TESTING PROCEDURE FOR TRANSFORMER DIFFERENTIAL PROTECTION


RELAY USING CONVENTIONAL KIT

This test procedure is not for circulation and should be carried out by well
trained person. This procedure explained about operating value test and operating time test only.
Individual function only is considered for testing purposes and suitable setting can be adopted and
tested. It is not necessary to test the relay at all setting and one setting is enough for confirming
relay operation .Since P633/P32 is a numerical relay ,scheme operation check and load check
should be carried out by seeing measurement CHAPTER and DISTURBANCE RECORDER
WAVE FORM only.
Particulars of apparatus to be tested:
Designation
: Transformer Differential Protection Device(Relay)
Type P631/ P632/ P633/P634
Model No.
:
Sl.No.
:
Rating
: In=1/5 A, Vx=48-250 VDC/100-230VAC,Vn=50-130V AC
Rated Auxiliary supply : 220 VDC
Identification No.
:
Drawing No.
: P632
Mounting
: Vertical [Normal service]
Condition of sample
: New
Tests to be conducted:
PRODUCT DETAILS:
Rated Input current

: 1/5 A

Operating characteristics

:Differential Over current

Setting

: Idiff>0.1to2.5Amp,Idiff>>2.5to30Amp, Idiff>>>2.5to30Amp,

Rated Auxiliary supply

: 220 VDC

Range

: 48-250 VDC/100-230VAC

TERMINAL DETAILS:
Auxiliary supply terminals
Current input terminals
a- side (HV SIDE )

b-side ( LV SIDE)

: 20X25 (+) & 20X26 (-)


:
1/5 A
A -Phase
04X1 & 04X 2
B -Phase
04X3 & 04X 4
C -Phase
04X5 & 04X 6
N
04X7 & 04X 8
A -Phase
06X1 & 06X 2
B -Phase
06X3 & 06X 4
C -Phase
06X5 & 06X 6
N
06X7 & 06X 8

Page 2 of 14

Voltage input terminals

Output contacts (O/C) : Relay

OPTO INPUT

U1
U2
U3
U4

Test conditions:
Auxiliary voltage to be applied

04X13 & 04X16


K1 (Tripping) 20X1 & 20X 2 (N/O)
20X3 & 20X 4 (N/O)
K2
20X5 & 20X 6 (N/C)
20X7 & 20X 6 (N/O)
K3
20X8 & 20X 9 (N/O)
K4
20X10 & 20X11 (N/O)
K5
20X10 & 20X12 (N/O)
K6
20X10 & 20X13 (N/O)
K7
20X10 & 20X14 (N/O)
K8
20X15 & 20X16 (N/C)
20X17 & 20X16 (N/O)
20X18 (+ ive)& 20X19 (-ive)
20X20 (+ ive)& 20X21 (-ive)
20X22 (+ ive)& 20X24 (-ive)
20X23 (+ ive)& 20X24 (-ive)
: 220 VDC

1.0 ACCURACY TEST:


1.1 Determination of errors relating to characteristic quantity:
Output RL-3 is assigned permanently for following FUNCTIONS

Id>A
Id>B
Id>C
Id>>A
Id>>B
Id>>C
Io> HV
Io> LV1
Io> LV2
Aux0
Relay Setting
-- Operating value test:
1) DIFFERETIAL FUNCTION TEST
Relay setting

/Parameters/Function parameters/Parameter subset 1/DIFF


DIFF
Enable
PS1--Yes
DIFF
Idiff>
PS1--0.20 Iref
DIFF
Idiff>>
PS1--15.0 Iref
DIFF
Idiff>>>
PS1--BLOCKED
DIFF
m1
PS1--0.20
DIFF
m2
PS1--0.80
DIFF
IR,m2
PS1--1.5 Iref

Page 3 of 14

DIFF
DIFF
DIFF

Op.mode rush rst.PS1--With


RushI(2f0)/I(f0) PS1--20 %
0-seq. filt.a en.PS1--No

DIFF
DIFF
DIFF
DIFF
DIFF

0-seq. filt.b en.PS1--No


Overflux.bl. en. PS1--No
Ov. I(5f0)/I(f0) PS1--20 %
Op.del.,trip sig.PS1--0.00 s
Hyst. effective PS1--No

Procedure: Input energizing quantity (current) is increased slowly until relay contact operates
a- SIDE (HV SIDE )
Sl
No

