You are on page 1of 156

EDMT281536

Heat pump 50Hz


FHQ-DA + RZQS, RZQ series

EDMT281536

Part 1 SkyAir FHQ-DA + RZQS, RZQ series .................................. 5


1. External appearance ...............................................................................7
2. Model name, power supply and nomenclature .......................................9
2.1 Model name and power supply ................................................................9
2.2 Nomenclature .........................................................................................10

3. Functions...............................................................................................11
4. Specifications ........................................................................................12
4.1 RZQS .....................................................................................................12
4.2 RZQ-LV1 ................................................................................................13
4.3 RZQ-HAY4A...........................................................................................15

5. Dimensions and service space .............................................................17


5.1
5.2
5.3
5.4
5.5

Indoor unit ..............................................................................................17


Wired remote controller ..........................................................................20
Wireless remote controller......................................................................22
Outdoor unit............................................................................................23
Installation Service Space ......................................................................28

6. Piping diagrams ....................................................................................36


6.1 Indoor unit + outdoor unit .......................................................................36

7. Wiring diagrams ....................................................................................41


7.1 Indoor unit ..............................................................................................41
7.2 Outdoor unit............................................................................................42

8. Field wiring ............................................................................................48


9. Electric characteristics ..........................................................................49
9.1 FHQ-DA + RZQS....................................................................................49
9.2 FHQ-DA + RZQ-LV1 ..............................................................................50
9.3 FHQ-DA + RZQ-HAY4A .........................................................................51

10.Capacity tables......................................................................................52
10.1
10.2
10.3
10.4

RZQS .....................................................................................................52
RZQ-LV1 ................................................................................................54
RZQ-HAY4A...........................................................................................58
Capacity correction factor by the length of refrigerant piping .................61

11.Operation limits .....................................................................................62


12.Sound level ...........................................................................................63
12.1 Indoor unit ..............................................................................................63
12.2 Outdoor unit............................................................................................66

13.Accessories...........................................................................................74
13.1 Indoor unit ..............................................................................................74
13.2 Outdoor unit............................................................................................75

Part 2 Installation of indoor / outdoor unit ................................. 77


1. Centre of gravity....................................................................................78
2. Installation of indoor unit .......................................................................81
2.1 FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA /
FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA ..........................81

3. Installation of outdoor unit ...................................................................101


3.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 /
RZQ125LV1 .........................................................................................101
3.2 RZQ140LV1 .........................................................................................117
3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A ...........................133
Table of contents

EDMT281536

3.4 Equivalent piping length of joints (reference) .......................................149

Table of contents

EDMT281536

Publication list

Publication list
Refrigerant

Inverter/
Series
Non Inverter

Book No.

Type, Hz

Model name of
indoor / outdoor unit

Area

Note

Published
in

- Indoor units
FCQ71/100/125/140KVEA
FFQ25/35/50/60BV1B
FHQ35/50/60/71/100/125BVV1B
FBQ50/60BV1A
FBQ71/100/125/140DV1
EDHK281002 H/P 50Hz

RZQ

R410A

- Outdoor units
RZQ71KBV1
RZQ100/125/140HY4A
RXS25/35EBVMA
RXS50/60FVMA
RKS25/35EBVMA
RKS50/60FVMA

- Indoor units
FCQ50/60LUV1V
FCQ71-140LUV1
FFQ25-60BV1B
FHQ50/60BVV1V
FHQ35/71/100/125BVV1B
FHQ140CAVEA
FDXS25-60CVMA
FBQ50-71BV1A
FBQ50/60DV1V
EDVN281408 H/P 50Hz FBQ71-140DV1
FVQ50/60CVE
FVQ71-140CVEB
- Outdoor units
RZQ50/60KBV1V
RZQ50/60KBV4A
RZQ71-140KCV4A
RZQ100-140HAY4A
RXS25/35EBVMA
RXS50FAVMA
RXS50-71FVMA

Inverter

Hong Kong

Jun. 2010

- New lineup of indoor units:


FCQ50/60LUV1V
FHQ50/60BVV1V
Vietnam FBQ50/60DV1V
Sep. 2014
FVQ50/60CVE
- New lineup of outdoor units:
RZQ50/60KBV1V

- New lineup of indoor units:


FHQ71/100/125BWV1A
FBQ71/100/125/140DBVEA

- Indoor units
FCQ71/100/125/140KAVEA
FHQ71/100/125BWV1A
FHQ140CAVEA
FAQ71/100CVEA
FBQ71/100/125/140DBVEA Vietnam
India
EDMT281426 H/P 50Hz FVQ50/60CVE
FVQ71/100/125/140CVEB Hong Kong - Outdoor units
RZQS50/60AV1
RZQ71/100/125/140LV1
RZQ100/125/140HAY4A
RZQS
RZQ

Model change of indoor units:


FCQ71/100/125/140KVEA

FCQ71/100/125/140KAVEA
Mar. 2015
New lineup of outdoor units:
RZQS50/60AV1
RZQ71/100/125/140LV1

- Discontinued outdoor units:


RZQ71KBV1
RZQ50/60KBV4A
RZQ71-140KCV4A

- Indoor units
FBQ50/60/71/100/125/140EVE
H/P
EDMT281512 50/60Hz

- Outdoor units
RZQS50/60AV1
RZQ71/100/125/140LV1
RZQ100/125/140HAY4A
RZQ100/125/140KCTLT
RZQ100/125/140LUYLT

Vietnam
Philippines - New lineup of indoor units:
India
FBQ50/60/71/100/125/140EVE Aug. 2015
Hong Kong

- Indoor units
FHQ50/60/71/100/125/140DAVMA
EDMT281536 H/P 50Hz - Outdoor units
RZQS50/60AV1
RZQ71/100/125/140LV1
RZQ100/125/140HAY4A

EDMT281536 as shown by

Table of contents

Hong Kong
Vietnam - New lineup of indoor units: Dec. 2015
FHQ50/60/71/100/125/140DAVMA
India

Publication list

EDMT281536

Table of contents

EDMT281536

Part 1
SkyAir
FHQ-DA + RZQS, RZQ series
Model series
Class

50

Indoor
unit

FHQ 50DA
RZQS

Outdoor
unit
RZQ

50A

60
60DA

71

100

125

140

71DA 100DA 125DA 140DA

60A

Power
supply
VMA
V1

71L

100L

125L

140L

100HA 125HA 140HA

V1
Y4A

1. External appearance ...............................................................................7


2. Model name, power supply and nomenclature .......................................9
2.1 Model name and power supply ................................................................9
2.2 Nomenclature .........................................................................................10

3. Functions...............................................................................................11
4. Specifications ........................................................................................12
4.1 RZQS .....................................................................................................12
4.2 RZQ-LV1 ................................................................................................13
4.3 RZQ-HAY4A...........................................................................................15

5. Dimensions and service space .............................................................17


5.1
5.2
5.3
5.4
5.5

Indoor unit ..............................................................................................17


Wired remote controller ..........................................................................20
Wireless remote controller......................................................................22
Outdoor unit............................................................................................23
Installation Service Space ......................................................................28

6. Piping diagrams ....................................................................................36


6.1 Indoor unit + outdoor unit .......................................................................36

7. Wiring diagrams ....................................................................................41


7.1 Indoor unit ..............................................................................................41
7.2 Outdoor unit............................................................................................42

8. Field wiring ............................................................................................48


9. Electric characteristics ..........................................................................49
9.1 FHQ-DA + RZQS....................................................................................49
9.2 FHQ-DA + RZQ-LV1 ..............................................................................50
9.3 FHQ-DA + RZQ-HAY4A .........................................................................51

10.Capacity tables......................................................................................52
10.1
10.2
10.3
10.4

RZQS .....................................................................................................52
RZQ-LV1 ................................................................................................54
RZQ-HAY4A...........................................................................................58
Capacity correction factor by the length of refrigerant piping .................61

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

11.Operation limits .....................................................................................62


12.Sound level ...........................................................................................63
12.1 Indoor unit ..............................................................................................63
12.2 Outdoor unit............................................................................................66

13.Accessories...........................................................................................74
13.1 Indoor unit ..............................................................................................74
13.2 Outdoor unit............................................................................................75

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

External appearance

1. External appearance

Indoor unit

FHQ-DAVMA

Wired
remote controller

BRC1E62

BRC1C61

BRC1D61

Wireless
remote controller

BRC7GA53

SkyAir FHQ-DA + RZQS, RZQ series

Signal receiver unit

External appearance

EDMT281536

Outdoor unit

RZQS50AV1
RZQS60AV1

RZQ71LV1

RZQ100LV1

RZQ125LV1

RZQ140LV1

RZQ100HAY4A
RZQ125HAY4A
RZQ140HAY4A

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Model name, power supply and nomenclature

2. Model name, power supply and nomenclature


2.1

Model name and power supply


Indoor unit
Type

Ceiling suspended type

Model name
FHQ50DAVMA
FHQ60DAVMA
FHQ71DAVMA
FHQ100DAVMA
FHQ125DAVMA
FHQ140DAVMA
FHQ100DAVMA
FHQ125DAVMA
FHQ140DAVMA

SkyAir FHQ-DA + RZQS, RZQ series

Outdoor unit
Model name
RZQS50AV1
RZQS60AV1
RZQ71LV1
RZQ100LV1
RZQ125LV1
RZQ140LV1
RZQ100HAY4A
RZQ125HAY4A
RZQ140HAY4A

Power supply intake

Outdoor unit: 1 phase, 220-240V, 50Hz

Outdoor unit: 3 phase, 415V, 50Hz

Model name, power supply and nomenclature

2.2

EDMT281536

Nomenclature

Indoor unit

50

DA

VM

A
Standard symbol
A: Australia
Power supply symbol
V1: 1 phase, 220-240V, 50Hz
VE: 1 phase, 220-240/220V, 50/60Hz
VM: 1 phase, 220-240/220-230V, 50/60Hz
Indicates major design category
Capacity indication
Refrigerant and type
Q: R410A, Heat pump or Cooling only
Shape
C: Ceiling mounted cassette (Round flow)
H: Ceiling suspended
A: Wall mounted
B(-E): Middle static pressure ceiling mounted duct
Unit category
F: Air cooled split indoor unit

Outdoor unit

50

V1
Standard symbol
A: Australia
Power supply symbol
V1: 1 phase, 220-240V, 50Hz
Y4: 3 phase, 415V, 50Hz
Indicates major design category
Capacity indication
Grade and refrigerant symbol
S: Inverter, R410A
Refrigerant and type
Q: R410A, Heat Pump
Inverter / Non inverter
Z: Inverter
Unit category
R: Air cooled split outdoor unit

10

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Functions

3. Functions
Category

Function

1
Indoor
unit

FHQ50-60DAVMA

FHQ71-140DAVMA

Outdoor
unit

RZQS50-60AV1

RZQ71-140LV1
RZQ100-140HAY4A

Inverter control
Auto swing

Swing pattern selection

Draft prevention function (heating)

Independent up-and-down airflow

DC fan motor (Indoor unit)


Switchable fan speed
Comfort

{ (3 step)

{ (3 step)

Auto airflow rate

High fan speed mode

{ (*7)

{ (*7)

Two selectable temperature-sensors (*1)

Hot start

Year-round cooling applicable

Night quiet operation (*2)

Setpoint auto reset (*5)

Setpoint range set (*5)


Remote
Weekly schedule timer (*3)
controller
Off timer (programmed) (*5)

On/Off timer (*6)

Anti-bacterial air filter

Mould-proof air filter

Programme Dry
High ceiling application

Cleanliness

Silver ion anti-bacterial drain pan

Mould-proof drain pan

Drain pump mechanism (*4)

Pre-charged for up to 30 m (*2)

Pre-charged for up to 10 m (*2)

Long-life filter
Work & Filter sign
servicing
Ceiling soiling prevention

Control
features

Options
Others

Low gas pressure detection (*2)

Emergency operation

Self-diagnosis function

Auto-restart

Auto-cooling/heating change-over

Control by 2 remote controllers

Group control by 1 remote controller

External command control (*4)

Central remote control

Interlock control with Heat Reclaim Ventilator

DIII-NET communication standard

High-efficiency filter

Ultra long-life filter

Fresh air intake kit

Anti corrosion treated heat exchangers (*2)

Notes:

{: Functions exist.
: No functions
*1: Applicable when wired remote controller is used
*2: For the outdoor units
*3: Applicable when BRC1D61 or BRC1E62 is used
*4: Option
*5: Applicable when BRC1E62 is used
*6: Applicable when BRC1C61 is used
*7: Installable on max. 3.5m (50-71) and 4.3m (100-140) high ceiling.

