You are on page 1of 14

NOTES:

1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO


A 32A RATING AND PROVIDE THE LINKWAY VICINITY
AS SHOWN IN SLD (B)

Qualified Person Endorsement :

LTA Endorsement :

Project Title :

STANDARD INSTALLATION DETAILS

Drawing Title :

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX


(POB/LINKWAY/TAXI STAND/BUS SHELTER)

Designed Checked Approved

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (POB / LINKWAY / TAXI STAND / BUS SHELTER) NURLY MALVIN HO MELVYN THONG

Scale Drawn Date


SCALE: NTS
N.T.S. JULI JULY 2007

Drawing No. : Rev.

L/ROAD/MES/SD/1001 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1001-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
NOTES:

1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO


A 32A RATING AND PROVIDE THE LINKWAY VICINITY
AS SHOWN IN SLD(B)

Qualified Person Endorsement :

LTA Endorsement :

Project Title :

STANDARD INSTALLATION DETAILS

Drawing Title :

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX


(BUS SHELTER/LINKWAY)

Designed Checked Approved


TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER / LINKWAY)
NURLY MALVIN HO MELVYN THONG
SCALE: NTS
Scale Drawn Date

N.T.S. JULI JULY 2007

Drawing No. : Rev.

L/ROAD/MES/SD/1002 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1002-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
NOTES:

1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO


A 32A RATING AND PROVIDE THE LINKWAY VICINITY
AS SHOWN IN SLD(B).

Qualified Person Endorsement :

LTA Endorsement :

Project Title :

STANDARD INSTALLATION DETAILS

Drawing Title :

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX


(BUS SHELTER)

Designed Checked Approved

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER) NURLY MALVIN HO MELVYN THONG
SCALE: NTS Scale Drawn Date

N.T.S. JULI JULY 2007

Drawing No. : Rev.

L/ROAD/MES/SD/1003 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1003-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
NOTES:

1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO


A 32A RATING AND PROVIDE THE LINKWAY VICINITY
AS SHOWN IN SLD(B).

Qualified Person Endorsement :

LTA Endorsement :

Project Title :

STANDARD INSTALLATION DETAILS

Drawing Title :

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX


(DBO BUS SHELTER/POB/LINKWAY/TAXI STAND)

Designed Checked Approved

NURLY MALVIN HO MELVYN THONG


TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (DBO BUS SHELTER / POB / LINKWAY / TAXI STAND)
Scale Drawn Date
SCALE: NTS
N.T.S. JULI JULY 2007

Drawing No. : Rev.

L/ROAD/MES/SD/1004 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1004-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
LAND TRANSPORT
AUTHORITY
LOGO
UV RESISTANT
WINDOW C/W
LAND TRANSPORT

CONTRRACT NO:
SERIAL NO:

YEAR MANUFACTURE:
AUTHORITY
LOGO

NAME PLATE
SPANNERS INTERNATIONAL PTE LTD
6 CHANGI NORTH STREET 1 ISO
SPANNERS BUILDING 9002Company
Certified
SINGAPORE 498825

NEOPRENE SEAL

WEATHERPROOF
TO IP 54

ABLOY MASTER KEY 300


FOR POWERGRID 2 NOS. POWER GRID
KWH METER

ABLOY MASTER KEY


AS PER LTA’s
REQUIREMENTS

REMOVEABLE
PLATE
Qualified Person Endorsement :

PLINTH C/W
OPENING FOR
CABLE ENTRY
2 NOS 50mm LTA Endorsement :

HEAVY DUTY 2 NOS 100mm HEAVY DUTY uPVC


UPVC PIPE FOR LEAD IN C/W 90^ LONG BEND PIPES
POB ELECTRICAL FOR POWER GRID INCOMING CABLING
DISTRIBUTION

FRONT INTERNAL VIEW SIDE VIEW

EXTERNAL VIEW

2 NOS 50mm HEAVY DUTY


uPVC PIPE FOR FUTURE Project Title :

BUS SHELTER ELECTRICAL


DISTRIBUTION

STANDARD INSTALLATION DETAILS

TYPICAL DETAIL OF OG-BOX


SCALE: NTS

Drawing Title :

TYPICAL DETAIL OF POB OG-BOX

Designed Checked Approved

NURLY MALVIN HO MELVYN THONG

Scale Drawn Date

N.T.S. JULI JULY 2007

Drawing No. : Rev.

L/ROAD/MES/SD/1005 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1005-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
Back

EXTERNAL BACK DOOR FIX PLATE

100mm HEAVY DUTY UPVC PIPE 2 NOS 100mm HEAVY DUTY UPVC
FOR POB/LINKWAY ELECTRICAL DISTRIBUTION LEAD IN C/W 90^ LONG BEND PIPES
FOR POWER GRID INCOMING CABLING

PARTITION

100mm HEAVY DUTY UPVC PIPE


FOR BUS SHELTER ELECTRICAL DISTRIBUTION
SUPPORT FOR BREAKER

GLASS
PARTITION

50mm HEAVY DUTY UPVC PIPE


FOR BUS SHELTER ADVERTISING PANEL EXTERNAL FRONT DOOR
EXTERNAL FRONT DOOR Front

PLAN VIEW

Overall Length = min 1120mm Depth = min 450mm Depth = min 450mm
Overall Length = min 1120mm
420

POWER POWER
GRID GRID
1 KWH 1 KWH
METER METER
Qualified Person Endorsement :

GLASS GLASS POB/LINKWAY


SUPPORT
FOR BREAKER

FIX PLATE

LTA Endorsement :
BUS SHELTER BI Supply
and Installed
By PG
EXTERNAL
FRONT
DOOR

PARTITION

REMOVABLE PLATE REMOVABLE PLATE REMOVABLE PLATE

Project Title :