Idiff>

Measured Operating Value


A-PHASE
B-PHASE

(Amp)
C-PHASE

0.20 Iref
1.00 Iref
2.00 Iref

Sl
No

Idiff>>

Claimed Value
(Amp)
0.099 to 0.121
0.198 to 0.242
0.297 to 0.363

Measured Operating Value


A-PHASE
B-PHASE

(Amp)
C-PHASE

3.00 Iref
10.0 Iref
25.0 Iref

Claimed Value
(Amp)
0.099 to 0.121
0.198 to 0.242
0.297 to 0.363

b- SIDE (LV SIDE )


Sl
No

Idiff>

Measured Operating Value


A-PHASE
B-PHASE

(Amp)
C-PHASE

0.20 Iref
1.00 Iref
2.00 Iref

Sl
No

Idiff>>
3.00 Iref
10.0 Iref
25.0 Iref

Claimed Value
(Amp)
0.099 to 0.121
0.198 to 0.242
0.297 to 0.363

Measured Operating Value


A-PHASE
B-PHASE

(Amp)
C-PHASE

Claimed Value
(Amp)
0.099 to 0.121
0.198 to 0.242
0.297 to 0.363

Bias Test
Procedure: Apply equal value of current in a-SIDE (HV SIDE ) & b-SIDE (LV SIDE ).
a-SIDE (HV SIDE ) input energizing quantity (current) is increased slowly until relay
contact operates
Actual Differential Current = Vector sum of both current
Bias Current = ( Magnitude sum of currents) / 2

Page 4 of 14

Theoretical Diffl current = 0.2+0.2 XIb (for slope=20%)


=0.2 +0.2 X 1.5 +(Ib-1.5) X 0.8 (for slope=80%)
Phase
s

A-Ph

B-Ph

C-Ph

Applied
Current (LV1)

Measured
Current
(HVside1)

0.2 A
0.5 A
1.0 A
2.5 A
5.0 A
0.2 A
0.5 A
1.0 A
2.5 A
5.0 A
0.2 A
0.5 A
1.0 A
2.5 A
5.0 A

Calculated Calculated Claimed value


Diffl.
Bias
Diffl
Current
Current
(Amp)
0.239 to 0.293
0.301 to 0.369
0.582 to 0.712
2.381 to 2.911
5.418 to 6.622
0.239 to 0.293
0.301 to 0.369
0.582 to 0.712
2.381 to 2.911
5.418 to 6.622
0.239 to 0.293
0.301 to 0.369
0.582 to 0.712
2.381 to 2.911
5.418 to 6.622

SECOND HARMONIC TEST


Procedure: Rated Input energizing quantity (current-1A/50Hz is applied in A-PHASE and relay is
found to be in the operated condition .Apply current with frequency 100Hz in phase with 50Hz
current in A-PHASE and increase slowly until relay contact opens. Record 100Hz current as
Second harmonic restrain current
Sl
No

RushI(2f0)/I(f0)

Applied 50Hz
current (Amp)

Measured Resetting Value


of 100Hz
(Amp)

20 %
30%

Claimed Value
(Amp)
0.0925 to 0.1075
0.0925 to 0.1075

REF TEST
Procedure: Input energizing quantity (current) is increased slowly until relay contact operates
a- SIDE REF (HV SIDE )
Relay setting

/Parameters/Function parameters/Parameter subset 1/REF_1


REF_1
Enable
PS1--Yes
REF_1
Operating mode PS1--High impedance
REF_1
Idiff>
PS1--1.00 Iref
REF_1
Idiff>>>
PS1--Blocked

Page 5 of 14

Sl
No

REF_1
REF_1

m1
m2

PS1--0.20
PS1--1.50

REF_1

IR,m2

PS1--1.00 Iref

Measured Operating Value

Idiff>

(Amp)

Setting
0.2 Iref
0.3 Iref
0.5 Iref
0.7 Iref
1.0 Iref

Claimed Value
(Amp)
0.19 to 0.21
0.285 to 0.315
0.475 to 0.525
0.665 to 0.735
0..95 to 1.05

b- SIDE REF (LV SIDE )


