REINFORCEMENT DETAILING OF BUILDING

Project Name : -

Address

Owner : -

Structure Engg. : -

Photograph : -

General Details : -

a ) Different Grade of Steel Rein. Used =

b) Grade of Concrete =
Beam & Slab -
Column -
Footing -

b ) Width to Depth Ratio more than 0.3

Yes No.

c ) Width of Member > 200

Yes No.
1 FLEXURAL MEMBERS
Beam No. 1 2 3 4 5
A) At least two bars throughout the member length both at top and bottom.
Yes
No.
Positive steel at a joint face at least equal to half the negative steel at that face.
B)

Yes
No.
Steel provided at each of the top and bottom face of the member at any section along its length
at least equal to one-fourth of the maximum negative moment steel provided at the face of
C)
either joint .

Yes
No.
The lap length shall be the greater of
D) (a) bar development length in tension, and
(b) 30 times the bar diameter.
Yes
No.
E) Lap splices not within a joint
Yes
No.
F) Lap splices not within a dist. Of 2d from support
Yes
No.
G) Lap splices not within a Querter dist of member
Yes
No.
H) Not more than 50 % Bar splice at one place
Yes
No.
I) 6 mm dia not stirrups
Yes
No.
J) Dia of stirupps not less than 8 mm for 5 m or more than 5 m length beam
Yes
No.
Spacing of stirrups within 2d dist. Less than
K)
(a) d/4, (b) 8 x Dia of long. Bar
Yes
No.
L) Spacing of stirrups at mid section is Less than d/2
Yes
No.
M) Spacing of stirrups not Less than 100 mm
Yes
No.
2 COLUMN
Column No. 1 2 3 4 5
A) Width of column not less than 200 mm
Yes
No.
B) Ratio of least lateral dim. To perpendicular is not less than 0.4
Yes
No.
C) Lap splice near to joint ?
Yes
No.
D) Spacing of Stirrups within splice is not greter than 150 mm
Yes
No.
E) Length of hook is more than 75 or 10 x Dia of bar
Yes
No.
F) Angle of hook is 135 Degree
Yes
No.
G) C/c Dist between longtudinal rein is not more than 300 mm
Yes
No.
H) Spacing of ties is not more than half of least lateral dimension
Yes
No.

I) Length of Confined Rein. (a) Larger lateral Dimension (b) 1/6 of Span © 450 mm

Yes
No.
J) Confining reinforcement shall extend at least 300 mm into the footing or mat.
Yes
No.
K) Confining reinforcement at beam column joint
Yes
No.