You are on page 1of 55

Characteristics of

Electric Cables
and
Fault Localization

Shashidhar kasthala
Asst.professor
Indian Naval Academy,
Ezhimala, kerla
Shashidhar kasthala

Table of contents

Abstract

Chapter 1: Basics of power cable Engineering

1.1 Introduction

1.2 Underground System Designs

1.3 Cable conductors

1.4. Medium and High voltage power cables

Chapter 2: Materials in cables

2.1 Material used in cables

2.2 Cable Insulation

2.3 Paper Insulated cables

2.4 Polymer Insulated cables

2.5 Electrical stress distribution and calculation

2.6 Electrical shielding

2.7. Protection against fire

2.7.1 Levels of cable fire performance

2.7.2 Material Considerations

2.8. System Protection Devices

Chapter 3: Characteristics of Power cables

3.1 General basis of rating determination

3.2. Mathematical Treatment

3.3. Ambient and cable operating temparature

2
Shashidhar kasthala

3.3.1 Ambient Temparature

3.3.2 Maximum Cable operating Temparature

3.4. Effect of Installation condition on Cables

3.4.1 Thermal resistivity of soil

3.5. Calculation of losses

3.5.1 Conductor Resistance

3.5.2 Dielectric Losses

3.5.3 Sheath Loss Factor

3.5.4 Armor Loss Factor

3.6. Standard operating conditions & Rating Factors

3.6.1. Cables installed in air

3.6.2. Cables installed in ducts

Chapter 4: Mathemetical Analysis

4.1: The Cable and Insulator Parameters

4.2 Localization of cable faults

4.3 Example for fault localization

Conclusion

References

3
Shashidhar kasthala

List of Figures

Figure 1.1(a): Radial System


Figure 1.1(b): Looped System
Figure 1.2: Voltage distribution in the insulation with the cable shield removed.
Figure 1.3: Four core MV Cables
Figure 2.1: single core paper insulated lead sheath cable with PVC oversheath
Figure 2.2: 4 core, paper insulated lead sheath cable with STA and bituminous finish.
Figure 2.3: 3 –core screened PLIS cable with PVC oversheath
Figure 2.4: 3-core 19/33 kV SL cable
Figure 2.5: 3-core, circular stranded conductors, XLPE insulated, collective copper wire
screen,MDPE oversheathed, 6.35/11 kV cable
Figure 2.6: Paper insulated belted cable with top conductor at peak potential
Figure 3.1: Circuit diaram to represent heat generated in a 3-core metal sheathed cable
Figure 3.2: Heat flow for a circuit of single core cables installed in trefoil
Figure 3.3 (a): The ladder diagram for steady state computations on single core cable
Figure 3.3(b): The ladder diagram for steady state computations on three core cable
Figure 3.4(a) Diagrammatic representation of a cross bonded cable system, when cables
are not transposed
Figure 3.4(b) Diagrammatic representation of a cross bonded cable system when Cables
are transposed.
Figure 4.1 Typical High volatge cable
Figure 4.2 Faults in underfround cable
Figure 4.3: Ground fault of a single cable

4
Shashidhar kasthala

List of Tables

Table 2.1: Physical properties of metal used in cables


Table 2.2: Electrical properties of metals
Table 2.3: Permittivity, Dielectric constant, and SIC
Table 2.4: Insulation Thickness and stresses on polymeric cables
Table 2.5: Levels of fire performance for different types of cables
Table 3.1: Ambient air and ground temparature
Table 3.2: Conductor temparature limits for starnded cable types
Table 3.3: Soil thermal resistivities
Table 3.4: Material properties
Table 3.5: Values of skin and proximity effect
Table 3.6: Values of dielectric constant and loss factor

5
Shashidhar kasthala

Abstract

Underground cables are far expensive to install and maintain than overhead lines.

This is due to the large capital cost associated with cable installations making it necessary

that particular care be applied in selecting the proper cable type and size to serve the load

for the life of installation. In power cable engineering and operation it is extremely

important to know the maximum current carrying capacity in which a cable can tolerate

through out its life without risking deterioration or damage for which the cable and

insulation properties should be properly analyzed.

In this project in addition to the evaluation of cable and insulation properties, the

location of cable faults are estimated. Underground lines are susceptible to being

damaged by excavations and it being more expensive to repair and maintain, there is an

utmost importance to localize the cable fault. The mathematical analysis is carried out

using MATLAB Programming.

6
Shashidhar kasthala

Chapter 1

Basics of Power Cable Engineering

1.1. Introduction

Aesthetics is primarily the major reason for installing power cables underground,

providing open views of the landscape free of poles and wires. One could also argue that

underground lines are more reliable than overhead lines as they are not susceptible to

weather and tree caused outages, common to overhead power lines. This is particularly

true of temporary outages caused by wind, which represents approximately 80% of all

outages occurring on overhead systems.

However, underground lines are susceptible to being damaged by excavations.

The time required to repair a damaged underground line may be considerably longer than

an overhead line. Underground lines are typically ten times more expensive to install than

overhead lines. The ampacity, current carrying capacity, of an underground line is less

than an equivalent sized overhead line. Underground lines require a higher degree of

planning than overhead, because it is costly to add or change facilities in an existing

system. Underground cables do not have an infinite life, because the dielectric insulation

is subjected to aging; therefore, systems should be designed with future replacement or

repair as a consideration.

1.2 Underground System Designs

There are two types of underground systems

A. Radial —The transformers are served from a single source as in Figure 1.1(a).

7
Shashidhar kasthala

B. Looped—where the transformers are capable of being served from one of two

sources. During normal operation an open is located at one of the transformers,

usually the midpoint as in Figure 1.1(b).

Figure 1.1(a): Radial System

Figure 1.1(b): Looped System

A radial system has the lowest initial cost, because a looped system requires the

additional facilities to the second source. Outage restoration on a radial system requires

either a cable repair or replacement, whereas on a looped system, switching to the

alternate source is all that is required.

Underground cable can be directly buried in earth, which is the lowest initial cost,

allows splicing at the point of failure as a repair option and allows for maximum

ampacity. Cables may also be installed in conduit, which is an additional cost, requires

replacement of a complete section as the repair option, reduces the ampacity, because the

conduit wall and surrounding air are additional thermal resistances, but provides

protection to the cable.

8
Shashidhar kasthala

Underground power cables have three classifications.

1. Low voltage—limited to 2 kV. Primarily used as service cables

2. Medium voltage—2–11 kV. Primarily used to supply distribution transformers

3. High voltage—above 11 kV. Primarily used to supply substation transformers

1.3 Cable conductors

The conductors of cables is usually stranded, i.e, it consists of a number of strands

of wire of circular cross-section so that it may become flexible and carry more current. In

the stranded conductor each wire lies on helix the pitch of which is so adjusted that the

cross-section of the cable at right angle to its axis if practically circular. To avoid the

bending and deformation of the cable conductor under normal condition the alternate

layers have right and left spirals.