Relay Setting

/Parameters/Function parameters/Parameter subset 1/REF_2


REF_2
Enable
PS1-- Yes
REF_2
Operating mode PS1-- High impedance
REF_2
Idiff>
PS1-- 0.20 Iref
REF_2
Idiff>>>
PS1-- Blocked
REF_2
m1
PS1-- 0.20
REF_2
m2
PS1-- 1.50
REF_2
IR,m2
PS1-- 1.00 Iref

Sl
No

Measured Operating Value

Idiff>

(Amp)

Setting
0.2 Iref
0.3 Iref
0.5 Iref
0.7 Iref
1.0 Iref

Claimed Value
(Amp)
0.19 to 0.21
0.285 to 0.315
0.475 to 0.525
0.665 to 0.735
0.95 to 1.05

DTOC FUNCTION TEST

Procedure: Input energizing quantity (current) is increased slowly until relay contact operates
RELAY SETTING

/Parameters/Function parameters/Parameter subset 1/DTOC1

DTOC1
DTOC1
DTOC1
DTOC1

Enable
PS1--Yes
Block tim.st. IN PS1--Without
Gen.starting modePS1--W/o start. IN/Ineg
tGS
PS1--0.00 s

Page 6 of 14

DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1
DTOC1

Rush restr.enabl PS1--No


I>
PS1--1.00 Inom
I>>
PS1--30.00 Inom
I>>>
PS1--30.00 Inom
I> dynamic
PS1--1.00 Inom
I>> dynamic PS1--1.00 Inom
I>>> dynamic PS1--1.00 Inom
tI>
PS1--0.00 s
tI>>
PS1--0.00 s
tI>>>
PS1--0.00 s
Ineg>
PS1--0.25 Inom
Ineg>>
PS1--8.00 Inom
Ineg>>>
PS1--8.00 Inom
Ineg> dynamic PS1--1.00 Inom
Ineg>> dynamic PS1--1.00 Inom
Ineg>>> dynamic PS1--1.00 Inom
tIneg>
PS1--0.00 s
tIneg>>
PS1--0.00 s
tIneg>>>
PS1--0.00 s
IN>
PS1--0.25 Inom
IN>>
PS1--8.00 Inom
IN>>>
PS1--8.00 Inom
IN> dynamic PS1--1.00 Inom
IN>> dynamic PS1--1.00 Inom
IN>>> dynamic PS1--1.00 Inom
tIN>
PS1--0.00 s
tIN>>
PS1--0.00 s
tIN>>>
PS1--0.00 s

a.2.1) For phase fault (A,B,C) I >; tI> 0 sec


I> Setting

Value(A AC)

I nom

0.5 I nom
5 I nom
20 I nom

0.5
5
20

1
1
1

Measured operating value


A Ph
B Ph
C Ph

Claimed operating value


(AAC)
0.475 0.525
4.75 5.25
19 21

a.2.2) For phase fault (A,B,C) I>>; tI >> 0 sec


I>> Setting

Value(A AC)

I nom

0.5 I nom
5 I nom
20 I nom

0.5
5
20

1
1
1

Measured operating value


A Ph
B Ph
C Ph

Claimed operating value


(AAC)
0.475 0.525
4.75 5.25
19 21

a.2.3) For phase fault (A,B,C) I >>> ; tI>>> 0 sec


I>>> Setting Value(A AC)

I nom

Measured operating value

Claimed operating value

Page 7 of 14

A Ph
0.5 I nom
5 I nom
20 I nom

0.5
5
20

B Ph

C Ph

(AAC)
0.475 0.525
4.75 5.25
19 21

1
1
1

a.2.5) For earth fault IN> ; tIN> 0 sec


IN> Setting

Value(A AC)

I nom

0.2 I nom
1 I nom
8.0 I nom

0.2
1.0
8.0

1
1
1

Measured operating
value I neutral>

Claimed operating
value (AAC)
0.19 0.21
0.95 1.05
7.60 8.40

a.2.6) For earth fault IN>> ; tIN>> 0 sec


IN>> Setting

Value(A AC)

I nom

0.2 I nom
1 I nom
8.0 I nom

0.2
1.0
8.0

1
1
1

Measured
operating value
I neutral>>

Claimed operating
value (AAC)
0.19 0.21
0.95 1.05
7.60 8.40

a.2.7) For earth fault IN>>> ; tIN>>> 0 sec


IN>>> Setting

Value(A AC)

