Description

GUARANTEED TECHNICAL PARTICULARS FOR 100kVA, 33/0.400kV UNIT 100kVA Vijai Electricals Limited Conventional Non CSP, outdoor Three 100 33000 400 Yes +5% to -5% in steps of 2.5 50 Dyn11 75 Not Applicable Copper CRGO 40 45 325(+IS TOL) 1650(+IS TOL) 4.5% +/- IS tolerance 1.65 1.74 3.86 98.06 98.36 98.55 97.59 97.95 98.19 BARE BUSGINHS BARE BUSGINHS mm mm mm Kg.

6) 7) 8) 9) 10)

11) 12) 13)

14)

15)

Make Type Phases Rating Voltage: HV LV Tapping Tap Range Frequency Vector group Insualtion Level HV LV Winding material Core Material Temperature Rise: Oil Winding Losses i)No load Losses at 75 deg ii)Load losses at 75 deg Impedance Voltage

No. kVA V V

Hz

KV peak KV peak

C C W W % % % % % % % % % %

16) Percentage Resistance 17) Regulation at: Full Load UPF Full Load 0.8 PF 18) Efficiency at UPF at Full Load Full Load Full Load 19) Efficiency at 0.8 PF: Full Load Full Load Full Load 20) Terminal Arrangement: HV LV 21) Overall Dimensions: Length Width Height 22) Overall Weight Total Weight

As per OGA 900

NOTE: weights and Dimensions are subject to 10% tolerance 1.All 2. All the efficiencies and regulations are calculated at the nominal values of NLL,LL AT 75DegC and %Z at 75 Deg C