Y
STANDARD INSTALLATION DETAILS
2 NOS 100mm HEAVY DUTY UPVC 50mm HEAVY DUTY
LEAD IN C/W 90^ LONG BEND PIPES UPVC PIPE FOR BUS
FOR POWER GRID INCOMING CABLING SHELTER ADVERTISING
PLINTH C/W OPENING
PANEL
FOR CABLE ENTRY
100mm HEAVY DUTY
UPVC PIPE FOR BUS
100mm HEAVY DUTY UPVC PIPE Drawing Title :
SHELTER ELECTRICAL
FOR POB/LINKWAY ELECTRICAL DISTRIBUTION DISTRIBUTION

TYPICAL DETAIL OF POB OG-BOX


EXTERNAL BACK VIEW EXTERNAL VIEW INTERNAL FRONT VIEW INTERNAL SIDE VIEW SIDE VIEW

Designed Checked Approved

A
NURLY MALVIN HO MELVYN THONG

Scale Drawn Date

N.T.S. JULI JULY 2007


TYPICAL DETAIL OF OG-BOX
SCALE: NTS Drawing No. : Rev.

L/ROAD/MES/SD/1006 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1006-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
1 2 3

7500

750 3000 3000 750

1500 1500 1500 1500

MS ANGLE ROOF FASCIA TO ENGR’S DTL EARTH PIT


(TOTAL RESISTANCE < 10ohm)

M.S. RHS POST UNDERNEATH TO ENGR’S DTL

ROOF CAPPING @ 1500mm C/C TO


MFR’S DTL
PVC CABLE IN
MIN. 10mm THK. ALUM. HONEYCOMB ROOF FLEXIBLE CONDUIT
PANEL COMPLETE WITH MIN. 1 mm THK
3 TOP PANEL TO SO’S APPROVAL

PROPOSED 1 x 18W
(IP 65) LIGHT FITTING

50 X 50 X 3 THK ALUM. ANGLE PLATE FOR


BUS STOP ADDRESS & NUMBER SIGN PLATE

BUS STOP ADDRESS & NUMBER SIGN


PLATE TO FACE ONCOMING TRAFFIC IN
ACCORDANCE TO LTA STD DRAWING NO.
LTA/ARCH/CF/97/8/13 LATEST REVISION

Qualified Person Endorsement :

TYPICAL LIGHTING LAYOUT PLAN


SCALE: NTS

1 2 3

7500

750 3000 3000 750 LTA Endorsement :

EARTH PIT
2 NOS. 50mm HEAVY DUTY
ROOF EAVES ABOVE (TOTAL RESISTANCE < 10ohm)
UPVC PIPE C/W PULL WIRE

NOTICE BOARD WITH ALUM. FRAME C/W


10mm THK. TEMPERED GLASS 600 REFUSE BIN

A NEW
OG BOX
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DTL

ALUM. SEAT TO DTL


2 NOS. 100mm HEAVY DUTY UPVC
HEAD-IN 90^ LONG BEND PIPES FOR
POWERGRID’S INCOMING CABLE

3
1 NO. 50mm HEAVY DUTY
1400 100 1400 UPVC PIPE C/W PULL WIRES
FROM 0G-BOX TO ADVERTISING PANEL
1 NO. ELECT. PIPE FOR ADVERTISEMENT
PANEL (AP) TO BE LOCATED AT THE
DOWNSTREAM EDGE OF BUS SHELTER Project Title :

STANDARD INSTALLATION DETAILS


CONC. SLAB TO ENGR’S DTLS COMPLETE WITH 20mm THK
GRANOLITHIC FINISHES TO SO’S APPROVAL

200 WIDE YELLOW LINE IN HOT APPLIED


THERMOPLASTIC ROAD MARKING MATERIALS

LINE OF ROAD KERB OR ROAD RESERVE LINE


Drawing Title :

TYPICAL LIGHTING LAYOUT PLAN AND


LIGHTNING PROTECTION SYSTEM
FOR BUS SHELTER (WITH OR WITHOUT RAILING)

Designed Checked Approved

NURLY MALVIN HO MELVYN THONG


ROAD
Scale Drawn Date

N.T.S. JULI JULY 2007

TYPICAL LIGHTNING PROTECTION SYSTEM LAYOUT PLAN Drawing No. : Rev.

SCALE: NTS
L/ROAD/MES/SD/1007 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1007-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
A

3000 MIN. 600


1 2 3
300 2700

7500

750 3000 3000 750

1500 1500 1500 1500


MIN. 10mm THK. ALUM. HONEYCOMB ROOF
PANEL COMPLETE WITH MIN. 1 mm THK
BUS STOP ADDRESS & NUMBER SIGN TOP PANEL TO SO’S APPROVAL
PLATE TO FACE ONCOMING TRAFFIC IN
ACCORDANCE TO LTA STD DRAWING NO.
LTA/ARCH/CF/97/8/13 LATEST REVISION
MS ANGLE ROOF FASCIA TO ENGR’S DTL
(TO BE BOLTED TO ALUM. ANGLE PLATE)
PROPOSED 1 x 18W (IP65) LIGHT FITTING
3^ FALL

LIGHT FITTING TO M&E SPECS & SHALL


M.S. RHS TO ENGR’S DETAIL
NOT PROTRUDE FROM M.S. RAFTER /
PVC CABLE IN PVC CONTRACTOR TO PROPOSE FIXING
1000 1000 M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C BRACKET FOR LIGHT FITTING
FLEXIBLE CONDUIT
TO ENGR’S DETAIL
G.I. PIPE ALONG BACK OF M.S. FASCIA FOR
ELECT. CABLES TO M&E DWG. & SPEC.
LIGHT FITTING TO M&E SPECS