In general the total number of conductors N in a n layer cable is given as

N = 1+3n(n+1) … (1.1)

Note: It should be remembered that the central conductor is not counted as layer.

The overall diameter D of a stranded cable with n layers is given as

D = (1 + 2n)d …(1.2)

Where d is the diameter of single strand conductor

1.4. Medium and High voltage power cables

Medium and high voltage power cables, in addition to being insulated, are

shielded to contain and evenly distribute the electric field within the insulation.

9
Shashidhar kasthala

Since medium- and high-voltage cables are shielded, special methods are required

to connect them to devices or other cables. Since the insulation shield is conductive and

effectively grounded, it must be carefully removed a specific distance from the conductor

end, on the basis of the operating voltage. Once the insulation shield has been removed,

the electric field will no longer be contained within the insulation and the highest

electrical stress will be concentrated at the end of the insulation shield.

Figure 1.2: Voltage distribution in the insulation with the cable shield removed.

The general construction of cable is given below:

(a) Core: All cables have one central core or a number of cores of stranded copper

or aluminum conductors having highest conductivity.

(b) Insulation: The different insulations used to insulate the conductors are paper,

varnished, cambric and vulcanized bitumen for low voltages. But mostly

impregnated paper is used which is an excellent insulating material.

10
Shashidhar kasthala

(c) Metallic sheath: It is provided over the insulation so as to prevent the entry of

moisture into the insulating material. The metallic sheath is usually of lead or lead

alloy and in case of cables having copper as conductor sometimes aluminum is

used for providing metallic sheath.

Figure 1.3: Four core MV Cables

(d) Bedding: Over the metallic sheath comes the layer of bedding which consists of

paper tape compounded with a fibrous material to protect it from mechanical

injury from armoring. Also sometimes jute strands or Hessian tape is also used for

bedding.

(e) Armoring: Armoring is provided to avoid mechanical injury to the cable and it

consists of one or two layers of galvanized steel wires or two layers of steel tape.

(f) Serving: Over and above armoring a layer of fibrous material is again provided

which is similar to that of bedding but is called as serving.

11
Shashidhar kasthala

Chapter 2

Materials in cables

2.1 Material used in cables

Electrical properties

The table 2.1 indicates the electrical properties of the common metals used in

cables. Copper and aluminum are clearly the best choice for conductors till date for

various reasons. But in the recent days there has been some experience with sodium.

Table 2.1: Physical properties of metal used in cables

Physical Properties

The physical properties of metals used for conductors and sheaths are given in

Table 2.2. Except for the conductors of self supporting overhead cables, copper is

invariably used in the annealed condition. Aluminum sheaths are now extruded directly

onto cables and hence of soft temper but a small amount of work hardening occur during

corrugation.

12
Shashidhar kasthala

Table 2.2: Electrical properties of metals

2.2 Cable Insulation

Electrical conductors must be covered with some form of electrical insulation.

Cables are usually classified according to the type of insulation used. An ideal insulating

material for this purpose should have the following characteristics

1. It should have a high specific resistance

2. It should have high dielectric strength

3. It should be tough and tensile

4. It should not be hygroscopic i.e, it should not absorb moisture from air

5. It should be capable of standing high temperature without deterioration

6. It should be non-inflammable

7. It should be capable of withstanding high rupturing voltages.

The selection of a particular insulation to be used is dependent upon the purpose

for which the cable is required and qualities of the insulation to be aimed at. The

following are the chief types of insulation groups which can be used are tabulated along

with their dielectric constants:

13
Shashidhar kasthala

Material Range Typical


Butyl Rubber 3.0 – 4.5 3.2
PVC 3.4 – 10 6.0
Varnished Cambric 4.0 – 6.0 5.0
Impregnated Paper 3.3 – 3.7 3.5
Rubber-GRS or Natural 2.7 – 7.0 3.5
HMWPE 2.1 – 2.6 2.2
XLPE or TR-XLPE 2.1 – 2.6 2.3
XLPE, filled 3.5 – 6.0 4.5
EPR 2.5 – 3.5 3.2
Silicone Rubber 2.9 – 6.0 4.0
Table 2.3: Permittivity, Dielectric constant, and SIC

2.3 Paper Insulated cables

For distribution and transmission purposes impregnated paper insulated cables

have had an impressive record of reliability in the 20th century. Impregnated-paper

insulation provides the highest electrical breakdown strength, greatest reliability, and

longest life of any of the materials employed for the electrical insulation of conductors. It

will safely withstand higher operating temperatures than either rubber or varnished-

cambric insulations. On the other hand, it is not moisture-resistant and must always have

a covering which will protect the insulation from moisture, such as a lead sheath.

Paper-insulated cables are not so flexible and easy to handle as varnished-cambric

or rubber-insulated cables and require greater care and time for the making of splices.

They are available in the following types:

1. Solid-type insulation

2. Low-pressure gas-filled

3. Medium-pressure gas-filled

4. Low-pressure oil-filled

5. High-pressure oil-filled (pipe enclosed)

14
Shashidhar kasthala

6. High-pressure gas-filled (pipe enclosed)

7. High-pressure gas-filled (self-contained)

Construction

Paper cables in the 1-33 kV range are often referred to as ‘solid type’ as they are

designed to operate without internal or external pressure.

The insulation consists of helically applied paper tapes with a small gap between

turns. The registration of tapes in relation to each other is important to avoid successive

butt gaps in a radial direction.

Figure 2.1: single core paper insulated lead sheath cable with PVC over sheath

The conductors in multi core cables are usually sector shaped upto 11 kV and oval

for 33 kV. Solid aluminum is used extensively at 1 kV.

Belted construction

The cable design with a belt of insulation over the laid-up cores (Figure 2.2) is the

most economical in terms of total material cost. Such cables are nearly always used upto

6.6 kV and are most common type at 11 kV.

The spaces between the cable cores under the belt are filled with jute or paper.

Whereas the main insulation consists of paper tapes precisely applied, the filler insulation

has to be softer and less dense so as to compress into the space available and is weaker

15
Shashidhar kasthala

electrically. Stresses in the filler have to be limited to an acceptable level and therefore

belted cables are not generally used at voltages greater than 11 kV.

Figure 2.2: 4 cores, paper insulated lead sheath cable with STA and bituminous finish.

Screened cable

The dielectric strength of impregnated paper is weaker in the tangential direction

than in the radial direction and for cables at voltages above 11 kV it is necessary to

ensure that the electrical field is radial. As operating temperature were raised with 3-core

cable in the early 1920’s, non radial fields were the cause of extensive cable failures of

belted cables.

Screening consists of a thin metallic layer in contact with the metallic sheath

(Figure 2.3). As it carries only a small charging current, the thickness is unimportant but

it is necessary to have smooth contact with the insulation together with an ability to

withstand cable bending without damage.

