2105.5738

13

17

16.84
0.11

38.17 ft

B- Accessories Losses
Dia

AHU

Pump

Item

Qty.

Equ. L

in.

ft.

Flow

Fr. losses

gpm

ft/100ft

Gate Valve

12

13

1683

Strainer

12

250

1683

Globe valve

12

320

1683

Check Valve

12

120

1683

Gate Valve

284.00

2-way control valve 5

9.9

284.00

Balancing valve

140

284.00

Strainer

80

284.00

Coil

Losses
ft

0.63
0.63

0.16

0.63
0.63

2.02

2.90
2.90

0.35

2.90
2.90

4.06

284.00

1.58
0.76
0.29
2.32
9.90

21.43 ft

Sub-Total-2

Sum

59.60

ft

Friction Losses

18.17

Static head

sub total=

18.2

Total with 10% safety=

20.0

Say

22.00

Design calculation sheet


Project no:

SN07010/2

Date:

12/3/07

Chilled Water Secondary Pumps

Subject:

Sheet no.:

of

in CUC

Computed by:

S.A.

Checked by:

to the ATCT

Approved by:

57 l/s
903 gpm

3 Pumps acting; flow per pump=

Pump Head
A- Pipe Losses
Dia

Length

in

8
100
4
1138
Sub-Total-1

Eq.leng

Flow

Fr. losses

Losses

ft

ft

GPM

L/s

ft/100ft

ft

328.08
3731.15

393.70
4477.38

903
312

57.00
19.70

1.40
1.75

5.51
78.35

83.87 ft

B- Accessories Losses
Dia

AHU

Pump

Item

Qty.

Equ. L

Flow

Fr. losses

ft.

gpm

ft/100ft

in.

Losses
ft

Gate Valve

903.5

1.4

0.25

Globe valve

220

903.5

1.4

3.08

Check Valve

80

903.5

1.4

1.12

Gate Valve

2.5

2.8

65.00

1.40

0.04

2-way control valve 2.5

29

65.00

1.40

0.41

Balancing valve

2.5

69

65.00

1.40

0.97

Strainer

2.5

35

65.00

1.40

0.49

Coil

65.00

9.70

16.05 ft

Sub-Total-2

Sum

99.92

ft

Friction Losses

30.46

Static head

sub total=

30.5

Total with 10% safety=

33.5

Design calculation sheet


Project no:
Subject:

PS05396

Date:

4/11/06

Sheet no.:

Computed by:

S.A.

Chilled Water Primary Pumps

Checked by:

H.A.

CUC

Approved by:

H.A.

of

38 l/s
602 gpm

5 Pumps acting; flow per pump

Pump Head
A- Pipe Losses
Dia

Length

Eq.leng

Flow

Fr. losses

Losses

in

ft

ft

GPM

L/s

ft/100ft

ft

60

196.85

226.38

602

38.00

4.50

10.19

10.19 ft

Sub-Total-1

B- Accessories Losses
Dia

Chiller

Pump

Item

Qty.

Equ. L

Flow

Fr. losses

Losses

ft.

gpm

ft/100ft

ft

in.

Gate Valve

4.5

602

4.5

0.41

Globe valve

120

602

4.5

5.40

Isolating valve

4.5

602

4.5

0.20

Gate Valve

4.5

602

4.5

0.20

Globe valve

120

602

4.5

5.40

Cooler pressure drop

324

9.40

21.01 ft

Sub-Total-2

Sum

31.20

ft

Friction Losses

9.51

Static head

2.0

sub total=

11.5

Total with 10% safety=

12.7

Design calculation sheet


Project no:

D0521-4.2-6

Date:

3/7/07

Sheet no.:

of

Chilled Water Secondary Pumps

Subject:

Computed by:

H.S

Checked by:

S.A

Approved by:

40 l/s
634 gpm

3 Pumps acting; flow per pump=

Pump Head
A- Pipe Losses
Dia

Length

Eq.leng

in

0.75

25.2

ft

135

442.26

574.93

5
5

339
66

1111.55
216.54

1445.01
281.50

6
Sub-Total-1

20

65.62

85.30

Flow

ft

Fr. losses

GPM

Losses

L/s

ft/100ft

ft

0.0652

1.5

1.54918

170

10.74

1.65

9.49

388
431

24.47
27.21

2.5
3

36.13
8.44

634

40.00

2.7

2.30

82.62295 103.27869 1.0332805

57.91 ft

B- Accessories Losses
Dia

FCU

Pump

Item

Qty.

Equ. L

Flow

Fr. losses

ft.

gpm

ft/100ft

in.