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C


TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

NEW OG BOX (IP55) M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
LOCATION SHALL BE SUBJECTED TO
SITE CONDITIONS AND POWERGRID’S APPROVAL
ELECTRICAL CABLE IN PVC
FLEXIBLE PIPE IN SUPPORT POST

CONC. SLAB TO ENGR’S DTL COMPLETE WITH 20mm THK


GRANOLITHIC FINISHES TO SO’S APPROVAL

NOTICE BOARD WITH ALUM. FRAME REFUSE BIN TO BE FIXED IN POSITION


ALUM SEAT TO DETAIL
C/W 10mm THK. TEMPERED GLASS

ALUM. SEAT TO DTL 300

CONC. SLAB TO ENGR’S DTLS COMPLETE WITH


20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL

CABLE ENTRY CONDUIT


ACCESS PANEL ENCASED IN
(REFER TO TYPICAL CONCRETE
SUPPORT POST DETAIL) FFL FFL

ROAD
FOOTING TO ENGR’ S DETAIL
6m PVC EARTH BONDING CABLE IN 2 NOS 50mm HEAVY DUTY UPVC PIPES
25mm HEAVY DUTY UPVC PIPE

ELEVATION 1 2 NOS 100mm HEAVY DUTY UPVC


PIPES LEAD IN 90^ LONG BEND PIPES
FOR POWERGRID INCOMING CABLING
SECTION A-A
CATCH BASIN AND UPVC PIPE IN Qualified Person Endorsement :
(REFUSE BIN NOT SHOWN FOR CLARITY) ACCORDANCE WITH THE CURRENT
Scale 1 :20 LTA STANDARD DETAILS OF ROAD
ELEMENTS

TYPICAL FRONT ELEVATION OF BUS SHELTER (WITHOUT RAILING) TYPICAL SECTION OF BUS SHELTER (WITHOUT RAILING)
REF. DWG. NO. L/STLBS/AR/STD/0002

SCALE: NTS SCALE: NTS


A

3000 MIN. 600


1 2 3
300 2700

7500

750 3000 3000 750

1500 1500 1500 1500


MIN. 10mm THK. ALUM. HONEYCOMB ROOF LTA Endorsement :
PANEL COMPLETE WITH MIN. 1 mm THK
BUS STOP ADDRESS & NUMBER SIGN TOP PANEL TO SO’S APPROVAL
PLATE TO FACE ONCOMING TRAFFIC IN
ACCORDANCE TO LTA STD DRAWING NO.
LTA/ARCH/CF/97/8/13 LATEST REVISION
MS ANGLE ROOF FASCIA TO ENGR’S DTL
(TO BE BOLTED TO ALUM. ANGLE PLATE) PROPOSED 1 x 18W (IP65) LIGHT FITTING
3^ FALL

LIGHT FITTING TO M&E SPECS & SHALL


M.S. RHS TO ENGR’S DETAIL
NOT PROTRUDE FROM M.S. RAFTER /
PVC CABLE IN PVC CONTRACTOR TO PROPOSE FIXING
1000 1000 M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C BRACKET FOR LIGHT FITTING
FLEXIBLE CONDUIT
TO ENGR’S DETAIL
G.I. PIPE ALONG BACK OF M.S. FASCIA FOR
ELECT. CABLES TO M&E DWG. & SPEC.
LIGHT FITTING TO M&E SPECS

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C


TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

NEW OG BOX (IP55) M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
S/S RAILING TO BE PROVIDED WHERE THERE
LOCATION SHALL BE SUBJECTED TO
IS SUDDEN GREAT DIFFERENCE IN LEVEL
SITE CONDITIONS AND POWERGRID’S APPROVAL
ELECTRICAL CABLE IN PVC
REFUSE BIN TO BE FIXED IN POSITION Project Title :
FLEXIBLE PIPE IN SUPPORT POST

CONC. SLAB TO ENGR’S DTL COMPLETE WITH 20mm THK


GRANOLITHIC FINISHES TO SO’S APPROVAL

NOTICE BOARD WITH ALUM. FRAME


ALUM SEAT TO DETAIL
C/W 10mm THK. TEMPERED GLASS
BONDING TO ALUMINIUM SEAT
ALUM. SEAT TO DTL 300
STANDARD INSTALLATION DETAILS
CONDUIT
ENCASED IN
CONCRETE
FFL FFL

ROAD
CABLE ENTRY Drawing Title :
ACCESS PANEL
FOOTING TO ENGR’ S DETAIL
(REFER TO TYPICAL
6m PVC EARTH BONDING CABLE IN
SUPPORT POST DETAIL) 2 NOS 50mm HEAVY DUTY UPVC PIPES
25mm HEAVY DUTY UPVC PIPE
TYPICAL ELECTRICAL INSTALLATION DETAILS
ELEVATION 1 2 NOS 100mm HEAVY DUTY UPVC
PIPES LEAD IN 90^ LONG BEND PIPES
FOR POWERGRID INCOMING CABLING
SECTION A-A FOR BUS SHELTER (WITH AND WITHOUT RAILING)
(REFUSE BIN NOT SHOWN FOR CLARITY) CATCH BASIN AND UPVC PIPE IN
ACCORDANCE WITH THE CURRENT
Scale 1 :20
LTA STANDARD DETAILS OF ROAD
REF. DWG. NO. L/STLBS/AR/STD/0004 ELEMENTS

TYPICAL FRONT ELEVATION OF BUS SHELTER (WITH RAILING) TYPICAL SECTION OF BUS SHELTER (WITH RAILING) Designed Checked Approved

SCALE: NTS SCALE: NTS NURLY MALVIN HO MELVYN THONG

Scale Drawn Date

N.T.S. JULI JULY 2007

Drawing No. : Rev.

