ARC FLASH STUDY REPORT

FOR

EMERSON PROCESS MANAGEMENT CHENNAI PVT LTD


PLANT AT

147, Karapakkam Village Chennai PIN-600097, INDIA.

STUDY CONDUCTED BY

INTERFACE ELECTRONICS PVT LTD CHENNAI


EMAIL:IFE@VSNL.COM.MOBILE NO: +919884370326

Contents
Sl.No
1
2
3
4
4(i)
4(ii)
4(iii)
4(iv)
5
6
7
8
9
10
11
12
13
14
15
16

Description
Executive Summary
Purpose of the Report
Single Line Diagram
Short Circuit Report
Short circuit currents in SLD for source fault 250MVA sec (min)
Short circuit currents in Table for source fault 250MVA sec (min)
Short circuit currents in SLD for source fault 500MVA sec (max)
Short circuit currents in Table for source fault 500MVA sec (max)
Transformer setting calculation
Cable schedule
Fuse Details
Setting Details for Panels
TCC Curves
Arc Flash Energy Calculation Report
Labels
Energy Plots with boundry limits
Arc Flash Boundries Illustration
PPE Clothing Description
PPE Illustration
Work Permit Sample

Page No
3
5
9
11
12
13
17
18
22
24
25
26
28
30
33
58
82
84
86
95

EXECUTIVE SUMMARY
Calculations were prepared utilizing EDSA Paladin Design Base 5, a commercially
available, computer aided engineering tool for the analysis of industrial, utility, and
commercial electrical power systems.
Arc flash hazard analysis was developed within the short circuit module of EDSA
Paladin Design base 5. A copy of the one line diagram developed within EDSA is
included as an attachment.
A table giving the details BUS NAME, ARC GAP, BOLTED FAULT, ESTIMATED ARC
FAULT, ESTMATED ARC FLASH BOUNDARY, INCIDENT OF ENERGY, WORKING
DISTANCE and REQUIRED CLOTHING CLASS is included in the report
Illustrations of different PPE are given in the Report.
Warning Labels as Generated for various Buses based on the Energy incident
calculations is given in the report.
Graph giving the Incident of Energy with reference to Distance is given for all
the Busses for reference.
Incident energy and arc flash boundary calculations were prepared utilizing EDSAPaladin Design Base 5. The analysis yields results as required by IEEE, namely,
specification of the arc flash boundary (AFB) and the incident arc energy at a probable
working distance. Complete results are listed in Table. The graphs and the warning
Labels are prepared based on Table
An explanation of the data presented in Table 1 is as follows:

B us Name: This is the name of the buses where an arc flash is postulated.

LL Voltage: The nominal voltage of the bus where an arc flash is postulated.

Bolted Fault (kA): This is the calculated current for a 3-phase bolted fault at the
faulted bus.

C o n t r o l l i n g b r a n c h Arc Fault (kA): This is the estimated current when arc


resistance is included in calculation. When calculating incident energy, bolted fault
current at the faulted bus is used.

Trip Time (sec): Total duration of arc fault as explained in assumptions and
inputs.

3P Arc Flash Boundary: The flash protection boundary distance in cm for the arc

gap, bolted fault current, and arc time as explained above.

Working Distance: Approximate working distance in cm

3P Energy (cal/cm): This is the incident energy from arc flash


corresponding to the trip device. The trip time associated with the trip
device is used in the calculation. The rating of personal protective
equipment (PPE) worn by workers should be based on this value.

Required Clothing Class: This is the hazard/risk category as per NFPA 70E/IEEE
Appropriate PPE, as listed in Table, is recommended according to this classification.

Purpose of the report


The purpose of this report is to document and tabulate Incident Energy and
the Flash Protection Boundary at various 11 KV, and 433 Volt unit substation
buses at EMERSON PROCESS MANAGEMENT CHENNAI PVT LTD, 147,
Karapakkam Village Chennai PIN-600097, INDIA. PLANT in the unlikely event
that electrical equipment failures occur when work is being performed in
accordance with plant policies and procedures.
The results presented in this report are to be used as a guide in the selection of
Personal Protective Equipment (PPE) if work must be performed on or near
energized electrical equipment.
DISCUSSION
Regulatory Background

U.S. Department o f Labor, Occupational S a f e t y and Health Administration


(OSHA)

is the enforcement

agency for workplace

incidents

involving

personnel. If there is an arc flash incident, it will most likely be investigated by


OSHA.
Currently, OSHA is r e c o m m e n d i n g tha t c o m p a n i e s follow NFPA 70E as
a guideline for worker safety. In addition, OSHA has begun to review NFPA 70E
guidelines as a part of their routine inspection procedures.
NFPA 70E (Standard for Electrical Safety Requirements for Employee
Workplaces) and NFPA 70 (National Electrical Code) provide the basis for
employers to determine if electrical hazards are present and to determine the
proper types of Personal Protective Equipment (PPE) that will protect
employees in the unlikely event that electrical equipment failures occur when
work is being performed in accordance with plant policies and procedures. NEC
Article 110.16 (Flash Protection) states: Switchboards, panel boards, industrial
control panels, meter socket enclosures, and motor control centre, that are
likely to require examination, adjustment, servicing, or maintenance while
energized, shall be field marked to warn qualified persons of potential

Electric arc flash hazards. The marking shall be located so as to be clearly visible
to qualified persons before examination, adjustment, servicing or maintenance of
the equipment.
EMERSON PROCESS MANAGEMENT CHENNAI PVT LTD were in the interest of safety
requested M/s Interface electronics to

to do ARC FLASH STUDY for the

entire Electrical distribution system at t h e i r K a l a p a k k a m Plant,Chennai


and submit the Report for selection of PPE and to indicate the Flash Protection
boundary

for each Electrical

Equipment

such as Switch

Boards, Panel

boards, Control panels etc.


What is Arc Flash?

Arc Flash is the rapid release of energy due to an arcing fault between a
phase conductor and another phase conductor, neutral conductor, ground
conductor, or grounded surface. During an arcing fault, ionized gases in the air
gap between conductive surfaces become current conducting plasma. Arcing
faults are generally limited to systems where the bus voltage is in excess of
250 volts, AC.
In AC systems, lower voltage levels normally will not sustain an arc as voltage
recovery is not quick enough for an arc to restrike after a zero current occurs. An
arcing fault is similar to the arc obtained during electric welding. Arcing faults
can be the result of a failure, such as: breakdown of insulation, accidental
contact, or momentary contact.
Hazardous Arc-Flash can occur in any electrical device in which voltage is high
enough to sustain an arc. In industrial settings, this includes:

P a n e l boards and switchboards

M o t o r control centre

M e t a l -clad switchgear

Transformers

M o t o r starters

H i g h voltage switching and grounding equipment

P a d -mounted switching equipment

M e t e r bases and meter banks

Any electrical equipment that has sufficient voltage to ionize the air
gap in the unlikely event that electrical equipment failure occurs

Flash Hazard Analysis and Flash Protection Boundary


Prior to commencing work o n electrically energized conductors > 50 volts, NFPA
70E 130.3 requires that a flash hazard analysis be completed in order to protect
personnel from the possibility of being injured by an arc flash. The analysis shall
determine the Flash Protection Boundary and the personal protective equipment
that shall be used within the Flash Protective Boundary. For tasks not listed, or
for power systems with greater short-circuit
capacity

or l o n g e r

fault

clearing

times,

current
a f l a s h hazard analysis shall be

required.
NFPA 70E 130.3(A) requires employers to establish a flash protection
boundary a distance from exposed energized electrical parts at which an
employee would sustain no more than a second degree burn if an electric arc
flash were to occur. Employees performing work on energized conductors
inside the flash protection boundary must be protected with appropriate PPE. At
voltage levels below 600 volts, the flash protection boundary is the distance at
which incident energy level is equal to 1.2 cal/cm2. For situations where faultclearing time is 0.1 seconds or less, the flash protection boundary is the distance
at which incident energy level is equal to 1.5 cal/cm 2.
When work is to be performed within the flash protection boundary, the flash
hazard analysis determines t he incident energy exposure of the worker
(cal/cm2). This incident energy exposure

level is based on the working

distance of the employees face and the chest areas from a potential arc
source for the specified task to be performed. Flame resistant clothing and
PPE used by the worker must be based upon the incident energy exposure

associated with the specific task. Recognizing that incident energy increases as
distance from arc flash decreases, additional PPE shall be used for any parts of
the body that are closer than the distance at which the incident energy was
determined.
NFPA 70E 2004 is a safety standard for worker safety as a part of National Fire
Protection Association (NFPA) guidelines. Among other safe workplace practices,
it provides awareness on the hazards of arc flash incidents.
Steps required to comply with NFPA 70E, Chapter 1 Article 110.8 (B)(1)(b),
130.3, and 130.7 (C)(9)(a) include:
A Comprehensive Safety Program.

