Meter Pooling System Operation & Maintenance Manual

Page 8 of 170

(1)

Meter Pool Station (MPS)

Introduction
MPS collects Energy Datas from EDC Software in Text File Format for three Different Generating Sets Viz Gas Turbine 1 (GT1), Gas Turbine 2 (GT2) and Steam Turbine (ST) and convert the Data into blocks Viz Block1, Block2 and Blcok0 and Load the Block Data into MK6 Meters and Create the Data log files for Auditing. MPS also logs the Data into a Database for Secondary backup, using the MPS software as below.

Page 9 of 170

(2)

The Schematic Diagram of the MPS is as below

How to Use
Setup This menu will be used to change the configuration parameters of the MPS. When this Menu is enabled MPS will automatically stop polling. Execute This menu is used to Instruct MPS to start polling. It has two sub Menus viz Manual and Auto. If selected to Manual the MPS will search immediately for the Raw Data from the Test file since the last block and perform other operations. If selection is made to Auto the MPS will automatically start polling the Data from the Raw Data text file at every 15th and 45th Min of an hour.

Page 10 of 170

(3)

Database MPS uses Oracle Database for storing the Secondary Backup of the Raw Data and the Block Datas. This has two Sub Menus Backup This will be used to back up the Data from the Database. Select the Start time and End time of the Records for which the Report has to be prepared. This will produce a Text file in the Folder viz Data with the File Name same as Data type Selected. Eg. Raw Data, Block1, Block2, Block 0 and All. If all is selected the File will contain all the Dates viz Raw Data, Block1, Block 2, Block 0.

Page 11 of 170

(4)

Delete This will be used to delete the Data from the Database. Select the Start time and End Time of the Record, which has to be deleted from the Database. Select the Appropriate data type, which has to delete viz Raw Data, Block1, and Block2, Block 0 and all. If all is selected then all the Data for the selected duration will be deleted. Log Files A Log File Named as MPS .txt will be Generated in the same folder where MPS is running. The Log file contains the following log Datas a. The Start /Stop Date time of the MPS b. All communication Errors raised with Meters during the time of Writing or Time Sync. c. Any Errors in Reading Text Files. d. Any Errors in the MPS software due to any other reasons like changes in configuration /Formats. e. The Change in configurations made in the setup screen of the interface. In addition to the above you can select the following in the Log View Combo Box. A. If Selected L&G 1. The Retry attempt to locate the Text file after a lapse of 15 Min i.e. after the lapse of processing time for the EDC to prepare the Text file. This retry will continue every second till the file is found and the entry will be made in the log file. 2. Raw Data as read from the Text file for the current block 3. The Error Description of the Status Fields of Raw Data as furnished in the Text File B. If Selected MK6 Meters 1. Data written to the Block1, Block2, Block0 Meters including all the Data. 2. Status of Operations on MK6 Meters like Time Sync etc after successful completion. C. If Selected All In addition to the above it will contain

Page 12 of 170

(5)

1. The Last Block Read 2. The Current Block 3. Status of Raw Data Backup D. If Selected None None of the above will be recorded

Setting up
The Setting up Wizard is used to configure the MPS. The following parameters are setup

System
Mode - Set the Mode to Main to configure the Software to Read Meter Group Main. Set up the Mode to check to configure the Software to read Meter Group Check

Page 13 of 170

(6)

Last Interval - Set the Last Interval to fill the Backlog data. Due to Error or other reasons if the MPS fails to collects data and updates the Block meters, this feature can be used to fill up the back log Data. First find out the last interval up to which the Data are available in the Block Meters and set this time as Last Interval. This time will be taken as reference starting time and the Data will be collected from this time Block onwards. Please ensure that EDC software is also setup to provide the Backlog data in Text File format. Number of Meters -Number of Meters in the Main Group or Check group Raw Data Folder - The System Folder where EDC provide the Raw Data file.

Com Server
IP Address - Set the IP Address of the Communication server (COM server). If the Com server is located in the same PC then set the value as local host Port - Set the Port of the COM server. The Default Port is 6830 User Name - Set the User name for accessing the Com Server. Default value is Null Password - Set the Password for accessing the Com server. Default value is Null

EDMI Meters
All the Meters as available in the Main Group or Check Group will be seen in the Tree view. Select any Meter and right click and edit the Meter parameters. The following meter parameters shall be configurable. Enabled -Select enabled if the Meter Data is to be included in the Schedule. Select Disabled otherwise Survey Type - Select the Load Profile survey type as set up in the Meter Meter Name - Enter the Meter Name Meter type - Select the Meter type. Select MK3 for EDMI MK3 Meters and Select MK6 for EDMI MK6 Meters Meter Config. - Meter Configurations. Select MK3 for EDMI MK3 meter and select MK6 for EDMI MK6 Meters Serial Number - Enter the Serial Number of the Meter User Name -Enter the User Name to log into the Meter

Page 14 of 170

(7)

Password - Enter the Password to log into the Meter Description - Enter the Description of the Meter

