You are on page 1of 6

Requirements for Single-Phase (1-Ø) Overhead Electric Service

Service Requirements

General The meter base, conduit, and any CT enclosure


must be adequately supported on a pole or on the
Contact Idaho Power before beginning work on outside of an outside structure wall so that it will
any new service. be readily accessible to Idaho Power.
All meter installations must meet current The meter cannot be covered or enclosed.
electrical code requirements and display the
proper electrical permit.
To help prevent damage, always call Dig-Line Meter Poles
for locations at least 2 business days before
digging, excavating, or driving a ground rod. All poles for mounting metering equipment are
provided, installed and owned by the Customer.
Dial 811 (Nationwide)
They must be tall enough to provide adequate
clearance above the finished grade or obstacles
Standard Service Voltages for the service conductor and drip loop and be in
good “climbable” condition.
Single Phase (1–Ø) 120/240 volts Each pole must have a minimum setting depth of
240/480 volts 10% of the length of the pole plus 2'-6".
120/208 volts (“network”) Additional bracing must be installed if the
tension of the service conductor will cause the
NOTE. Use the correct meter base for 1-Ø, pole to lean. A minimum Class 6 pole is required
120/208 volt “Network” applications. for permanent service.
See Definitions for Class 6 pole.
120/240 Volt 120/208 Volt
240/480 Volt "Network Meter"

Meter Height
Permanent meters must be 5'-6" (+/- 6") above
the finished grade or other accessible surface
1-Ø Self-contained Meter such as a deck or stairs, except as noted below.
Lug Arrangements
Multiple meter bases must be installed so that
the lowest meter is at least 4'-0" above the
Meter Location finished grade.

The meter and any associated equipment must


be suitably located so that the installation and
any future maintenance can be performed Multiple Meters
without undue inconvenience to the Customer or
Idaho Power. The meter must be located in a Each meter base or service disconnect that is
reasonably protected area so that the risk of part of an installation with more than one meter
inadvertent damage is minimized. is required to be plainly and permanently
marked with numbers or letters that corresponds
to the address, suite, office, or room it serves.

Requirements for 1-Ø Overhead Service, DFE 047 1-Ø


Page 1 of 6 Revised 06/08
Requirements for Single-Phase (1-Ø) Overhead Electric Service

Requirement for 480 Volt Meter Bases Propane Tanks. Any regulator, pressure relief
valve, or fill connection associated with a
The Customer must provide a means to propane tank or its delivery system must be at
de-energize and isolate any self-contained, 1–Ø least 10' away from any source of ignition,
or 3–Ø meter base over 250 volts line-to-line by which includes the electric meter, air
installing a EUSERC approved safety socket conditioning unit, etc. Keep the service cable
meter base with factory installed test bypass and conduit at least 3' away from the tank.
facilities. These meter bases must have an
NOTE. Propane tanks used for
interlocking device, a screw-type meter ring, and
dispensing must be at least 20' from any
be capable of being sealed by Idaho Power.
source of ignition.
Meter Base Guidelines
Refer to the Meter Base Identification Working Space. Keep the 36" x 36" area in
Guidelines located on www.idahopower.com. front of the meter clear of any equipment,
landscaping or other obstacles that could
interfere with access to the meter.
Clearances Meter base
& meter

Separation Between Electric and Gas. The


electric meter (or any electrical equipment) and
a gas meter must be separated by at least 36" 18" 18"
measured in any direction, except that the Keep shaded
horizontal separation shall not be less than 18". 36" area clear

Electric

18" min.

Keep the electric meter


out of the shaded area

in. Caution: Portable Generators


"m
36 Do not connect a portable generator to a
Gas
building’s electrical wiring unless a transfer
switch has been installed per NEC 702. Doing so
can allow the generator to feed back into the
36" min. Idaho Power electrical system and produce
unexpected high voltage on an otherwise
de-energized circuit, exposing workers to
unforeseeable hazards. The generator can also be
damaged if the electrical system becomes
energized while the generator is operating.
Connect appliances and tools directly to the
generator using the plug-ins provided.

Requirements for 1-Ø Overhead Service, DFE 047 1-Ø


Page 2 of 6 Revised 06/08
Requirements for Single-Phase (1-Ø) Overhead Electric Service

Heights for Overhead Services. Overhead Contact Idaho Power to determine the minimum
services must meet the minimum clearance conductor height requirement when the service
above the finished grade or other accessible wire must cross over areas that are not addressed
surface as shown below. Make sure the point of here (such as a road, highway, railroad track,
attachment is high enough to meet these canal, waterway, etc.).
requirements.