Employee arc flash awareness safety training.


Safety procedures and manuals that are updated to comply with the NFPA
70E guidelines.
Up to date facility single line diagrams, short circuit
studies and protective device coordination studies

Arc flash assessment and analysis


Personal Protective Equipment
NFPA specifies the requirements f o r PPE for workers within flash protection
boundaries. All parts of the body, which may be exposed to arc flash, need to be
covered by appropriate PPE.
The entire PPE set may be comprised of fire retardant clothing, helmet,
headgear, face shield, safety glasses, gloves, shoes, etc. The amount of PPE required
needs to be determined on the basis of calculated incident energy on a worker.
The calculations need to be performed by a qualified person, such as an
engineer.

The protective clothing should limit the incident energy

reaching the chest/face of the worker to less than 1.2 cal/cm 2. Fire retardant
clothing provides thermal insulation and is also self-extinguishing.
clothing is rated in cal/cm 2.

Protective

Sample WorkPermit
SINGLE LINE DIAGRAM

GRID

GRID

CAB:rmg
10 Meters
#/PH: 1
HT VCB
50
51

CAB:TRHVS
15 Meters
#/PH: 1
DG1

GEN

DGPNL_IC1

TR
11000/433 V
Z%: 6.25
1600 kVA

DG2

BUSDUCT
10 Meters
#/PH: 1

CAB:DG2
50 Meters
#/PH: 2
DGPNL_IC2

MPNL_IC
M_PNL

DGPNL RHS

DGPNL LHS

OG1

CAB:DG_SSB12
50 Meters
#/PH: 2

CAB:OG1
28 Meters
#/PH: 6

SSB1_IC1

SSB1_OG1

APFC
SSB1_OG3

CAB:SSB1_OG3
25 Meters
#/PH: 4

CAB:MLSB
15 Meters
#/PH: 1

STAB_IC
STAB2
Z%: 0.65
500 kVA

MLSB_IC

CAB:STAB1
20 Meters
#/PH: 6

165

SSB2_IC

BBT3

102

96

48

108

114

120

PHS_OG4

PHS_OG5

PHS_OG6

87

178

PHS_OG3

SSB2_OG4
BBTSP

PH_PNL_LHS

168

PHS_OG2

SSB2_OG3

CAB:BBT SP
CAB:BBT2
CAB:BBT1
CAB:BBT3
50 Meters
50 Meters
50 Meters
50 Meters
#/PH: 1
#/PH: 1
#/PH: 1
#/PH: 1

86

PHS_OG1

81

MLSB_OG2

76

PH_IC

MLSB

MLSB_OG1

71
SSB2_OG2

SSB2

CAB:OG2
15 Meters
#/PH: 1

APFC_IC
SSB1 RHS

SSB1_OG2_F

STAB1
Z%: 0.65
1000 kVA

SSB2_OG1

SSB1_IC3

SSB1_OG2

CAB:SSB1_OG1
14 Meters
#/PH: 6

BBT1

OG2

CAB:OG4
9 Meters
#/PH: 2
SSB1_BC

SSB1_IC2
SSB1 LHS

BBT2

OG4

DGPNL_OG2

DGPNL_OG1
CAB:DG_SSB11
50 Meters
#/PH: 2

66

OG3

CAB:LSB1
50 Meters CAB:LSB2
#/PH: 1
50 Meters
#/PH: 1
LSB1

CAB:CAN
50 Meters
#/PH: 1

LSB2 CANTEEN

CAB:SSB5
50 Meters
#/PH: 1
SSB5

CAB:PAINT
50 Meters
#/PH: 1

PAINTING

APFC1

CAB:APFC1
50 Meters
#/PH: 1
SSB6

CAB:SSB6
50 Meters
#/PH: 1

SSB1

PH_BC

CAB:DG1
50 Meters
#/PH: 2

DGPNL_BC

GEN

PH_PNL_RHS

126

134

127

140

SSB61

CAB:SSB1
50 Meters
#/PH: 1

SSB3

SSB21

CAB:SSB21
50 Meters
#/PH: 1

CAB:SSB61
50 Meters
#/PH: 1

SSB61

146

SSB21

SSB3

CAB:SSB3
50 Meters
#/PH: 1

152

NEWOFFICE

CAB:NO
50 Meters
#/PH: 1
NEWOFFICE

REV. DATE

ECO#

DESCRIPTION

DWN APP

T HIS D R AW ING I S P R O PR I ET AR Y INFO R MAT IO N

Your Company Name


Address
Address
Phone and web site

Electrical
Electrical One-Line
One-Line Diagram
Diagram

D RA WN B Y/ D ATE:

DWG No.:

EN G. AP P./ DA TE:

M FG . AP P ./ D ATE:

SC A LE:

PART No.:
D WG S IZE:

REV.

Sample WorkPermit
SHORT CIRCUIT REPORT

GRID
Ik" : 13121.6A

GRID

CAB:rmg
10 Meters
#/PH: 1
HT VCB
50
51

DGPNL_IC1

GEN

CAB:TRHVS
15 Meters
#/PH: 1
TR
11000/433 V
Z%: 6.25
1600 kVA

DG2

BUSDUCT
10 Meters
#/PH: 1

CAB:DG2
50 Meters
#/PH: 2
DGPNL_IC2

MPNL_IC

OG3

OG1
CAB:DG_SSB12
50 Meters
#/PH: 2

CAB:OG1
28 Meters
#/PH: 6

SSB1_IC2

SSB1_IC1

SSB1 LHS
Ik" : 25507.47A

APFC_IC
SSB1 RHS
Ik" : 25467.38A

STAB_IC
STAB2
Z%: 4
600 kVA

MLSB_IC

CAB:STAB1
20 Meters
#/PH: 6

102

96

48

108

114

120

PHS_OG5

PHS_OG6

SSB2_OG4

178

PHS_OG4

SSB2_OG3
BBT3
Ik" : 9952.17A

87

168

PHS_OG3

SSB2_OG2

CAB:BBT SP
CAB:BBT2
CAB:BBT1
CAB:BBT3
50 Meters
50 Meters
50 Meters
50 Meters
#/PH: 1
#/PH: 1
#/PH: 1BBT2
#/PH: 1
BBTSP
Ik" : 9952.17A
Ik" : 9681.97A

