You are on page 1of 61

Introduction to Automatic UNITROL® 1000-15

Voltage Regulators UNITROL® 1000-40


© ABB Group - 1 -
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 2 -
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Modes of operation
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 3 -
11-Dec-08
The Duties of an Excitation System

 Provide variable DC current


with short time overload
capability
 Control terminal voltage with
suitable accuracy
 Ensure stable operation with
network and / or other
machines
 Keep machine within
permissible operating range
 Contribute to transient
stability subsequent to a fault.
E AVR
 Communicate with the power
plant control system
© ABB Group - 4 -
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 5 -
11-Dec-08
Positioning of UNITROL 1000 Family

Indirect excitation with


Static Excitation Systems
Complexity of performance
rotating machines

UNITROL® 5000

UNITROL® F

UNITROL® 1000
Family
Ifn [ADC]
© ABB Group - 6 -

40 800 >10‘000
Generator Power / Excitation current
11-Dec-08
UNITROL 1000 Family

UNITROL 1000-15

UNITROL 1000-PM40
© ABB Group - 7 -
11-Dec-08

UNITROL 1000-7
Application Range

UNITROL 1000 Family is


applicable for:

Synchronous Motors and


Synchronous Generators
up to approx. 50 MVA
© ABB Group - 8 -
11-Dec-08
The UNITROL 1000-15

 The first member of the


UNITROL 1000 Family
 Launched in the year 2000
 Field current 15 A
 More than 1000 pieces sold
till today

UNITROL 1000-15
© ABB Group - 9 -
11-Dec-08
The UNITROL 1000-40

UNITROL 1000-PM40 Power Module


 Used in conjunction with
UNITROL 1000-15 AVR
 Field current up to 40 A
 CAN Bus interface
 Mainly for retrofit CAN Bus .
market
UNITROL 1000-15 UNITROL 1000-PM40

UNITROL 1000-40
© ABB Group - 10 -
11-Dec-08
The UNITROL 1000-7

Prototypes 2Q04
 Single print design
 Field current 7 A (70°C
ambient)
 Without local display
 Suitable for harsh
environmental
conditions
 EN, ANSI norms
 CE, UL, CSA certified UNITROL 1000-7
© ABB Group - 11 -
11-Dec-08
Comparison table

UNITROL UNITROL UNITROL


1000-7 1000-15 1000-40
Excitation 7 A cont. 15 A cont. 40 A cont.
current 14 A ceiling 30 A ceiling 80 A ceiling
Digital I/O 4 in, 4 in/out 4 in, 4 in/out 4 in, 4 in/out
Analogue I/O 2 in, 1 out 3 in, 2 out 3 in, 2 out
Local display No Yes Yes
I/O Extension No Yes Yes
Mounting Inside the Cubicle Cubicle
Machine
© ABB Group - 12 -
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 13 -
11-Dec-08
UNITROL 1000-15 Block Diagram

Auxiliary supply U AUX for control electronics


Digital I/O L1 L2 L3
(+) (-)
Analog I/O

UN1000

Measurement
U NET ~/=

and control
interface
=
UM RS-232
AVR
I M2 RS-485
CAN
PWM
Power electronics
supply
IGBT U PWR
Ie - (+) L1

M E
E (-) L2
L3
+
© ABB Group - 14 -
11-Dec-08
UNITROL 1000-15 Technical Data (1)

 Large supply voltage range for the auxiliary power


9...250 V AC 3-phase
50...250 V AC 1-phase
18…300 V DC
 Power electronics supply 0…250 V AC/DC
 Excitation output 15 A DC cont. 30 A DC 10 sec
 3-phase or single phase stator voltage measurement
 Single phase current measurement (1 A)
 Single phase measurement of line voltage for
synchronisation
© ABB Group - 15 -
11-Dec-08
UNITROL 1000-15 Technical Data (2)

 4 digital inputs
 4 configurable digital inputs/outputs (convertible)
 3 configurable analog inputs
(can also be used as 2, 4 or 6 digital inputs)
 2 analog outputs
 RS-485 port for reactive load sharing application
(future Modbus)
 CAN Bus for controlling local extension modules
 RS-232 port for connecting a PC (CMT 1000)
© ABB Group - 16 -
11-Dec-08
© ABB Group - 17 -
11-Dec-08
UN1000-15 Mechanical Lay Out
© ABB Group - 18 -
11-Dec-08
UNITROL 1000-15 Terminal block
© ABB Group - 19 -
11-Dec-08
UN1000-PM40 Mechanical Lay Out
© ABB Group - 20 -
11-Dec-08
UNITROL 1000-PM40 Terminal block
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 21 -
11-Dec-08
PMG supplied

