1.

- Consumo de aire en herramientas (Tomas de Servicio general):

Tools or equipment Size or type Air pressure (PSI)

Hoists 1 Ton 70 - 100


Blow guns 70 - 90
Bus or truck lifts 14, 000 - lb cap 70 - 90
Car lifts 8,000- lb cap 70 - 90
Car rockers 70 - 90
Drills, rotary 1/4" cap 70 - 90
Engine, cleaning 70 - 90
Grease Guns 70 - 90
Grinders 8"-wheel 70 - 90
Grinders 6"-wheel 70 - 90
Paint Sprayers Production gun 40 - 70
Spring oliers 40 - 70
Paint Sprayers Small hand 70 - 90
Riveters Small to large 70 - 90
Drills, piston 1/2" cap, 3" cap 70 - 90
Spark plug cleaners Reach 36- 45 70 - 90
Carving tools 70 - 90
Rotary sanders 70 - 90
Rotary sanders 70 - 90
Tire changers 70 - 90
Tire inflaters 70 - 90
Tire spreaders 70 - 90
Valve Grinders 70 - 90
Air hammers Light to heavy 70 - 90
Sand Hammers 70 - 90
Nut setters and runners 1/4" cap to 3/4" cap 70 - 90
Impact wrenches/screwdrivers Small to large 70 - 90
Air bushings Small to large 80 - 90
Pneumatic doors 40 - 90
File and burr tools 70 - 90
wood borers 1" - 2" 70 - 90
Rim strippers 100 - 120
Body polishers 70 - 90
Vaccum cleaners 100 - 120
Carbon removers 70 - 100
Sand blasters wide variation 90

* Condiciones estandar @ P = 14.696 PSI y T = 60°F


** Condiciones Normales @ P = 14.696 PSI y T = 273.15 K

2.- Consumo de aire en boquillas ("soplado"):


Diámetro Presión de Trabajo (Bar)
(mm) 2 3 4
0.5 8 10 12
1.0 25 35 45
1.5 60 75 95
2.0 105 145 180
2.5 175 225 280
3.0 230 370 400
(Consumo de aire comprimido en l/min)

3.- Consumo de aire en pistolas de pintado:

Presión de Trabajo (Bar)


Diámetro Spray Amplio y Plano
(mm) 2 3 4
0,5 100 115 135
0,8 110 130 155
1,0 125 150 175
1,2 140 165 185
1,5 160 180 200
1,8 175 200 220
2,0 185 210 235
2,5 210 230 260
3,0 230 250 290

Presión de Trabajo (Bar)


Diámetro Spray Circular
(mm) 2 3 4
0,5 75 90 105
0,8 85 100 120
1,0 95 115 135
1,2 110 125 150
1,5 120 140 155
(Consumo de aire comprimido en l/min)

4.- Factor de simultaneidad:

FACTOR DE SIMULTANEIDAD
Cantidad Factor
1 1
2 0.94
3 0.89
4 0.86
5 0.83
6 0.8
7 0.77
8 0.75
9 0.73
10 0.71
11 0.69
12 0.68
13 0.67
14 0.66
15 0.64
16 0.63

4.- Factor de uso (FU) :

Maquina ó Herramienta Factor


Maquinas rectificadoras 0.5
Maquinas de Pulir 0.3
Taladradoras 0.4
Terrajadoras 0.2
Atornilladoras 0.2
Aprietatuercas 0.2
Mordazas 0.1
Conceladores 0.4
Remachadores 0.1
Pistones 0.2
Chorros de arena 0.1
Pistolas de pintura 0.5
Cilindros de aire 0.2

5.- Factor por expansiones futuras:

Años Factor
1 1.1
2 1.2
3 1.3

6.- Margen por fúgas:

Críterio

Sistema correctamente diseñado e instalado :

Con buen mantenimiento


Intermedio :
Negligencia o poco mantenimiento :

7.- Factor por error :

FACTORES RANGO
ERROR 1.05
ERROR 1.1
ERROR 1.15
Factores de conversión
Units of Flow Sm^3/hr Nm^3/hr
Air consumed,
(scfm)* 1 Sm^3/hr 1 0.9461
@1.0135
1 1 Nm^3/hr 1.0569 1
BarA & 15oC
@1.0315
3 BarA & 0oC
10
6
6
20 - 90
5
4
50
20
20
4
2-7
10 - 35
50 - 110
5
10 - 15
50
30
1
1.5
1
2
30 - 40
25 - 40
20 - 30
4 - 10
4 - 10
2
20
40 - 80
6
2
6
3
6 - 400
ón de Trabajo (Bar)
5 6 7 8
15 18 22 28
55 65 75 85
110 130 150 170
220 250 290 330
325 380 430 480
465 540 710 790

ón de Trabajo (Bar)
ray Amplio y Plano
5 6 7 8
160 185 - -
180 225 - -
200 240 - -
210 250 - -
225 260 - -
250 280 - -
265 295 - -
300 340 - -
330 375 - -

ón de Trabajo (Bar)
Spray Circular
5 6 7 8
- - - -
- - - -
- - - -
- - - -
- - - -
Calculo teórico del "FU" :

donde:
Tu : tiempo d eutilizacion de la herramienta (min)
Tr : tiempo de referencia (min)
Fu : factor de utilizacion (%)

Fu = 100.0 %
Tu = 24 min
Tr = 24 min

Margen
1.05
1.10
1.05
1.15
1.30
1.- Registro de la demanda de consumo de aire comprimido:

Maquina, herramienta o
No equipo.
TAG Planta Area

Tanque de
Servicios
1 Bomba de diafragma Wilden M2 ----
Auxiliares
tratamiento quimico a
calderas
Tanque de
Servicios
2 Agitador neumatico ----
Auxiliares
tratamiento quimico a
calderas
Tanque de
Servicios
3 Transmisor de nivel neumatico ----
Auxiliares
recoleccion de
condensados

Taller soldadura
4 Toma de servicio gral. ----
de Mantto
Mantenimiento

Factor Consumo Unidad


Futuras Ampliaciones = 1.1 0.7 SCFM
Margen por Fugas = 1.05 0.8 SCFM
Factor por error = 1.05 0.8 SCFM
Total de diseño = 0.8 SCFM
1.4 S m3/hr
Presión de Consumo Factor de
Factor de Uso Tr (min) Tu (min) Cantidad
trabajo (PSI) unitario SCFM simultaneidad

0.0035 1440 5 1 90 30.0 0.77

0.0035 1440 5 1 91 72.8 1

0.0208 1440 30 1 20 4.8 0.86

0.0035 1440 5 2 100 68.7 0.53

Demanda =
Demanda Total
SCFM

0.0802

0.2529

0.0860

0.2527

0.7 SCFM
1.1 S m3/hr