SkyAir FHQ-DA + RZQS, RZQ series

11

Specifications

EDMT281536

4. Specifications
4.1

RZQS

FHQ-DA (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

Power supply
Power supply intake
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h

Cooling capacity *1 *2

Heating capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

HWD
Type
Type
Motor output

mm

Fan
Airflow rate (H/M/L)
Sound pressure level (H/M/L) *3
Air filter
Mass
Liquid
Piping
Gas
connections
Drain
Wired
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimensions
HWD
Coil
Type
Type
Comp.
Motor output
Type
Motor output
Fan
Airflow rate
Cooling
Sound pressure
Heating
level *3
Night quiet mode
Mass
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Specification
Drawing No.
Sound (Indoor)
Sound (Outdoor)

Notes:

W
m/min
l/s
cfm
dB(A)
kg
mm
mm
mm

mm

kW
W
m/min
dB(A)
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FHQ50DAVMA
RZQS50AV1
1 phase, 220-240V, 50Hz
Outdoor unit side
5.0 (3.2-5.6)
17,100 (10,900-19,100)
4,300 (2,800-4,800)
6.0 (3.5-7.0)
20,500 (11,900-23,900)
5,200 (3,000-6,000)
FHQ50DAVMA
Light ivory
235960690
Cross fin coil
Sirocco fan
87
15/12/10
250/200/167
530/424/353
37/35/32
Resin net (with mould resistance)
25
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQS50AV1
Ivory white
770900320
Cross fin coil
Hermetically sealed swing type
1.3
Propeller fan
70
52
48
50
44
64
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
50 (Equivalent length 70m)
30
R410A
2.0 (Charged for 30m)
Refer to the nameplate of compressor.
0.75
C: 3D096268A
C: 4D079992A
C: 4D090424, C: 4D090423

FHQ60DAVMA
RZQS60AV1
1 phase, 220-240V, 50Hz
Outdoor unit side
6.0 (3.2-6.0)
20,500 (10,900-20,500)
5,200 (2,800-5,200)
6.8 (3.5-8.0)
23,200 (11,900-27,300)
5,900 (3,000-6,900)
FHQ60DAVMA
Light ivory
235960690
Cross fin coil
Sirocco fan
87
15/12/10
250/200/167
530/424/353
37/35/32
Resin net (with mould resistance)
25
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQS60AV1
Ivory white
770900320
Cross fin coil
Hermetically sealed swing type
1.6
Propeller fan
70
52
48
50
44
64
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
50 (Equivalent length 70m)
30
R410A
2.0 (Charged for 30m)
Refer to the nameplate of compressor.
0.75
C: 3D096268A
C: 4D079992A
C: 4D090424, C: 4D090423

*1. The above data are based on the following conditions:


Cooling
Indoor: 27CDB, 19CWB
Outdoor: 35CDB, 24CWB

Heating
Indoor: 20CDB, 15CWB
Outdoor: 7CDB, 6CWB

Conversion formulae
Piping length
7.5m
(Horizontal)

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation

kcal/h=kW860
Btu/h=kW3412
l/s=m/min1000/60
cfm=m/min35.3

condition, it is normally over the set value due to the environmental noise and sound reflection.

12

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

4.2

Specifications

RZQ-LV1

FHQ-DA (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

Power supply
Power supply intake
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h

Cooling capacity *1 *2

Heating capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

HWD
Type
Type
Motor output

mm

Fan
Airflow rate (H/M/L)
Sound pressure level (H/M/L) *3
Air filter
Mass
Liquid
Piping
Gas
connections
Drain
Wired
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimensions
HWD
Coil
Type
Type
Comp.
Motor output
Type
Motor output
Fan
Airflow rate
Cooling
Sound pressure
Heating
level *3
Night quiet mode
Mass
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Specification
Drawing No.
Sound (Indoor)
Sound (Outdoor)

Notes:

W
m/min
l/s
cfm
dB(A)
kg
mm
mm
mm

mm

kW
W
m/min
dB(A)
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FHQ71DAVMA
RZQ71LV1
1 phase, 220-240V, 50Hz
Outdoor unit side
7.1 (3.2-8.0)
24,200 (10,900-27,300)
6,100 (2,800-6,900)
8.0 (3.5-9.0)
27,300 (11,900-30,700)
6,900 (3,000-7,700)
FHQ71DAVMA
Light ivory
2351,270690
Cross fin coil
Sirocco fan
117
20.5/17/14
342/283/233
724/600/494
38/36/34
Resin net (with mould resistance)
32
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQ71LV1
Ivory white
770900320
Cross fin coil
Hermetically sealed swing type
1.7
Propeller fan
70
52
49
51
45
64
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
50 (Equivalent length 70m)
30
R410A
2.0 (Charged for 30m)
Refer to the nameplate of compressor.
0.75
C: 3D096434B
C: 4D069649C
C: 4D075745A, C: 4D075748A

FHQ100DAVMA
RZQ100LV1
1 phase, 220-240V, 50Hz
Outdoor unit side
10.0 (5.0-11.2)
34,100 (17,100-38,200)
8,600 (4,300-9,600)
11.2 (5.1-12.8)
38,200 (17,400-43,700)
9,600 (4,400-11,000)
FHQ100DAVMA
Light ivory
2351,590690
Cross fin coil
Sirocco fan
150
28/24/20
467/400/333
988/847/706
42/38/34
Resin net (with mould resistance)
38
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQ100LV1
Ivory white
990940320
Cross fin coil
Hermetically sealed swing type
2.08
Propeller fan
200
76
51
53
47
75
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
75 (Equivalent length 90m)
30
R410A
2.9 (Charged for 30m)
Refer to the nameplate of compressor.
0.75
C: 3D096434B
C: 4D069652D
C: 4D089676, C: 4D089677A

*1. The above data are based on the following conditions:


Cooling
Indoor: 27CDB, 19CWB
Outdoor: 35CDB, 24CWB

Heating
Indoor: 20CDB, 15CWB
Outdoor: 7CDB, 6CWB

Conversion formulae
Piping length
7.5m
(Horizontal)

kcal/h=kW860
Btu/h=kW3412
l/s=m/min1000/60
cfm=m/min35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation
condition, it is normally over the set value due to the environmental noise and sound reflection.

SkyAir FHQ-DA + RZQS, RZQ series

13

Specifications

EDMT281536

FHQ-DA (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

Power supply
Power supply intake
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h

Cooling capacity *1 *2

Heating capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

HWD
Type
Type
Motor output

mm

Fan
Airflow rate (H/M/L)
Sound pressure level (H/M/L) *3
Air filter
Mass
Liquid
Piping
Gas
connections
Drain
Wired
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimensions
HWD
Coil
Type
Type
Comp.
Motor output
Type
Motor output
Fan
Airflow rate
Cooling
Sound pressure
Heating
level *3
Night quiet mode
Mass
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Specification
Drawing No.
Sound (Indoor)
Sound (Outdoor)

Notes:

W
m/min
l/s
cfm
dB(A)
kg
mm
mm
mm

mm

kW
W
m/min
dB(A)
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FHQ125DAVMA
RZQ125LV1
1 phase, 220-240V, 50Hz
Outdoor unit side
12.5 (5.7-14.0)
42,700 (19,500-47,800)
10,800 (4,900-12,000)
14.0 (6.0-16.2)
47,800 (20,500-55,300)
12,000 (5,200-13,900)
FHQ125DAVMA
Light ivory
2351,590690
Cross fin coil
Sirocco fan
150
31/27/23
517/450/383
1,094/953/812
44/41/37
Resin net (with mould resistance)
38
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQ125LV1
Ivory white
1,170900320
Cross fin coil
Hermetically sealed scroll type
2.4
Propeller fan
70+70
95
51
53
47
98
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
75 (Equivalent length 90m)
30
R410A
3.15 (Charged for 30m)
Refer to the nameplate of compressor.
1.2
C: 3D096434B
C: 4D069650E
C: 4D075741A, C: 4D075747A

FHQ140DAVMA
RZQ140LV1
1 phase, 220-240V, 50Hz
Outdoor unit side
13.2 (6.2-15.5)
45,000 (21,200-52,900)
11,400 (5,300-13,300)
16.0 (6.2-18.0)
54,600 (21,200-61,400)
13,800 (5,300-15,500)
FHQ140DAVMA
Light ivory
2351,590690
Cross fin coil
Sirocco fan
150
34/29/24
567/483/400
1,200/1,024/847
46/42/38
Resin net (with mould resistance)
38
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQ140LV1
Ivory white
1,430940320
Cross fin coil
Hermetically sealed scroll type
3.15
Propeller fan
200+200
140
54
56
50
108
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
75 (Equivalent length 90m)
30
R410A
4.2 (Charged for 30m)
Refer to the nameplate of compressor.
1.5
C: 3D096434B
C: 4D069651E
C: 4D089680A, C: 4D089681A

*1. The above data are based on the following conditions:


Cooling
Indoor: 27CDB, 19CWB
Outdoor: 35CDB, 24CWB

Heating
Indoor: 20CDB, 15CWB
Outdoor: 7CDB, 6CWB

Conversion formulae
Piping length
7.5m
(Horizontal)

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation

kcal/h=kW860
Btu/h=kW3412
l/s=m/min1000/60
cfm=m/min35.3

condition, it is normally over the set value due to the environmental noise and sound reflection.

14

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

4.3

Specifications

RZQ-HAY4A

FHQ-DA (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

Power supply
Power supply intake
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h

Cooling capacity *1 *2

Heating capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

HWD
Type
Type
Motor output

mm

Fan
Airflow rate (H/M/L)
Sound pressure level (H/M/L) *3
Air filter
Mass
Liquid
Piping
Gas
connections
Drain
Wired
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimensions
HWD
Coil
Type
Type
Comp.
Motor output
Type
Motor output
Fan
Airflow rate
Cooling
Sound pressure
Heating
level *3
Night quiet mode
Mass
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Specification
Drawing No.
Sound (Indoor)
Sound (Outdoor)

Notes:

W
m/min
l/s
cfm
dB(A)
kg
mm
mm
mm

mm

kW
W
m/min
dB(A)
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FHQ100DAVMA
RZQ100HAY4A
3 phase, 415V, 50Hz
Outdoor unit side
10.0 (5.0-11.2)
34,100 (17,100-38,200)
8,600 (4,300-9,600)
11.2 (5.1-12.8)
38,200 (17,400-43,700)
9,600 (4,400-11,000)
FHQ100DAVMA
Light ivory
2351,590690
Cross fin coil
Sirocco fan
150
28/24/20
467/400/333
988/847/706
42/38/34
Resin net (with mould resistance)
38
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQ100HAY4A
Ivory white
1,345900320
Cross fin coil
Hermetically sealed scroll type
2.3
Propeller fan
70+70
100
49
51
45
108
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
75 (Equivalent length 90m)
30
R410A
4.3 (Charged for 30m)
Refer to the nameplate of compressor.
1.2
C: 3D096435
C: 4D069652D
C: 4D061464A, C: 4D061483A

FHQ125DAVMA
RZQ125HAY4A
3 phase, 415V, 50Hz
Outdoor unit side
12.5 (5.7-14.0)
42,700 (19,500-47,800)
10,800 (4,900-12,000)
14.0 (6.0-16.2)
47,800 (20,500-55,300)
12,000 (5,200-13,900)
FHQ125DAVMA
Light ivory
2351,590690
Cross fin coil
Sirocco fan
150
31/27/23
517/450/383
1,094/953/812
44/41/37
Resin net (with mould resistance)
38
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQ125HAY4A
Ivory white
1,345900320
Cross fin coil
Hermetically sealed scroll type
2.7
Propeller fan
70+70
100
50
52
45
108
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
75 (Equivalent length 90m)
30
R410A
4.3 (Charged for 30m)
Refer to the nameplate of compressor.
1.2
C: 3D096435
C: 4D069650E
C: 4D061473A, C: 4D061484A

*1. The above data are based on the following conditions:


Cooling
Indoor: 27CDB, 19CWB
Outdoor: 35CDB, 24CWB

Heating
Indoor: 20CDB, 15CWB
Outdoor: 7CDB, 6CWB

Conversion formulae
Piping length
7.5m
(Horizontal)

kcal/h=kW860
Btu/h=kW3412
l/s=m/min1000/60
cfm=m/min35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation
condition, it is normally over the set value due to the environmental noise and sound reflection.

SkyAir FHQ-DA + RZQS, RZQ series

15

Specifications

EDMT281536

FHQ-DA (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

FHQ140DAVMA
RZQ140HAY4A
3 phase, 415V, 50Hz
Outdoor unit side
13.2 (6.2-15.5)
45,000 (21,200-52,900)
11,400 (5,300-13,300)
16.0 (6.2-18.0)
54,600 (21,200-61,400)
13,800 (5,300-15,500)
FHQ140DAVMA
Light ivory
2351,590690
Cross fin coil
Sirocco fan
150
34/29/24
567/483/400
1,200/1,024/847
46/42/38
Resin net (with mould resistance)
38
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20O.D.26)
BRC1E62 / BRC1C61 / BRC1D61
BRC7GA53
RZQ140HAY4A
Ivory white
1,345900320
Cross fin coil
Hermetically sealed scroll type
2.9
Propeller fan
70+70
100
50
52
46
108
9.5 (Flare)
15.9 (Flare)
26 (Hole)
High pressure switch, Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
75 (Equivalent length 90m)
30
R410A
4.3 (Charged for 30m)
Refer to the nameplate of compressor.
1.2
C: 3D096435
C: 4D069651E
C: 4D061482B, C: 4D061485B

Power supply
Power supply intake
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h

Cooling capacity *1 *2

Heating capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

HWD
Type
Type
Motor output

mm

Fan
Airflow rate (H/M/L)
Sound pressure level (H/M/L) *3
Air filter
Mass
Liquid
Piping
Gas
connections
Drain
Wired
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimensions
HWD
Coil
Type
Type
Comp.
Motor output
Type
Motor output
Fan
Airflow rate
Cooling
Sound pressure
Heating
level *3
Night quiet mode
Mass
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Specification
Drawing No.
Sound (Indoor)
Sound (Outdoor)

Notes:

W
m/min
l/s
cfm
dB(A)
kg
mm
mm
mm

mm

kW
W
m/min
dB(A)
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

*1. The above data are based on the following conditions:


Cooling
Indoor: 27CDB, 19CWB
Outdoor: 35CDB, 24CWB

Heating
Indoor: 20CDB, 15CWB
Outdoor: 7CDB, 6CWB

Conversion formulae
Piping length

kcal/h=kW860
Btu/h=kW3412
l/s=m/min1000/60
cfm=m/min35.3

7.5m
(Horizontal)

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. The operation sound is measured in anechoic chamber. If it is measured under the actual installation
condition, it is normally over the set value due to the environmental noise and sound reflection.

