The design experience covers all aspects from the incoming feed to the
factory, down to smallest transmitter, from turn key engineering to co-
engineering. This will make FLSmidth Automation the ideal partner both
in design of new production lines, as well as a partner in renovation of
existing production lines.
High Voltage
Switchgear
FLS/PCI
Many years experience in designing the electrical Power Power
transformer transformer
systems for a cement factory is needed in order to
ensure that all aspects are incorporated.
Incoming overhead line Incoming overhead line
M M M
I I I I I I I
> > Variable Variable > > > >
Variable >
speed speed UPS speed
M M M M M M M
drive drive drive
MCC MCC MCC MCC MCC
Motor Control Center (MCC)
I I I I I I
> > > > > >
M M M M M M
ACE
2
FLSmidth Automation Configurations
System Example 1:
This configuration drawing is from a
retrofit project with FLS ACE/SYS
software concept and Rockwell
Automation CLX PLC. The client at this
factory preferred Rockwell CLX PLC
but had recently installed a new cooler
with a Siemens S7 PLC. As the
FLSmidth Automation system is able to
interface with several PLC systems the
investment with S7 was not wasted.
System Example 2:
This configuration drawing is from a retrofit
project with FLS ACE/SYS software concept and
S7.
System Example 3:
This configuration drawing is from a
retrofit project with FLS ACE/SYS
software concept and Schneider
Quantum PLC.
3
Control room layout
The ACE/Woodware system comprise of a range of control room Features
furniture especially designed to modern process control • Independent of hardware
equipment such as computer displays, keyboards and printers • Pleasant “office look”
etc. • Cabinet maker quality
• Electrical adjustable working heights
The furniture is independent of the particular hardware and is • Ventilated cabinets for the PC
well constructed to integrate equipment of different sizes and • Concealed cable ducts
styles.
Center unit
The center unit consists of either a plate or a cabinet for
separating and supporting the electrical unit for adjusting
the height of the table.
4
Adaptable Control Engineering System
ACE/SYS Standard is an acronym for Adaptable Control Engineering
SYStem. It is a Programmable Logic Controller (PLC) programming
standard, defining control objects, data and program structures
needed to implement an efficient PLC-based process control system for
cement. The ACE/SYS standard is based on experience gained from
the successful engineering, programming and commissioning of more
than 300 control systems worldwide in cement factories.
Right click on the selected object will bring the menu down, a left click
on the faceplate line will open the faceplate.
5
Operator Station
In the ECS series, the ECS/OpStation software program for advanced Human-Machine-Interface (HMI) runs on Microsoft’s Windows
2000 operating system. Integrated in the ECS environment it offers a set of basic process-control functionalities with object-based
drivers to process controllers, process object database, object and event treatment, and data logging and trending.
ECS/OpStation’s object-based control structure enables access to all related supervision information and control commands with a
simple right-button mouse-click on any mimic object.
Faceplate for a
measuring
point
ECS
6
Operator station Trend and Alarm System
The trend and alarm handling in the ECS/Opstation system is a very powerful and easy to use tool both for the operator in the daily
operation of the plant, but also for the management and the maintenance department in the ongoing optimization of the production
and improvement of the run factor.
7
FLS Automation`s Engineering Station • Word and textual documents
ECS/SmartStation is an engineering and software tool • Photos of the object
integrating the process control with on-line view to PLC • Interlocking diagram
programs and key electrical documentation. The • Video and Audio documentation
ECS/SmartStation integrates software, program applications • Software for remote support
and support functions, and automatically finds the object in (via modem or Internet)
the database for:
ECS/SmartStation runs in a client/server environment using
• Live process HMI’s from ECS/OpStation standard PC’s with Microsoft’s Windows 2000 operating
• PLC programming software system. It is normally connected to the same plant network as
• CAD/CAM software and key electrical documentation the ECS/OpStation (NT) and the PLC’s.
8
High-level Control
FLSmidth Automation has long been acknowledged as being the pioneer of using Fuzzy Logic techniques for high level process
control. Around 200 systems have been installed worldwide since the ECS/ FuzzyExpert system was introduced in the late 70's.
Initially, the ECS/FuzzyExpert system was mainly used for kiln control but in the recent years a number of installations for mill
and cooler control has also been successfully commissioned bt FLSmidth Automation
Using high-level advanced process control, ECS/FuzzyExpert has resulted in the following benefits:
! Improved process stability through continuous, accurate and consistent process evaluation and control actions
! Rapid control and suppression of process upsets
! Lower operating costs through energy and maintenance savings
! Better, more uniform end-product quality
! Better utilization of human, capital and material resources
! Minimized emissions and environmental effects
! Release of operators from routine control actions
P2
Optimum operation point
The ECS/FuzzyExpert system aims at forcing the
Limits operation trends towards the optimum point.
Operator Control
ECS/FuzzyExpert
P1
ECS/FuzzyExpert-
CementMillOptimisation has
typically resulted in:
The operator interface of ECS/FuzzyExpert-CementMillOptimisation system is based on the proven concept of ECS/PlantControl HMI
enabling operators fast and easy access to control performance measures and trends, select/de-selct control loops, insert off line
quality measurements, process alarms and event diagnostic.