86

PHS_OG2

81

PHS_OG1

76

PH_PNL_LHS
Ik" : 9871.6A

MLSB_OG2

71

PH_IC

MLSB_OG1

165
MLSB
Ik" : 18547.37A

SSB2
Ik" : 13149.79A

APFC
Ik" : 25545.67A

CAB:SSB1_OG3
25 Meters
#/PH: 4

CAB:MLSB
15 Meters
#/PH: 1

STAB1
Z%: 4
1000 kVA

CAB:OG2
15 Meters
#/PH: 1

SSB1_OG3

SSB1_OG2_F

CAB:SSB1_OG1
14 Meters
#/PH: 6

SSB2_OG1

SSB1_IC3

SSB1_OG2

SSB1_OG1

BBT1
Ik" : 9952.17A

OG2

CAB:OG4
9 Meters
#/PH: 2
SSB1_BC

CAB:DG_SSB11
50 Meters
#/PH: 2

SSB2_IC

OG4

DGPNL_OG2

DGPNL_OG1

66

M_PNL
Ik" : 26680.02A

DGPNL RHS

DGPNL LHS

CAB:LSB1
50 Meters CAB:LSB2
#/PH: 1
50 Meters
#/PH: 1
LSB1
Ik" : 12503.96A

CAB:CAN
50 Meters
#/PH: 1

LSB2 CANTEEN
Ik" : 7754.5A
Ik" : 12503.96A

CAB:SSB5
50 Meters
#/PH: 1
SSB5
Ik" : 7754.5A

CAB:PAINT
50 Meters
#/PH: 1

PAINTING
Ik" : 7754.5A

CAB:APFC1
50 Meters
#/PH: 1

APFC1
Ik" : 7754.5A

CAB:SSB6
50 Meters
#/PH: 1

SSB6
Ik" : 7754.5A

CAB:SSB1
50 Meters
#/PH: 1

SSB1
Ik" : 7754.5A

PH_BC

CAB:DG1
50 Meters
#/PH: 2

DGPNL_BC

GEN

DG1

VCB PNL
Ik" : 13089.11A

126

127

PH_PNL_RHS
Ik" : 9854.58A
134

SSB61

CAB:SSB61
50 Meters
#/PH: 1
SSB61
Ik" : 7246.88A

140

146

SSB3

SSB21

CAB:SSB21
50 Meters
#/PH: 1
SSB21
Ik" : 7246.88A

CAB:SSB3
50 Meters
#/PH: 1

SSB3
Ik" : 7246.88A

152

NEWOFFICE

CAB:NO
50 Meters
#/PH: 1
NEWOFFICE
Ik" : 7246.88A

REV. DATE

ECO#

DESCRIPTION

DWN APP

TH IS DRAWING IS PROPRIE TARY INFORM AT ION

You r C omp any Na me


Add ress
Add ress
Ph one a nd web site

Electrical One-Line DiagramShort Circuit Currents-Source 250 MVA SEC


DRAWN BY/DATE:

DWG No .:

ENG. APP./DATE:
MFG. APP./DATE:
SCALE:

PAR T No.:
DWG SIZE:

RE V.

Short Circuit Detailed Report for source Fault 250 MVA Sec

(GRID FEED)

3P Fault - IEC60909 Method at the Following Times


Bus Description
Pre fault Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts current in current in current in current in current in current in current in
A
Amps
Amps
Amps
Amps
Amps
Amps
GRID
VCB PNL
M_PNL
APFC
SSB1 LHS
SSB1 RHS
MLSB
SSB2
LSB1
LSB2
BBT1
BBT2
BBT3
PH_PNL_LHS
PH_PNL_RHS
BBTSP
APFC1
CANTEEN
PAINTING
SSB1
SSB5
SSB6
NEWOFFICE
SSB21
SSB3
SSB61

11000
11000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

37113
37022
67916
63986
63818
63233
39764
25075
24033
24033
18537
18537
18537
18057
18007
17744
13916
13916
13916
13916
13916
13916
12683
12683
12683
12683

13122
13089
26680
25546
25507
25467
18547
13150
12504
12504
9952
9952
9952
9872
9855
9682
7755
7755
7755
7755
7755
7755
7247
7247
7247
7247

13122
13089
26680
25546
25507
25467
18547
13150
12504
12504
9952
9952
9952
9872
9855
9682
7755
7755
7755
7755
7755
7755
7247
7247
7247
7247

13122
13089
26680
25546
25507
25467
18547
13150
12504
12504
9952
9952
9952
9872
9855
9682
7755
7755
7755
7755
7755
7755
7247
7247
7247
7247

13122
13089
26680
25546
25507
25467
18547
13150
12504
12504
9952
9952
9952
9872
9855
9682
7755
7755
7755
7755
7755
7755
7247
7247
7247
7247

13122
13089
26680
25546
25507
25467
18547
13150
12504
12504
9952
9952
9952
9872
9855
9682
7755
7755
7755
7755
7755
7755
7247
7247
7247
7247

13122
13089
26680
25546
25507
25467
18547
13150
12504
12504
9952
9952
9952
9872
9855
9682
7755
7755
7755
7755
7755
7755
7247
7247
7247
7247

Short Circuit Detailed Report for source Fault 250 MVA Sec

(GRID FEED)

LL Fault - IEC60909 Method at the Following Times


Bus Description
Pre fault Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts current in current in current in current in current in current in current in
A
Amps
Amps
Amps
Amps
Amps
Amps
GRID
VCB PNL
M_PNL
APFC
SSB1 LHS
SSB1 RHS
MLSB
SSB2
LSB1
LSB2
BBT1
BBT2
BBT3
PH_PNL_LHS
PH_PNL_RHS
BBTSP
APFC1
CANTEEN
PAINTING
SSB1
SSB5
SSB6
NEWOFFICE
SSB21
SSB3
SSB61

11000
11000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

37113
37007
59478
55905
55757
55241
34624
21790
20881
20881
16093
16093
16093
15676
15633
15403
12074
12074
12074
12074
12074
12074
11003
11003
11003
11003

13122
13084
23365
22360
22326
22290
16182
11443
10879
10879
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13122
13084
23365
22360
22326
22290
16182
11443
10879
10879
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13122
13084
23365
22360
22326
22290
16182
11443
10879
10879
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13122
13084
23365
22360
22326
22290
16182
11443
10879
10879
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13122
13084
23365
22360
22326
22290
16182
11443
10879
10879
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13122
13084
23365
22360
22326
22290
16182
11443
10879
10879
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

Short Circuit Detailed Report for source Fault 250 MVA Sec

(GRID FEED)

LG Fault - IEC60909 Method at the Following Times


Bus Description
Pre fault Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts current in current in current in current in current in current in current in
A
Amps
Amps
Amps
Amps
Amps
Amps
GRID
VCB PNL
M_PNL
APFC
SSB1 LHS
SSB1 RHS
MLSB
LSB1
LSB2
APFC1
BBT1
BBT2
BBT3
BBTSP
CANTEEN
NEWOFFICE
PAINTING
PH_PNL_LHS
PH_PNL_RHS
SSB1
SSB2
SSB21
SSB3
SSB5
SSB6
SSB61

11000
11000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

37113
36961
64105
55343
55097
54651
33004
17302
17302
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

13122
13068
26390
24035
23958
23909
15923
9041
9041
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

13122
13068
26390
24035
23958
23909
15923
9041
9041
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

13122
13068
26390
24035
23958
23909
15923
9041
9041
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

13122
13068
26390
24035
23958
23909
15923
9041
9041
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

13122
13068
26390
24035
23958
23909
15923
9041
9041
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

13122
13068
26390
24035
23958
23909
15923
9041
9041
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Short Circuit Detailed Report for source Fault 250 MVA Sec

(GRID FEED)

LLG Fault - IEC60909 Method at the Following Times


Bus Description
Pre fault Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts current in current in current in current in current in current in current in
A
Amps
Amps
Amps
Amps
Amps
Amps
GRID
VCB PNL
M_PNL
APFC
SSB1 LHS
SSB1 RHS
MLSB
LSB1
LSB2
SSB2
BBT1
BBT2
BBT3
PH_PNL_LHS
PH_PNL_RHS
BBTSP
APFC1
CANTEEN
PAINTING
SSB1
SSB5
SSB6
NEWOFFICE
SSB21
SSB3
SSB61

11000
11000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

38476
38368
71131
63709
63507
62927
38128
21960
21960
21790
16093
16093
16093
15676
15633
15403
12074
12074
12074
12074
12074
12074
11003
11003
11003
11003

13603
13565
28077
26374
26318
26260
18005
11445
11445
11443
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13603
13565
28077
26374
26318
26260
18005
11445
11445
11443
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13603
13565
28077
26374
26318
26260
18005
11445
11445
11443
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13603
13565
28077
26374
26318
26260
18005
11445
11445
11443
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13603
13565
28077
26374
26318
26260
18005
11445
11445
11443
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