16

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

5. Dimensions and service space


5.1

Indoor unit

5.1.1

FHQ-DA

SkyAir FHQ-DA + RZQS, RZQ series

3D096238A

Unit (mm)

FHQ50DAVMA / FHQ60DAVMA

17

Dimensions and service space

EDMT281536

18

3D096239A

Unit (mm)

FHQ71DAVMA

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

SkyAir FHQ-DA + RZQS, RZQ series

3D096240A

Unit (mm)

FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA

19

Dimensions and service space

5.2

EDMT281536

Wired remote controller

BRC1E62
Unit (mm)

3D081567

BRC1C61
Unit (mm)

3D028952A

20

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

BRC1D61
Unit (mm)

3D048117

SkyAir FHQ-DA + RZQS, RZQ series

21

Dimensions and service space

5.3

EDMT281536

Wireless remote controller

BRC7GA53

Unit (mm)

3D079916

22

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

5.4

Dimensions and service space

Outdoor unit

SkyAir FHQ-DA + RZQS, RZQ series

3D064945G

Unit (mm)

RZQS50AV1 / RZQS60AV1 / RZQ71LV1

23

Dimensions and service space

EDMT281536

24

3D089674B

Unit (mm)

RZQ100LV1

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

SkyAir FHQ-DA + RZQS, RZQ series

3D058488F

Unit (mm)

RZQ125LV1

25

Dimensions and service space

EDMT281536

26

3D077411C

Unit (mm)

RZQ140LV1

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

SkyAir FHQ-DA + RZQS, RZQ series

3D060941B

Unit (mm)

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

27

Dimensions and service space

5.5

EDMT281536

Installation Service Space

RZQS50AV1 / RZQS60AV1 / RZQ71LV1

C: 3D073764B

28

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

C: 3D073764B

SkyAir FHQ-DA + RZQS, RZQ series

29

Dimensions and service space

EDMT281536

RZQ100LV1

C: 3D089675A

30

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

C: 3D089675A

SkyAir FHQ-DA + RZQS, RZQ series

31

Dimensions and service space

EDMT281536

RZQ125LV1 / RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

C: 3D073763B

32

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

C: 3D073763B

SkyAir FHQ-DA + RZQS, RZQ series

33

Dimensions and service space

EDMT281536

RZQ140LV1

C: 3D077417B

34

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Dimensions and service space

C: 3D077417B

SkyAir FHQ-DA + RZQS, RZQ series

35

Piping diagrams

EDMT281536

6. Piping diagrams
6.1

Indoor unit + outdoor unit

3D089740

FHQ50DAVMA + RZQS50AV1
FHQ60DAVMA + RZQS60AV1

36

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Piping diagrams

1
3D064949F

FHQ71DAVMA + RZQ71LV1

SkyAir FHQ-DA + RZQS, RZQ series

37

Piping diagrams

EDMT281536

3D089678

FHQ100DAVMA + RZQ100LV1

38

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Piping diagrams

1
3D058486H

FHQ125DAVMA + RZQ125LV1
FHQ140DAVMA + RZQ140LV1

SkyAir FHQ-DA + RZQS, RZQ series

39

Piping diagrams

EDMT281536

3D060712B

FHQ100DAVMA + RZQ100HAY4A
FHQ125DAVMA + RZQ125HAY4A
FHQ140DAVMA + RZQ140HAY4A

40

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Wiring diagrams

7. Wiring diagrams
7.1

Indoor unit

3D096206

FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA / FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA

SkyAir FHQ-DA + RZQS, RZQ series

41

Wiring diagrams

7.2

EDMT281536

Outdoor unit

3D089620

RZQS50AV1 / RZQS60AV1

42

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Wiring diagrams

1
3D064851L

RZQ71LV1

SkyAir FHQ-DA + RZQS, RZQ series

43

Wiring diagrams

EDMT281536

3D089520

RZQ100LV1

44

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Wiring diagrams

1
3D056474K

RZQ125LV1

SkyAir FHQ-DA + RZQS, RZQ series

45

Wiring diagrams

EDMT281536

3D077448D

RZQ140LV1

46

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Wiring diagrams

1
C: 3D047451H

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

SkyAir FHQ-DA + RZQS, RZQ series

47

Field wiring

EDMT281536

8. Field wiring
FHQ50DAVMA + RZQS50AV1
FHQ60DAVMA + RZQS60AV1
FHQ71DAVMA + RZQ71LV1
FHQ100DAVMA + RZQ100LV1 / RZQ100HAY4A
FHQ125DAVMA + RZQ125LV1 / RZQ125HAY4A
FHQ140DAVMA + RZQ140LV1 / RZQ140HAY4A

4D044483M

48

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Electric characteristics

9. Electric characteristics
9.1

FHQ-DA + RZQS

FHQ50DAVMA + RZQS50AV1
FHQ60DAVMA + RZQS60AV1

4D096569A

SkyAir FHQ-DA + RZQS, RZQ series

49

Electric characteristics

9.2

EDMT281536

FHQ-DA + RZQ-LV1

FHQ71DAVMA + RZQ71LV1
FHQ100DAVMA + RZQ100LV1
FHQ125DAVMA + RZQ125LV1
FHQ140DAVMA + RZQ140LV1

4D096559A

50

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

9.3

Electric characteristics

FHQ-DA + RZQ-HAY4A

FHQ100DAVMA + RZQ100HAY4A
FHQ125DAVMA + RZQ125HAY4A
FHQ140DAVMA + RZQ140HAY4A

4D096646

SkyAir FHQ-DA + RZQS, RZQ series

51

Capacity tables

EDMT281536

10. Capacity tables


10.1

RZQS

3D089737D

FHQ50DAVMA + RZQS50AV1

52

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Capacity tables

1
3D089738C

FHQ60DAVMA + RZQS60AV1

SkyAir FHQ-DA + RZQS, RZQ series

53

Capacity tables

10.2

EDMT281536

RZQ-LV1

3D089698C

FHQ71DAVMA + RZQ71LV1

54

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Capacity tables

1
3D089699E

FHQ100DAVMA + RZQ100LV1

SkyAir FHQ-DA + RZQS, RZQ series

55

Capacity tables

EDMT281536

3D089701A

FHQ125DAVMA + RZQ125LV1

56

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Capacity tables

1
3D096968

FHQ140DAVMA + RZQ140LV1

SkyAir FHQ-DA + RZQS, RZQ series

57

Capacity tables

10.3

EDMT281536

RZQ-HAY4A

3D093044A

FHQ100DAVMA + RZQ100HAY4A

58

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Capacity tables

1
3D093045A

FHQ125DAVMA + RZQ125HAY4A

SkyAir FHQ-DA + RZQS, RZQ series

59

Capacity tables

EDMT281536

3D073995C

FHQ140DAVMA + RZQ140HAY4A

60

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

10.4

Capacity tables

Capacity correction factor by the length of refrigerant piping

RZQS50AV1 / RZQS60AV1
RZQ71LV1 / RZQ100LV1 / RZQ125LV1 / RZQ140LV1

3D089679

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A


The capacity of the unit has to be corrected in accordance with the length of refrigerant piping.
(The distance between the indoor unit and the outdoor unit)
RZQ50/60: Heating (98.8%)

Capacity correction factor

(%)
100
95

RZQ71: Heating (97.9%)


RZQ100-140: Heating (96.7%)
RZQ71: Cooling (95%)

90
85

RZQ100: Cooling (84.2%)

80
RZQ125: Cooling (75.2%)

75
70

RZQ140: Cooling (70.0%)

05

Notes:

RZQ50/60: Cooling (97.2%)


7.5

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 (m)
Length of refrigerant piping (Total length)

1. line: Correction factor for Cooling Capacity,


line: Correction factor for Heating Capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below
the indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table.

SkyAir FHQ-DA + RZQS, RZQ series

61

Operation limits

EDMT281536

11. Operation limits


RZQS50AV1 / RZQS60AV1
RZQ71LV1 / RZQ100LV1 / RZQ125LV1 / RZQ140LV1
RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

3D046720M

62

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Sound level

12. Sound level


12.1

Indoor unit

12.1.1 FHQ-DA

4D079992A

FHQ50DAVMA / FHQ60DAVMA

4D069649C

FHQ71DAVMA

SkyAir FHQ-DA + RZQS, RZQ series

63

Sound level

EDMT281536

4D069652D

FHQ100DAVMA

4D069650E

FHQ125DAVMA

64

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Sound level

1
4D069651E

FHQ140DAVMA

SkyAir FHQ-DA + RZQS, RZQ series

65

Sound level

12.2

EDMT281536

Outdoor unit

12.2.1 RZQS

4D090424

RZQS50AV1 / RZQS60AV1 (Cooling)

4D090423

RZQS50AV1 / RZQS60AV1 (Heating)

66

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Sound level

12.2.2 RZQ-L

1
4D075745A

RZQ71LV1 (Cooling)

4D075748A

RZQ71LV1 (Heating)

SkyAir FHQ-DA + RZQS, RZQ series

67

Sound level

EDMT281536

4D089676

RZQ100LV1 (Cooling)

4D089677A

RZQ100LV1 (Heating)

68

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Sound level

1
4D075741A

RZQ125LV1 (Cooling)

4D075747A

RZQ125LV1 (Heating)

SkyAir FHQ-DA + RZQS, RZQ series

69

Sound level

EDMT281536

4D089680A

RZQ140LV1 (Cooling)

4D089681A

RZQ140LV1 (Heating)

70

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Sound level

12.2.3 RZQ-HA

1
4D061464A

RZQ100HAY4A (Cooling)

4D061483A

RZQ100HAY4A (Heating)

SkyAir FHQ-DA + RZQS, RZQ series

71

Sound level

EDMT281536

4D061473A

RZQ125HAY4A (Cooling)

4D061484A

RZQ125HAY4A (Heating)

72

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Sound level

1
4D061482B

RZQ140HAY4A (Cooling)

4D061485B

RZQ140HAY4A (Heating)

SkyAir FHQ-DA + RZQS, RZQ series

73

Accessories

EDMT281536

13. Accessories
13.1

Indoor unit

13.1.1 FHQ-DA
Optional
accessories

Model
Item

FHQ50DAVMA
FHQ60DAVMA

Replacement long-life filter

KAFP501A56

FHQ71DAVMA

FHQ100DAVMA
FHQ125DAVMA
FHQ140DAVMA

KAFP501A80

KAFP501A160

Fresh air intake kit

KDDQ50A140

Drain pump kit

KDU50P140VE

L-type piping kit (for upward direction)

KHFP5N160

Wired type (Note 1)


Remote controller

Wireless
type

BRC1E62 / BRC1C61 / BRC1D61

Heat
Pump

BRC7GA53

Simplified remote controller


(With operation mode selection button)

Simplified remote controller


(Without operation mode selection button)

Central remote controller

DCS302CA61

Unified ON/OFF controller

DCS301BA61

Schedule timer

DST301BA61

intelligent Touch Controller (Note 2)

DCS601C51

Wiring adaptor for electrical appendices

KRP1BA54

Wiring adaptor for electrical appendices (Note 3)

KRP4AA52

Wiring adaptor for electrical appendices (Note 3)

External adaptor for outdoor unit


(installation on indoor unit)

Installation box for adaptor printed circuit board


Adaptor box mounting plate
Remote sensor
Remote ON/OFF (Connector for forced on, forced off)
Noise filter (for electromagnetic use only)

KRP1D93A
KKSAP50A56

KRCS01-4B

Electrical box with earth terminal (3 blocks)

KJB311AA

Electrical box with earth terminal (2 blocks)

KJB212AA

Digital input adaptor (Note 3)

C: 3D096220D

Notes:

74

1. Wiring for wired remote controller to be procured locally.


2. The interface adaptor for SkyAir series is not necessary because it is equipped to this indoor unit as standard.
3. Installation box for adaptor PCB (KRP1D93A) is necessary.