L/ROAD/MES/SD/1008 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1008-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
A

3000

300 2700

1500

MIN. 10mm THK. ALUM. HONEYCOMB ROOF


PANEL COMPLETE WITH MIN. 1mm THK.
TOP PANEL TO SO’S APPROVAL

´
S/S SCREW

CENTRE LINE OF LIGHT FITTING

K
S/S SCREW
-

C MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE


3^ FALL
- WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL

ISOLATOR / BONDING TAPE BETWEEN


ALUM. ROOF FRAME & M.S. MEMBER
3%%d

ISOLATOR / BONDING TAPE BETWEEN


ALUM. ROOF FRAME & M.S. MEMBER

3%%d
200

DETAIL 2
DETAIL 2 Scale 1:5

K
-
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL

C LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /
- CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
ELECTRICAL CABLE CONCEALED IN PVC TO SO’S APPROVAL
FLEXIBLE CONDUIT IN SUPPORT POST
´
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

´ ELECTRICAL CABLE CONCEALED IN PVC Qualified Person Endorsement :


50 mm PVC FLEXIBLE CONDUIT
FOR INCOMING CABLES TO M&E DETAIL FLEXIBLE CONDUIT TO M&E DWG. & SPEC.

OPENING FOR INCOMING CABLES COVERED


BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY) M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

SECTION B-B G.I. PIPE ALONG BACK OF M.S. FASCIA


FOR ELECT. CABLES TO M&E DWG. & SPEC.

DETAIL
DETAIL 1 1 SECTION B-B
Scale 1:5
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
Scale 1:5
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

SECTION C-C Y
LTA Endorsement :
SECTION C-C
-
PVC CABLE + 2.5m PVC EARTH CABLE
IN FLEXIBLE CONDUIT Scale 1:5

TERMINAL BLOCK CONNECTOR


TEAKWOOD FOR MOUNTING
MOUNTED ON TEAKWOOD BLOCK

FLAT BAR TO SUPPORT TEAKWOOD BLOCK


M8 ALUMINIUM COPPER BOLT
TO STEEL SUPPORT POST
SEE DETAIL X OPENING FOR INCOMING CABLES COVERED
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY) 25mm x 3mm COPPER TAPE

B 40 B
750 1500
- - ALUMINIUM OR
STEEL SUPPORT POST
EARTH PIT CABLE GLAND FOR ARMOURED CABLE
100 100
40

(TOTAL EARTH
RESISTANCE FFL
C1 WELDED ALL-ROUND TO
<10 ohms)
300x300x20 THK MS PLATE
10

Y
-
SECTION Y-Y
BUS STOP ADDRESS & NUMBER SIGN
PLATE TO FACE ONCOMING TRAFFIC IN ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL
ACCORDANCE TO LTA STD DRAWING NO.
LTA/ARCH/CF/97/8/13 LATEST REVISION GASKET

10mm THK NON SHRINK GROUT


(TO BE BOLTED TO ALUM. ANGLE PLATE)
´ MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
´
DETAIL X
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL

Project Title :
CONC. SLAB TO ENGR’S DTL COMPLETE WITH
25mm x 3mm COPPER TAPE
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL

RC FOOTING TO ENGR’S DETAIL

MS BASE PLATE TO ENGR’S DETAIL

STANDARD INSTALLATION DETAILS


TYPICAL SUPPORT POST DETAIL
FROM OG BOX TO FIRST LIGHTING POINT M.S. ANGLE ROOF FASCIA
Scale 1:5 ISOLATOR / BONDING TAPE BETWEEN TO ENGR’S DETAIL
ARMOURED CABLE IN UPVC PIPE ALUM. ROOF FRAME & M.S. MEMBER
MS RHS TO ENGR’S DETAIL

LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

TYPICAL SUPPORT POST DETAIL LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /
Drawing Title :
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

SECTION K-K
SECTION K-K Scale 1:5
TYPICAL CABLE ENTRY DETAIL FOR BUS SHELTER

Designed Checked Approved

NURLY MALVIN HO MELVYN THONG

Scale Drawn Date

N.T.S. JULI JULY 2007

Drawing No. : Rev.

L/ROAD/MES/SD/1009 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1009-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
2800 2800

370 2060 370 370 2060 370

EQ EQ EQ EQ

MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE
WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL

12%%d 12%%d

´ OF POB DECK ´ OF POB DECK


AND ROOF AND ROOF

CHS HOT-DIPPED GALVANISED M.S. MEMBER CHS HOT-DIPPED GALVANISED M.S. MEMBER
TO ENGR’S DETAIL COMPLETE WITH SPRAY TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL COATING FINISH TO SO’S APPROVAL
PURPOSE MADE BOND PURPOSE MADE BOND
CHS HOT-DIPPED GALVANISED M.S. POST CONTRACTOR TO ENSURE THAT BONDED CHS HOT-DIPPED GALVANISED M.S. POST CONTRACTOR TO ENSURE THAT BONDED
TO ENGR’S DETAIL COMPLETE WITH SPRAY IN ACCORDANCE TO CP33 REQUIREMENTS TO ENGR’S DETAIL COMPLETE WITH SPRAY IN ACCORDANCE TO CP33 REQUIREMENTS
COATING FINISH TO SO’S APPROVAL COATING FINISH TO SO’S APPROVAL

MIN. 40 MIN. 40 MIN. 40 MIN. 40

1800 1800

BI-METALLIC BOND/CLAMP AND


45mm S.S. RAILING 45mm S.S. RAILING ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE.
CONCRETE SURFACE PAINTED OVER
TO PREVENT ALUMINIUM TAPE
15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR 15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR TO HAVE DIRECT CONTACT
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE WITH CONCRETE SURFACE
BOLTED ON BEARING PLATE CONCRETE SURFACE BOLTED ON BEARING PLATE CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE PAINTED OVER TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
(SEE DETAIL X) (SEE DETAIL X) UPVC PIPE SEALED
WITH APPROVED
SEALANT TO PREVENT
675 2200 700 675 2200 700 WATER INGRESS