13603
13565
28077
26374
26318
26260
18005
11445
11445
11443
8650
8650
8650
8579
8564
8413
6733
6733
6733
6733
6733
6733
6290
6290
6290
6290

GRID
Ik" : 26243.19A

GRID

CAB:rmg
10 Meters
#/PH: 1
HT VCB
50
51

DGPNL_IC1

GEN

CAB:TRHVS
15 Meters
#/PH: 1
TR
11000/433 V
Z%: 6.25
1600 kVA

DG2

BUSDUCT
10 Meters
#/PH: 1

CAB:DG2
50 Meters
#/PH: 2
DGPNL_IC2

MPNL_IC

OG3

OG1
CAB:DG_SSB12
50 Meters
#/PH: 2

CAB:OG1
28 Meters
#/PH: 6

SSB1_IC2

SSB1_IC1

SSB1 LHS
Ik" : 26553.51A
SSB1_OG1

APFC_IC
SSB1 RHS
Ik" : 26508.72A

STAB_IC
STAB2
Z%: 4
600 kVA

MLSB_IC

CAB:STAB1
20 Meters
#/PH: 6

102

96

48

108

114

120

PHS_OG5

PHS_OG6

SSB2_OG4

178

PHS_OG4

SSB2_OG3
BBT3
Ik" : 10085.65A

87

168

PHS_OG3

SSB2_OG2

CAB:BBT SP
CAB:BBT2
CAB:BBT1
CAB:BBT3
50 Meters
50 Meters
50 Meters
50 Meters
#/PH: 1
#/PH: 1
#/PH: 1BBT2
#/PH: 1
BBTSP
Ik" : 10085.65A
Ik" : 9805.39A

86

PHS_OG2

81

PHS_OG1

76

PH_PNL_LHS
Ik" : 9999.53A

MLSB_OG2

71

PH_IC

MLSB_OG1

165
MLSB
Ik" : 19070.64A

SSB2
Ik" : 13390.27A

APFC
Ik" : 26595.11A

CAB:SSB1_OG3
25 Meters
#/PH: 4

CAB:MLSB
15 Meters
#/PH: 1

STAB1
Z%: 4
1000 kVA

CAB:OG2
15 Meters
#/PH: 1

SSB1_OG3

SSB1_OG2_F

CAB:SSB1_OG1
14 Meters
#/PH: 6

SSB2_OG1

SSB1_IC3

SSB1_OG2

BBT1
Ik" : 10085.65A

OG2

CAB:OG4
9 Meters
#/PH: 2
SSB1_BC

CAB:DG_SSB11
50 Meters
#/PH: 2

SSB2_IC

OG4

DGPNL_OG2

DGPNL_OG1

66

M_PNL
Ik" : 27834.54A

DGPNL RHS

DGPNL LHS

CAB:LSB1
50 Meters CAB:LSB2
#/PH: 1
50 Meters
#/PH: 1
LSB1
Ik" : 12723A

CAB:CAN
50 Meters
#/PH: 1

LSB2 CANTEEN
Ik" : 7830.66A
Ik" : 12723A

CAB:SSB5
50 Meters
#/PH: 1
SSB5
Ik" : 7830.66A

CAB:PAINT
50 Meters
#/PH: 1

PAINTING
Ik" : 7830.66A

CAB:APFC1
50 Meters
#/PH: 1

APFC1
Ik" : 7830.66A

CAB:SSB6
50 Meters
#/PH: 1

SSB6
Ik" : 7830.66A

CAB:SSB1
50 Meters
#/PH: 1

SSB1
Ik" : 7830.66A

PH_BC

CAB:DG1
50 Meters
#/PH: 2

DGPNL_BC

GEN

DG1

VCB PNL
Ik" : 26113.29A

126

127

PH_PNL_RHS
Ik" : 9981.87A
134

SSB61

CAB:SSB61
50 Meters
#/PH: 1
SSB61
Ik" : 7309.46A

140

146

SSB3

SSB21

CAB:SSB21
50 Meters
#/PH: 1
SSB21
Ik" : 7309.46A

CAB:SSB3
50 Meters
#/PH: 1

SSB3
Ik" : 7309.46A

152

NEWOFFICE

CAB:NO
50 Meters
#/PH: 1
NEWOFFICE
Ik" : 7309.46A

REV. DATE

ECO#

DESCRIPTION

DWN APP

TH IS DRAWING IS PROPRIE TARY INFORM AT ION

You r C omp any Na me


Add ress
Add ress
Ph one a nd web site

Electrical One-Line DiagramShort Circuit Currents-Source 500 MVA SEC


DRAWN BY/DATE:

DWG No .:

ENG. APP./DATE:
MFG. APP./DATE:
SCALE:

PAR T No.:
DWG SIZE:

RE V.

Short Circuit Detailed Report for source Fault 500 MVA Sec

(GRID FEED)

3P Fault - IEC60909 Method at the Following Times


Bus Description
Pre fault Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts current in current in current in current in current in current in current in
A
Amps
Amps
Amps
Amps
Amps
Amps
GRID
VCB PNL
M_PNL
APFC
SSB1 LHS
SSB1 RHS
MLSB
SSB2
LSB1
LSB2
BBT1
BBT2
BBT3
PH_PNL_LHS
PH_PNL_RHS
BBTSP
APFC1
CANTEEN
PAINTING
SSB1
SSB5
SSB6
NEWOFFICE
SSB21
SSB3
SSB61

11000
11000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

74227
73860
70855
66157
65977
65350
40582
25396
24328
24328
18711
18711
18711
18222
18172
17904
14014
14014
14014
14014
14014
14014
12764
12764
12764
12764

26243
26113
27835
26595
26554
26509
19071
13390
12723
12723
10086
10086
10086
10000
9982
9805
7831
7831
7831
7831
7831
7831
7309
7309
7309
7309

26243
26113
27835
26595
26554
26509
19071
13390
12723
12723
10086
10086
10086
10000
9982
9805
7831
7831
7831
7831
7831
7831
7309
7309
7309
7309

26243
26113
27835
26595
26554
26509
19071
13390
12723
12723
10086
10086
10086
10000
9982
9805
7831
7831
7831
7831
7831
7831
7309
7309
7309
7309

26243
26113
27835
26595
26554
26509
19071
13390
12723
12723
10086
10086
10086
10000
9982
9805
7831
7831
7831
7831
7831
7831
7309
7309
7309
7309

26243
26113
27835
26595
26554
26509
19071
13390
12723
12723
10086
10086
10086
10000
9982
9805
7831
7831
7831
7831
7831
7831
7309
7309
7309
7309

26243
26113
27835
26595
26554
26509
19071
13390
12723
12723
10086
10086
10086
10000
9982
9805
7831
7831
7831
7831
7831
7831
7309
7309
7309
7309

Short Circuit Detailed Report for source Fault 500 MVA Sec

(GRID FEED)

LL Fault - IEC60909 Method at the Following Times

Bus Description

GRID
VCB PNL
M_PNL
APFC
SSB1 LHS
SSB1 RHS
MLSB
SSB2
LSB1
LSB2
BBT1
BBT2
BBT3
PH_PNL_LHS
PH_PNL_RHS
BBTSP
APFC1
CANTEEN
PAINTING
SSB1
SSB5
SSB6
NEWOFFICE
SSB21
SSB3
SSB61

Pre fault Instantan 1/2 cycle 1 cycle


3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts current in current in current in current in current in current in current in
A
Amps
Amps
Amps
Amps
Amps
Amps
11000
11000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

74227
73803
61720
57555
57398
56850
35242
22031
21103
21103
16225
16225
16225
15800
15757
15524
12148
12148
12148
12148
12148
12148
11064
11064
11064
11064

26243
26093
24246
23159
23123
23084
16578
11625
11044
11044
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

26243
26093
24246
23159
23123
23084
16578
11625
11044
11044
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

26243
26093
24246
23159
23123
23084
16578
11625
11044
11044
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

26243
26093
24246
23159
23123
23084
16578
11625
11044
11044
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