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

13.2

Accessories

Outdoor unit

13.2.1 RZQS
Kit name
Name of option

RZQS50AV1
RZQS60AV1

Central drain plug

KKPJ5F180

Wire fixture for preventing


overturning

K-KYZP15C

Fixture for preventing


overturning

KPT-60B160

Demand adaptor

KRP58M51
C: 4D046721M

13.2.2 RZQ-L / HA
Optional
accessories

Kit name
Name of option
Central drain plug

RZQ71LV1
RZQ125LV1

RZQ100LV1
RZQ140LV1

RZQ100HAY4A
RZQ125HAY4A
RZQ140HAY4A

KKPJ5F180

KKPJ5G280

KKPJ5F180

Wire fixture for preventing overturning


Fixture for preventing overturning
Demand adaptor

K-KYZP15C
KPT-60B160

KKTP5B112

KPT-60B160

KRP58M51
C: 4D046721M
C: 4D077521E

SkyAir FHQ-DA + RZQS, RZQ series

75

Accessories

76

EDMT281536

SkyAir FHQ-DA + RZQS, RZQ series

EDMT281536

Part 2
Installation of
indoor / outdoor unit
1. Centre of gravity....................................................................................78
2. Installation of indoor unit .......................................................................81
2.1 FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA /
FHQ100DAVMA / FHQ125DAVMA / FHQ140DAVMA ..........................81

3. Installation of outdoor unit ...................................................................101


3.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 /
RZQ125LV1 .........................................................................................101
3.2 RZQ140LV1 .........................................................................................117
3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A ...........................133
3.4 Equivalent piping length of joints (reference) .......................................149

Installation of indoor / outdoor unit

77

Centre of gravity

EDMT281536

1. Centre of gravity
RZQS50AV1 / RZQS60AV1 / RZQ71LV1

Unit (mm)

4D064948F

RZQ100LV1

Unit (mm)

4D089656B

78

Installation of indoor / outdoor unit

EDMT281536

Centre of gravity

RZQ125LV1

Unit (mm)

4D058487H

RZQ140LV1

Unit (mm)

4D077529C

Installation of indoor / outdoor unit

79

Centre of gravity

EDMT281536

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

Unit (mm)

4D061670B

80

Installation of indoor / outdoor unit

EDMT281536

Installation of indoor unit

2. Installation of indoor unit


2.1

FHQ50DAVMA / FHQ60DAVMA / FHQ71DAVMA / FHQ100DAVMA /


FHQ125DAVMA / FHQ140DAVMA

2.1.1

Names and Functions of Parts

C: 3P400449-1E

Installation of indoor / outdoor unit

81

Installation of indoor unit

2.1.2

EDMT281536

Installation

FHQ50DAVMA
FHQ60DAVMA
FHQ71DAVMA

FHQ100DAVMA
FHQ125DAVMA
FHQ140DAVMA

CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.

SAFETY PRECAUTIONS ................................................1


BEFORE INSTALLATION.................................................2
SELECTION OF INSTALLATION LOCATION ..................4
PREPARATION BEFORE INSTALLATION.......................4
INSTALLATION OF THE INDOOR UNIT .........................6
REFRIGERANT PIPING WORK ......................................6
DRAIN PIPING WORK.....................................................9
ELECTRIC WIRING WORK...........................................11
HOW TO CONNECT WIRINGS AND
WIRING EXAMPLE........................................................11
10. MOUNTING SUCTION GRILLE
DECORATION SIDE PANEL..........................................15
11. FIELD SETTING ............................................................15
12. TEST OPERATION ........................................................16

1.

SAFETY PRECAUTIONS

Please read the these "SAFETY CONSIDERATIONS"


carefully before installing air conditioning unit and be sure to
install it correctly. After completing the installation, make sure
that the unit operates properly during the start-up operation.
Please instruct the customer on how to operate the unit and
keep it maintained.
Also, inform customers that they should store this installation
manual along with the operation manual for future reference.
This air conditioner comes under the term "appliances not
accessible to the general public".
In a domestic environment this product may cause radio
interference in which case the user may be required to
take adequate measures.
r This manual classies the precautions into WARNINGS and
CAUTIONS.
Be sure to follow all the precautions below: They are all
important for ensuring safety.
WARNING ............... Indicates a potentially hazardous
situation which, if not avoided,
could result in death or serious
injury.
CAUTION .................Indicates a potentially hazardous
situation which, if not avoided,
may result in minor or moderate
injury.
It may also be used to alert
against unsafe practices.

SPLIT SYSTEM Air Conditioners

Installation manual

r After the installation is completed, test the air conditioner and


check if the air conditioner operates properly. Give the user
adequate instructions concerning the use and cleaning of the
indoor unit according to the Operation Manual. Ask the user
to keep this manual and the Operation Manual together in a
handy place for future reference.
WARNING
r Ask your local dealer or qualied personnel to carry out
installation work.
Improper installation may result in water leakage, electric
shocks or a re.
r Perform installation work in accordance with this installation
manual.
Improper installation may result in water leakage, electric
shocks or a re.
r Consult your dealer regarding what to do in case of
refrigerant leakage.
When the air conditioner is installed in a small room, it is
necessary to take proper measures so that the amount of any
leaked refrigerant does not exceed the concentration limit in
the event of a leakage.
Otherwise, this may lead to an accident due to oxygen deciency.
r Be sure to use only the specied parts and accessories for
installation work.
Failure to use the specied parts may result in the air conditioner
falling down, water leakage, electric shocks, are, etc.
r Install the air conditioner on a foundation that can withstand
its mass.
Insufcient strength may result in the air conditioner falling
down and causing injury.
In addition, it may lead to vibration of indoor units and cause
unpleasant chattering noise.
r Carry out the specied installation work in consideration of
strong winds, typhoons, or earthquakes.
Improper installation may result in an accident such as air
conditioner falling.
r Make certain that all electrical work is carried out by qualied
personnel according to the applicable legislation (note 1) and
this installation manual, using a separate circuit.
In addition, even if the wiring is short, make sure to use a wiring
that has sufcient length and never connect additional
wiring to make the length sufcient.
Insufcient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or a re.
(note 1) applicable legislation means All international,
national and local directives, laws, regulations and/
or codes which are relevant and applicable for a
certain product or domain.
r Earth the air conditioner.
Do not connect the earth wiring to gas or water piping,
lightning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a re.
r Be sure to install an earth leakage breaker.
Failure to do so may cause electric shocks and a re.
r Disconnect the power supply before touching the electric
components.
If you touch the live part, you may get an electric shocks.

1
3P400451-1E

82

Installation of indoor / outdoor unit

EDMT281536

r Make sure that all wiring is secure, using the specied wirings
and ensuring that external forces do not act on the terminal
connections or wirings.
Incomplete connection or xing may cause an overheat or a re.
r

When wiring between the indoor and outdoor units, and wiring
the power supply, form the wirings orderly so that the control
box lid can be securely fastened.
If the control box lid is not in place, overheat of the terminals,
electric shocks or a re may be caused.

r If refrigerant gas leaks during installation work, ventilate the


area immediately.
Toxic gas may be produced if refrigerant gas comes into
contact with a re.
r

After completing the installation work, check to make sure


that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the
room and comes into contact with a source of a re, such as
a fan heater, stove or cooker.

Never directly touch any accidental leaking refrigerant. This


could result in severe wounds caused by frostbite.

Installation of indoor unit

3. Where there is machinery which emits electromagnetic


waves.
Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
4. Where ammable gases may leak, where carbon bre or
ignitable dust is suspended in the air or where volatile
ammables, such as thinner or gasoline, are handled.
If the gas should leak and remained around the air
conditioner, it may cause ignition.
r The air conditioner is not intended for use in a potentially
explosive atomosphere.

SPECIAL NOTICE PRODUCT


r The refrigerant R410A requires that strict precautions be
observed for keeping the system clean, dry and tightly sealed.
Clean and dry
Strict measures must be taken to keep impurities
(including SUNISO oil and other mineral oils as well as
moisture) out of the system.
Tightly sealed
R410A contains no chlorine, does not destroy the ozone
layer and so does not reduce the earth's protection against
harmful ultraviolet radiation. R410A will contribute only slightly
to the greenhouse effect if released into the atmosphere.

r Be sure to switch off the unit before touching any electrical parts.

CAUTION
r Do not allow children to climb on the outdoor unit and avoid
placing objects on the unit.
Injury may result if the unit becomes loose and falls.
r Make sure to provide for adequate measures in order to prevent
that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause
OCNHWPEVKQPUUOQMGQTTG2NGCUGKPUVTWEVVJGEWUVQOGTVQ
keep the area around the unit clean.
r Install in a machine room that is free of moisture. The unit is
designed for indoor use.
r Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of
other parts must be done in accordance with relevant local and
national legislation.
r Install drain piping according to this installation manual to
ensure good drainage, and insulate the piping to prevent
condensation.
Improper drain piping may cause water leakage, make the
furniture get wet.
r Install the air conditioner, power supply wiring, remote
controller wiring and transmission wiring at least 1 meter away
from televisions or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufcient to eliminate the noise.)
r Install the indoor unit as far as possible from Worescent
lamps.
If a wireless remote controller kit is installed, the transmission
distance may be shorter in a room where an electronic
lighting type (inverter or rapid start type) uorescent lamp is
installed.
r Do not install the air conditioner in places such as the
following:
1. Where there is mist of oil, oil spray or vapour for example
a kitchen.
Resin parts may deteriorate, and cause them to fall out or
water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is
produced.
Corrosion of copper pipings or brazed parts may cause
the refrigerant to leak.

r 5KPEGFGUKIPRTGUUWTGKU/2CQTDCT
HQT4%WPKVU
/2CQTDCT VJGVJKEMPGUUQHRKRGUOWUVDGITGCVGT
than previously. Since R410A is a mixed refrigerant, the
required additional refrigerant must be charged in its liquid state.
(If the system is charged with refrigerant in its gaseous state,
due to composition change, the system will not function
normally). The indoor unit is designed for R410A use.
See the catalogue for indoor unit models that can be
connected. (Normal operation is not possible when connecting
units that are originally designed for other refrigerants.)

2.

BEFORE INSTALLATION

When unpacking and moving the indoor unit after


unpacked, do not apply force to the piping (refrigerant and
drain) and resin parts.
r Make sure to check in advance that the refrigerant to be used
for installation work is R410A.
(The air conditioner will not properly operate if a wrong
refrigerant is used.)
r For installation of the outdoor unit, refer to the installation
manual attached to the outdoor unit.
r Do not throw away the accessories until the installation work
is completed.
r After the indoor unit is carried into the room, to avoid the
indoor unit from getting damaged, take measures to protect
the indoor unit with packing materials.
(1) Determine the route to carry the unit into the room.
(2) Do not unpack the unit until it is carried to the installation
location.
Where unpacking is unavoidable, use a sling of soft
material or protective plates together with a rope when
lifting, to avoid damage or scratches to the indoor units.
r Have the customer actually operate the air conditioner while
looking at the manual.
Instruct the customer how to operate the air conditioner
(particularly cleaning of the air lters, operation procedures,
and temperature adjustment).

2
3P400451-1E

Installation of indoor / outdoor unit

83

Installation of indoor unit

EDMT281536

r For selection of installation location, use the installation


pattern paper (used in common with the packing case.)
as reference.

CARRY OUT THE WORK GIVING CAUTION TO THE


FOLLOWING ITEMS AND AFTER THE WORK IS
COMPLETED CHECK THESE AGAIN.

r Do not use the air conditioner where in the salty atmosphere


such as coastal areas, vehicles, vessels or the voltage
WEtuation is frequent such as factories.

1. Items to be checked after the installation work is completed

r Take off static electricity from the body when carrying out
wiring and the control box lid is removed.
The electric parts may be damaged.

2-1

ACCESSORIES

Check if the following accessories are attached to the


indoor unit.
Name

(1) Drain
hose

(2) Metal
clamp

(3) Washer
for hanger

(4) Clamp

Quantity

1 pc.

1 pc.

8 pcs.

7 pcs.

Shape

Name
Quantity

(5) Installation Joint insulating


pattern paper
material
1 sheet

Shape

(10) Resin
bushing

1 each

1 each

1 pc.

(6) For gas


piping

(8) Large

(7) For liquid


piping

Name

(11) Wiring
xture

Quantity

2 pcs.

Shape

Sealing
material

(9) Small

(12) Screw
for wiring
xture
(Miscellaneous)
2 pcs.
r Operation manual
M4 12
r Installation manual
r Declaration of conformity

Items to be checked

In case of defective

Are the indoor and outdoor


units rigidly xed?

Drop vibration
noise

Are the installation work of the


outdoor and indoor units complete?

Does not operate


burnout

Have you carried out a leakage


test with the test pressure
specied in the outdoor unit
installation manual?

Does not cool /


Does not heat

Is the insulation of refrigerant


piping and drain piping
completely carried out?

Water leakage

Does the drCKPow out


smoothly?

Water leakage

Is the power supply voltage


identical to that stated in the
manufacturers label on the air
conditioner?

Does not operate


burnout

Are you sure that there is no


wrong wiring or piping or no
loose wiring?

Does not operate


burnout

Is earthing completed?

Danger in case of
leakage

Are the sizes of electric wiring


according to the specication?