FFL OF FFL OF
TYPICAL CROSS BEAM TYPICAL CROSS BEAM
POB DECK FALL FALL POB DECK FALL FALL
TO ENGR’S DETAIL TO ENGR’S DETAIL

DETAIL X
75 75
PLANTING TROUGH WITH WATERPROOFING PLANTING TROUGH WITH WATERPROOFING
MEMBRANE TO SO’S APPROVAL MEMBRANE TO SO’S APPROVAL

PIPE SLEEVE PIPE SLEEVE

20mm THK PRECASTED GRANOLITHIC 20mm THK PRECASTED GRANOLITHIC


CHIPPING FINISHED TO S.O’S APPROVAL CHIPPING FINISHED TO S.O’S APPROVAL

625 625
Y
-

10x10mm CHAMFER 10x10mm CHAMFER

25mm x 3mm
ALUMINIUM TAPE

RC COLUMN TO ENGR’S DETAIL WITH RC COLUMN TO ENGR’S DETAIL WITH Qualified Person Endorsement :
20mm THK PRECASTED GRANOLITHIC 20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL CHIPPING FINISHED TO S.O’S APPROVAL
M5 COUNTERSUNK BOLT NUT INSERT

LIGHTNING

PROTECTION
BI-METALLIC
TEST
CONNECTOR
BOX

25mm x 3mm
STAINLESS STEEL
COPPER TAPE
COVER PLATE

LTA Endorsement :
Y
-

ELEVATION VIEW ELEVATION VIEW


25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE
(WITH COVER) (WITHOUT COVER)
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE

150mm x 150mm TEST LINK BOX ENCASED HEAVY


AT 1500mm HEIGHT FROM DUTY UPVC PIPES
25mm x 3mm
GROUND LEVEL (SURFACE MOUNT) ALUMINIUM TAPE
IN ACCORDANCE TO CP33 REQUIREMENTS STAINLESS STEEL
(SEE TYPICAL LIGHTNING PROTECTION COVER PLATE
150mm x 150mm TEST LINK BOX TEST BOX AT POB)
AT 1500mm HEIGHT FROM BI-METALLIC
GROUND LEVEL (SURFACE MOUNT) CONNECTOR
IN ACCORDANCE TO CP33 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION
Project Title :
TEST BOX AT POB)

25mm x 3mm R.C. COLUMN


COPPER TAPE
ENCASED HEAVY
25mm x 3mm COPPER CONDUCTOR TAPE DUTY UPVC PIPES
ENCASED IN 50mm HEAVY DUTY UPVC PIPE

50mm PVC PIPE FOR LIGHTING CIRCUITS


STANDARD INSTALLATION DETAILS
TO OG BOX TO M&E SPECIFICATIONS
25mm x 3mm COPPER CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE

R.C. GRATING EARTH PIT SECTION Y-Y


(TOTAL EARTH RESISTANCE 10ohms)
FOOTPATH LEVEL

R.C. GRATING EARTH PIT ROAD LEVEL


(TOTAL EARTH RESISTANCE 10ohms) Drawing Title :
FOOTPATH LEVEL TO ROADSIDE DRAIN
EARTH ROD
TYPICAL LIGHTNING PROTECTION
ROAD LEVEL
TEST BOX AT POB TYPICAL LIGHTNING PROTECTION SYSTEM
TO ROADSIDE DRAIN
EARTH ROD
FOR COVERED PEDESTRIAN OVERHEAD BRIDGE

PILE CAP TO ENGR’S DETAIL

Designed Checked Approved

PILE CAP TO ENGR’S DETAIL NURLY MALVIN HO MELVYN THONG

FOR COVERED POB (NON-EXPRESSWAY) Scale Drawn Date

N.T.S. JULI JULY 2007

Drawing No. : Rev.


FOR COVERED POB (EXPRESSWAY)
L/ROAD/MES/SD/1010 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1010-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
LOCATION OF SUPPORT POST FOR FUTURE COVER LOCATION OF SUPPORT POST FOR FUTURE COVER

MIN. 40 MIN. 40 MIN. 40 MIN. 40

1800 1800

BI-METALLIC BOND/CLAMP AND


ALUMINIUM CONDUCTOR TAPE
45mm S.S. RAILING 45mm S.S. RAILING BOLTED ON BEARING PLATE.
CONCRETE SURFACE PAINTED OVER
TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT
15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR
WITH CONCRETE SURFACE
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
S.S. LIGHTING ENCASEMENT TO DETAIL BOLTED ON BEARING PLATE CONCRETE SURFACE S.S. LIGHTING ENCASEMENT TO DETAIL BOLTED ON BEARING PLATE CONCRETE SURFACE
LIGHT FITTING TO M&E SPEC. & SO’S APPROVAL
PAINTED OVER TO PREVENT ALUMINIUM TAPE PAINTED OVER TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
UPVC PIPE SEALED
(SEE DETAIL X) (SEE DETAIL X)
25mm x 3mm ALUMINIUM CONDUCTOR TAPE 25mm x 3mm ALUMINIUM CONDUCTOR TAPE WITH APPROVED
SEALANT TO PREVENT
WATER INGRESS
675 2200 700 675 2200 700

FFL OF FFL OF
TYPICAL CROSS BEAM TYPICAL CROSS BEAM
POB DECK FALL FALL POB DECK FALL FALL
TO ENGR’S DETAIL TO ENGR’S DETAIL