I nom

0.2 I nom
1 I nom
8.0 I nom

0.2
1.0
8

1
1
1

Measured
operating value
I neutral>>>

Claimed operating
value (AAC)
0.19 0.21
0.95 1.05
7.60 8.40

a.2.9) For NEGATIVE SEQUENCE Ineg > ; tIneg > 0 sec


Procedure:
Apply 3 phase Negative sequence current and increase till the function assigned contact closes
INEG> Setting Value(A AC)

I nom

0.5 I nom
5 I nom
8.0 I nom

1
1
1

0.5
5
8.0

Measured operating
value Ineg>

Claimed operating
value (AAC)
0.475 0.525
4.75 5.25
7.60 8.40

a.2.10) For NEGATIVE SEQUEMCE Ineg > >; tIneg >> 0 sec
INEG>> Setting
0.5 A
5A
8.0 I nom

Value(A
AC)
0.5
5
8.0

I nom
1
1
1

Measured operating
value Ineg>>

Claimed operating
value (AAC)
0.475 0.525
4.75 5.25
7.60 8.40

a.2.11) For NEGATIVE SEQUEMCE Ineg > >>; tIneg >>> 0 sec

Page 8 of 14

INEG>>>
Setting
0.5 I nom
5 I nom
8.0 I nom

Value(A AC)

I nom

0.5
5
8.0

1
1
1

Measured operating
value I neg>>>

Claimed operating
value (AAC)
0.475 0.525
4.75 5.25
7.60 8.40

a.3) IDMT FUNCTION TEST

/Parameters/Function parameters/Parameter subset 1/IDMT1

IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1
IDMT1

Enable
PS1-- Yes
Block tim.st. IN PS1-- Without
Gen.starting modePS1-- W/o start. IN/Ineg
tGS
PS1-- 0.00 s
Rush restr.enabl PS1-- No
Iref,P
PS1-- 1.00 Inom
Iref,P dynamic PS1-- 1.00 Inom
Characteristic P PS1-- Definite Time
Factor kt,P
PS1-- 1.00
Min. trip t. P PS1-- 0.00 s
Hold time P
PS1-- 0.00 s
Release P
PS1-- Without delay
Iref,neg
PS1-- 0.80 Inom
Iref,neg dynamic PS1-- Blocked
Character. neg. PS1-- Definite Time
Factor kt,neg PS1-- 1.00
Min. trip t. neg PS1-- 1.00 s
Hold time neg PS1-- 0.00 s
Release neg PS1-- Without delay
Iref,N
PS1-- 0.80 Inom
Iref,N dynamic PS1-- Blocked
Characteristic N PS1-- Definite Time
Factor kt,N
PS1-- 1.00
Min. trip t. N PS1-- 1.00 s
Hold time N
PS1-- 0.00 s
Release N
PS1-- Without delay

a.3.1) For phase fault (A,B,C) ; Min. trip t. P= 0 sec

Iref,P

Value(A AC)

I nom

Setting
0.2 I nom
1 I nom
4 I nom

0.2
1.0
4.0

1
1
1

Measured operating value


A Ph
B Ph
C Ph

Claimed operating value


(AAC)
0.19 2.1
0.95 1.05
3.8 4.2

Page 9 of 14

a.3.2) For NEGATIVE SEQUENCE Iref,neg Min. trip t. neg= 0 sec


Procedure:
Apply 3 phase Negative sequence current and increase till the function assigned contact closes

Iref,neg

Value(A AC)

I nom

Setting
0.2 I nom
0.4 I nom
0.8 I nom

0.2
0.4
0.8

1
1
1

Measured operating
value Ineg

Claimed operating
value (AAC)
0.19 2.1
0.380.42
0.76 0.84

a.3.3) For earth fault Iref,N ; Min. trip t. N= 0 sec

Iref,N Setting

Value(A AC)

I nom

0.2 I nom
0.4 I nom
0.8 I nom

0.2
0.4
0.8

1
1
1

Measured operating
value I neutral

Claimed operating
value (AAC)
0.19 2.1
0.380.42
0.76 0.84

a.4 ) V < > (UNDER/OVER VOLTAGE)


Procedure:
Apply 3ph-n voltage(63.5V) and increase one phase voltage for over voltage or decrease one phase
voltage for under voltage function till the function assigned contact closes
RELAY SETTING