Does not operate


burnout

Is any of air outlets or inlets of


the indoor and outdoor units
blocked with obstacles?
(It may lead to capacity drop
due to fan speed drop or
malfunction of equipment.)

Does not cool /


Does not heat

Have you recorded the


refrigerant piping length and the
refrigerant charge added?

Refrigerant charge
amount is not clear

Check
column

*Make sure to recheck the items of SAFETY PRECAUTIONS


2. Items to be checked at delivery
Check
column

Items to be checked
Have you carried out eld setting? (if necessary)

2-2

OPTIONAL ACCESSORIES

rFor this indoor unit, the remote controller is separately


required.
rThere are 2 kinds of remote controller; wired type and
wireless type.
Install the remote controller to the place where the customer
has given consent.
Refer to the catalog for the applicable model.
(Refer to the installation manual attached to the remote
controller for how to install.)

Are the control box lid, the air lter and the suction grille
attached?
Does the cool air discharge during the cooling operation and
the warm air discharge during heating operation?
Have you explained how to operate the air conditioner
showing the operation manual to the customer?
Have you explained the description of cooling, heating,
program dry and automatic (cooling/heating) given in
the operation manual to the customer?
If you set the fan speed at thermostat OFF, did you
explain the set fan speed to the customer?
Have you handed the operation manual and the
installation manual to the customer?

3
3P400451-1E

84

Installation of indoor / outdoor unit

EDMT281536

Installation of indoor unit

SELECTION OF INSTALLATION
LOCATION

When unpacking and moving the indoor unit after


unpacked, do not apply force to the piping (refrigerant and
drain) and resin parts.
(1) Select the installation location that meets the following
conditions and get approval of the customer.
r Where the cool and warm air spreads evenly in the room.
r Where there is no obstacles in the air passage.
r Where drainage can be ensured.
r Where the ceiling lower surface is not inclined.
r Where there is sufcient strength to withstand the mass
of the indoor unit (if the strength is insufcient, the indoor
unit may vibrate and get in contact with the ceiling and
generate unpleasant chattering noise).
r Where a space sufcient for installation and service can
be ensured. (Refer to Fig. 1 and Fig. 2)
r Where the piping length between the indoor and the
outdoor units is ensured within the allowable length. (Refer
to the installation manual attached to the outdoor unit.)
r Where there is no risk of ammable gas leak.

(2) Use hanging bolts for installation.


Investigate if the installation place can withstand the mass
of the indoor unit and, if necessary, hang the indoor unit
with bolts after it is reinforced by beams etc. (Refer to the
installation pattern paper (5) for the mounting pitch.).
(3) Ceiling height
This indoor unit can be installed up to 4.3m (for 50-71
model, 3.5m) of the ceiling.

4.

PREPARATION BEFORE INSTALLATION

(1) For the locations of indoor unit hanging bolts, piping


outlet holes, drain piping outlet hole, and electric
wiring inlet hole. (Refer to Fig. 3)
G

H
J

View from the front


Left back drain
piping outlet hole

[ Required installation space (mm) ]


*30 or more

175

3.

CAUTION
r Install the indoor and outdoor units, power supply wiring,
remote controller wiring and transmission wiring at least 1
meter away from televisions or radios to prevent image
interference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufcient to eliminate the noise.)
r Install the indoor unit as far as possible from Worescent
lamps.
If a wireless remote controller kit is installed, the transmission
distance may be shorter in a room where an electronic lighting
type (inverter or rapid start type) uorescent lamp is installed.

In addition to the general usage, since the items in the


operation manual with the
WARNING and
CAUTION
marks are likely to result in human bodily injuries and
property damages, it is necessary not only to explain
these items to the customer but also to have the
customer read them.
It is also necessary to explain the items of NOT
MALFUNCTION OF THE AIR CONDITIONER to the
customer and have the customer read them carefully.

200

Points of the operation explanation

Wall hole for back side


piping outlet
(I100 hole)

*30 or more

Back side wiring


outlet location

Top panel gas side


piping connection
position

Discharge
Fig. 3
Top panel wiring outlet position

Fig. 2
Unit : mm

Hanging bolt (4 pieces)


Top panel liquid side piping
connection positions

NOTE
r If there is extra space required for * part, servicing can be
conducted more easily if 200mm or more is secured.

189

210

For high
installation

Floor level

View from
the ceiling

260

Hanging bolt pitch

2500 or more
HTQOQQTNevel

690 Unit dimension

Discharge

Obstacles

30
87
163

300 or more

Fig. 1

Suction

Top panel drain piping


connection position

A Unit dimension
B Hanging bolt pitch
C
D

Model name (FHQ-)

Type 50 60

960 920 378 324 270 375 398 377 260

Type 71

1270 1230 533 479 425 530 553 532 415

Type 100 125 140 1590 1550 693 639 585 690 713 692 575

4
3P400451-1E

Installation of indoor / outdoor unit

85

Installation of indoor unit

EDMT281536

(2) Make holes for hanging bolts, piping outlet, drain


piping outlet, and electric wiring inlet.
r Use the installation pattern paper (5).
r Determine the locations of hanging bolts, piping outlet,
drain piping outlet and electric wiring inlet. And make the
hole.
(3) Remove the parts of the indoor unit.
1) Remove the suction grille.
r Slide the suction grille xing knobs (50, 60 type: 2
places for each, 71~140 type: 3 places for each) toward
backward direction (as shown by an arrow) to open the
suction grille widely. (Refer to Fig. 4)
r Keeping the suction grille opened, hold the knob at the
back of the suction grille and at the same time, pull the
suction grille forward to remove. (Refer to Fig. 5)

3) Remove the hanger.


r Loosen 2 bolts for installing the hanger at both sides
(M8) (4 places at left and right) within 10mm.
(Refer to Fig. 7 and Fig. 8)
r Remove the xture screw for hanger at the back side
(M5), pull the hanger backward (the arrow direction) to
remove. (Refer to Fig. 8)
Bolt (M8)
Indoor unit

Loosen within
10mm

Hanger
Fig. 7

Suction grille

Fixing knob

*CPIGTZKPI
screw (M5)

Hanger installing bolt (M8)

Fig. 4

Loosen

Hanger

Rear knob

Fig. 8

CAUTION
Do not remove the tape (milky white) applied to the outside
of the indoor unit. It may cause electric shocks or a re.
Fig. 5

2) Remove the decoration side panel (right, left).


r Remove the xture screw of the decoration side panel
(one for each), pull forward (arrow direction) to remove.
(Refer to Fig. 6)
r Take out accessories. (Refer to Fig. 6)
r Open the knock hole at the wiring inlet side at the rear
surface or top surface, and install the attached resin
bushing (10).

(4) Install the hanging bolts.


r Use M8 or M10 bolts for hanging the indoor unit.
r Adjust the length of the hanging bolt from the ceiling in
advance. (Refer to Fig. 9)
r Use hole-in-anchors for the existing bolts and embedded
inserts or foundation bolts for new bolts, and x the unit
rmly to the building so that it may withstand the mass of
the unit.
In addition, adjust the distance from the ceiling in
advance.
CAUTION
If the hanging bolt is too long, it may damage or break the
indoor unit or options.

Resin bushing (10)


(accessory)
Removable part
(for leading in from the upward-facing)

Ceiling slab

Resin bushing (10)


(accessory)

Foundation bolt

25 - 55 mm

Removable part
(for leading in from the rear-facing)

Hanging bolt
Fig. 9

Accessories

Ceiling surface

NOTE
r Parts shown Fig. 9 will be all eld supply.

Fixing screw for decoration side Panel


(M4)

Decoration side panel

Fig. 6

5
3P400451-1E

86

Installation of indoor / outdoor unit

EDMT281536

5.

Installation of indoor unit

INSTALLATION OF THE INDOOR UNIT

It is easy to attach the optional parts before installing the


indoor unit. Refer to also the installation manual attached
to the optional parts.
For installation, use the attached installation parts and
URGEKGF parts.
(1) Fix the hanger to the hanging bolt. (Refer to Fig. 10)



2
B


CAUTION
For safety, make sure to use a washer for hanger (3)
(accessory) and x by double nuts rmly.
Hanging bolt

0WV
GNFUWRRN[

A.B


Washer for hanger (3) (accessory)

Fig. 12
Double nuts

A. When the drain piping is tilted to the right, or to the right


and back.
Place it level, or tilt it slightly to the right or the back.
(Within 1)

Fig. 10

Hanger

(2) Lift up the indoor unit, slide from the front and put the
hanger installing bolt (M8) into the securely for temporary
hanging. (Refer to Fig. 11)
(3) Tighten the hanger xing screws (M5) at 2 places, which
were removed, as they were before.
(Refer to Fig. 11)
It is necessary to prevent misalignment of the indoor unit.
(4) Tighten the hanger installing bolts (M8) at 4 places
securely. (Refer to Fig. 11)
Attachment part

B. When the drain piping is tilted to the left, or to the left


and back.
Place it level, or tilt it slightly to the left or the back.
(Within 1)
WARNING
The indoor unit must be securely installed on a place
that can withstand the mass.
If the strength is insufcient, the indoor unit may fall down
and cause injuries.

Hanger

6.
Hanger installing
bolt (M8)
Hanger
ZKPIUETew
(M5)
Reinforcing plate (left/right)
When carrying the indoor unit,
do not hold the reinforcing plates.

Fig. 11

(5) When hanging the indoor unit, make sure to use the level to
have better drainage and install it horizontally. Also, if it is
possible at the installation site, install so that the drain
piping side is slightly lower.
(Refer to Fig. 12)
CAUTION
r Setting the indoor unit at an angle opposite to the drain
piping might cause a water leakage.
r Do not insert materials other than that URGEKGF into
the clearance between the hanger and the washer for
hanger (3).
Unless the washers are properly attached, the hanging
bolts may come off from the hanger.

REFRIGERANT PIPING WORK

r For the outdoor unit refrigerant piping, refer to the installation


manual attached to the outdoor unit.
r Carry out insulation of both gas and liquid refrigerant piping
securely. If not insulated, it may cause water leakage. For
gas piping, use insulation material of which heat resistant
temperature is not less than 120C. For use under high
humidity, strengthen the insulation material for refrigerant
piping. If not strengthened, the surface of insulation material
may sweat.
r Before installation work, make sure that the refrigerant is
R410A. (Unless the refrigerant is R410A, the normal
operation cannot be expected.)
CAUTION
This air conditioner is a dedicated model for new refrigerant
R410A. Make sure to meet the requirements shown right
and carry out installation work.
r Use dedicated piping cutters and aring tools for R410A.
r When making a are connection, coat the CTGd inner
surface only with ether oil or ester oil.
r Use only the are nuts attached to the air conditioner. If
other CTG nuts are used, it may cause refrigerant leakage.
r To prevent contamination or moisture from getting into the
piping, take measures such as pinching or taping the
pipings.
Do not mix substance other than the specied refrigerant
such as air into the refrigeration circuit.
If the refrigerant leaks during the work, ventilate the room.

6
3P400451-1E

Installation of indoor / outdoor unit

87

Installation of indoor unit

EDMT281536

r Remove the stay for packing and delivering (reinforcing


plate) before refrigerant piping work.
(Refer to Fig. 18)
r The refrigerant is pre-charged in the outdoor unit.
r When connecting the pipings to the air conditioner, make sure
to use a spanner and a torque wrench as shown in Fig.13.
For the dimension of ared part, refer to the Table 1.
Torque wrench

r After leak test, referring to Fig. 15, insulate both the gas and
liquid piping connection with the attached joint insulating
material (6) and (7) to prevent the piping from getting
exposed. Then, tighten the both ends of insulating material
with the clamp (4).
r Wrap the sealing material (Small) (9) around the joint insulating
material (6)
CTG nut section), only the gas piping side.
r Make sure to bring the seam of joint insulating material (6)
and (7) to the top.

Spanner

Flare nut

Union joint

CAUTION
Insulation of eld piping must be carried out up to the
connection inside the casing. If the piping is exposed to the
atmosphere, it may cause sweating or burn due to touching
the piping, electric shocks or a re due to the wiring touching
the piping.

Fig. 13

r When making a are connection, coat the ared inner surface


only with ether oil or ester oil. (Refer to Fig. 14) Then, turn the
are nut 3 to 4 times with your hand and screw in the nut.
%QCVVJGCTGFKPPGTUWTface
only with ether oil or ester oil.

Fig. 14

r For the tightening torque, refer to the Table 1.


