Water-Cooled Series R(TM)

Job Information
D1F1F2 TIG

Tag Model number Quantity Product Version

RTHD-1 RTHD 1 2.6

Compressor configuration Evap configuration Cond configuration

D1 F1 F2

Unit Information
Capacity NPLV Refrigerant charge (HFC-134a) Full load sound pressure (ARI Condition) 300.00 tons 0.486 kW/ton 283 kg 78 dBA Efficiency Operating weight Shipping weight Oil cooler 0.609 kW/ton 7955 kg 7342 kg Without Oil Cooler

Evaporator Information
Evap leaving temp Evap entering temp Minimum evap flow rate Number of evap passes Evap fluid type 8.00 C 17.00 C 23.72 L/s 3 Pass Water Evap flow rate Evap pressure drop Evap fouling factor Evap fluid freeze point Evap fluid concentration 27.93 L/s 12.9 kPa 0.017615 m2-deg K/kW 0.00 C 0.00 %

Condenser Information
Cond entering temp Cond leaving temp Cond flow rate Cond fluid type Cond tube type 31.00 C 37.00 C 49.67 L/s Water Enhanced Fin - Copper Number of cond passes Cond fouling factor Cond pressure drop Cond fluid concentration 2 Pass 0.044037 m2-deg K/kW 33.8 kPa 0.00 %

Electrical Information
Unit voltage Unit power Max overcurrent protection Motor locked rotor amps 380/50/3 182.60 kW 700.00 A 2303.00 A Starter type Min circuit ampacity Run load amps Starter expected inrush Wye-delta 405.00 A 324.00 A 711.00 A

Notes: All weights +- 3%. Weights include 150 psig water boxes. Operating weights include refrigerant, oil, and water charges. Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is based on ARI Standard 550/590. This unit complies with the efficiency requirements of ASHRAE Standard 90.1 and CAN/CSA C743. Sound pressure measured in accordance with ARI Standard 575-94.

7/16/2009

Product Version

2.6

E:\REE\M&C TOWER\July 15 09\300RT\D1F1F2.psd Page 1 of 2

Water-Cooled Series R(TM)


Job Information
D1F1F2 TIG

Tag Model number Quantity Product Version

RTHD-1 RTHD 1 2.6

Compressor configuration Evap configuration Cond configuration

D1 F1 F2

Information for LEED Projects


ASHRAE 90.1/CSA compliance Refrigerant charge (HFC-134a) Rated capacity (ARI)
Note:

ASHRAE 283 kg 1114.22 kW

Efficiency IPLV

0.609 kW/ton 0.474 kW/ton

This product meets the minimum equipment efficiency requirements of ASHRAE Standard 90.1-2004 and -2007 (which are based on ARI standard rating conditions) and, therefore, also meets the LEED "Minimum Energy Performance" prerequisite in the Energy and Atmosphere section. The efficiencies and power data listed above are at actual user-entered conditions. Refer to the product catalog for performance at ARI standard rating conditions.

The LEED Green Building Rating System, developed by the U.S. Green Building Council, provides independent, third-party verification that a building project meets green building and performance measures.

7/16/2009

Product Version

2.6

E:\REE\M&C TOWER\July 15 09\300RT\D1F1F2.psd Page 2 of 2