/Parameters/Function parameters/Parameter subset 1/V<>


V<>
V<>
V<>
V<>
V<>
V<>
V<>
V<>
V<>
V<>
V<>
V<>

Enable
PS1-- Yes
V>
PS1-- 1. Vnom
V>>
PS1-- 1. Vnom
tV>
PS1-- 0.00 s
tV>>
PS1-- 0.00 s
V<
PS1-- 0.80 Vnom
V<<
PS1-- 0.80 Vnom
Vmin>
PS1-- 0.25 Vnom
tV<
PS1-- Blocked
tV<<
PS1-- Blocked
tTransient
PS1-- 1.00 s
Hyst. V<> meas. PS1-- 1 %

a.4.1)OVER VOLTAGE V> ;tV > 0 sec


V> Setting
1.1 V nom

Value(V
AC)
69.859/121

V nom
110/3 V

Measured operating value V>


AN
BN
CN

Claimed operating
value (V AC)
67.76371.955

Page 10 of 14

1.25 V nom
1.5 V nom

79.385/137
.5
95.263/165

110/3 V

77.003 --- 81.766

110/3 V

92.40598.121

a.3.2) OVER VOLTAGE V>> ;tV> > 0 sec


V> >
Setting
1.1 V nom
1.25 V nom
1.5 V nom

Value(V
AC)
69.859
79.385
95.263

V nom

Measured operating value V>>


AN
BN
CN

Claimed operating
value (V AC)
67.76371.955
77.003 --- 81.766
92.40598.121

110/3 V
110/3 V
110/3 V

a.3.3) UNDER VOLTAGE V< ;tV< 0 sec


V< Setting

Value(V AC)

V nom

Measured operating value V<


AN
BN
CN

0.3 V nom
0.6 V nom
0.9 V nom

19.05
38.10
57.15

110/3 V
110/3 V
110/3 V

Claimed operating
value (V AC)
18.47819.622
36.957---39.243
55.43558.865

a.3.4) UNDER VOLTAGE V<< ;tV<< 0 sec


V<< Setting

Value(V AC)

V nom

V<< Optd
AN

0.3 V nom
0.6 V nom
0.9 V nom

19.05
38.10
57.15

BN

110/3 V
110/3 V
110/3 V

CN

Claimed operating
value AAC
18.47819.622
36.957---39.243
55.43558.865

aa.4) f < > (UNDER/OVER FREQUENCY)


Procedure:
Apply3 phase voltage(63.5V) with rated frequency and increase or decrease the frequency till the
function assigned contact closes
RELAY SETTING

/Parameters/Function parameters/General functions/f<>


General enable USER -- Yes
Selection meas. volt -- Voltage A-G
Evaluation time
-- 4 Periods
Undervolt. block. V< -- 0.65 Vnom(/3)
Other functions in General functions -- General enable USER -- No
/Parameters/Config. parameters/OUTP
Fct. assignm. K 7 --- f<> Trip signal f1

Page 11 of 14

/Parameters/Function parameters/Parameter subset 1/f<>


Enable
PS1 --- Yes
Oper. mode f1 PS1 --- f
f1
PS1 --- 49.80 Hz
tf1
PS1 --- 0.00 s
df1/dt
PS1 --- 2.0 Hz/s
Delta f1
PS1 --- 0.30 Hz
Delta t1
PS1 --- 0.30 s
Oper. mode f2 PS1 --- f
f2
PS1 --- 69.80 Hz
tf2
PS1 --- 0.00 s
df2/dt
PS1 --- 2.0 Hz/s
Delta f2
PS1 --- 0.30 Hz
Delta t2
PS1 --- 0.30 s
Oper. mode f3 PS1 --- f
f3
PS1 --- 69.80 Hz
tf3
PS1 --- 0.00 s
df3/dt
PS1 --- 2.0 Hz/s
Delta f3
PS1 --- 0.30 Hz
Delta t3
PS1 --- 0.30 s
Oper. mode f4 PS1 --- f
f4
PS1 --- 69.80 Hz
tf4
PS1 --- 0.00 s
df4/dt
PS1 --- 2.0 Hz/s
Delta f4
PS1 --- 0.30 Hz
Delta t4
PS1 --- 0.30 s
Frequency setting f<> Function
f1 Setting
45 Hz
48 Hz
52 Hz

Measured operating value ( Hz )