Table 1
Tightening
torque (Nm)

Dimension
for processing
CTe A (mm)

I 6.4

15.7 1.5

8.9 0.2

I 9.5

36.3 3.6

13.0 0.2

I 12.7

54.9 5.4

16.4 0.2

I 15.9

68.6 6.8

19.5 0.2

Flare shape

R0.4-0.8

902

452

Piping size
(mm)

CAUTION
r Do not have oil adhere to the screw ZKng part of resin
parts.
If oil adheres, it may weaken the strength of screwed part.
r Do not tighten CTe nuts too tight.
If a CTG nut cracks, the refrigerant may leak.
r If there is no torque wrench, use Table 2 as a rule of thumb.
When tightening a CTG nut with a spanner harder and
harder, there is a point where the tightening torque suddenly
increases. From that position, tighten the nut additionally the
angle shown in Table 2. After the work is nished, check
securely that there is no gas leak. If the nut is not tightened
as instructed, it may cause slow refrigerant leak and result in
malfunction (such as does not cool or heat).
Table 2
Piping size
(mm)

Tightening angle

Recommended arm length


of tool used

I 6.4

60 90

Approximately 150mm

I 9.5

60 90

Approximately 200mm

I 12.7

30 60

Approximately 250mm

I 15.9

30 60

Approximately 300mm

7
3P400451-1E

88

Installation of indoor / outdoor unit

EDMT281536

Installation of indoor unit

(1) For rear side piping


r Remove the rear piping penetration cover, and connect
the piping. (Refer to Fig. 16 and Fig. 18)

Gas side piping insulating method

Piping insulating material (unit side)

Do not leave
clearance

Joint insulating material (6) (accessory)


Bring the seam
to the top

Flare nut
connection

(2) For upward piping


r For upward piping, L-shaped connection piping kit
(optional accessory) will be required.
r Remove the top panel penetration cover, and use the Lshaped connection piping kit (optional accessory) to conduct piping. (Refer to Fig. 16 and Fig. 17)

(3) For right side piping


r Remove the stay for packing and delivering (reinforcing
plate) at the right side, and put back the screw to the original position of the indoor unit. (Refer to Fig. 18)
r Open the knockout hole at the decoration side panel
(right), and connect piping. (Refer to Fig. 18)

Piping insulating material

GNFUWRRN[
For prevention of sweating,
do not expose the piping
Clamp (4) (accessory)

Tighten the piping


insulating material

Rear piping penetration cover


Cutoff

Top panel

View from
air inlet side

Wrap from the


root of the unit
Sealing material (Small) (9)
(accessory)

Cut at the position avoiding


the knob part of the
penetration cover
Cutoff

Top panel penetration cover

Fig. 16

Gas piping

Upward refrigerant piping


L-shaped branch piping kit
(Optional accessory)

Liquid piping
Indoor unit

Fig. 17

Liquid side piping insulating method


Joint insulating material (7)
(accessory)
Bring the seam
to the top

Piping insulating material


(unit side)

Screw
(put back to the indoor unit)

Do not leave clearance


Flare nut
connection

Rear side refrigerant piping


Rear side drain piping
Clamp (4)
(accessory)
Piping insulating
materKCN
GNFUWRRN[
Tighten the piping
insulating material

For prevention of sweating,


do not expose the piping
Fig. 15

Right side refrigerant piping


Right side drain piping
Stay for packing and delivering
(reinforcing plate)
Decoration side panel (right)
Separating parts

Fig. 18

Cut only this part when laying only


the drain piping on the right side.

8
3P400451-1E

Installation of indoor / outdoor unit

89

Installation of indoor unit

EDMT281536

r After piping is nished, cut the removed penetration cover


along the shape of piping, and install.
Also, for top panel penetration cover, as it was before
removed, put the horizontal blade motor and thermistor
lead through the clamp of the top panel penetration cover
and x. (Refer to Fig. 16 and Fig. 19)
When doing this, block any gaps between the piping
penetration cover and the piping using putty to prevent
dust from entering the indoor unit.
Horizontal blade motor lead
Top panel penetration
cover clamp part

Thermistor lead

View from air inlet side

Fig. 19

* Before brazing refrigerant piping, have nitrogen ow through


the refrigerant piping and substitute air with nitrogen. Then,
carry out brazing (NOTE 2). (Refer to Fig. 20) After all the
brazing works are nished, carry out CTG connection with the
indoor unit.

7.

DRAIN PIPING WORK

(1) Carry out drain piping.


r Carry out drain piping so that drainage can ensured.
r Drain piping can be connected from the following
directions: For right rear/right side, refer to Fig. 18 of
6. REFRIGERANT PIPING WORK, and for left rear/
left side, refer to Fig. 21.
r When conducting left rear/left side drain piping, remove
the protection net. Then, remove the drain socket cap and
insulation material applied to left side drain socket and
apply them to the right side drain socket. When doing
this, insert the drain socket cap all the way in to prevent a
water leakage.
After the drain hose (1) (accessory) installing, attach the
protection net by reversing the steps taken to remove it.
(Refer to Fig. 22)
r Select the piping diameter equal to or larger than that of
the drain hose (1) (accessory) (polyvinyl chloride piping,
nominal diameter 20mm, outside diameter 26mm).
r Install the drain piping as short as possible with
downward inclination of 1/100 or more by avoiding air
stagnation. (Refer to Fig. 23 and Fig. 24)
(It may cause abnormal sound such as bubbling noise.)

Putty or insulation

GNFUWRRN[

Pressure reducing valve


Brazing place

Taping

Left side
Drain piping

Nitrogen

Refrigerant piping

Stop valve Nitrogen


Fig. 20

Left rear side


Drain piping

NOTE
1. The proper pressure for having nitrogen ow through the

piping is approximately 0.02MPa, a pressure that makes


one feel like breeze and can be obtained through a
pressure reducing valve.
2. Do not use ux when brazing refrigerant piping. Use
phosphor copper brazing ller metal (BCuP-2: JIS Z 3264/
BCu93P-710/795: ISO 3677) that does not require WZ (If
chlorinated ux is used, the piping will be corroded and, in
addition if Worine is contained, the refrigerant oil will be
deteriorated and the refrigerant circuit will be affected
badly.)
3. When carrying out leakage test of refrigerant piping and the
indoor unit after the installation of indoor unit is nished,
conrm the connecting outdoor unit installation manual for
test pressure. Refer to also the outdoor unit installation
manual or technical document for refrigerant piping.
4. In case of refrigerant shortage due to forgetting additional
refrigerant charge etc., it will result in malfunction such as
does not cool or does not heat. Refer to the outdoor unit
installation manual or technical document for refrigerant
piping.

Left side
Detach parts

Back side (sheet metal)


Detach parts

Fig. 21

Fixing
screw for
protection net

Protection net
Fig. 22

CAUTION
Do not use antioxidant when brazing piping.
It may result in malfunction of components and clogging of
piping due to residue.

9
3P400451-1E

90

Installation of indoor / outdoor unit

EDMT281536

Installation of indoor unit

3P400451-1E

Installation of indoor / outdoor unit

91

EDMT281536

100mm
or more

Installation of indoor unit

Centralized drain piping


If water stagnates in the
drain piping, the piping
may be clogged.

Install with downward inclination


of 1/100 or more so that no air
will be stagnated.

Fig. 28

r Connecting drain piping.


Do not connect the drain piping directly to the sewage
that gives off ammonia odor. The ammonia in the sewage
may go through the drain piping and corrode the heat
exchanger of the indoor unit.
r When installing the drain pump kit (optional accessory),
also refer to the installation manual included to the drain
pump kit.
(2) After piping is PKUJGF, check if the drain ows
smoothly.
r Gradually put about 0.6 liter of water for drain conrmation
into the drain pan from the air outlet.
(Refer to Fig. 29)
Air outlet

r Make sure to earth the air conditioner.


Earthing resistance should be according to applicable legislation.
r Do not connect the earth wiring to gas or water piping,
lightning conductor or telephone earth wiring.
r Gas piping ............Ignition or explosion may occur if the
gas leaks.
r Water piping .........Hard vinyl tubes are not effective
earths.
r Lightning conductor or telephone earth wiring..................
Electric potential may rise abnormally if struck by a
lightning bolt.
r For electric wiring work, refer to also the WIRING DIAGRAM
attached to the control box lid.
r Never connect the power supply wiring to the terminal block
for remote controller wiring, or otherwise the entire system
may be damaged.
r Carry out installation and wiring of the remote controller
according to the installation manual attached to the remote
controller.
r Do not touch the Printed Circuit Board assy during the wiring
work. Otherwise, it may cause damage.

8-2

SPECIFICATIONS FOR FIELD WIRING

For the wiring of outdoor units, refer to the installation manual


attached to the outdoor units.
r Remote controller and transmission wiring are eld supply.
(Refer to Table 3)

100mm
or more

Table 3
Plastic container for pouring water
(Tube length of 100mm is necessary)

Fig. 29

r After the drain piping work, install the stay for packing and
delivering (reinforcing plate), which was removed in the
section of 6. REFRIGERANT PIPING WORK.
However, it is not necessary to install the stay for packing
and delivering at the right side (reinforcing plate).
(Refer to Fig. 30)

Wire

Size (mm )

Length

Transmission wiring

H05VV-U4G
(NOTE 1)

2.5

Remote controller
wiring

Vinyl cord with


sheath or cable
(2 wire) (NOTE 2)

0.75 - 1.25

Max.
500m*

* This will be the total extended length in the system when


doing group control.
Wiring specications are shown on the condition that the wiring
has a voltage drop of 2%.
1.It shows the case when conduit piping are used. When the
conduit piping are not used, use H07RN-F.
2.Sheathed vinyl cord or cable (insulation thickness: 1mm or
more)

Stay for packing and delivering


(reinforcing plate)

Screw
Fig. 30

8.
8-1

ELECTRIC WIRING WORK


GENERAL INSTRUCTIONS

r Make certain that all electric wiring work is carried out by


qualied personnel according to the applicable legislation
and this installation manual, using a separate circuit. Insufcient
capacity of the power supply circuit or improper electrical
construction may lead to electric shocks or a re.
r Make sure to install an earth leakage breaker in accordance
with applicable legislation. Failure to do so may cause
electrical shock and a re.
r Do not turn on the power supply (of the indoor unit) until all
the installation work is completed.

9.

HOW TO CONNECT WIRINGS AND


WIRING EXAMPLE

Wiring connection method


Caution for wiring
r The indoor units in the same system can be connected to the
power supply from one branch switch. However, selection of
branch switch, branch over current circuit breaker and wiring
size must be according to applicable legislation.
r For connection to the terminal block, use ring type crimp style
terminals with insulation sleeve or treat the wiring with insulation.
Insulation sleeve

Wiring

Ring type crimp


style terminals

11
3P400451-1E

92

Installation of indoor / outdoor unit

EDMT281536

Installation of indoor unit

r If the above is not available, make sure to observe the following items.
r 2 wirings of different sizes to the terminal block for power
supply is prohibited.
Connection of 2
wirings of same size
must be carried out
on both sides.

Connection of 2
wirings on one side
is prohibited.

Connection of
wirings of different
sizes is prohibited.

(4) Connect the remote controller wiring led from the routing
hole to the terminals (P1 and P2) of the terminal block
(X1M: 4P). (There is no polarity.)
After this is done, use the wiring xture (11) and clamp (4)
attached to bind the wiring without applying tension to the
connecting section of the wirings.

Terminal block (X2M)


Earth terminal
R10 or more
R10 or more

Transmission wiring
and Earth wiring

(Abnormal heating may occur if the wirings are not tightened


securely.)
r Use the required wirings, connect them securely and x
these wirings so that external force may not apply to the
terminals.
r Use a proper screw driver for tightening the terminal screws.
If an improper screw driver is used, it may damage the screw
head and a proper tightening cannot be carried out.
r If a terminal is over tightened, it may be damaged. Refer to
the table shown below for tightening torque of terminals.

Transmission and earth wiringconnection method


Outdoor unit

Terminal block
Terminal block
Terminal numbers of outdoor and
indoor units must be matched
Transmission wiring connection method

Tightening torqWG
0O
Terminal block for remote controller
and transmission wiring

Forbidden
r&QPQVECTry out solderKPIPKUJ

0.88 0.08

Terminal block for power supply

1.47 0.14

Ear th terminal

1.69 0.25

r Conduct wiring so that the earth lead comes out from the
notched part of the cup washer. (Otherwise, earth lead
contact will be insufcient and grounding effect may be lost.)
r &o not carry out soldering nish when stranded wirings are
used.

Forbidden
r0ever connect the power supply
wiring.
r&QPQVECTry out solderKPIPKUJ.
Terminal block (X1M)

Remote controller
wiring
(no polarity)

R10 or more
Ring type crimp style terminals
Cup washer

Indoor unit

Remote controller wiring


connection method
Printed Circuit
Board

Wiring penetration
hole

Control box
0QVEJGFRCrt

9-1 CONNECTION OF TRANSMISSION WIRING,


EARTH WIRING AND FOR THE REMOTE
CONTROLLER WIRING
(1) Loosen the xing screws (2 pcs.) while holding the control
box lid, and then remove the control box lid.
(2) Cut off the knockout hole and put the resin bushing (10)
(accessory) on the back side (sheet metal).
(3) Connect the transmission wiring through the resin bushing
(10) accessory to the terminal block (X2M: 3P) while
matching up the numbers (1 to 3), and then connect the earth
wiring to the earth terminal.
After this is done, use the wiring xture (11) and clamp (4)
attached to bind the wiring without applying tension to the
connecting section of the wirings.

Cut off the


knockout hole and
put the resin
bushing
(10) (accessory)

Transmission
wiring and
Earth wiring

Rear piping
penetration
cover

Remote controller
wiring

Control box lid


ZKPIUETews
(2 pieces)

Control box lid

Wiring diagram Label (Rear)

12
3P400451-1E

Installation of indoor / outdoor unit

93

Installation of indoor unit

EDMT281536

9-2

WARNING
When wiring, form the wirings orderly so that the control
box lid can be securely fastened. If the control box lid is not
in place, the wirings may QCV up or be sandwiched by the
box and the panel and cause electric shocks or a re.