26243
26093
24246
23159
23123
23084
16578
11625
11044
11044
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

26243
26093
24246
23159
23123
23084
16578
11625
11044
11044
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

Short Circuit Detailed Report for source Fault 500 MVA Sec

(GRID FEED)

LG Fault - IEC60909 Method at the Following Times

Bus Description

GRID
VCB PNL
M_PNL
APFC
SSB1 LHS
SSB1 RHS
MLSB
LSB1
LSB2
APFC1
BBT1
BBT2
BBT3
BBTSP
CANTEEN
NEWOFFICE
PAINTING
PH_PNL_LHS
PH_PNL_RHS
SSB1
SSB2
SSB21
SSB3
SSB5
SSB6
SSB61

Pre fault Instantan 1/2 cycle 1 cycle


3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts current in current in current in current in current in current in current in
A
Amps
Amps
Amps
Amps
Amps
Amps
11000
11000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

74227
73618
65343
56259
56004
55543
33325
17389
17389
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

26243
26028
27023
24552
24472
24420
16139
9106
9106
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

26243
26028
27023
24552
24472
24420
16139
9106
9106
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

26243
26028
27023
24552
24472
24420
16139
9106
9106
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

26243
26028
27023
24552
24472
24420
16139
9106
9106
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

26243
26028
27023
24552
24472
24420
16139
9106
9106
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

26243
26028
27023
24552
24472
24420
16139
9106
9106
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Short Circuit Detailed Report for source Fault 500 MVA Sec

(GRID FEED)

LLG Fault - IEC60909 Method at the Following Times

Bus Description

GRID
VCB PNL
M_PNL
APFC
SSB1 LHS
SSB1 RHS
MLSB
LSB1
LSB2
SSB2
BBT1
BBT2
BBT3
PH_PNL_LHS
PH_PNL_RHS
BBTSP
APFC1
CANTEEN
PAINTING
SSB1
SSB5
SSB6
NEWOFFICE
SSB21
SSB3
SSB61

Pre fault Instantan 1/2 cycle 1 cycle


3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts current in current in current in current in current in current in current in
A
Amps
Amps
Amps
Amps
Amps
Amps
11000
11000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

76952
76522
73185
65370
65158
64543
38703
22153
22153
22031
16225
16225
16225
15800
15757
15524
12148
12148
12148
12148
12148
12148
11064
11064
11064
11064

27206
27055
29009
27201
27142
27077
18382
11593
11593
11625
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

27206
27055
29009
27201
27142
27077
18382
11593
11593
11625
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

27206
27055
29009
27201
27142
27077
18382
11593
11593
11625
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

27206
27055
29009
27201
27142
27077
18382
11593
11593
11625
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

27206
27055
29009
27201
27142
27077
18382
11593
11593
11625
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

27206
27055
29009
27201
27142
27077
18382
11593
11593
11625
8750
8750
8750
8675
8659
8506
6790
6790
6790
6790
6790
6790
6337
6337
6337
6337

Sample WorkPermit
TRANSFORMER
SETTING
CALCULATIONS

Setting Calculation for Transformers 1.6 MVA TR

433 V

11 kV
2500A

50/5 A
1600 kVA
Transformer capacity

PT

1600

kVA

Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus at max source fault
Fault Current at 11 kV Bus at min source fault
min Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Vp
Vs

11
0.433
50/5
10
2500/1
2500
6.25%

kV
kV

26113
13089
23365

Amps
Amps
Amps
Amps

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11 kV side
Minimum Setting proposed on HV side Ip
Curve
Transformer LV side current as per name plate
Relay drop off Ratio
LV Pick up Current

Isfl

CTRP
CTRS
Z

Transformer LV side CT Secondary Pick up Current


Relay setting for over current

83.98
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 83.98/0.95
97.24
9.72
2
2
Normal Inverse
2133.45
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x2133.45/0.95
2470.31
=2470/2500
0.988124211

Minimum Setting proposed on LV side Ip


Minimum Setting proposed on LV side ACB I>>

1
6

CABLE SCHEDULE
Branch Long Name
CAB:rmg
CAB:TRHVS
CAB:OG1
CAB:OG2
CAB:OG4
CAB:DG2
CAB:SSB1_OG3
CAB:PAINT
CAB:SSB1_OG1
CAB:BBT1
CAB:BBT2
CAB:BBT3
CAB:BBT SP
CAB:SSB5
CAB:CAN
CAB:APFC1
CAB:SSB6
CAB:SSB1
CAB:SSB61
CAB:SSB21
CAB:SSB3
CAB:NO
CAB:MLSB
CAB:LSB1
CAB:LSB2
CAB:DG1
CAB:STAB1
DGPNL
DGPNL

From Bus
GRID
VCB
MPNL_OG1
MPNL_OG2
MPNL_OG4
DG2
SSB1
PHPNL
SSB1
SSB2
SSB2
SSB2
SSB2
PHP
PHP
PHP
PHP
PHP
PHP
PHP
PHP
PHP
SSB1
MLSB
MLSB
DG2
SSB1
SSB1
SSB1

To Bus
VCB
TR
SSB_IC1
HARMONIC PNL
APFC PNL
DG PNL
STAB2
PAINTING
STAB1
BBT1
BBT2
BBT3
BBTSP
SSB5
CANTEEN
APFC1
SSB6
SSB1
SSB61
SSB21
SSB3
NEWOFFICE
MLSB
LSB1
LSB2
DG PNL
STAB1
193
198

Description
3C X 185 Sq.mm AL
3C X 185 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 185 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 185 Sq.mm AL
3.5C X 185 Sq.mm AL
3.5C X 185 Sq.mm AL
3.5C X 185 Sq.mm AL
3.5C X 185 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 300 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 400 Sq.mm AL
3.5C X 400 Sq.mm AL

Length
(MET)
10
15
28
15
9
50
25
50
14
50
50
50
50
50
50
50
50
50
50
50
50
50
15
50
50
50
20
50
50

NO OF RUNS
PER PH
1
1
6
1
2
2
4
1
6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
6
2
2

Cable Voltage
11000.00
11000.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00
415.00

FUSES DETAILS

REF
SSB2_OG1
SSB2_OG2
SSB2_OG3
SSB2_OG4

Interrupt Rating [kA]


50
50
50
50

MAKE
L&T
L&T
L&T
L&T

SIZE OF FUSE
LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3

AMP RATING
400
400
400
250

TYPE
Standard
Standard
Standard
Standard

PHS_OG1
PHS_OG2
PHS_OG3
PHS_OG4
PHS_OG5
PHS_OG6

50
50
50
50
50
50

L&T
L&T
L&T
L&T
L&T
L&T

LV HRC SIZE 1, 2 & 3


LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3

250
250
250
630
630
400

Standard
Standard
Standard
Standard
Standard
Standard

SSB61
SSB21
SSB3
NEWOFFICE

50
50
50
50

L&T
L&T
L&T
L&T

LV HRC SIZE 1, 2 & 3


LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3

100
100
100
100

Standard
Standard
Standard
Standard

MLSB_IC
MLSB_OG1
MLSB_OG2

50 L&T
50 L&T
50 L&T

LV HRC SIZE 1, 2 & 3


LV HRC SIZE 1, 2 & 3
LV HRC SIZE 1, 2 & 3

630
63
63

Standard
Standard
Standard

SSB1_OG2

50 L&T

LV HRC SIZE 1, 2 & 3

630

Standard

Sample WorkPermit
SETTING DETAILS
FOR PANELS

Setting Details for Panels


Location of
device

Device
description and
release

Sevice ID

Breaker
Set
Current In

OVERLOAD PROTECTION
SETTING
Long time Primary
RANGE IR=In Pick up
Current
X
Current
setting (I1)

time lag
setting in
sec 2.5
sec @6 Ir

Main LT Panel
IC
2500 A ACB
OG1
2000 A ACB
OG2
800 A ACB
OG3
800 A ACB
SSB1 Panel
SSB1_IC1
1600 A ACB
SSB1_IC2
800 A ACB
SSB1_IC3
800 A ACB
SSB1_OG1
1600 A ACB
SSB1_OG3
1250 A ACB
DG Panel
DGPNL_IC1
800 A ACB
DGPNL_IC2
800 A ACB
DGPNL_OG1 800 A ACB
DGPNL_OG2 800 A ACB
Power House Panel
PH PNL IC
1250 A ACB
SSB2 Panel
SSB2_IC
1600 A ACB