DETAIL X
75 75
PLANTING TROUGH WITH WATERPROOFING PLANTING TROUGH WITH WATERPROOFING
MEMBRANE TO SO’S APPROVAL MEMBRANE TO SO’S APPROVAL

PIPE SLEEVE 100mm PVC PIPE WITH 5mm HOLES


PIPE SLEEVE 100mm PVC PIPE WITH 5mm HOLES
PERFORATION AT 100mm C/C ALL DIRECTIONS PERFORATION AT 100mm C/C ALL DIRECTIONS

20mm THK PRECASTED GRANOLITHIC 20mm THK PRECASTED GRANOLITHIC


CHIPPING FINISHED TO S.O’S APPROVAL CHIPPING FINISHED TO S.O’S APPROVAL Y
-
625 625

25mm x 3mm
ALUMINIUM TAPE

RC COLUMN TO ENGR’S DETAIL WITH RC COLUMN TO ENGR’S DETAIL WITH M5 COUNTERSUNK BOLT NUT INSERT
Qualified Person Endorsement :
20mm THK PRECASTED GRANOLITHIC 20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL CHIPPING FINISHED TO S.O’S APPROVAL
LIGHTNING

PROTECTION
BI-METALLIC
TEST
CONNECTOR
BOX

25mm x 3mm
STAINLESS STEEL
COPPER TAPE
COVER PLATE

Y
- LTA Endorsement :

ELEVATION VIEW ELEVATION VIEW


(WITH COVER) (WITHOUT COVER)
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE

25mm x 3mm ALUMINIUM CONDUCTOR TAPE


ENCASED IN 50mm HEAVY DUTY UPVC PIPE

ENCASED HEAVY
DUTY UPVC PIPES
25mm x 3mm
150mm x 150mm TEST LINK BOX ALUMINIUM TAPE
AT 1500mm HEIGHT FROM STAINLESS STEEL
COVER PLATE
GROUND LEVEL (SURFACE MOUNT)
IN ACCORDANCE TO CP33 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION BI-METALLIC
150mm x 150mm TEST LINK BOX TEST BOX AT POB) CONNECTOR
AT 1500mm HEIGHT FROM
GROUND LEVEL (SURFACE MOUNT)
IN ACCORDANCE TO CP33 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION
TEST BOX AT POB) Project Title :
25mm x 3mm R.C. COLUMN
COPPER TAPE
ENCASED HEAVY
DUTY UPVC PIPES

25mm x 3mm COPPER CONDUCTOR TAPE


ENCASED IN 50mm HEAVY DUTY UPVC PIPE
STANDARD INSTALLATION DETAILS
25mm x 3mm COPPER CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE
SECTION Y-Y
R.C. GRATING EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
FOOTPATH LEVEL

R.C. GRATING
EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
ROAD LEVEL TYPICAL LIGHTNING PROTECTION Drawing Title :
FOOTPATH LEVEL TO ROADSIDE DRAIN
EARTH ROD TEST BOX AT POB
ROAD LEVEL
TYPICAL LIGHTNING PROTECTION SYSTEM
TO ROADSIDE DRAIN
EARTH ROD
FOR UNCOVERED PEDESTRIAN OVERHEAD BRIDGE

PILE CAP TO ENGR’S DETAIL

Designed Checked Approved

PILE CAP TO ENGR’S DETAIL NURLY MALVIN HO MELVYN THONG

FOR UNCOVERED POB (NON-EXPRESSWAY) Scale Drawn Date

N.T.S. JULI JULY 2007

Drawing No. : Rev.


FOR UNCOVERED POB (EXPRESSWAY)
L/ROAD/MES/SD/1011 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1011-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
750

¨81

ALUM. ROOF CAPPING FOR ROOF PANEL


TO MFR’S DETAIL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL


COMPLETE WITH MIN. 1mm THK. TOP PANEL M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
TO SO’S APPROVAL

ELECTRICAL CABLE CONCEALED IN PVC


FLEXIBLE CONDUIT TO M&E DWG. & SPEC.
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

G.I. PIPE ALONG BACK OF M.S. FASCIA ALUM FLASHING PIECE BOLTED AT BOTH END
FOR ELECT. CABLES TO M&E DWG. & SPEC. LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
50 x 50 x 3 ALUM ANGLE PLATE
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
TO SO’S APPROVAL
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT IN SUPPORT POST
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL

750

SECTION C-C
SECTION C-C Scale 1:5

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

´
50 mm PVC FLEXIBLE CONDUIT
FOR INCOMING CABLES TO M&E DETAIL

LIGHT FITTING TO M&E SPEC


OPENING FOR INCOMING CABLES COVERED
(DESIGN TO REFER TO ARCH DWG)
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)

SECTION B-B
Scale 1:5

SECTION B-B
SECTION J-J
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
Scale 1:5
REF. DWG. NO. L/STLLW/AR/STD/1002
Qualified Person Endorsement :

A
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
PANEL COMPLETE WITH MIN. 1mm THK.
300 TOP PANEL TO SO’S APPROVAL

S/S SCREW S/S SCREW

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE


C WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL 3^ FALL
-
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER

Y
-

LTA Endorsement :

DETAIL 2
Scale 1:5

M8 ALUMINIUM COPPER BOLT


TO STEEL SUPPORT POST

25mm x 3mm COPPER TAPE


C LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
-
ALUMINIUM OR
G.I. PIPE ALONG BACK OF M.S. FASCIA STEEL SUPPORT POST
FOR ELECT. CABLES TO M&E DWG. & SPEC.