Figure 2.3: 3–core screened PLIS cable with PVC over sheath

16
Shashidhar kasthala

At voltage levels where it is necessary to adopt insulation screening a screening

layer over the conductor is also required. This provides a smooth interface between the

wires of a stranded conductor and the insulation, thus limits discharge which may rise

due to electrical stress enhancement on the strands or voids at the interface. Conventional

practice is to apply two semiconductor carbon paper tapes over the conductors.

SL and SA screened cables

These are radial field single core metallic sheath cables with electrostatic type

acting as the insulation screen. SL and SA refer to sheathing with lead and aluminum

respectively. The three corrosion protected cores of SL cables are laid up together,

armored and finished with further corrosion protection (Figure 2. 4). SA cables are laid

up similarly with a PVC over sheath on each core but are not normally armored.

Figure 2.4: 3-core 19/33 kV SL cable

Although the amount of metal in the three individual sheaths is little different

from that in the cable having three core within a single sheath, the greater diameter

results in extra bedding and armoring material, thereby increasing the total cable cost.

However, jointing and terminating is more convenient.

17
Shashidhar kasthala

2.4 Polymer Insulated cables

The conductors of polymeric cables are generally circular with either stranded

copper, stranded aluminum or solid aluminum. For three-core cable in the range 3.6/6.0

kV to 8.7/15 kV some use has been made of both sector . shaped stranded and solid

conductors.

At 3.6/6kV and above, as a means of containing the electrical field within the

insulation, semi conducting screens are applied over the conductor and insulation. By

this means it is possible to eliminate any electrical discharges arising from air gaps

adjacent to the insulation. The coefficient of thermal expansion of polyethylene and

EPR is approximately ten times greater than that of either aluminum or copper, and

when the conductor is at its maximum operating temperature of 90°C a sufficiently large

gap is formed between the insulation and conductor to enable electrical discharges to

occur. This discharge site and any others which are formed around a conductor when

the cable is bent can be eliminated by applying a semi conducting layer over the

conductor. Similarly, any discharges arising from air gaps between laid-up cores can be

nullified by the use of a screen over the insulation.

The insulation thicknesses for the three insulants PE, XLPE and EPR are identical

at each voltage level above 3.6/6 kV; at this voltage EPR is thicker. The radial

thicknesses and electrical stresses are given in table 24.1. The outer semiconducting

screen is normally an extruded layer of semiconducting material. The extruded screen can

be a compatible material which bonds itself to the insulation or a compound, such as

ethylene-(vinyl acetate) (EVA), which is strippable from the insulation.

18
Shashidhar kasthala

In order for the strippable screen to have sufficient tear strength during removal

from the insulation, it is necessary for the thickness to be approximately 1.0mm, but it

may be thinner for harder materials. There are no such constraints with a bonded screen

and, because semiconducting materials are very expensive, thickness is kept to a

minimum, 0.5 mm being a typical figure.

Rated Voltage Insulation Thickness Electrical stress


(kV) PE (mm) EPR
XLPE (kV/mm) 185
Maximum mm2
Minimum
3.6/6 2.5 2.5 3.0 1.63 1.28
6/10 3.4 3.4 3.4 2.07 1.52
8.7/15 4.5 4.5 4.5 2.38 1.60
12/20 5.5 5.5 5.5 2.79 1.74
18/30 8.0 8.0 8.0 3.12 1.67
Table 2.4: Insulation Thickness and stresses on polymeric cables

The manufacture of single core cables is generally completed by the application

of a layer of copper wires to provide an earth envelope with a cross-sectional area of 16

to 50mm 2, depending upon the phase to earth fault level existing on the network. The

cable is finished with an extruded oversheath. For networks with a very much higher fault

level, or where increased mechanical protection is required, a copper tape is applied over

the semiconducting layer, followed by an extruded bedding, then a helical application of

aluminum armour wires and finally an extruded over sheath.

19
Shashidhar kasthala

Figure 2.5: 3-core, circular stranded conductors, XLPE insulated, collective copper wire screen,
MDPE oversheathed, 6.35/11 kV cable to IEC 502: (1) circular stranded conductor; (2) conductor
screen; (3) XLPE insulation; (4) extruded semiconducting screen; (5) non-hygroscopic fillers;
(6) semiconducting tapes; (7) copper wire screen; (8) synthetic tape; (9) MDPE oversheath

2.5 Electrical stress distribution and calculation

The current in the conductor, in the sheath and dielectric loss increases the

temperature of the cable, and this heat produced is dissipated to the soil and when the

temperature becomes constant at that instant the heat generated is equal to the heat

dissipated. The flux distribution in a.c belted cable insulation is complex and is shown

diagrammatically. The path of heat dissipation in through the dielectric, sheath, cable and

serving to the soil and is represented in figure 2.5. The electric field in case of single

cable is radial but in 3-phase cables the electric field is no longer radial.

20
Shashidhar kasthala

Figure 2.6: Paper insulated belted cable with top conductor at peak potential

The direction and intensity of the electric stress constantly changes of potential.

The field within the dielectric is rotating and during the different instants the parts of the

dielectric are subjected to tangential stress. The distorted nature of the electric stress will

have a component parallel to the layers of the insulation.

2.6 Electrical shielding

Electrical shielding is often necessary on power cable to confine the dielectric

field to the inside of the cable insulation so as to prevent damage from corona or

ionization. The shield usually consists of a thin (3-mil, or 0.076-mm) conducting tape of

copper or aluminum applied over the insulation of each conductor. The shielding tape

sometimes is perforated to reduce power losses due to eddy currents set up in the shield.

Sometimes semiconducting tapes consisting of specially treated fibrous tapes or braids

are used. These semiconducting tapes are frequently employed for the shielding of aerial

cable, since they adhere more closely to the insulation and thus tend to prevent corona.

21
Shashidhar kasthala

2.7. Protection against fire

The bedding materials used over the sheath make the cable inflammable, in

certain indoor works such as substations, factories etc. To avoid fire hazard, the wire

armoring is used directly over the sheath. Also the outer serving is omitted.

Sometimes asbestos tape or fire-resiting paint is provided over the armoring which

perfectly makes it fireproof.

2.7.1 Levels of Cable Fire Performance

A wide spectrum of fire performance is available from the many types of

cables on the market. This can range from cables at one extreme which have no

enhanced for properties, which are readily ignitable and burn with ease, to, at the

other extreme fire survival mineral insulated cables which contain no

combustible materials and which present no hazard in a fire. The choice of cable

for a given application depends on the degree of hazard which can be tolerated

and the level of performance required. The level of fire performance and the

potential hazard resulting from the combustion of a given cable depend on the

materials from which the cable is made and the cable construction. Table 2.4

summarizes the different levels of performance that can be achieved by different

categories of cables, along with typical areas of application.

S.No Cable Type Fire Application


Characteristics
Fire survival and
circuit integrity up For maintaining essential
to the melting point circuits such as emergency
Mineral insulated of copper lighting and fire alarms,
1. (copper circuits for the safe
sheathed) Negligible fire shutdown of critical
hazard processes, etc.