Phase Current Settings


Ground Current Settings
Short-time delayed short-circuit protection
Ground-fault protection
Setting
Short time
Primary
Setting
Short
Setting
Operati Primar Setting range
range Isd
Pick up
Current range for
time
range of the
ng
y
of the delay
= I1 ...
Current
delay
delay in operating current Current time tg in ms
Settint (Isd)
time tsd sec (Tsd)
current Ig setting
in ms
Ig
in ms

Delay
time tg
in ms

Incomer
Outgoing to SSB1
Outgoing Filter Panel
Outgoing to APFC

2500
2000
800
800

0.5-1.0 X In
0.5-1.0 X In
0.5-1.0 X In
0.5-1.0 X In

1
0.7
0.7
0.7

2500
1400
560
560

2.5
2.5
2.5
2.5

2-10 xIR
2-10 xIR
2-10 xIR
2-10 xIR

2.5
2.5
2.5
2.5

6250
3500
1400
1400

20-600
20-600
20-600
20-600

400
400
400
400

0.2-0.6
0.2-0.6
0.2-0.6
0.2-0.6

xIn
xIn
xIn
xIn

0.3
0.2
0.2
0.2

750
400
160
160

OFF-/100-400
OFF-/100-400
OFF-/100-400
OFF-/100-400

400
300
200
200

Incomer from Main Panel


Incomer from DG Panel
Incomer from DG Panel
Outgoing to1000 kVA Stablizer
Outgoing to 500 kVA Stablizer

1600
800
800
1600
1250

0.5-1.0 X In
0.5-1.0 X In
0.5-1.0 X In
0.5-1.0 X In
0.5-1.0 X In

1
0.9
0.9
0.95
0.65

1600
720
720
1520
812.5

2.5
2.5
2.5
2.5
2.5

2-10 xIR
2-10 xIR
2-10 xIR
2-10 xIR
2-10 xIR

2.5
2.5
2.5
2.5
2.5

4000
1800
1800
3800
2031

20-600
20-600
20-600
20-600
20-600

400
400
400
400
400

0.2-0.6
0.2-0.6
0.2-0.6
0.2-0.6
0.2-0.6

xIn
xIn
xIn
xIn
xIn

0.2
0.2
0.2
0.2
0.3

320
160
160
320
375

OFF-/100-400
OFF-/100-400
OFF-/100-400
OFF-/100-400
OFF-/100-400

200
200
200
300
200

800
800
800
800

0.5-1.0 X In
0.5-1.0 X In
0.5-1.0 X In
0.5-1.0 X In

0.9
0.7
0.9
0.9

720
560
720
720

2.5
2.5
2.5
2.5

2-10 xIR
2-10 xIR
2-10 xIR
2-10 xIR

2.5
2.5
2.5
2.5

1800
1400
1800
1800

20-600
20-600
20-600
20-600

400
400
400
400

0.2-0.6
0.2-0.6
0.2-0.6
0.2-0.6

xIn
xIn
xIn
xIn

0.2
0.2
0.2
0.2

160
160
160
160

OFF-/100-400
OFF-/100-400
OFF-/100-400
OFF-/100-400

200
200
200
200

Incomer from 500 kVA Stabilizer

1250 0.5-1.0 X In

0.6

750

2.5 2-10 xIR

2.5

1875 20-600

400 0.2-0.6 xIn

0.2

250 OFF-/100-400

200

Incoming from 1000 kVA Stablizer

1600 0.5-1.0 X In

0.9

1440

2.5 2-10 xIR

2.5

3600 20-600

400 0.2-0.6 xIn

0.2

320 OFF-/100-400

200

Incomer from DG1


Incomer from DG2
Outgoing to SSB1 LHS
Outgoing to SSB1 RHS

TIME CURRENT
CHARACTERSTIC
CURVES

10000
1000

MPNL_IC

100

SSB1_IC1
SSB1_OG1
SSB2_IC

Time in Seconds

10

BBT1_fuse

HT VCB

TR 1600.0 KVA
Transformer

.01

.1

.5

415 Volt Phase


1 - path1_BBT1

10

100
Current in Amperes X 100
Time-Current Characteristic Curves

1000

10000
05-01-2016
13:56:59
EMER_NEW_180416

ARC FLASH ENERGY


CALCULATIONS &
REPORT

ARC Flash Energy and PPE requirement


Bus Name

Protective Device Name

Bus kV

3P Bolted
Fault (kA)

Branch
Current
(kAmp)

3P Arcing
Trip Delay
Current (kA) Time (sec)

3P Fault
Duration
(sec)

Working
Distance
(cm)

3P Energy
(cal/cm2)

Required
IEEE 1584
PPE Class

APFC1
BBT1
BBT2
BBT3
BBTSP
CANTEEN
LSB1
LSB2
M_PNL
MLSB
NEWOFFICE
PAINTING
PH_PNL_LHS
PH_PNL_RHS
SSB1
SSB1 LHS
SSB1 RHS
SSB2
SSB21
SSB3
SSB5
SSB6
SSB61
DGPNL LHS
DGPNL RHS
VCB PNL

PH_IC
BBT1_fuse
BBT2 fuse
BBT3 FUSE
BBTSP_FUSE
CANTEEN FUSE
MLSB1 FUSE
MLSB2 FUSE
MPNL_IC
163
NEW OFFICE FUSE
PAINTING FUSE
PH_IC
PH_IC
PH_IC
SSB1_IC1
SSB1_IC1
SSB2_IC
SSB21FUSE
SSB3 FUSE
SSB5 FUSE
PH_IC
SSB61_FUSE
DGPNL_IC1
DGPNL_IC2
HT VCB

0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
11.000

7.75
10.97
10.97
10.97
10.65
7.75
12.50
12.50
26.68
18.55
7.25
7.75
9.87
9.85
7.75
25.51
25.47
14.95
7.25
7.25
7.75
7.75
7.25
7.31
5.92
13.09

7.75
10.97
10.97
10.97
10.65
7.75
12.50
12.50
26.68
18.55
7.25
7.75
9.87
9.85
7.75
25.51
25.47
14.95
7.25
7.25
7.75
7.75
7.25
7.31
5.92
13.09

4.662
5.223
5.450
5.450
5.103
3.963
6.821
6.821
12.475
7.937
4.417
3.963
5.650
5.643
4.662
12.037
12.022
7.863
4.417
4.417
3.963
4.662
4.417
4.448
3.871
12.646

0.150
0.248
0.162
0.200
0.033
0.084
0.010
0.010
0.450
0.356
0.010
0.104
0.150
0.150
0.150
0.450
0.450
0.450
0.010
0.010
0.084
0.150
0.010
0.150
0.150
1.116

61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
61.00
91.00

1.38
2.58
2.81
3.47
0.34
0.65
0.14
0.14
12.03
5.84
0.09
0.80
1.70
1.70
1.38
11.57
11.55
7.30
0.09
0.09
0.65
1.38
0.09
1.31
1.80
18.57

1
1
1
1
0
0
0
0
3
2
0
0
1
1
1
3
3
2
0
0
0
1
0
1
1
3

0.150
0.248
0.162
0.200
0.033
0.084
0.010
0.010
0.450
0.356
0.010
0.104
0.150
0.150
0.150
0.450
0.450
0.450
0.010
0.010
0.084
0.150
0.010
0.150
0.150
1.116

DETAILED ARC FLASH ENERGY,BOUNDRY CALCULATIONS

Bus Name

Protective Device Name Branch Name

LL Voltage 3P Bolted
(kV)
Fault
(Amp)

Branch
Current
(Amp)