ELECTRICAL CABLE CONCEALED IN PVC


FLEXIBLE CONDUIT IN SUPPORT POST
Y
-
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL SECTION Y-Y

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL

750 1500
DETAIL X
DETAIL 1
DETAIL 1
Scale 1:5
ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL

GASKET Project Title :


´
M.S. ANGLE ROOF FASCIA
´ MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
PVC CABLE + 2.5m PVC EARTH CABLE COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO ENGR’S DETAIL
IN FLEXIBLE CONDUIT TO SO’S APPROVAL

TERMINAL BLOCK CONNECTOR


MOUNTED ON TEAKWOOD BLOCK

TEAKWOOD FOR MOUNTING


STANDARD INSTALLATION DETAILS
SEE DETAIL X OPENING FOR INCOMING CABLES COVERED
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)

B 40 B FLAT BAR TO SUPPORT TEAKWOOD BLOCK

- - ISOLATOR / BONDING TAPE BETWEEN M.S. ANGLE ROOF FASCIA


CABLE GLAND FOR ARMOURED CABLE
EARTH PIT ALUM. ROOF FRAME & M.S. MEMBER TO ENGR’S DETAIL
100 100
(TOTAL EARTH
RESISTANCE FFL MS RHS TO ENGR’S DETAIL
<10 ohms)
Drawing Title :
C1 WELDED ALL-ROUND TO
300x300x20 THK MS PLATE LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL


TYPICAL CABLE ENTRY DETAIL
LIGHT FITTING TO M&E SPEC. & SHALL NOT PROTRUDE FROM M.S. RAFTER /
10mm THK NON SHRINK GROUT
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
FOR SINGLE POST COVERED LINKWAY
SECTION K-K
SECTION K-K
Scale 1:5
Designed Checked Approved
CONC. SLAB TO ENGR’S DTL COMPLETE WITH REF. DWG. NO. L/STLLW/AR/STD/1002
25mm x 3mm
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL
COPPER TAPE
NURLY MALVIN HO MELVYN THONG
RC FOOTING TO ENGR’S DETAIL
Scale Drawn Date
MS BASE PLATE TO ENGR’S DETAIL

ARMOURED CABLE IN UPVC PIPE


TYPICAL SUPPORT POST DETAIL N.T.S. JULI JULY 2007
FROM OG BOX TO FIRST LIGHTING POINT
Scale 1:5
Drawing No. : Rev.

TYPICAL CROSS SECTION FOR SINGLE POST COVERED LINKWAY L/ROAD/MES/SD/1012 -


Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1012-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
ALUM. ROOF CAPPING FOR ROOF PANEL 750
TO MFR’S DETAIL
¨81
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

ELECTRICAL CABLE CONCEALED IN PVC


FLEXIBLE CONDUIT TO M&E DWG. & SPEC.

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL


M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
ALUM FLASHING PIECE BOLTED AT BOTH END LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL PROPOSE MOUNTING BRACKET FOR LIGHT FITTING

M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL 50 X 50 X 3 ALUM ANGLE PLATE
M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL


COMPLETE WITH MIN. 1mm THK. TOP PANEL

SECTION C-C
SECTION C-C
TO SO’S APPROVAL

Scale 1:5
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT IN SUPPORT POST

750 1500 750

ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL

GASKET
´
M.S. ANGLE ROOF FASCIA
´ MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO ENGR’S DETAIL
TO SO’S APPROVAL

ISOLATOR / BONDING TAPE BETWEEN 40 LIGHT FITTING TO M&E SPEC


M.S. RHS TO ENGR’S DETAIL (DESIGN TO REFER TO ARCH DWG)
ALUM. ROOF FRAME & M.S. MEMBER

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL

100 LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL

LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO


PROPOSE MOUNTING BRACKET FOR LIGHT FITTING

M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL SECTION E-E


TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
SECTION D-D
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE Scale 1:5

SECTION D-D Scale 1:5 REF. DWG. NO. L/STLLW/AR/STD/2002


Qualified Person Endorsement :

Y
-
A B

2400

300 1800 300

1200 M8 ALUMINIUM COPPER BOLT


TO STEEL SUPPORT POST

25mm x 3mm COPPER TAPE

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE


WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL ALUMINIUM OR
C STEEL SUPPORT POST
ISOLATOR / BONDING TAPE BETWEEN
3^ FALL LTA Endorsement :
-
ALUM. ROOF FRAME & M.S. MEMBER

S/S SCREW Y
-
SECTION Y-Y

DETAIL X
M.S. ANGLE ROOF FASCIA
TO ENGR’S DETAIL

LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO


PROPOSE MOUNTING BRACKET FOR LIGHT FITTING
80
CENTRE OF LIGHT FITTING
C
- ´
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL PVC FLEXIBLE CONDUIT FOR
INCOMING CABLES TO M&E DETAIL

ELECTRICAL CABLE CONCEALED IN PVC


M.S. SUPPORT POST @ 3000 mm C/C
FLEXIBLE CONDUIT IN SUPPORT POST
TO ENGR’S DETAIL
´
G.I. PIPE ALONG BACK OF M.S. FASCIA
FOR ELECT. CABLES TO M&E DWG. & SPEC.
1720 BOTTOM OPENING FOR INCOMING CABLES
Project Title :
COVERED BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST)
M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL

SECTION B-B

PVC CABLE + 2.5m PVC EARTH CABLE


SECTION B-B
Scale 1:5

IN FLEXIBLE CONDUIT
STANDARD INSTALLATION DETAILS
TERMINAL BLOCK CONNECTOR
MOUNTED ON TEAKWOOD BLOCK

TEAKWOOD FOR MOUNTING

SEE DETAIL X

B B
- -
FLAT BAR TO SUPPORT TEAKWOOD BLOCK Drawing Title :
100 40 100
CABLE GLAND FOR ARMOURED CABLE
EARTH PIT
(TOTAL EARTH OPENING FOR INCOMING CABLES COVERED
RESISTANCE
<10 ohms)
FFL BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
FFL
TYPICAL CABLE ENTRY DETAIL
C1 WELDED ALL-ROUND TO
300x300x20 THK MS PLATE FOR DOUBLE POST COVERED LINKWAY
CONC. SLAB TO ENGR’S DTL COMPLETE WITH
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL

10mm THK NON SHRINK GROUT


Designed Checked Approved
M.S. BASE PLATE TO ENGR’S DETAIL

NURLY MALVIN HO MELVYN THONG

25mm x 3mm
RC FOOTING TO ENGR’S DETAIL TYPICAL CROSS SECTION Scale Drawn Date
COPPER TAPE Scale 1:5
N.T.S. JULI JULY 2007
ARMOURED CABLE IN UPVC PIPE

Drawing No. : Rev.