Claimed operating value Hz


43.6546.35
46.56 --- 49.44
50.44 --- 53.56

V/f FUNCTION-ALARM
Relay Setting

/Parameters/Function parameters/Parameter subset 1/V/f


V/f
Enable
PS1-- Yes
V/f
V/f> (alarm) PS1-- 1.05 Vnom/fnom
V/f
V/f(t)>
PS1-- Blocked
V/f
V/f>>
PS1-- Blocked
V/f
tV/f>
PS1-- 0 s
V/f
t at V/f=1.05 PS1-- 72.8 s
V/f
t at V/f=1.10 PS1-- 18.8 s
V/f
t at V/f=1.15 PS1-- 8.8 s
V/f
t at V/f=1.20 PS1-- 5.3 s
V/f
t at V/f=1.25 PS1-- 3.7 s

Page 12 of 14

V/f
V/f
V/f
V/f
V/f
V/f
V/f
V/f
V/f

t at V/f=1.30 PS1-- 2.8 s


t at V/f=1.35 PS1-- 2.3 s
t at V/f=1.40 PS1-- 1.9 s
t at V/f=1.45 PS1-- 1.7 s
t at V/f=1.50 PS1-- 1.5 s
t at V/f=1.55 PS1-- 1.4 s
t at V/f=1.60 PS1-- 1.3 s
Reset time
PS1-- 0 s
tV/f>>
PS1-- 0 s

Procedure :Apply AC voltage (50Hz) less than setting and increase the voltage with time
delay of 200mSec till it operates. Record the value (Operating value = setting X supply
frequency )
Sl No

V/f> (alarm)

Value(V AC)

Measured Operating
Value (Volt)

Setting
(Vnom/fnom)

1.00 110.0
1.10 121.0
1.19 130.9

Claimed Value
(Volt)
106.70 to 113.30
117.37 to 124.63
126.973 to 134.83

1.2 Operating time test


LOW SET OPERATING TIME;
Relay Setting

SETTINGS(1)
S1 Id>
200.0e-3PU
Procedure: Apply 1ph current with 5 times setting value & measure operating time ..
HV SIDE1
Sl No Measured Operating Time
Claimed Operating Time
A-PHASE

B-PHASE

C-PHASE
30 to 40 m Sec

HIGH SET OPERATING TIME;


Relay Setting

SETTINGS(1)
S1 Id>>

5 PU

Procedure: Apply 1ph current with 5 times setting value & measure operating time ..
LV 1
Sl No Measured Operating Time
Claimed Operating Time
A-PHASE

B-PHASE

C-PHASE
10 to 20 m Sec

REF OPERATING TIME;


Relay Setting

Page 13 of 14

SETTINGS(1)
S1 Io> HV
S1 Io> LV1
S1 Io> LV2

100.0e-3PU
100.0e-3PU
100.0e-3PU

Procedure: Apply 1ph current with 5 times setting value & measure operating time ..
Sl No Measured Operating Time
Claimed Operating Time
HV

LV1

LV2
20 to 40 m Sec

OVERFLUX OPERATING TIME(TRIP);


Relay Setting

SETTINGS(1)
S1 V/f(Trip)Char DT
S1 V/f (Trip) 2.20Procedure: Apply voltage 121VAC (110% OF SETTING) ,50Hz and measure operating
time
Sl No tV/f (Trip) setting Measured Operating Time
Claimed Operating Time
(Sec)

(Sec)
1.90 to 2.1S
19.0 to 21.0S
47.5 to 52.5

2S
20 S
50 S
Relay Setting

SETTINGS(1)
S1 V/f(Trip) I DMT
S1 V/f (Trip) 2.20S1 TMS
1
Procedure: Apply voltage 121VAC (110% OF SETTING) ,50Hz and measure operating
time
Sl No Applied Voltage
Measured Operating Time
Claimed Operating Time
(Sec)

(Sec)
16.92 to 20.68
4.770 to 5.83
2.520 to 3.08

121V
132V
143V
OVERFLUX OPERATING TIME(ALARM);
Relay Setting

SETTINGS(1)
S1 V/f(Trip)Char DT
S1 V/f (ALARM) 2.20Procedure: Apply voltage 121VAC (110% OF SETTING) ,50Hz and measure operating
time
Sl No tV/f (ALARM) setting
Measured Operating Time
Claimed Operating Time
(Sec)
2S
20 S

(Sec)
1.90 to 2.1S
19.0 to 21.0S

Page 14 of 14

50 S

47.5 to 52.5