3P Arcing
Current
(kA) at
100%

Controlling Trip Delay 3P Fault


Branch
Time (sec) Duration
Arcing
(sec)
Current (kA)
at 100%

Gap
3P Arc
(mm) Flash
Boundary
(cm) at
100%

Worki 3P Energy
ng
(cal/cm^2)
Distan at 100%
ce
(cm)

Required
IEEE 1584
PPE Class
(100%)

3P Arcing Controlling Trip Delay


Current
Branch
Time (sec)
(kA) at 85% Arcing
at 85%
Current
(kA) at 85%

3P Fault
Duration
at 85%
(sec)

3P Energy 3P Arc
(cal/cm^2) Flash
at 85%
Boundary
(cm) at
85%

Required
IEEE 1584
PPE Class
(85%)

Max
Required
Energy
IEEE 1584
(cal/cm^2) PPE Class
(Max)

Max 3P
Arc Flash
Boundary
(cm)

Max Trip Max 3P


Delay
Fault
Time (sec) Duration
(sec)

Limited
Approach
Distance
(cm)

Restricted
Approach
Distance
(cm)

Prohibited Bus Name


Approach
Distance
(cm)

APFC1
BBT1
BBT2
BBT3
BBTSP
CANTEEN
LSB1
LSB2
M_PNL
MLSB
NEWOFFICE
PAINTING
PH_PNL_LHS
PH_PNL_RHS
SSB1
SSB1 LHS
SSB1 RHS
SSB2
SSB21
SSB3
SSB5
SSB6
SSB61
VCB PNL

PH_IC
!#
BBT1_fuse
BBT2 fuse
BBT3 FUSE
BBTSP_FUSE
CANTEEN FUSE
MLSB1 FUSE
MLSB2 FUSE
MPNL_IC
163
NEW OFFICE FUSE
PAINTING FUSE
PH_IC
PH_IC
PH_IC
!#
SSB1_IC1
SSB1_IC1
SSB2_IC
SSB21FUSE
SSB3 FUSE
SSB5 FUSE
PH_IC
!#
SSB61_FUSE
HT VCB

0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
0.415
11.000

7754.5
10968.3
10968.3
10968.3
10652.0
7754.5
12504.0
12504.0
26680.0
18547.4
7246.9
7754.5
9871.6
9854.6
7754.5
25507.5
25467.4
14947.4
7246.9
7246.9
7754.5
7754.5
7246.9
13089.1

4.662
6.145
6.145
6.145
6.003
4.662
6.821
6.821
12.475
9.338
4.417
4.662
5.650
5.643
4.662
12.037
12.022
7.863
4.417
4.417
4.662
4.662
4.417
12.646

4.662
6.145
6.145
6.145
6.003
4.662
6.821
6.821
12.475
9.338
4.417
4.662
5.650
5.643
4.662
12.037
12.022
7.863
4.417
4.417
4.662
4.662
4.417
12.646

32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
153

61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
91

1
1
0
1
0
0
0
0
3
1
0
0
1
1
1
3
3
2
0
0
0
1
0
3

3.963
5.223
5.223
5.223
5.103
3.963
5.798
5.798
10.604
7.937
3.755
3.963
4.803
4.796
3.963
10.231
10.218
6.684
3.755
3.755
3.963
3.963
3.755
N/A

0.150
0.248
0.200
0.248
0.033
0.084
0.010
0.010
0.450
0.356
0.010
0.104
0.150
0.150
0.150
0.450
0.450
0.450
0.010
0.010
0.084
0.150
0.010
N/A

1.16
2.58
2.09
2.58
0.34
0.65
0.12
0.12
10.09
5.84
0.07
0.80
1.43
1.43
1.16
9.70
9.69
6.13
0.07
0.07
0.65
1.16
0.07
N/A

0
1
1
1
0
0
0
0
3
2
0
0
1
1
0
3
3
2
0
0
0
0
0
N/A

1.38
2.58
2.09
2.58
0.34
0.65
0.14
0.14
12.03
5.84
0.09
0.80
1.70
1.70
1.38
11.57
11.55
7.30
0.09
0.09
0.65
1.38
0.09
18.57

67.4
103.0
89.1
103.0
25.8
40.3
14.2
14.2
292.6
179.2
10.3
46.5
77.6
77.5
67.4
285.0
284.7
208.5
10.3
10.3
40.3
67.4
10.3
1527.0

0.150
0.248
0.200
0.248
0.033
0.084
0.010
0.010
0.450
0.356
0.010
0.104
0.150
0.150
0.150
0.450
0.450
0.450
0.010
0.010
0.084
0.150
0.010
1.116

106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
106.7
152.4

30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5
66.0

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
17.8

PH_IC
SSB2_OG1
SSB2_OG2
SSB2_OG3
SSB2_OG4
PHS_OG1
MLSB_OG1
MLSB_OG2
MPNL_IC
MLSB_IC
NEWOFFICE
PHS_OG3
PH_IC
PH_IC
PH_IC
SSB1_IC1
SSB1_IC1
SSB2_IC
SSB21
SSB3
PHS_OG2
PH_IC
SSB61
HT VCB

7754.5
10968.3
10968.3
10968.3
10652.0
7754.5
12504.0
12504.0
26680.0
18547.4
7246.9
7754.5
9871.6
9854.6
7754.5
25507.5
25467.4
14947.4
7246.9
7246.9
7754.5
7754.5
7246.9
13089.1

0.150
0.110
0.089
0.110
0.017
0.041
0.010
0.010
0.450
0.130
0.010
0.049
0.150
0.150
0.150
0.450
0.450
0.450
0.010
0.010
0.041
0.150
0.010
1.116

0.150
0.110
0.089
0.110
0.017
0.041
0.010
0.010
0.450
0.130
0.010
0.049
0.150
0.150
0.150
0.450
0.450
0.450
0.010
0.010
0.041
0.150
0.010
1.116

67.4
66.8
57.9
66.8
18.7
27.8
14.2
14.2
292.6
102.1
10.3
31.6
77.6
77.5
67.4
285.0
284.7
208.5
10.3
10.3
27.8
67.4
10.3
1527.0

1.38
1.36
1.11
1.36
0.21
0.38
0.14
0.14
12.03
2.55
0.09
0.45
1.70
1.70
1.38
11.57
11.55
7.30
0.09
0.09
0.38
1.38
0.09
18.57

3.963
5.223
5.223
5.223
5.103
3.963
5.798
5.798
10.604
7.937
3.755
3.963
4.803
4.796
3.963
10.231
10.218
6.684
3.755
3.755
3.963
3.963
3.755
N/A

0.150
0.248
0.200
0.248
0.033
0.084
0.010
0.010
0.450
0.356
0.010
0.104
0.150
0.150
0.150
0.450
0.450
0.450
0.010
0.010
0.084
0.150
0.010
N/A

59.8
103.0
89.1
103.0
25.8
40.3
12.6
12.6
259.7
179.2
9.1
46.5
68.9
68.8
59.8
252.9
252.7
185.1
9.1
9.1
40.3
59.8
9.1
N/A

1
1
1
1
0
0
0
0
3
2
0
0
1
1
1
3
3
2
0
0
0
1
0
3

0.150
0.248
0.200
0.248
0.033
0.084
0.010
0.010
0.450
0.356
0.010
0.104
0.150
0.150
0.150
0.450
0.450
0.450
0.010
0.010
0.084
0.150
0.010
1.116

APFC1
BBT1
BBT2
BBT3
BBTSP
CANTEEN
LSB1
LSB2
M_PNL
MLSB
NEWOFFICE
PAINTING
PH_PNL_LHS
PH_PNL_RHS
SSB1
SSB1 LHS
SSB1 RHS
SSB2
SSB21
SSB3
SSB5
SSB6
SSB61
VCB PNL

Sample WorkPermit

Labels

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 152.4, Restricted = 66.0, Prohibited = 17.8

Volts

11000.0

Max Short Circuit kA

13.1

PPE Based on 91 cm Working Distance


(Arc Flash boundary, PPE required within 1527.0 cm)