22
Shashidhar kasthala

Limited fire survival As above but circuit


Limited circuit
Flame retardant integrity maintained for
integrity,
2. shorter time periods.
low fire hazard, Low smoke and acid Reduced hazard from
zerohalogen gas emission cable combustion.
Limited circuit Limited fire survival
Flame retardant As above, but increased
integrity, reduced
3. hazard from smoke and
hazard (halogen Reduced acid gas
acid gas emission.
containing) emission
Reduced smoke
4. Low fire hazard, emission
Flame retardant, low For installation in areas
low, smoke, smoke retardant
Flame and acid gas where smoke and acid gas
In situations where reduced
grades possible
Reduced smoke levels of smoke and
Low emission and/or acid gas corrosive gases are needed,
PVC based
5. compared to
(or chlorinated Reduced flame ordinary PVC or
polymer) propagation possible chlorinated polymer based
cables.
Where flame retardance is
PVC or desirable, but smoke and
6. chlorinated Flame retardant acid gas evolution is not
polymer considered to pose a
serious hazard.
Where cables are exposed
Fluor polymer Inherently flame to high temperatures or
7.
based retardant aggressive environments in
normal use.
Non-flame In situations when fire
retarded performance requirements
8. (e.g. Readily combustible are low and where cable
polyethylene combustion poses little
orEPR based) hazard.
Table 2.5: Levels of fire performance for different types of cables

2.7.2 Material Considerations

The range of flammability is wide however and many polymeric cable

components are formulated so as to reduce their tendency to burn. It should be

noted that polymeric materials overall are no more hazardous in their combustion

behavior than other flammable materials such as wood, paper, cotton or wool.

23
Shashidhar kasthala

There are several factors that describe a material's flammability and

combustion behavior, although how these are measured and their relevance is

often a cause of debate. The major factors are:

1. Ease of ignition (flammability)

2. Resistance to propagation (flame spread)

3. Heat of combustion (heat release)

4. Smoke emission

5. Toxic gas evolution

6. Corrosive gas evolution.

2.8. System Protection Devices

Two types of protecting devices are used on cable systems.

A. Overcurrent—fuses or circuit breakers. These devices isolate the cable from its

source, preventing the flow of damaging levels of current during an overload, or

remove a faulted cable from the system allowing restoration of the unfaulted parts.

B. Overvoltage—surge arrester. This device prevents damaging overvoltages caused

by lightning or switching surges from entering the cable by clamping the voltage to a

level tolerated by the cable insulation.

24
Shashidhar kasthala

Chapter 3

Characteristics of Power cables

3. Current carrying capacity

The current-carrying capability of a cable system will depend on several

parameters. The most important of these are:

1. The number of cables and the different cable types in the installation under study

2. The cable construction and materials used for the different cable types

3. The medium in which the cables are installed

4. Cable locations with respect to each other and with respect to the earth surface

5. The cable bonding arrangement

Selection of optimum size of conductor is an important aspect to achieve

maximum economy in first cost and subsequent operation of cables. In addition to this

the voltage drop, cost of losses and ability to carry short circuit currents must also be

estimated.

To establish a rating for a particular cable design, the most convenient way is to

calculate amperage (sustained rating) which can be carried continuously under prescribed

standard conditions.

3.1 General basis of rating determination

During service operation, cables suffer electric loss which appear has heat in the

conductor, insulation and metallic components. The current rating is dependent on the

way this heat is transmitted to the cable surface and then dissipated to the surroundings.

A maximum temperature is fixed, which is commonly the limit for insulating material

without undue aging for a reasonable maximum life.

25
Shashidhar kasthala

Figure 3.1: Circuit diagram to represent heat generated in a 3-core


metal sheathed cable

The figure 3.1 explains the heat flow corresponding to current, temperature,

difference to voltage and the total thermal resistance to the cable and the surroundings to

electrical resistance. The heat flow within the cable is radial but externally must be made

for the method of installation. Figure 3.2 shows the pattern of heat flow for three buried

single core cables.

Figure 3.2: Heat flow for a circuit of single core cables installed in trefoil

Mathematical treatment is most conveniently expressed for steady state

conditions, i.e for continuous (sustained) ratings. A small cable in air will heat up very

quickly to a steady state condition but a large buried power cable takes some time.

3.2. Mathematical Treatment

The temperature rise in the cable is due to the heat generated in the conductors

(I2R), in the insulation (W) and in the sheath and armour (λ2R), with allowance being

26
Shashidhar kasthala

made by multiplying each of these by the thermal resistance of the layers through which

the heat flows(T).

Since losses occur at several positions in the cable system (for this lumped

parameter network), the heat flow in the thermal circuit shown in Figure will increase in

steps. Thus, the total joule loss WF in a cable can be expressed as

… (3.1)

Figure 3.3 (a): The ladder diagram for steady state computations on single core cable

Figure 3.3(b): The ladder diagram for steady state computations on three core cable

The temperature rise in AC cables is given by

…. (3.2)

Where, Δθ = Conductor temperature rise (k)


I = Current flowing in one conductor (A)
R = alternating current Resistance per unit length of the conductor at maximum
operating temperature.
WC = I2R
Wd = dielectric strength/ unit length for insulation surrounding the conductor
n = number of load carrying conductors in cable
T1 = Thermal resistance per unit length between one conductor and the sheath

27
Shashidhar kasthala

T2 = Thermal resistance per unit length of the bedding between sheath and armor,
T3 = Thermal resistance per unit length of the external serving of the cable, and
T4 = Thermal resistance per unit length between the cable surface and the
surrounding medium.
λ1 = sheath loss factor and is equal to the ratio of the total losses in the
metallic sheath to the total conductor losses.
λ 2 = the armor loss factor and is equal to the ratio of the total losses in the
metallic armor to the total conductor losses.

The unknown quantity is either the conductor current / or its operating

temperature 6C (°C). In the first case, the maximum operating conductor temperature is

given, and in the second case, the conductor current is specified. The obtainable

permissible current limit is written as

…. (3.3)

This formula accounts needs to be taken of the fact that it only provides rating for

the prescribed representative conditions.

Note: In case of 1 kV 4-core cables, n may be assumed to be 3 if the fourth conductor is

neutral or is a protective conductor. This assumes that the neutral conductor is not

carrying currents which are due to the presence of harmonics.

3.3. Ambient and cable operating temperature

3.3.1 Ambient Temperature:

Representative average ambient temperature may vary within any individual

country, according to whether the cables are buried or in air outdoors or within a building

and between counties according to the geographical climate.

28
Shashidhar kasthala

For convenience, the normal tabulated ratings in UK are based on 15oC for cables

in the ground, 250C outdoors in air, 300C in air within buildings and 450C for conditions

in ships.

Air temperature Ground Temperature


Climate (at 1M depth)
Minimum Maximum Minimum Maximum
Tropical 25 55 25 40
Subtropical 10 40 15 30
Temperate 0 25 10 20
Table 3.1: Ambient air and ground temperature

3.3.2 Maximum Cable operating Temperature:

Maximum cable operating temperature according to the insulation material, cable

deign and voltage has been agreed in IEC and the standard values are almost universally

accepted throughout the world for continuous operation.