Losses
ft

Gate Valve

634.0

3.2

0.45

Strainer

110

634.0

3.2

3.55

Globe valve

170

634.0

3.2

5.49

Check Valve

60

634.0

3.2

1.94

Gate Valve

0.75

0.9

1.08

1.50

0.01

2-way control valve 0.75

29

1.08

1.50

3.00

Strainer

0.75

1.08

1.50

0.06

Coil

0.75

Globe valve

0.75

1.08
22

1.1

3.00
0.6

0.26

17.51 ft

Sub-Total-2
B- Equipment Losses
1-HEAT EXCHANGER
P.D=

2- AIR SEPARATOR

P.D=

1.6

Sum

75.42

ft

Friction Losses

22.99

Static head

sub total=
30% safty factor to account for
the expansion tak and fittings

31.617

41.102096

Total with 10% safety=

say

46

45.2

B- Accessories Losses
Size

Corresponding pipe length(m)


900 Elbow
R/d=1

10
15
20
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
500
600

3/4"
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
3-1/2"
4"
5"
6"
8"
10"
12"
14"
16"
18"
20"
24"

1.4
1.6
2
2.6
3.3
4
5
6
7.5
9
10
13
16
20
25
30
34
38
42
50
60

900 Elbow
R/d=1.5
0.9
1
1.4
1.7
2.3
2.6
3.3
4.1
5
5.9
10
13
16
20
25
30
34
38
42
50
60

900 Elbow
Street
2.3
2.5
3.2
4.1
5.6
6.3
8.2
10
12
15
17
21
25
-

450 Elbow
Std
0.7
0.8
0.9
1.3
1.7
2.1
2.6
3.2
4
4.7
5.2
6.5
7.9
10
13
16
18
20
23
26
30

450 Elbow
Street
1.1
1.3
1.6
2.1
3
3.4
4.5
5.2
6.4
7.3
8.5
11
13
-

1800 Elbow
Std
2.3
2.5
3.2
4.1
5.6
6.3
8.2
10
12
15
17
21
25
33
42
50
55
62
70
81
94

900 T(Separate
Flow)
2.7
3
4
5
7
8
10
12
15
18
21
25
30
40
50
60
68
78
85
100
115

T(Straight
Flow) No
Reduction
0.9
1
1.4
1.7
2.3
2.6
3.3
4.1
5
5.9
6.7
8.2
10
13
16
19
23
26
29
33
40

T(Straight
T(Straight
Flow) Reduced Flow) Reduced
1/4
1/2
1.2
1.4
1.9
2.3
3.1
3.7
4.7
5.6
7
8
9
12
14
18
23
26
30
35
40
44
50

1.4
1.6
2
2.6
3.3
4
5
6
7.5
9
10
13
16
20
25
30
34
38
42
50
60

Mitre Elbow
900
2.7
3
4
5
7
8
10
12
15
18
21
25
30
40
50
60
68
78
85
100
115

Mitre Elbow
600
1.1
1.3
1.6
2.1
3
3.4
4.5
5.2
6.4
7.3
8.5
11
13
17
21
25
29
31
37
41
49

Mitre Elbow
450
0.6
0.7
0.9
1
1.5
1.8
2.3
2.8
3.2
4
4.5
6
7
9
12
13
15
17
19
22
25

Mitre Elbow
300
0.3
0.4
0.5
0.7
0.9
1.1
1.3
1.7
2
2.4
2.7
3.2
4
5.1
7.2
8
9
10
11
13
16

Reduce

Sluice Valve
3.5
3.5
2.3
1.7
1.3
1.7
1.9
0.48
0.63
0.81
0.99
1.2
1.4
1.7

Globe Valve
17
18
22
29
38
43
55
69
84
100
120
140
170
220
280
320
360
410
460
520
610

Angle Valve
6
7
9
12
15
18
24
29
35
41
47
58
70
85
105
130
155
180
200
235
265

Foot Valve
2.4
2.4
3.6
4.5
5.4
6.6
8.4
10.2
12
16.5
21
24
33
43

Check
Valve(Swing
Type)
5
6
8
10
14
16
20
25
30
35
40
50
60
80
100
120
135
150
165
200
240

Gate
Valve
0.6
0.7
0.9
1
1.5
1.8
2.3
2.8
3.2
4
4.5
6
7
9
12
13
15
17
19
22
25

Y-Strainer
Flanged End
-

27
28
42
48
60
80
110
150
190
250
-

Y-Strainer
Butterfly
Screwed End
Valve

3
4
5
9
10
14
20
40
-