Remote controller wiring


Clamp (4) (accessory)

WirKPIZVWTG
(11) (accessory)

(2) Fix the wiring to the


ZVWTGby clamps so
that no tension will be
given to the terminal
connection.

 +PUVCNNVJGZVWTGCV
the wiring entrance
side.
Power supply wiring
and Earth wiring

DETAIL

Clamp (4) (accessory)


(3) To avoid the loosing of
the power supply
wiring and Earth
wiring, band the clamp
VQVKIJVN[VVJGZVWTG
at terminal block side.

WIRING EXAMPLE

CAUTION
Be sure to install an earth leakage breaker to the outdoor
unit.
This is to avoid electric shocks or a re.
For the wiring of outdoor units, refer to the installation manual
attached to the outdoor units. Conrm the system type.
r Pair type:
1 remote controller controls 1 indoor unit (standard system).
(Refer to Fig. 31)
r Simultaneous operation system:
1 remote controller controls 2 indoor units
(2 indoor units operates equally). (Refer to Fig. 32)
r Group control:
1 remote controller controls up to 16 indoor units
(All indoor units operate according to the remote controller).
(Refer to Fig. 33)
r 2 remote controllers control:
2 remote controllers control 1 indoor unit. (Refer to Fig. 36)
Pair type

r In case the piping penetration cover is cut off and used as


wiring penetration hole, after the wiring connection is nished,
mend the cover.
r Seal the clearance around the wirings with putty and insulating
material (eld supply).
(If insects and small animals get into the indoor unit, short
circuiting may occur inside the control box.)
r If the low voltage wiring (remote controller wiring) and the
high voltage wiring (transmission wiring, earth wiring) are
brought into the indoor unit from the same place, they may be
affected by electric noise (outside noise) and cause
malfunction or failure.
r Keep the distance of 50mm or more between the low voltage
wiring (remote controller wiring) and the high voltage wiring
(transmission wiring, earth wiring) at anywhere outside the
indoor unit. If both the wirings are laid down together, they
may be affected by electric noise (outside noise) and cause
malfunction or failure.

Power supply
220 - 240V
~
50Hz

Earth leakage
breaker

Outdoor unit
1 2 3

NOTE 1)
1 2 3
P1 P2

Indoor unit
Remote controller
(Optional accessory)

P1P2

Fig. 31
Putty or insulation

GNFUWRRN[
Transmission
wiring and
Earth wiring

Refrigerant piping

Drain piping
Resin bushing
(10)(accessory)
High voltage wiring

Simultaneous operation system

Remote controller
wiring

Power supply
220 - 240V
~
50Hz

Earth leakage
breaker

Low voltage wiring


Outdoor unit
1 2 3

Distance of 50mm between


NOTE 1)

1 2 3

1 2 3
P1 P2

Indoor unit (Master)

P1 P2

Indoor unit (slave)


P1 P2

NOTE 2)

Remote
controller
(Optional accessory)

Fig. 32

13
3P400451-1E

94

Installation of indoor / outdoor unit

EDMT281536

Installation of indoor unit

3P400451-1E

Installation of indoor / outdoor unit

95

Installation of indoor unit

EDMT281536

10. MOUNTING SUCTION GRILLE


DECORATION SIDE PANEL

11-1 SETTING WHEN AN OPTIONAL ACCESSORY


IS ATTACHED

Install securely in the reverse order when decoration side panel


and suction grille were removed.
r When installing the suction grille, hang the string of the
suction grille to the hanging part of the indoor unit shown Fig. 38.
CAUTION
When closing the suction grille, the strap may get caught.
Conrm that the strap does not stick out of the side of the
suction grille before closing.
Round hole

Hook

Round hole

r For setting when attaching an optional accessory, refer to the


installation manual attached to the optional accessory.

11-2 WHEN USING WIRELESS REMOTE


CONTROLLER
r When using a wireless remote controller, it is necessary to
set the wireless remote controller address.
Refer to the installation manual attached to the wireless
remote controller.

11-3 SETTING CEILING HEIGHT (TYPE 100 OR


LESS)
r When installing indoor unit type 50 - 100, specify the
SECOND CODE No. in accordance with the ceiling height.

Strap

Table 4
Indoor unit
Suction grille

Hook
Cross hole

Ceiling height (m)

Strap

Fig. 38

11. FIELD SETTING


<<Refer to also the installation manual attached to the outdoor unit.>>
CAUTION
Before carrying out eld setting, check the items mentioned
in the clause 2 1. Items to be checked after the installation
tion work is completed on page 3.
r Check if all the installation and piping works for the air
conditioner are completed.
r Check if the control box lids of air conditioner are closed.
<FIELD SETTING>
<After turn on the power supply, carry out eld setting from the
remote controller according to the installation state.>
r Carry out setting at 3 places, Mode No., FIRST CODE No.
and SECOND CODE No..
The settings shown by
in the table indicate those
when shipped from the factory.
r The method of setting procedure and operation is shown in
the installation manual attached to the remote controller.
(Note) Though setting of Mode No. is carried out as a
group, if you intend to carry out individual setting by
each indoor unit or conrmation after setting, carry
out setting with the Mode No. shown in the
parenthesis ( ).
r In case of remote control, for changeover of input to
FORCED OFF or to ON/OFF OPERATION.
[1] Enter into the eld setting mode with the remote controller.

Type
50,60

Standard
High ceiling

Type
71

Type
100

2.7
2.7
3.8
or less or less or less
2.7 3.5

2.7 3.5

3.8 4.3

Mode
No.

FIRST
CODE
No.

13 (23)

SECOND
CODE
No.

01
02

11-4 SETTING FILTER SIGN


r A message to inform the air lter cleaning time will be
indicated on the remote controller.
r Set the SECOND CODE No. shown in the Table 5 according
to the amount of dust or pollution in the room.
r Though the indoor unit is equipped with the long life lter, it is
necessary to periodically clean the lter to avoid clogging of
the lter. Please also explain the set time to the customer.
r The periodical lter cleaning time can be shortened depending
on the environment.
Table 5
Contamination

Normal
More
contaminated

Filter hours
FIRST
Mode No.
(long life type)
CODE No.
Approx.
2500 hrs
Approx.
1250 hrs

With indication
No indication

SECOND
CORD
No.
01

0
02

10 (20)
3

01
02

* Use No indication setting when cleaning indication is not


necessary such as the case of periodical cleaning being
carried out.

[2] Select Mode No. 12.


[3] Set the FIRST CODE No. to 1.
[4-1] For FORCE OFF, set the SECOND CODE No. to 01.
[4-2] For ON/OFF OPERATION, set the SECOND CODE No.
to 02.
(It is set to FORCED OFF when shipped from the factory.)
r Ask your customer to keep the manual attached to the
remote controller together with the operation manual.
r Do not carry out setting other than those shown in the table.

15
3P400451-1E

96

Installation of indoor / outdoor unit

EDMT281536

Installation of indoor unit

11-5 SETTING FAN SPEED DURING THERMOSTAT


OFF
r Set the fan speed according to the using environment after
consultation with your customer.
Table 6
FIRST
SECOND
Mode No.
CODE No. CORD No.

Setting
Fan operates / stops Operates
during thermo OFF
(Cooling heating)
Stops
Fan speed during
cooling
thermostat OFF

(Extra low)

Fan speed during


heating
thermostat OFF

(Extra low)

Setting

Setting

01
11 (21)

2
02
01

12 (22)

12 (22)

02
01
02

11-6 SETTING NUMBER OF THE CONNECTED


INDOOR UNITS AS SIMULTANEOUS OPERATION SYSTEM
r When using in simultaneous operation system mode, change
the SECOND CODE No. as shown in Table 7.
r When using in simultaneous operation system mode, refer to
SIMULTANEOUS OPERATION SYSTEM INDIVIDUAL
SETTING section to set master and slave units separately.
Table 7
Setting

(5) Turn on the main power supply switch again, and as in (1),
change the SECOND CODE No. to 02, individual setting.
(6) Perform eld setting (Refer to 11-1 to 11-4) for the slave
unit.
(7) Turn off the main power supply switch after (6) is nished.
(8) If there is more than one slave unit, repeat steps (4) to (7).
(9) Detach the remote controller from the slave unit after the
setting, and reattach to the master unit. This is the end of
the setting procedure.
* You do not need to rewire the remote controller from the
master unit if the optional remote controller for slave unit
is used. (However, remove the wiring attached to the
remote controller terminal block of the master unit.) After
the slave unit setting, remove the remote controller wiring,
and rewire the remote controller to the master unit.
(The indoor unit does not operate properly when two or
more remote controllers are attached to the unit in the
simultaneous operation system mode.)
(3)(7)
Earth
leakage
breaker

Power supply
220 - 240V
~
50Hz

Outdoor
unit

Mode No.

SECOND
CODE No.

Pair system (1 unit)

01

Simultaneous
operation
system (2-unit)

02
11 (21)

1 2 3

1 2 3

NOTE)
1 2 3

1 2 3

04

It is easier if the optional remote controller is used when setting


the slave unit.
< Procedure >
r Perform the following procedure when setting the master and
slave unit separately.
r
in the tables indicates factory settings.
(Note) The Mode No. is set on a group basis. To individually
set a Mode No. for each indoor unit or conrm the
settings, set the Mode No. in the parenthesis.
(1) Change the SECOND CODE No. to 02, individual setting,
so that the slave unit can be individually set.
Table 8

Unied setting
Individual setting

FIRST
CODE No.

11 (21)

1 2 3
P1 P2

P1 P2

(1)
(2)

Indoor unit
Indoor unit
(Slave)
(Master)
P1 P2
Remote controller ( 4 )
( 9 ) Remote controller
(5)
(6)
Fig. 39

NOTE
r Terminal numbers of outdoor and indoor units must be
matched.

11-7 SIMULTANEOUS OPERATION SYSTEM


INDIVIDUAL SETTING

Mode No.

1 2 3
P1 P2

Indoor unit
(Slave)

P1 P2

03

Double twin multi


(4-unit)

Setting

Indoor unit
(Master)

Power supply
220 - 240V
~
50Hz

Outdoor
unit

P1 P2

Simultaneous
operation
system (3-unit)

Earth
leakage
breaker

NOTE)
FIRST
CODE No.

SECOND
CODE No.
01
02

(2) Perform eld setting (Refer to 11-1 to 11-5) for the master
unit.
(3) Turn off the main power supply switch after (2) is nished.
(4) Detach remote controller from the master unit and connect
it to the slave unit.

12. TEST OPERATION


Complete all the 1. Items to be checked after the
installation work is completed on page 3. Please also refer
to the installation manual attached to with outdoor unit.
(1) The settings of the wired remote controller should be
switched while referring to the manual attached to the
remote controller.
(2) The settings of the other remote controller should be
switched in accordance with the following procedure.
r Make sure that the installation work for the indoor and
outdoor units is all completed.
r Make sure that the following items are all closed: the
control box lid of the indoor unit and the outer board
and piping cover of the outdoor unit.
r After completing the refrigerant piping, drain piping,
and electrical wiring, clean the interior of the indoor unit
and front panel. Next, perform test operation in accordance
with the installation manual attached to with the outdoor
unit in order to protect the unit. (It is recommended
that the test operation is performed in the presence
of qualied electrical technician or engineer.)
r In test operation, make sure that CKTow direction and
fan speed can be obtained according to the settings.

16
3P400451-1E

Installation of indoor / outdoor unit

97

Installation of indoor unit

EDMT281536

r If interior work is still unnished when test operation


nishes, explain to the customer that the air conditioner
must not be operated until interior work is completed in
order to protect the indoor units.
(If the indoor unit is operated under this condition,
paint, glue, and other materials used during the interior
nishing work will contaminate the indoor unit. This
may cause water splashes or leakage.)
r If a malfunction occurs and the air conditioner cannot
operate, refer to 12-1 HOW TO DIAGNOSE FOR
PROBLEMS.
r After completing the test operation, press the INSPECTION/
TEST OPERATION button once to put the indoor
unit in inspection mode, and make sure the malfunction
code is 00 (= normal).
If the code reads anything other than 00, refer to
12-1 HOW TO DIAGNOSE FOR PROBLEMS.
r Press the INSPECTION/TEST OPERATION button
four times to return to normal operation mode.

(1) Press the INSPECTION /TEST OPERATION


button,
is displayed and 0 CUJes.
(2) Press the PROGRAMMING TIME button and nd
the unit No. which stopped due to trouble.
Number of beeps 3 short beeps
................. Perform all the following operations
1 short beep
................. Perform (3) and (6)
1 long beep
................. No trouble
(3) Press the OPERATION MODE SELECTOR button
and upper gure of the malfunction code CUhes.
(4) Continue pressing the PROGRAMMING TIME button
unit it makes 2 short beeps and nd the upper code.
(5) Press the OPERATION MODE SELECTOR button
and lower gure of the malfunction code ashes.
(6) Continue pressing the PROGRAMMING TIME button
unit it makes a long beep and nd the lower code.
r A long beep indicate the malfunction code.
NOTE

[Mode switching]

1. When the INSPECTION/OPERATION button on the remote

BRC1C, BRC1D,
Normal
operating
mode

Once

Field setting
* After leaving 10
seconds or
more, the mode
returns to the
normal
operating mode.