In using these values an important proviso is that attention must be given to soil

resistivity. Continuous operation at cable surface temperature above 500C will cause

movement of moisture away from the cables and with many types of cable drying out of

the backfill may occur and the cable could exceed the permissible temperature.

Insulation Cable Design Max Conductor


Impregnated paper (U0/U) temp (0C)

0.6/1, 1.8/3, 3.6/6 Belted 80


6/10 Belted 65
6/10,8.7/15 Screened 70
12/20,18/30 MIND Screened 65
Polyvinyl Chloride All 70
Polyethylene All 70
Butyl Rubber All 85
Ethylene Propylene Rubber All 90
Cross-linked polyethylene All 90
Natural Rubber All 60
Table 3.2: Conductor temperature limits for stranded cable types

29
Shashidhar kasthala

3.4. Effect of Installation condition on Cables

3.4.1 Thermal resistivity of soil:

It is of not much importance for distribution cables to consider thermal resistivity,

unless because of fully continuous operation there is a danger of the soil drying out.

The presence of moisture has a predominant effect on resistivity of any type of

soil ans so it is necessary to take the weather conditions into account. IEC 287 gives

guidance and ignores the make up of particular ground types.

Thermal Resistivity Soil conditions Weather


(Km /W) Conditions
0.7 Very moist Continuously moist
1.0 Moist Regular rainfall
2.0 Dry Seldom rains
3.0 Very dry Little or no rain
Table 3.3: Soil thermal resistivity

3.5. Calculation of losses

3.5.1 Conductor Resistance

Conductor resistance is calculated in two stages. First, the dc value R' (ohm/m) is

obtained from the following expression:

…. (3.4)

In the second stage, the DC value is modified to take into account the skin and proximity

effects. The resistance of a conductor when carrying an alternating current is higher than

that of the conductor when carrying a direct current. The principal reasons for the

increase are: skin effect, proximity effect, hysteresis and eddy current losses in nearby

ferromagnetic materials, and induced losses in short-circuited non ferromagnetic

materials nearby. The degree of complexity of the calculations that can economically be

30
Shashidhar kasthala

justified varies considerably. Except in very high voltage cables consisting of large

segmental conductors, it is common to consider only skin effect, proximity effect, and in

some cases, an approximation of the effect of metallic sheath and/or conduit. The

relevant expressions are:

…. (3.5)

For cables in magnetic pipes and conduits:

…. (3.6)

Material properties and the expressions for the skin and proximity factors are:

Resistivity. (ρ20).10-8 Ω.m Temperature coefficient


Material
at 200C (α20).10-3 per K at 200C
Copper 1.7241 3.93
Aluminum 2.8264 4.03
Table 3.4: Material properties

Skin and proximity factors are computed from the following expressions:

… (3.7)

Where,

The proximity factor is obtained from

For sector-shaped conductors:

31
Shashidhar kasthala

For oval conductors:

…(3.8)

The above expressions apply when x<= 2.8

3.5.2 Dielectric Losses

When paper and solid dielectric insulations are subjected to alternating voltage,

they act as large capacitors and charging currents flow in them. The work required to

effect the realignment of electrons each time the voltage direction changes (i.e., 50 or 60

times a second) produces heat and results in a loss of real power that is called dielectric

loss, which should be distinguished from reactive loss. For a unit length of a cable, the

magnitude of the required charging current is a function of the dielectric constant of the

insulation, the dimensions of the cable, and the operating voltage. For some cable

constructions, notably for high-voltage, paper-insulated cables, this loss can have a

significant effect on the cable rating. The dielectric losses are computed from the

following expression:

32
Shashidhar kasthala

Table 3.5: Values of skin and proximity effect

…. (3.9)

where the electrical capacitance and the phase-to-to-ground voltage are obtained from

…. (3.10)

The dielectric constants and the loss factor tanδ are taken from Table 3.6

33
Shashidhar kasthala

.
Table 3.6: Values of dielectric constant and loss factor

3.5.3 Sheath Loss Factor

Sheath losses are current dependent, and can be divided into two categories

according to the type of bonding. These are losses due to circulating currents that flow in

the sheaths of single-core cables if the sheaths are bonded together at two points, and

losses due to eddy currents, which circulate radially (skin effect) and azimuthally

(proximity effect). Eddy current losses occur in both three-core and single- core cables,

irrespective of the method of bonding. Eddy current losses in the sheaths of single-core

cables, which are solidly bonded are considerably smaller than circulating current losses,

and are ignored except for cables with large segmental conductors.

Sheath Bonding Arrangements

Sheath losses in single-core cables depend on a number of factors, one of which is

the sheath bonding arrangement. In fact, the bonding arrangement is the second most

34
Shashidhar kasthala

important parameter in cable ampacity computations after the external thermal resistance

of the cable. For safety reasons, cable sheaths must be earthed, and hence bonded, at least

at one point in a run. There are three basic options for bonding sheaths of single-core

cables. These are: single-point bonding, solid bonding, and cross bonding.

In a single-point-bonded system, the considerable heating effect of circulating

currents is avoided, but voltages will be induced along the length of the cable. These

voltages are proportional to the conductor current and length of run, and increase as the

cable spacing increases. Particular care must be taken to insulate and provide surge

protection at the free end of the sheath to avoid danger from the induced voltages. One

way of eliminating the induced voltages is to bond the sheath at both ends of the run

(solid bonding). The disadvantage of this is that the circulating currents that then flow in

the sheaths reduce the current-carrying capacity of the cable.

Cross bonding of single-core cable sheaths is a method of avoiding circulating

currents and excessive sheath voltages while permitting increased cable spacing and long

run lengths. The increase in cable spacing increases the thermal independence of each

cable and, hence, increases its current-carrying capacity. The cross bonding divides the

cable run into three sections, and cross connects the sheaths in such a manner that the

induced voltages cancel. One disadvantage of this system is that it is very expensive and,

therefore, is applied mostly in high-voltage installations. Figure 3 gives a diagrammatic

representation of the cross connections. The cable route is divided into three equal

lengths, and the sheath continuity is broken at each joint. The induced sheath voltages in

each section of each phase are equal in magnitude and 120° out of phase. When the

sheaths are cross connected, as shown in Figure 1-11, each sheath circuit contains one

35
Shashidhar kasthala

section from each phase such that the total voltage in each sheath circuit sums to zero. If

the sheaths are then bonded and earthed at the end of the run, the net voltage in the loop

and the circulating currents will be zero and the only sheath losses will be those caused

by eddy currents.

Figure 3.4(a) Diagrammatic representation of a cross bonded cable system,


when cables are not transposed.

Figure 3.4(b) Diagrammatic representation of a cross bonded cable system


when Cables are transposed.