ECS
9
Cement Plant Simulation
ECS/CEMulator is an advanced cement process simulator that encompasses the extensive knowledge of F.L.Smidth in process
modelling and the long experience of FLSmidth Automation in process simulation.
With a vast amount of functions and features in ECS/CEMulator, the product aims at
A typical pay-time of an ECS/CEMulator investment can be justified by the savings in a production stop/waste of one shift in a middle
size cement plant of 3000tpd. Thus systematic training of operators in a cement production plant has a direct impact on, not only
plant safety and environment protection but also the overall plant economy.
10
Management Information System
FLSmidth Automation's Management Infomation System, MIS, solution is called ECS/PlantGuide. The purpose of the ECS/PlantGuide
system is to be a "Data Warehouse" and to integrate and archive all relevant plant data (process, chemical analysis and cement
dispatch data) into one single dedicated database.
Today's plants are typically supported by several computer systems linked together by a Local, Wide Area or Satellite Network. The
ECS/PlantGuide server makes process data available to any client that has a requirement, regardless of physical location.
! Enable a user-frindly access to the key plant data for management use
! Ensure consistency and reliability of data for management use
The main focus of a MIS system is data storage and general data availability. This means that important requirements to a MIS
database are storage capacity, flexibility, data availability and security. To meet these requirements the ECS/PlantGuide server database
has been developed based on the Microsoft SQL server database. The SQL server database has the flexibility to store both process and
lab data in a readily accessible format, and has the capacity to store large amount of data. The data archiving facility of SQL server
allows the user to store and retrieve data for a period of several years.
In addition, ECS/PlantGuide has the following features in order to fulfill the above mentioned objectives:
ECS
11
Kiln Shell Temperature Scanner
The ECS/CemScanner is a system for online measurement of the kiln shell
temperature. The principle of using infrared line scanners to measure the
kiln shell temperature was introduced by FLSmidth Automation in the
mid 80's and has since then proven to be the most effective tool.
The operator interface of the system is specially designed for easy access to all the functions and features used in daily
operations. The next two pages outline some of the software features in displaying both actual and historic kiln shell
temperature distribution as well as calculated brick and coating thickness.
A click on the history button from the toolbar turns the actual operation window into a history data
view. Historical data are saved in a set of user configurable short, medium and long term time spans.
ECS
12
Special Instruments
The FLSAutomation Advance Measurement Equipment (FLS/AME) contains several special instruments for instrumentation in the
cement industry. The instruments are: Induterm II, Folaphone and Gas analysis equipment.
Indutherm II
The FLSAutomation Indutherm II
system is designed for
temperature measurement in a
rotary kiln or cement mill. The
system provides useful
temperature information, for
better control of the kiln or
cement mill.
Features
• Online and continuous
temperature measurement
• Wireless transmission
• Simple system, easy to install
• Minimum maintenance
Folaphone
The FLSAutomation - Folaphone
system is designed for monitoring and
supervision of the material charge in a
ball mill. The system is developed for
applications in the cement industry.
Features
• Online and continues control of the
filling charge of material
• Minimum maintenance
• Simply system, easy installation
AME
13
Gas Analysis - Process optimization
FLSmidth Automation supplies gas analysis
equipment giving large production benefits,
lower emission, and a safer working
environment.
The Kiln Inlet equipment is the most important gas analysis system for
kiln process control. Through this analysis, the burning input and
production throughput are optimised
14
Gas Analysis -
Emission measurement and
Reporting
Traditionally Continuous Emission
Monitoring (CEM) on cement plants has
been limited to dust monitoring in order to
fulfill legislational demands set by the local
authorities.
D-R 290 AW
D-R 290 AW
DURAG
D-R 290 AW
06.4
STO MOD + --
full data integration and safety. Please see separate ECS detailst
for CEM reporting FLS Airloq
180
15
Power Concept Integration
The Power Concept Integration, PCI, is the FLSmidth Automations concept in power design. The concept covers the complete range of
electrical engineering from the incoming power to the factory to the smallest transmitter. FLSAutomation is specializing in cement, the
specialists are able to advise in new and retrofit projects either to replace or repair the system. FLSAutomation is hardware
independed, we are always able to design and supply the best and most economical solution.
Main substation
installation, an installation
at a new factory
3-winding
Distribution Distribution step-down Step-down Distribution Emergency Distribution Distribution Step-down Distribution
transf. transf. transf. transf. transf. Diesel Generator transf. transf. transf. transformer
G
Emergency
MV Slipring motor~~ ~~ Distribution MV Slipring motor ~~
MV Slipring motor Main Distribution
MDB MDB MDB Board MDB MDB Board (MDB)
M M M
I I I I I I I
> > Variable Variable > > > >
Variable >
speed speed UPS speed
M M M M M M M
drive drive drive
MCC MCC MCC MCC MCC
Motor Control Center (MCC)
I I I I I I
> > > > > >
M M M M M M
16
Motor Control Center (MCC)
Retrofit projects always require a decision whether to replace or repair the MCC. If the decision is to replace, always remember that
old cables, which have been subject to heat for many years can be damaged during disconnection, bending and reinstallation to the
new MCC. Normally the MCC can be upgrated with new intelligent interface and contactors for less than 50% of new a MCC.
17