ME-AGS wiring diagram –

For Lister Petter Generator (GS Series Diesel with remote start)

Input DC Voltage

12/24/48V
jumper - set to
Monitored battery
bank voltage
(on 12V setting)
These 5 adjustments
are not active when a
ME-RC Remote
Control with revision

1 2 3 4
1.5 or higher is used. Dip-switch
They are set using configuration
displays under the (2-Wire Maintain)

ON
AGS button on the
remote control.

≤ 30 amp
fuse Lister Petter Generator
(GS Series Diesel)
85 30
≤ 5 amp Customer Connections
fuse
Relay
Run

≤5
amp
Remote
fuse TP1 Start
86 87 87A Connection
Gen Run Signal
(input to pin 2 must Ground
be 10 to 40 DC volts
only while generator
12 volt
Inside Generator
is running);
can be the generator Inverter Ground
hour-meter or a battery 0123
12vdc pilot/run light
Gen
Gen
≤ 5 amp
Hour Meter Battery
fuse

Relay used is a SPDT 30 Amp, 12 VDC coil relays [shown in the non-energized (N.C.) position];
popular in automotive sound and security installations. Equivalent to Bosch #0 332 209 150. Mfg. #V23234-A1001-X036.

GEN AND POWER I/O RUN TIME HOURS

Relay 1 Sense B+ Another start attempt Stop


(terminals 5 & 6)
Delay

Relay 2 R2
(terminals 6 & 7)

Timing Information
Time to sense B+ signal 2 min. Time between start attempts 2 min.
R2 (Relay 2) Time 10 sec. Total Start attempts 4
Delay time 4 sec.
ME-AGS relay timing for 2-Wire Maintain Mode

Magnum Energy, Inc. provides this diagram to assist in the installation of the Auto-Generator Start controller.
Since the use of this diagram and the conditions or methods of installation, operation and use are beyond the
control of Magnum Energy, Inc., we do not assume responsibility and expressly disclaim liability for loss,
damage or expense arising out of the installation, operation and use of this unit.