This method of bonding allows the cables to be spaced to take advantage of

improved heat dissipation without incurring the penalty of increased circulating current

losses. In practice, the lengths and cable spacings in each section may not be identical,

and, therefore, some circulating currents will be present. The length of each section and

cable spacings are limited by the voltages that exist between the sheaths and between the

36
Shashidhar kasthala

sheaths and earth at each cross-bonding position. For long runs, the route is divided into a

number of lengths, each of which is divided into three sections. Cross bonding as

described above can be applied to each length independently.

The cross-bonding scheme described above assumes that the cables are arranged

symmetrically; that is, in a trefoil pattern. It is usual that single-core cables are laid in a

flat configuration. In this case, it is a common practice in long-cable circuits or heavily

loaded cable lines to transpose the cables as shown in Figure 3(b) so that each cable

occupies each position for a third of the run.

3.5.4 Armor Loss Factor

Armored single-core cables for general use in ac systems usually have

nonmagnetic armor. This is because of the very high losses that would occur in closely

spaced single-core cables with magnetic armor. On the other hand, when magnetic armor

is used, losses due to eddy currents and hysteresis in the steel must be considered. The

armoring or reinforcement on two-core or three-core cables can be either magnetic or

nonmagnetic. These cases are treated separately in what follows. Steel wires or tapes are

generally used for magnetic armor.

When nonmagnetic armor is used, the losses are calculated as a combination of

sheath and armor losses. The equations set out above for sheath losses are applied, but the

resistance used is that of the parallel combination of sheath and armor, and the sheath

diameter is replaced by the misvalue of the mean armor and sheath diameters.

For nonmagnetic tape reinforcement where the tapes do not overlap, the resistance

of the reinforcement is a function of the lay length of the tape. The advice given in IEC

60287 to deal with this is as follows:

37
Shashidhar kasthala

1. If the tapes have a very long lay length, that is, are almost longitudinal tapes, the

resistance taken is that of the equivalent tube, that is, a tube having the same mass

per unit length and the same internal diameter as the tapes.

2. If the tapes are wound at about 54° to the axis of the cable, the resistance is taken

to be twice the equivalent tube resistance.

3. If the tapes are wound with a very short lay, the resistance is assumed to be

infinite; hence, the reinforcement has no effect on the losses.

4. If there are two or more layers of tape in contact with each other and having a

very short lay, the resistance is taken to be twice the equivalent tube resistance.

This is intended to take account of the effect of the contact resistance between the

tapes.

3.6. Electromagnetic Fields

Insulated distribution and transmission cables have an advantage over overhead

lines; the external electrostatic field is zero because of the shielding effect of the

conducting insulation screen within the cable. The magnetic field external to a three-core

distribution cable carrying balanced load currents rapidly reduces to zero because the

vector sum of the spatial and time resolved components of the field is zero. A useful

degree of ferromagnetic shielding is achieved for three-core cables by the application of

steel wire amour which helps to contain the flux. The shielding effect can be significantly

increased by eliminating the air gaps with steel tape amour (suitable for small diameter

cables) or by the installation of the cable within a steel pipe (as employed with high

pressure fluid-filled and high pressure gas-filled cables) The magnetic field external to

single-core cables laid in flat formation does not sum to zero close to the cables because

38
Shashidhar kasthala

of the geometric asymmetry. The distribution of flux. density can be calculated

analytically by the application of the Biot-Savart law to each individual current carrying

conductor and metallic sheath and by making a vectorially and temporally resolved

summation (equations (3.11) and (3.12)). The simple analytical method can be used in

those applications which have one value of permeability and which do not use eddy

current shielding. For more complex application, such as those employing ferrous

materials, specialized computer programs are required which usually employ a finite

element algorithm with the ability to model a non-linear B-H hysteresis curve. It is usual

in calculations to use the peak value of current. The waveform of the resultant flux

density is complex, comprising both sinusoidal and bias components and with a polarized

vector rotating about an axis and pulsating in magnitude. In consequence it is usual to

quote either the r.m.s, value or the mean value of flux density, the preferred unit being µT

(1 µT = 10 mG).

… (3.11)

… (3.12)

39
Shashidhar kasthala

For comparative purposes it has become practice to calculate the magnetic flux

density above a buried cable circuit at a height of 1 m above ground level. At this height

the ratio of distance to cable center-line spacing is comparatively large such that the

maximum magnitude of the flux density is low and, compared with an overhead line,

rapidly reduces in magnitude on both sides of the cable circuit, i.e. within the width of a

roadway (fig. 2.12). Should it be required, significant further reduction in flux density

can be achieved; however this is in varying degrees detrimental to the cable thermal

rating and to the cost of the circuit.

Fig 3.5: Horizontal flux density distribution I m above ground level


for 400kV underground double cable circuits carrying 1000 A.
Examples of flux density distributions are shown in fig. 3.5 for the 400kV double

circuit configuration given in table 3.7. The simplest methods are to lay the cables closer

together and at greater depth, the most effective compromise being to lay the cables in an

open trefoil formation.

40
Shashidhar kasthala

Configuration Cable Circuit Flux density Rating


Depth
(Double Spacing spacing at 1000Fig
Max A per
(mm)
Circuit) (mm) (mm) circuit (A)
Flat – XBa 300 1500 900 30 a 2432
Flat – XBb 300 1500 900 23 b 2432
Flat - XB 200 800 900 13 c 1934
Flat - XB 300 1500 1800 11 d 1886
Trefoil - XB 300 1500 900 11 e 2248
Flat -SB 300 1500 900 2 f 1370
Table 3.7: of installation configuration on magnetic flux density and cable rating

A degree of cancellation of the magnetic field is obtained by solidly bonding the

metallic sheaths of single core cables thereby permitting the induced voltages to drive a

current which, in ideal theoretical circumstances, would be of equal magnitude and in

antiphase to the conductor current. In practice the finite resistances of the metallic sheath

and earth return wires, if present, reduce the magnitude and alter the phase of the sheath

current thereby achieving only partial magnetic screening and with the disadvantage of

generating sheath heat loss of comparatively high magnitude.

3.7. Standard operating conditions & Rating Factors

3.7.1. Cables installed in air:

Standard conditions

(a) Ambient air temperature is taken to be 250C for paper insulated cables for XLPE
cables above 1.9/3.3 KV. 300C is chosen for PVC insulated cables ans for XLPE
cabled of 1.9/3.3 KV and below in order to be in conformity with IEE wiring
regulations.

(b) Air Circulation is not restricted significantly. e.g. if cables are fastened to a wall they
should be spaced at least 20mm from it.

(c) Adjacent circuits are spaced at least 160mm apart and suitable disposed to prevent
mutual heating.

(d) Cables are shielded from direct sunshine.

41
Shashidhar kasthala

3.7.2. Cables installed in ducts

Standard conditions

(a) Ground temperature 150C

(b) Soil Thermal resistivity 1.2 Km/W

(c) Adjacent circuits at least 1.8m distance

(d) Depth of laying 0.5m for 1KV cables


0.8 m for cables above 1kV and upto 33kV

42
Shashidhar kasthala

Chapter 4

Mathematical Analysis

4.1 The Cable and Insulator Parameters

The following figure shows a typical high-voltage cable.