Once
*

ce

Once

Test
operation
mode

On

Once

Once
(Press 4
seconds
or more)

Wireless remote controller

Outdoor
Indoor
Malfunction
unit type
unit type
code
Once code
Once
code
display
display
display
Inspection mode

12-1 HOW TO DIAGNOSE FOR PROBLEMS


With the power on. Troubles can be monitored on the
remote controller.
The fault diagnosis for the BRC1E model remote controller
should be performed while referring to the installation manual
supplied with the remote controller. For the other remote
controllers, perform the fault diagnosis using the following
procedure.
Trouble shooting with the remote controller display.
1 With the wired remote controller. (NOTE 1)
When the operation stops due to trouble, the operation
lamp CUhes, and the display indicates

and the malfunction code. Diagnosis can be carried


out using the malfunction code list according to the
indicated malfunction code.
In addition, when in group control it indicates the
unit No., so the malfunction detected unit No. will be
claried. For resetting the malfunction, see (NOTE
2).
2 With the wireless remote controller.
(Also refer to the operation manual attached to the
wireless remote controller.)
When the operation stops due to trouble, the display
on the indoor unit CUhes. In such a case, diagnose
the fault contents with the table on the
Malfunction code list looking for the Malfunction
code which can be found by following procedures.
(NOTE 2)

controller is pressed, the


indication starts ashing.
2. When the ON/OFF button is kept pressed for 5 seconds or
longer during the inspection mode, the above trouble history
indication disappears. In this case, after the malfunction
code indication ashes twice, the indication of code
becomes 00 (normal) and unit NO. becomes 0. Then,
the display automatically changes from the inspection
mode to the normal mode.

12-2 MALFUNCTION CODE


r For places where the malfunction code is left blank, the

indication is not displayed. Though the system


continues operating, be sure to inspect the system and make
repairs as necessary.
r Depending on the type of indoor or outdoor unit, the
malfunction code may or may not be displayed.
Malfunction code

Descriptions and measures

A1

Indoor Printed Circuit


Board failure

A3

Drain level abnormal

A5

Freeze-up protector or
stopped by high pressure
control (NOTE 1)

A6

A7

AF

Remarks

Indoor fan motor overload,


over current, lock
Indoor Printed Circuit
Board connection failure
Horizontal blade motor
locked
1PN[VJGCKTow direction
can not be controlled.
Humidier system
malfunction
Capacity setting adapter or
capacity data error, or
disconnection of the capacity
setting adapter, failure to connect
the adapter, or the capacity is not
set to the data-retention IC.

AJ

Capacity setting failure

C1

Transmission error
between indoor
Printed Circuit Board
(Master) and indoor Printed
Circuit Board (Slave)

17
3P400451-1E

98

Installation of indoor / outdoor unit

EDMT281536

Installation of indoor unit

C4

Indoor heat exchanger


liquid pipe temperature
sensor malfunction

Abnormal stop is applied


depending on the model or
condition.

J5

Suction piping thermistor


system malfunction
(Outdoor unit)

C5

Indoor heat exchanger


condenser / evaporator
temperature sensor
malfunction

Abnormal stop is applied


depending on the model or
condition.

J6

Outdoor heat exchanger


distributor liquid piping
thermistor malfunction
(Outdoor unit)

Abnormal stop is applied


depending on the model or
condition.

C9

Suction air thermistor


malfunction

Abnormal stop is applied


depending on the model or
condition.

J7

CC

Humidity sensor abnormal

Outdoor heat exchanger


condenser / evaporator
thermistor malfunction
(Outdoor unit)

Abnormal stop is applied


depending on the model or
condition.

CJ

Remote controller air


thermistor malfunction

J8

Liquid piping thermistor


system malfunction
(Outdoor unit)

Abnormal stop is applied


depending on the model or
condition.

E0

Action of safety device


(Outdoor unit)

J9

E1

Outdoor Printed Circuit


Board failure (Outdoor unit)

Gas piping thermistor


malfunction (cooling)
(Outdoor unit)

JA

E3

High pressure malfunction


(Outdoor unit)

Discharge piping pressure sensor system


malfunction (Outdoor unit)

E4

Low pressure malfunction


(Outdoor unit)

JC

E5

Compressor motor lock


malfunction (Outdoor unit)

Suction piping pressure


sensor system malfunction
(Outdoor unit)

L1

E6

Compressor motor lock by


over current (Outdoor unit)

Inverter system malfunction


(Outdoor unit)

L3

Outdoor fan motor lock


malfunction (Outdoor unit)

Reactor thermistor
malfunction (Outdoor unit)

L4

Overheated heat-radiating
Inverter cooling failure.
n (Outdoor unit)

L5

The compressor engines and


Instantaneous overcurrent
turbines may be experiencing
(Outdoor unit)
a ground fault or short circuit.

L8

Electric thermal (Outdoor


unit)

The compressor engines and


turbines may be overloaded
and disconnected.

L9

Stall prevention (Outdoor


unit)

The compressor may be locked.

E7

E8

Remote controller thermo


does not function, but body
thermo operation is enabled.

Outdoor fan instant


overcurrent malfunction
(Outdoor unit)
Input overcurrent (outdoor
unit)

E9

Electric expansion valve


malfunction (Outdoor unit)

EA

Cooling/heating switch
malfunction (Outdoor unit)

F3

Discharge piping
temperature malfunction
(Outdoor unit)

LC

Transmission malfunction
between inverter and
outdoor control unit
(Outdoor unit)

F6

High pressure control


(in cooling) (Outdoor unit)

P1

Open-phase (Outdoor
unit)

H0

Sensor fault for inverter


(Outdoor unit) (NOTE 1)

P3

DCL sensor system


malfunction (Outdoor unit)

H3

High pressure switch


failure (Outdoor unit)

P4

Heat-radiating n
thermistor malfunction
(Outdoor unit)

P6

DC output current sensor


system malfunction
(Outdoor unit)

H4

Low pressure switch


failure (Outdoor unit)

H6

Faulty position detection


sensor (Outdoor unit)
(NOTE 1)

H7

Outdoor fan motor position


signal malfunction
(Outdoor unit)

H8

CT abnormality
(Outdoor unit) (NOTE 1)

H9

Outdoor air thermistor


system malfunction
(Outdoor unit)

J1

Pressure sensor system


malfunction (batch)
(Outdoor unit)

J2

Current sensor system


malfunction (Outdoor
unit)

J3

Discharge piping thermistor Abnormal stop is applied


system malfunction
depending on the model or
(Outdoor unit)
condition.

Abnormal stop is applied


depending on the model or
condition.

Abnormal stop is applied


depending on the model or
condition.

Abnormal stop is applied


depending on the model or
condition.

Capacity setting adapter or


capacity data error, or
disconnection of the capacity
setting adapter, failure to connect
the adapter, or the capacity is not
set to the data-retention IC.

PJ

Capacity setting failure


(Outdoor unit)

U0

The refrigerant may be


Suction piping temperature
insufcient.
abnormal (Outdoor
Abnormal stop is applied depending
unit)
on the model or condition.

U1

Reverse phase (Outdoor


unit)

U2

The inverter open-phase or


main circuit condenser may
Power voltage malfunction be malfunctioning.
(Outdoor unit)
Abnormal stop is applied
depending on the model or
condition.

Reverse two phase of L1, L2


and L3 leads.

18
3P400451-1E

Installation of indoor / outdoor unit

99

Installation of indoor unit

EDMT281536

U4
UF

Transmission error
(between indoor and
outdoor units)

Wiring error between indoor


and outdoor unit. Or Indoor
and outdoor Printed Circuit
Board failure.

U5

Transmission error
(between indoor and
remote controller units)

Transmission between indoor


unit and remote controller is
not performed properly.

U7

Transmission error of the


inverter module

U8

Transmission error
between main and sub
remote controllers (sub
remote controller
malfunction)

UA

Field setting error

UE

Transmission error
(between indoor unit and
centralized remote
controller)

UC

Remote controller
address setting error

UJ

Accessory equipment
transmission error

System setting error of the


simultaneous on/off multi-split
type.

Abnormal stop is applied


depending on the model or
condition.

CAUTION
After test operation is completed, check the items mentioned in
the clause 2 2. Items to be checked at delivery on page 3.
If the interior nish work is not completed when the test
operation is nished, for protection of the air conditioner, ask the
customer not operate the air conditioner until the interior nish work
is completed.
If the air conditioner is operated, the inside of the indoor units
may be polluted by substances generated from the coating and
adhesives used for the interior nish work and cause water
splash and leakage.
To the operator carrying out test operation
After test operation is completed, before delivering the air
conditioner to the customer, conrm that the control box lid is
closed.
In addition, explain the power supply status (power supply ON/
OFF) to the customer.

19
3P400451-1E

100

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

3. Installation of outdoor unit


3.1

RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 / RZQ125LV1

1P379050-1A

Installation of indoor / outdoor unit

101

Installation of outdoor unit

EDMT281536

1P379050-1A

102

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P379050-1A

Installation of indoor / outdoor unit

103

Installation of outdoor unit

EDMT281536

C: 1P379050-1A

104

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

C: 1P379050-1A

Installation of indoor / outdoor unit

105

Installation of outdoor unit

EDMT281536

C: 1P379050-1A

106

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P379050-1A

Installation of indoor / outdoor unit

107

Installation of outdoor unit

EDMT281536

1P379050-1A

108

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P379051-1A

Installation of indoor / outdoor unit

109

Installation of outdoor unit

EDMT281536

1P379051-1A

110

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P379051-1A

Installation of indoor / outdoor unit

111

Installation of outdoor unit

EDMT281536

1P379051-1A

112

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P379051-1A

Installation of indoor / outdoor unit

113

Installation of outdoor unit

EDMT281536

1P379051-1A

114

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P379051-1A

Installation of indoor / outdoor unit

115

Installation of outdoor unit

EDMT281536

1P379051-1A

116

Installation of indoor / outdoor unit

EDMT281536

3.2

Installation of outdoor unit

RZQ140LV1

1P325929-1E

Installation of indoor / outdoor unit

117

Installation of outdoor unit

EDMT281536

1P325929-1E

118

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P325929-1E

Installation of indoor / outdoor unit

119

Installation of outdoor unit

EDMT281536

C: 1P325929-1E

120

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

C: 1P325929-1E

Installation of indoor / outdoor unit

121

Installation of outdoor unit

EDMT281536

C: 1P325929-1E

122

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P325929-1E

Installation of indoor / outdoor unit

123

Installation of outdoor unit

EDMT281536

1P325929-1E

124

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P325930-1E

Installation of indoor / outdoor unit

125

Installation of outdoor unit

EDMT281536

1P325930-1E

126

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P325930-1E

Installation of indoor / outdoor unit

127

Installation of outdoor unit

EDMT281536

1P325930-1E

128

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P325930-1E

Installation of indoor / outdoor unit

129

Installation of outdoor unit

EDMT281536

1P325930-1E

130

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P325930-1E

Installation of indoor / outdoor unit

131

Installation of outdoor unit

EDMT281536

1P325930-1E

132

Installation of indoor / outdoor unit

EDMT281536

3.3

Installation of outdoor unit

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

1P296089-1B

Installation of indoor / outdoor unit

133

Installation of outdoor unit

EDMT281536

1P296089-1B

134

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P296089-1B

Installation of indoor / outdoor unit

135

Installation of outdoor unit

EDMT281536

C: 1P296089-1B

136

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

C: 1P296089-1B

Installation of indoor / outdoor unit

137

Installation of outdoor unit

EDMT281536

C: 1P296089-1B

138

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P296089-1B

Installation of indoor / outdoor unit

139

Installation of outdoor unit

EDMT281536

1P296089-1B

140

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P296090-1B

Installation of indoor / outdoor unit

141

Installation of outdoor unit

EDMT281536

1P296090-1B

142

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P296090-1B

Installation of indoor / outdoor unit

143

Installation of outdoor unit

EDMT281536

1P296090-1B

144

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P296090-1B

Installation of indoor / outdoor unit

145

Installation of outdoor unit

EDMT281536

1P296090-1B

146

Installation of indoor / outdoor unit

EDMT281536

Installation of outdoor unit

1P296090-1B

Installation of indoor / outdoor unit

147

Installation of outdoor unit

EDMT281536

1P296090-1B

148

Installation of indoor / outdoor unit

EDMT281536

3.4

Installation of outdoor unit

Equivalent piping length of joints (reference)


Pipe Size
L Joints

Installation of indoor / outdoor unit

(mm)

6.4

9.5

12.7

15.9

19.1

22.2

25.4

31.8

38.1

0.16

0.18

0.20

0.25

0.35

0.40

0.45

0.55

0.65

(m)

149

Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Specifications, designs and other content appearing in this brochure are current as of December 2015 but subject to change without notice.
c All rights reserved 12/15 FS

You might also like