FROM OG BOX TO FIRST LIGHTING POINT

L/ROAD/MES/SD/1013 -
TYPICAL CROSS SECTION FOR DOUBLE POST COVERED LINKWAY Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1013-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$
1 2 3 4 5 6 7 8 9 10
750 3000 3000 750
BONDING DETAILS TO
750 3000 3000 750
ROOF SPECIALIST’S REQUIREMENTS
750 3000 3000 3000 750 ¨81

¨81
BONDING TO UPPER ROOF
LIGHTNING PROTECTION SYSTEM
(BONDING DETAILS TO ROOF
SPECIALIST’S REQUIREMENTS) ALUM FLASHING PIECE
J
BONDING DETAILS TO L/STLLW/AR/STD/1006 MS ANGLE ROOF FASCIA
ROOF SPECIALIST’S REQUIREMENTS TO ENGR’S DETAIL

SUPPORT POST TO ENGR’S DETAIL


MS ANGLE ROOF FASCIA
BONDING TO UPPER ROOF TO ENGR’S DETAIL
LIGHTNING PROTECTION SYSTEM
200 820
(BONDING DETAILS TO ROOF FFL
(CLEAR) SPECIALIST’S REQUIREMENTS) SUPPORT POST TO ENGR’S DETAIL

EARTH
PIT

OG BOX FFL

FFL

SUPPORT POST TO ENGR’S DETAIL

OG BOX ON CONC. PLINTH TO M&E DTLS


FRONT ELEVATION WITH LEVEL DIFFERENCE
(LOCATION TO BE DETERMINED ON SITE &
TO POWERGRID’S APPROVAL) FRONT ELEVATION OF LIGHTNING PROTECTION LAYOUT PLAN
Scale 1:50

1 2 3 4 5 6 7
750 3000 3000 3000 3000 3000 3000 750

ROOF CAPPING TO MFR’S DETAIL

MS ANGLE ROOF FASCIA TO BONDING DETAILS TO


200 820 ENGR’S DETAIL ROOF SPECIALIST’S REQUIREMENTS

(CLEAR)
SUPPORT POST TO ENGR’S DETAIL

OG BOX

FFL
Qualified Person Endorsement :
EARTH
OG BOX ON CONC. PLINTH TO M&E DTLS PIT
(LOCATION TO BE DETERMINED ON SITE &
TO POWERGRID’S APPROVAL)
FRONT ELEVATION 1 (WITHOUT LEVEL DIFFERENCE)
FRONT ELEVATION OF OG BOX POSITION Scale 1:50

1 2 3 4 5 6 7

750 3000 3000 3000 3000 3000 3000 750

1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500

(LOCATION TO BE DETERMINED LTA Endorsement :


ON SITE & TO RO APPROVAL)
SUPPORT POST TO ENGR’S DETAIL

K K
L/STLLW/AR/STD/1006 -

ROOF CAPPING TO MFR’S DETAIL

MS ANGLE ROOF FASCIA TO ENGR’S DETAIL

ROOF CAPPING TO MFR’S DETAIL

MS ANGLE ROOF FASCIA TO ENGR’S DETAIL

1
MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL TO -
SO’S APPROVAL

ROOF PLAN OF LINKWAY (WITHOUT LEVEL DIFFERENCE)


LIGHTNING PROTECTION LAYOUT PLAN Scale 1:50
Project Title :

1 2 3 4 5 6 7 STANDARD INSTALLATION DETAILS


750 3000 3000 3000 3000 3000 3000 750

1500 1500
OG BOX ON CONC. PLINTH TO M&E DTLS
200 820 (LOCATION TO BE DETERMINED ON SITE & ROOF EAVES ABOVE
TO POWERGRID’S APPROVAL)
(CLEAR)

A OG BOX Drawing Title :

SUPPORT POST TO ENGR’S DETAIL

2 NOS. 100mm HEAVY DUTY UPVC PIPE


TYPICAL OG BOX POSITION FOR COVERED LINKWAY
EXPANSION JOINT AT REGULAR INTERVAL
EMBEDED UNDER GROUND FOR POWERGRID
ALONG CENTRE OF GRID TO ENGR’S DETAIL
INCOMING CABLES TO M&E SPEC. & APPROVAL
(LOCATION & ORIENTATION TO BE
CONC. SLAB TO ENGR’S DTLS COMPLETE WITH
DETERMINED ON SITE)
20mm THK. GRANOLITHIC FINISHES TO SO’S APPROVAL

Designed Checked Approved

NURLY MALVIN HO MELVYN THONG

Scale Drawn Date

N.T.S. JULI JULY 2007


LINE OF ROAD KERB ROAD
1
Drawing No. : Rev.
-

LAYOUT PLAN OF LINKWAY (WITHOUT LEVEL DIFFERENCE)


OG BOX POSITION LAYOUT PLAN L/ROAD/MES/SD/1014 -
Rev. Date By Description Chk’d App’d
CAD File Name : LROADMES-SD1014-.dgn Sheet 1 of 1 A4
$DATE$ $TIME$ $FILE$

You might also like