AVR

UN 1000

PMG SM E
© ABB Group - 22 -
11-Dec-08
Externally supplied

External Power Supply

AVR

UN 1000

SM E
© ABB Group - 23 -
11-Dec-08
Shunt supplied

AVR

UN 1000

SM E
© ABB Group - 24 -
11-Dec-08
Shunt supplied with AC boost

AVR

Boost for short


circuit support
UN 1000

boost

SM E
© ABB Group - 25 -
11-Dec-08
Shunt supplied with DC boost

AVR
Boost for short
circuit support
UN 1000

Station battery boost

SM E
© ABB Group - 26 -
11-Dec-08
DC-Exciter supplied

Retrofitting systems with DC Exciter machines

AVR

UN 1000

start

SM =
© ABB Group - 27 -

-
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 28 -
11-Dec-08
Software Functions for Start-up

 Soft start
 Field Flashing Off
 Voltage Relay function
 Automatic Synchronizing (optional) more info
© ABB Group - 29 -
11-Dec-08
Basic operation modes

 Voltage control mode with PID control algorithm


 Power factor controller with PID control algorithm
 Reactive power (Var) controller with PID control algorithm
 Excitation current controller (manual control) with PI
control algorithm

Bump-less change over between all operation modes

Illustration: PF/Var
© ABB Group - 30 -
11-Dec-08
Software functions for on-line operation

 Reactive current droop for parallel operation


 Analogue input for superimposed voltage regulation
 Voltage Droop Compensation (VDC) mode in island
operation more info
© ABB Group - 31 -
11-Dec-08
Limiters

 V/Hz limiter
 Minimum excitation current limiter
 Underexcited reactive current limiter as a function of
active power (P/Q)
 Three step delayed maximum excitation current limiter
 Machine voltage min/max limiters

“Limit Active” indications are provided


© ABB Group - 32 -

Power chart
11-Dec-08
Monitoring and Protective functions

 Software alarm function (Watchdog)


 Under voltage detection to activate external current
boost for short circuit support
 Rotating Diode Monitoring (optional)
 Channel monitoring (for redundant systems) more info
© ABB Group - 33 -
11-Dec-08
Software Functions for commissioning

 Open loop control of output voltage for test purposes


 Built-in step test function for regulator tuning, together
with CMT 1000 commissioning software
© ABB Group - 34 -
11-Dec-08
Future Software Functions

To be implemented:
 Power System Stabilizer (PSS)
 Dual channel system using CAN Bus
 Data / Event logger
© ABB Group - 35 -
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 36 -
11-Dec-08
Human Machine Interface (HMI) Local Panel
UNITROL 1000-15

 Actual value indication


 Setting of parameters
 Configuration of digital and
analog I/O’s
© ABB Group - 37 -
11-Dec-08
CMT 1000 Software ...
... a user friendly tool for commissioning and maintenance
of UNITROL 1000 Family
 Actual value measurements
 Parameter settings
 Status indications
 Power chart
 Oscilloscope
 Synchronoscope
 Parameter files
 Windows 98, NT,
2000 and XP compatible
© ABB Group - 38 -
11-Dec-08
CMT 1000 Software – Device Configurator

 I/O Configuration
 System Data
© ABB Group - 39 -
11-Dec-08
CMT 1000 Software - Oscilloscope

 Trending
20 channels
 50 ms resolution
 File save in
numerical form
 Cursor
measurements
 Bitmap export
© ABB Group - 40 -
11-Dec-08
CMT 1000 Software – Other features

 Synchronoscope
 Power Chart
 Measurements
© ABB Group - 41 -
11-Dec-08
Future Communication Functions

To be implemented:
 Modbus communication
 Digital/Analogue I/O Extension over CAN Bus
 Enhanced CMT 1000
© ABB Group - 42 -
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 43 -
11-Dec-08
AVR System

What components are needed around the AVR for safe and
reliable operation?
 Power circuits
 Excitation breaker
 Over current protection
 Field flashing / boosting circuit (shunt supply only)
 Interposing supply transformer
 Auxiliary (electronics) supply
 Signals
 Galvanic isolation for I/O signals (relays, transducers)
© ABB Group - 44 -
11-Dec-08
Standard Cubicle with UNITROL 1000-15