Point of
Conductor Attachment
Height
Drip Loop
Height

TABLE 1. MINIMUM CONDUCTOR HEIGHTS


Tx & Qx Conductors Use the heights shown in
up to 750 Volts Table 1 for All applications
Pedestrian Areas 15'-0" min.
EXCEPTION:
(no vehicles, horses, or trampolines)
Where the Building Limits
Residential Driveways 16'-0" min. the Drip Loop Height,
Areas with Truck Traffic 18'-6" min. use 10'-6" minimum for
(alleys, parking lots, etc.) Tx & Qx Conductors in
Pedestrian Only Areas
NOTES. (Up to 150V line-to-ground) 5'-6" (+/-6")
1. Height over pedestrian areas can be reduced
to 12'-0" for voltages up to 300V line-to-ground.
2. Add 6" to all heights for open wire conductors.

Finished grade or other accessible surface (such as a deck or stairs)

Services Over Building Roofs. A service Exception 1. A service conductor (or the drip
conductor or the drip loop that crosses over the loop) up to 600 volts line-to-line that crosses
roof of the building that it serves must meet the over a non-accessible roof must have a clearance
minimum conductor height over the roof shown of 8'-0" over the roof.
above in Table 1.
A roof may be considered non-accessible if it is
not accessible by a door, window, stairway, or
However, there are three exceptions where
fixed ladder.
reduced clearances are permitted:
Exception 2. A service conductor (or its drip
loop) up to 300 volts line-to-line that crosses
over a non-accessible roof with a slope of at
least 4 to 12 must have a clearance of 3'-0" over
the roof.

Requirements for 1-Ø Overhead Service, DFE 047 1-Ø


Page 3 of 6 Revised 06/08
Requirements for Single-Phase (1-Ø) Overhead Electric Service

Exception 3. A Tx or Qx service conductor (or The service mast must not be more than 4'-0"
its drip loop) up to 300 volts line-to-line that from the edge of the roof and only 6'-0" of the
crosses only the eave portion of the roof where it service conductor may be above the roof as
reaches the service mast must have an 18" shown below.
clearance over the roof.

18" (min.)
Top View of Roof

Service Mast

6' 4' (max.)


(m
ax
.)
4' (max.)

Requirements for 1-Ø Overhead Service, DFE 047 1-Ø


Page 4 of 6 Revised 06/08
Requirements for Single-Phase (1-Ø) Overhead Electric Service

1-Ø Overhead Service to a Building 1-Ø Overhead Service to a Pole

Leave 18" of
Leave 18" of conductor for
12"
conductor for the drip loop
the drip loop
Point of
attachment

Support bracket(s)
as needed Class 6 Pole
(See Definitions)

Meter base with ring


(ground to service
Support bracket(s) neutral per NEC)
as needed

Meter base with ring


(ground to service 5'-6"
neutral per NEC) (+/- 6")

5'-6"
(+/- 6")
Ground per
NEC

10% of pole Ground per


length + 2'-6" NEC

Idaho Power Provides


Meter Pole or building to attach the meter base
Service conductor Point of attachment
Connections at the drip loop Meter base
Conductor from the meter base to the drip loop
Ground electrode(s), ground wire and connections
to ground the meter base per NEC

NOTE. The service mast must be adequately supported so that it does not bend, lean,
or pull loose due to the tension of the service wire. Larger service wires or services
in high snow areas may require additional support.

Requirements for 1-Ø Overhead Service, DFE 047 1-Ø


Page 5 of 6 Revised 06/08
Requirements for Single-Phase (1-Ø) Overhead Electric Service

1-Ø Overhead CT Service 1-Ø Overhead CT Service to a Pole


to a Building or Structure
Idaho Power Customer-owned
service conductor conductor

Idaho Power
service conductor Support bracket(s)
as needed CTs

Customer-provided
1" EMT conduit Support bracket(s) Class 6 Pole
as needed (See Definitions)
CTs Idaho Power-owned
meter base is installed Idaho Power-owned
by the Customer and meter base is installed Customer-provided
Keep 6" between must be adequately 1" EMT conduit
by the Customer and
enclosures (including supported on a building attached to the pole
operating handles) wall or suitable structure

6"
Customer's
Service 5'-6" (+/- 6")
Disconnect
Ground per
5'-6" (+/- 6") NEC
Bond enclosures
together per NEC

Ground per
NEC 10% of pole
length + 2'-6"

Idaho Power Provides


Meter base Pole, structure, or building to attach the meter base
Meter and CTs Point of attachment
Metering wires Installation of the meter base
Service conductor 1" EMT conduit and entrance cap
Connections at the drip loop Conductor from the customer's service disconnect to the drip loop
Ground electrode(s), ground wire and connections to ground the
meter base per NEC

NOTES.
1) The service mast must be adequately supported so that it does not bend, lean, or pull loose
due to the tension of the service wire. Larger service wires or services in high snow areas may
require additional support.
2) There is an additional charge for CT metering when the customer’s main breaker or panel
size is 400 amps or less.

Requirements for 1-Ø Overhead Service, DFE 047 1-Ø


Page 6 of 6 Revised 06/08

You might also like