Figure 4.1 Typical High volatge cable

The variables used in the equations below are:

N: The number of cables

n: the number of strands contained in the phase conductor.

d: the diameter of one strand (m)

f: the nominal frequency of the cable application

r: the radius of the phase conductor

µr: the relative permittivity of phase conductor

rint, rext: the internal and external radius of phase-screen insulator

GMD: Geometric mean distance between the phase conductors.

ρ: Resistivity of the phase-screen insulator

ɛrax: Relative permittivity of the phase-screen insulator

ɛrxe: Relative permittivity of the outer screen insulator

43
Shashidhar kasthala

dax,Dax: the internal and external diameter of phase-screen insulator

dxe,Dxe: the internal and external diameter of the outer screen insulator

Self-Impedance of Phase Conductor(s)

The self-impedance of the copper phase conductor is calculated as follow

The DC resistance of phase conductor is given by

The resistance of earth return is given by

The frequency factor is given by

The distance to equivalent earth return path is given by

The geometric mean radius of phase conductor is given by

Self Impedance of Screen Conductor(s)

The self-impedance of the screen conductor is calculated as follow

The DC resistance of phase-screen insulator is given by

44
Shashidhar kasthala

The geometric mean radius of phase-screen insulator is given by

Mutual Impedance between the Phase and Screen Conductors

The mutual impedance between the phase conductor and its corresponding screen

conductor is calculated as follow

Dn corresponds to the distance between the phase conductor and the mean radius of the

phase-screen insulator.

Mutual Impedance between the Phase Conductors

If more than one cable is modeled (N>1), the mutual impedance between the N phase

conductors is calculated as follow

In general, the Geometric Mean Distance (GMD) between the phase conductors of a

given set of cables can be calculated as follow

where n is the total number of distances between the conductors.

However the GMD value is not calculated by the function and need to be specified

directly as an input parameter.

Capacitance between the Phase and Screen Conductors

The capacitance between the phase conductor and its corresponding screen conductor is

calculated as follow

45
Shashidhar kasthala

The cross-linked polyethylene (XLPE) insulator material is assumed in this equation.

Capacitance between the Screen Conductor and the Ground

The same equation is used to calculate the capacitance between the screen conductor and

the ground.

4.2 Localization of cable faults

The faults which are most likely to occur in the cables are:

Figure 4.2 Faults in underfround cable

1. Ground or Earth faults: When the insulation of the cable gets damaged, the

current starts flowing from the core to earth or to the cable sheath. Such faults

are known as ground or earth faults.

2. Cross or short-circuited fault: When the insulation between twoc ables or

between two cores of a multi-core cable gets damaged, the current starts flowing

from one cable to another cable or from one core to another core of multicore

cable directly. Such faults are known as short-circuit faults.

46
Shashidhar kasthala

3. Open-circuit faults: When the conductor of a cable is broken or joint is pulled

out there is no current in the cable. Such faults are known as open circuit faults.

The nature of fault is determined and then the point of fault is located. For

determination of nature of faults, the insulation resistance of each core to ground and

between cores is measured with help of megger. The low value of insulation resistance

between any core and earth indicates the ground fault whereas the low value of insulation

resistance indicates short-circuit fault.

Ground fault of a single fault

Blavier’s test is used to locate the ground fault of a single cable i.e when no other

cables run along with the faulty one.

This test is performed wih the aid of a low-voltage supply and either an ammeter or

voltmeter or a bridge network. In this test resistance between one end of the cable T1 and

earth is measured first with the far end T2 isolated from earth and then with the far end T2

earthed. Let the two readings be R1 and R2 respectively.

If r1 and r2 are the conductor resistance of the lengths of cable “Far end” to fault
and “Test end” of fault respectively and r is the resistance of fault to earth then

R1 = r2 + r …..(1)

…. (2)
The total resistance of conductor,
R = r1 + r2 …. (3)

47
Shashidhar kasthala

(a) (b) (c)


Figure 4.3: Ground fault of a single cable

Substituting r = R1 - r2 from eq (1) in eq (2) we have

or,
since r2 is obviously less than R2 (eq 2), the positive sign is rejected and therefore,

… (4)

If the total length of the cable is L meters, the length of cable between far end and

fault is L1 meters, length of cable between test end and fault is L2 meters and cross-

section of conductor is uniform then

and

or … (5)

Thus the distance from the fault can be determined.

Earth overlap test:

It is also performed to locate the ground fault of a single cable. In this test two

measurements are made one between line and earth, measured form testing end, with far

48
Shashidhar kasthala

end ground and second between line and earth, measured from far end, with testing end

grounded. Let the two readings be R1 and R2 respectively.

Then …. (6)

…. (7)

and R = r1 + r2 as before

By elimination, as blavier test, we have

…. (8)

…. (9)

Knowing the values of r1 or r2, the distance of fault from test end can be

determined, as discussed in case of Blavier test.

4.3 Example for fault localization

Input data:

Feeder cable length – 500 Mts

Fault type – fault to earth

Resistance measurements between earth and one of the cable

Distant end insulated : 7.0 Ohm

Distant end earthed : 1.7 Ohm

The cable has total resistance : 1.8 Ohm

49
Shashidhar kasthala

Calculation:

R1 = 7.0 Ω, R2 = 1.7 Ω, R = 1.8 Ω

If r1 and r2 are the conductor resistance of the length of cable for end to fault and test
end to fault respectively and r is the resistance of fault to earth then

r1 + r2 = R = 1.8 Ω … (i)

r + r2 = R1 = 7.0 Ω … (ii)

R2 = = 1.7 Ω … (iii)

Solving the above equations ,

Resistance of fault, r = 6.0275 Ω

Resistance per meter length = 1.8 / 500 = 0.0036 Ω

Therefore, distance from testing end = r2 / Resistance per meter length

= 0.9725 / 0.0036 = 270.14 Ω

4.4 Matlab Program

clc;
disp(' ')
%% Input parameters
% Nominal frequency
f = 50; % [Hz]
% Soil resistivity
rho_e = 100; % [ohm*m]
% Phase conductor - number of strands
n_ba = 58; % []
% Phase conductor - diameter of one strand
d_ba = 2.71e-3; % [m]
% Phase conductor - resistivity
disp('The material is assumed as Aluminium ')
disp(' ')
rho_ba = 2.8e-8; % [ohm*m]
% Phase conductor - permittivity