Clothing
Level

Suit
Hood

Glove
Class

Eye
Protection

Insulated
Tools
Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Non-melting AR
Hair/Beard Nets

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: VCB PNL
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.2

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 10.3 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB61
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.8

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 67.4 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB6
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.8

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 40.3 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB5
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.2

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 10.3 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB3
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.2

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 10.3 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB21
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

14.9

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 208.5 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB2
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

25.5

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 284.7 cm)

Clothing
Level

Suit
Hood

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB1 RHS
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

25.5

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 285.0 cm)

Clothing
Level

Suit
Hood

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB1 LHS
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.8

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 67.4 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: SSB1
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

9.9

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 77.5 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: PH_PNL_RHS
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

9.9

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 77.6 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: PH_PNL_LHS
May 01, 2016 15:00:38

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.8

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 46.5 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: PAINTING
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.2

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 10.3 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: NEWOFFICE
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

18.5

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 179.2 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: MLSB
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

26.7

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 292.6 cm)

Clothing
Level

Suit
Hood

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: M_PNL
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

12.5

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 14.2 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: LSB2
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

12.5

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 14.2 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: LSB1
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.8

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 40.3 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: CANTEEN
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

10.7

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 25.8 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: BBTSP
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

11.0

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 103.0 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: BBT3
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

11.0

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 89.1 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: BBT2
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

11.0

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 103.0 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: BBT1
May 01, 2016 15:00:37

Warning

Bus Electrical Shock and Arc Flash Hazard


Appropriate PPE Required

Shock Distances (cm) - Limited = 106.7, Restricted = 30.5, Prohibited = 2.5

Volts

415.0

Max Short Circuit kA

7.8

PPE Based on 61 cm Working Distance


(Arc Flash boundary, PPE required within 67.4 cm)

Clothing
Level

Face
Shield

Glove
Class

00

Eye
Protection

Insulated
Tools

Non-melting AR
Hair/Beard Nets

Required
Not Required

Not Allowed X

Project: EMER_NEW_180416

Arc Flash boundary at energy < 1.2 cal/cm^2


Equipment Name: APFC1
May 01, 2016 14:44:40

Sample WorkPermit
ENERGY PLOTS

Estimated Total Energy 3-Phase


Bus:VCB PNL,11000.0V, Bolted Short-circuit = 13089.107422A, 153 mm arc

100

Working Distance
PPE 3 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

500

1000

1500

2000

2500

3000

3500

4000

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB61,415.0V, Bolted Short-circuit = 7246.876465A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

5.0

10.0

15.0

20.0

25.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB6,415.0V, Bolted Short-circuit = 7754.501465A, 32 mm arc

100

Working Distance
PPE 1 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

20

40

60

80

100

120

140

160

180

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB5,415.0V, Bolted Short-circuit = 7754.501465A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB3,415.0V, Bolted Short-circuit = 7246.876465A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

5.0

10.0

15.0

20.0

25.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB21,415.0V, Bolted Short-circuit = 7246.876465A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

5.0

10.0

15.0

20.0

25.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB2,415.0V, Bolted Short-circuit = 14947.435547A, 32 mm arc

100

Working Distance
PPE 2 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

100

200

300

400

500

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB1 RHS,415.0V, Bolted Short-circuit = 25467.380859A, 32 mm arc

100

Working Distance
PPE 3 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

100

200

300

400

500

600

700

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB1 LHS,415.0V, Bolted Short-circuit = 25507.470703A, 32 mm arc

100

Working Distance
PPE 3 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

100

200

300

400

500

600

700

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:SSB1,415.0V, Bolted Short-circuit = 7754.501465A, 32 mm arc

100

Working Distance
PPE 1 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

20

40

60

80

100

120

140

160

180

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:PH_PNL_RHS,415.0V, Bolted Short-circuit = 9854.584961A, 32 mm arc

100

Working Distance
PPE 1 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

20

40

60

80

100

120

140

160

180

200

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:PH_PNL_LHS,415.0V, Bolted Short-circuit = 9871.598633A, 32 mm arc

100

Working Distance
PPE 1 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

20

40

60

80

100

120

140

160

180

200

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:PAINTING,415.0V, Bolted Short-circuit = 7754.501465A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:NEWOFFICE,415.0V, Bolted Short-circuit = 7246.876465A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

5.0

10.0

15.0

20.0

25.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:MLSB,415.0V, Bolted Short-circuit = 18547.365234A, 32 mm arc

100

Working Distance
PPE 2 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

50

100

150

200

250

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:M_PNL,415.0V, Bolted Short-circuit = 26680.019531A, 32 mm arc

100

Working Distance
PPE 3 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

100

200

300

400

500

600

700

800

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:LSB2,415.0V, Bolted Short-circuit = 12503.959961A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:LSB1,415.0V, Bolted Short-circuit = 12503.959961A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:CANTEEN,415.0V, Bolted Short-circuit = 7754.501465A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:BBTSP,415.0V, Bolted Short-circuit = 10651.997070A, 32 mm arc

100

Working Distance
PPE 0 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:BBT3,415.0V, Bolted Short-circuit = 10968.322266A, 32 mm arc

100

Working Distance
PPE 1 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

20

40

60

80

100

120

140

160

180

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:BBT2,415.0V, Bolted Short-circuit = 10968.322266A, 32 mm arc

100

Working Distance
PPE 1 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

20

40

60

80

100

120

140

160

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Estimated Total Energy 3-Phase


Bus:BBT1,415.0V, Bolted Short-circuit = 10968.322266A, 32 mm arc

100

Working Distance
PPE 1 Min Distance
>1.2 cal/ cm^2
<1.2 cal/ cm^2

)
2
^
m
c
/l
a
C
(
y
g
r
e
n
E

10.0

1.00

0.100
0

20

40

60

80

100

120

140

160

180

Distance from Arc Gap (cm)


0

10

20

30

40

50

Job File: EMER_NEW_180416

60

70

Date: 05/01/16

80

90

100

Sample WorkPermit
PPE ILLUSTRATIONS

Sample WorkPermit

ENERGIZED ELECTRICAL WORK PERMIT


Job/Work Order Number:
PART 1: TO BE COMPLETED BY THE REQUESTER
(1) Description of circuit / equipment / job location / bus name:
DB1

(2) Description of work to be done:

Work on energized parts, including voltage testing

(3) Reasons why the circuit / equipment cannot be de-energized or the work deferred until the next scheduled outage:

_________________________________________________

Requester / Title

______________________________________

Date

PART II: TO BE COMPLETED BY THE ELECTRICALLY QUALIFIED PERSONS DOING THE WORK:
Check
When
Complete
____
(1) Detailed job description procedure to be used in performing the above detailed work:

___________________________________________________________________________________________________________
___________________________________________________________________________________________________________
____
(2) Description of the Safe Work Practices to be employed:
___________________________________________________________________________________________________________
___________________________________________________________________________________________________________

Arc Flash Boundary

20.3 cm

Arc Flash Hazard

0.2 cal/cm^2

Limited Approach
304.8 cm
Restricted Approach
30.5 cm
Required PPE
0
Shock Hazard
0.415000 kV
Cotton underclothing plus FR shirt, pants, overalls or equivalent

Working Distance
Prohibited Approach
Glove Class

61.000000
cm
2.5 cm
00

(3) Means employed to restrict the access of unqualified persons from the work area:

____
___________________________________________________________________________________________________________
____
(4) Evidence of completion of a Job Briefing including discussion of any job-related hazards:
___________________________________________________________________________________________________________

(5) Do you agree the above described work can be done safely?

Yes

No (if no, return to requestor)

_________________________________________________

______________________________________

_________________________________________________

______________________________________

Electrically Qualified Person(s)

Electrically Qualified Person(s)

Date

Date

PART III: APPROVAL(S) TO PERFROM THE WORK WHILE ELECTRICALLY ENERGIZED


_________________________________________________

______________________________________

_________________________________________________

______________________________________

_________________________________________________

______________________________________

Maintenance / Engineering Manager


Safety Manager

General Manager

Manufacturing Manager

Electrically Knowledgeable Person


Date