 Pre-engineered
solution for end
users
 Configuration by
Internet tool
© ABB Group - 45 -
11-Dec-08
OEM Plate with UNITROL 1000-15

AVR system optimized for


 OEM specific solution
 End user specific
solution for repeat
projects
© ABB Group - 46 -
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 47 -
11-Dec-08
System Configurator in the Internet

 Requirements from the customer


 System engineering made by configurator
 Output:
 System description with a single line diagram
 Electrical schematics
 Layout drawing
 Parameter file for UNITROL 1000
 Material list
 Pricing
www.abb.com/unitrol
Look for “UNITROL 1000 Configurator”
© ABB Group - 48 -
11-Dec-08
E-Learning

 Interactive training course


 Excitation basics
 UNITROL 1000 connections, operation, panel, etc.
 CMT 1000 software
 Commissioning

 Available on a CD-ROM
© ABB Group - 49 -
11-Dec-08
Content

 Refresher AVR
 Introduction to UNITROL 1000 Family
 Block diagram, technical data
 Supply modes
 Software functions
 Communication, Interface
 AVR System
 E-Support
 UNITROL 1000 sales
© ABB Group - 50 -
11-Dec-08
Ordering information

UNITROL 1000-15 (version 4)


 Standard unit: 3BHE014557R0003
 With Synchronising: 3BHE014557R0004
 With RDM: 3BHE014557R0005
 With Sync & RDM: 3BHE014557R0006
Scope of delivery:
 CD-ROM with CMT 1000 software
 RS-232 cable
 User’s Manual

Power Unit UNITROL 1000-PM40


 Standard: 3BHE015411R0001
© ABB Group - 51 -
11-Dec-08
UNITROL 1000-15 Facts and Figures

Delivery times:
Module: 2 weeks
Standard system: 6 weeks
Custom system: 3 months

Sold: 2000 24 Units


2001 215 Units
2002 352 Units
2003 336 Units
© ABB Group - 52 -
11-Dec-08
Conclusion

 Proven technology  Decades of experience

 Compact product  Extensive software

 Low engineering cost  System configurator

 Low commissioning costs  CMT 1000, E-Learning

 High availability  World-wide support 24 h/day


© ABB Group - 53 -
11-Dec-08
Thank You for
Your attention
© ABB Group - 54 -
11-Dec-08
PF and Var Control Modes

POWER FACTOR Control


REACTIVE POWER Control
+P [MW]

Cos φ = 0.8 +P [MW]

-Q +Q [MVAR]

-Q +Q [MVAR]

Q = 0.2 p.u
-P
© ABB Group - 56 -
11-Dec-08
Power Chart with operational limits

Max. field current limiter


Min. field current limiter P
Under excitation P,Q limiter

-Q 1/Xd +Q
© ABB Group - 57 -
11-Dec-08
VDC - Voltage Droop Compensation

 Reactive power is shared equally between parallel


generators, without any drop in voltage level
 RS-485 bus communication between AVRs

Load A Load B

U = 100 %
RS-485

AVR 1 AVR 2 AVR 3 AVR 4


SM SM SM SM
© ABB Group - 58 -
11-Dec-08
VDC - Voltage Droop Compensation

 Reactive power is shared equally between parallel


generators, without any drop in voltage level
 RS-485 bus communication between AVRs
 Possible to divide into separate island networks
Load A Load B

U = 100 %
RS-485

AVR 1 AVR 2 AVR 3 AVR 4


SM SM SM SM
© ABB Group - 59 -

Prim. Net = 1
Prim. Net = 1 Din = Secondary Net
Sec. Net = 2
11-Dec-08
Synchronizing

 Voltage matching
 Speed control, analogue bias signal
 Breaker close command
 Synchrocheck UNET UNITROL 1000
Setpoint fSP = fNom
Command
CB
Fbias Sync
Speed Controller
Setpoint
UM
Regulator

T SM E
© ABB Group - 60 -
11-Dec-08
Redundant AVR system

 Auto follow
 redundant (stand by)
following actual values AVR

 Auto change over


 SW Alarm UN 1000

 MCB trip
AVR
 External command

UN 1000
Future: CAN Bus
© ABB Group - 61 -

G E
11-Dec-08

You might also like