50
Shashidhar kasthala

mu_r_ba = 1; % []
% Phase conductor - external diameter
D_a = 20.90e-3; % [m]
% Screen - resistivity
rho_x = 17.8e-9; % [ohm*m]
% Screen - total section
% Ecran - Section du conducteur
S_x = 169e-6; %[m*m]
% Screen - Internal diameter
d_x = 65.80e-3; % [m]
% Screen - External diameter
D_x = 69.80e-3; % [m]
% GMD between phase conductors
GMD_phi = 1.1225 * 22e-2; % [m] % See theorical examples
% Insulator phase to screen - Internal diameter
d_iax = 23.30e-3; % [m]
% Insulator phase to screen - External diameter
D_iax = 60.60e-3; % [m]
% Insulator phase to screen - Permittivity
epsilon_iax = 2.3; % []
% Insulator screen to soil - Internal diameter
d_ixe = 69.80e-3; % [m] %(Protection anti-corrosion + Gaine en PE)
% Insulator screen to soil - External diameter
D_ixe = 77.80e-3; % [m] %(Protection anti-corrosion + Gaine en PE)
% Insulator screen to soil - Permittivity
epsilon_ixe = 2.25; % []
%% Computed parameters
% Phase conductor - external radius
R_a = D_a/2; % [m]
% Phase conductor - section
S_a = n_ba * pi * d_ba^2 / 4; % [m*m]
% Phase conductor - R_phi
R_phi = rho_ba * 1000 / S_a; % [ohm/km]
% Current path return resistance
R_e = pi^2*10^(-4)*f; % [ohm/km]
% Frequency coefficient k_1
k_1 = 0.0529 * f / (0.3048*60); % main work unit: ohm/km
% Current path return depth
D_e = 1650*sqrt(rho_e/(2*pi*f)); % [m]
% Phase conductor - GMR
GMR_phi = R_a * exp(-mu_r_ba/4); % [m]
% Screen resistance
R_N = rho_x * 1000/S_x; % [ohm/km]
% Screen - GMR
GMR_N = d_x/2+(D_x-d_x)/4; % [m]
% Distance between phase conductor and screen mean radius
DN_2 = d_x/2 + (D_x/2-d_x/2)/2; % [m]
%% Impedance matrix Z
Z_aa = R_phi + R_e + j*k_1*log10(D_e/GMR_phi); % [ohm/km]
Z_xx = R_N + R_e + j*k_1*log10(D_e/GMR_N); % [ohm/km]

51
Shashidhar kasthala

Z_ab = R_e + j*k_1*log10(D_e/GMD_phi); % [ohm/km]


Z_ax = R_e + j*k_1*log10(D_e/DN_2); % [ohm/km]
fprintf(' Self Impedence of Phase conductor is %g ', Z_aa);
disp(' ')
fprintf(' Self Impedence of screen conductor is %g ', Z_xx);
disp(' ')
fprintf(' Mutual Impedence between phase and screen conductor is %g ', Z_ax);
disp(' ')
fprintf(' Mutual Impedence between phase conductors is %g ', Z_ab);
%% Capacity matrix
% Calcul des C
C_ax = 1/0.3048 * ((0.00736 * epsilon_iax) / (log10(D_iax/d_iax))); % [muF/km]
C_xe = 1/0.3048 * ((0.00736 * epsilon_ixe) / (log10(D_ixe/d_ixe))); % [muF/km]
C_ax = C_ax * 1e-6 % [F/km]
disp(' ')
fprintf('Capacitance between phase and screen conductor is %g ', C_ax);
disp(' ')
fprintf('Capacitance between screen conductor and the groundis %g ', C_xe);
C_xe = C_xe * 1e-6 % [F/km]
S_ax = C_ax * (2*pi*f); % [S/km]
S_xe = C_xe * (2*pi*f); % [S/km]
%% For a three phase system (three radial electromagnetic field cables)
Z = [Z_aa Z_ax Z_ab Z_ab Z_ab Z_ab ; ...
Z_ax Z_xx Z_ab Z_ab Z_ab Z_ab ; ...
Z_ab Z_ab Z_aa Z_ax Z_ab Z_ab ; ...
Z_ab Z_ab Z_ax Z_xx Z_ab Z_ab ; ...
Z_ab Z_ab Z_ab Z_ab Z_aa Z_ax ; ...
Z_ab Z_ab Z_ab Z_ab Z_ax Z_xx] % [ohm/km]
Y = [0+j*S_ax 0-j*S_ax 0 0 0 0 ; ...
0-j*S_ax 0+j*S_xe 0 0 0 0 ; ...
0 0 0+j*S_ax 0-j*S_ax 0 0 ; ...
0 0 0-j*S_ax 0+j*S_xe 0 0 ; ...
0 0 0 0 0+j*S_ax 0-j*S_ax ; ...
0 0 0 0 0-j*S_ax 0+j*S_xe] % [S/km]
% In [Y], with SimPowerSystem, it's possible to use epsilon instead of 0 for avoiding
errors
disp(' Wish to find the fault location ');
Cont = input(' if yes press Y or N :', 's');
error = 0;
switch Cont
case {'Y', 'y','Yes','yes','ye','Ye'}
Len = input(' The length of the cable in mts is : ');
ResIns = input(' Resistance measured for the distant end insulated is : ');
ResEart = input(' Resistance measured for the distant end earthed is : ');
TotRes = input(' Total resiatnce of the cable is :' );
Rtemp1 = ((ResIns *(TotRes - ResEart))/( ResEart *(TotRes - ResIns)));
Rtemp2 = ((TotRes - ResIns)/(ResEart - ResIns));
r1 = ResEart*Rtemp2*(1- sqrt(abs(Rtemp1)));
case {'NO','No','n','no','N'}
error =1;

52
Shashidhar kasthala

end
if error
disp(' ')
fprintf(' \t\t Thank You')
else
disp(' ')
r2 = TotRes - r1;
r = ResIns - r2;
disp(' ')
fprintf('conductor resistance of the length of cable far end to fault is %g Ohm',r1);
disp(' ')
fprintf('conductor resistance of the length of cable test end to fault is %g Ohm',r2);
disp(' ')
fprintf('conductor resistance of the fault to earth is %g Ohm',r);
disp(' ')
ResperLen = TotRes/Len;
DistTestEnd = r2/ResperLen;
fprintf('The resistance per meter length is %g Ohm', ResperLen);
disp(' ')
fprintf('The distance from testing end is %g mts', DistTestEnd);
disp(' -------------------------')
end

53
Shashidhar kasthala

Conclusion

In this project the characteristics of Electric power cables and its insulation is

studied and evaluated as per the standard IEC 187 and IEC 287. A mathematical analysis

is performed to analyze the cable and its insulation parameters. In addition to it

localization of ground fault in cables is evaluated using Blavier’s test and earth overlap

test.

54
Shashidhar kasthala

References

1. Electrical Cable Handbook by George F.Moore, BICC cables Ltd.

2. Rating of Electric power cables: Ampacity computations by George J.Anderson

3. Electric Power Cable Engineering by William A.Thue.

4. Switchgear Manual. 10th revised edition,ABB

5. Insulated power cables used in Underground applications by Michael J.Dyer, Salt

river project.

6. Review of Power cable Standard Rating Methods

55

You might also like