LG Meters
GT1 - Specify the Meter Name and Serial Number for GT1 GT2- Specify the Meter Name and Serial Number for GT2 ST - Specify the Meter Name and Serial Number for ST

Block calculations
Raw Data
GT1 MEE= GT1 Energy export (CH-1) Main Meter GT1 CEE= GT1 Energy export (CH-1) Check Meter GT1 MEI= GT1 Energy import (CH-2) Main Meter GT1 CEI= GT1 Energy Import (CH-2) Check Meter GT1 MVE= GT1 MVar export (CH-4) Main Meter GT1 CVE= GT1 MVar export (CH-4) Check Meter GT1 MVI= GT1 MVar Import (CH-5) Main Meter GT1 CVI= GT1 MVar import (CH-5) Check Meter GT2 MEE= GT2 Energy export (CH-1) Main Meter GT2 CEE= GT2 Energy export (CH-1) Check Meter GT2 MEI= GT2 Energy import (CH-2) Main Meter GT2 CEI= GT2 Energy Import (CH-2) Check Meter GT2 MVE= GT2 MVar export (CH-4) Main Meter GT2 CVE= GT2 MVar export (CH-4) Check Meter GT2 MVI= GT2 MVar Import (CH-5) Main Meter GT2 CVI= GT2 MVar import (CH-5) Check Meter ST MEE= ST Energy export (CH-1) Main Meter ST CEE= ST Energy export (CH-1) Check Meter ST MEI= ST Energy import (CH-2) Main Meter ST CEI= ST Energy Import (CH-2) Check Meter ST MVE= ST MVar export (CH-4) Main Meter ST CVE= ST MVar export (CH-4) Check Meter

Page 15 of 170

(8)

ST MVI= ST MVar Import (CH-5) Main Meter ST CVI= ST MVar import (CH-5) Check Meter

Calculated Data
BLK1 MEE= BLOCK1 Energy export (CH-1) Main Meter BLk1 CEE= BLOCK1Energy export (CH-1) Check Meter BLK1 MEI= BLOCK1Energy import (CH-2) Main Meter BLK1 CEI=BLOCK1 Energy Import (CH-2) Check Meter BLK1 MVE= BLOCK1MVar export (CH-4) Main Meter BLK1 CVE= BLOCK1 MVar export (CH-4) Check Meter BLK1 MVI=BLOCK1MVar Import (CH-5) Main Meter BLK1 CVI= BLOCK1 MVar import (CH-5) Check Meter

BLK2 MEE= BLOCK2 Energy export (CH-1) Main Meter BLK2 CEE=BLOCK2 Energy export (CH-1) Check Meter BLK2 MEI= BLOCK2 Energy import (CH-2) Main Meter BLK2 CEI= BLOCK2 Energy Import (CH-2) Check Meter BLK2 MVE= BLOCK2 MVar export (CH-4) Main Meter BLK2 CVE= BLOCK2 MVar export (CH-4) Check Meter BLK2 MVI= BLOCK2 MVar Import (CH-5) Main Meter BLK2 CVI= BLOCK2 MVar import (CH-5) Check Meter

BLk0 MEE= TOTAL Energy export (CH-1) Main Meter BLk0 CEE= TOTAL Energy export (CH-1) Check Meter BLk0 MEI= TOTAL Energy import (CH-2) Main Meter BLk0 CEI= TOTAL Energy Import (CH-2) Check Meter BLk0 MVE= TOTAL MVar export (CH-4) Main Meter BLk0 CVE= TOTAL MVar export (CH-4) Check Meter BLk0 MVI= TOTAL MVar Import (CH-5) Main Meter BLk0 CVI= TOTAL MVar import (CH-5) Check Meter

Definitions
If GT1 MEE= 0 Then Fraction1M = 0 Else Fraction1M= GT1 MEE/ (GT1 MEE+ GT2 MEE) If GT2 MEE= 0 Then Fraction2 M= 0 Else Fraction2M= GT2 MEE/ (GT1MEE+ GT2MEE)

Page 16 of 170

(9)

If GT1 CEE= 0 Then Fraction1C = 0 Else Fraction1C= GT1 CEE/ (GT1 CEE+ GT2 CEE) If GT2 CEE= 0 Then Fraction2C = 0 Else Fraction2C= GT2 CEE/ (GT1 CEE+ GT2 CEE)

Calculations
Energy Export 1. BLK1 MEE =GT1 MEE + ST MEE * fraction1M 2. BLK2 MEE =GT2 MEE + ST MEE * fraction2M 3. BLk1 CEE =GT1 CEE + ST CEE * fraction1C 4. BLK2 CEE =GT2 CEE + ST CEE * fraction2C 5. BLk0 MEE = BLK1 MEE +BLK2 MEE 6. BLk0 CEE = BLk1 CEE+ BLK2 CEE Energy import 1. BLK1 MEI =GT1 MEI + ST MEI * fraction1M 2. BLK2 MEI =GT2 MEI + ST MEI * fraction2M 3. BLk1 CEI =GT1 CEI + ST CEI * fraction1C 4. BLK2 CEI =GT2 CEI + ST CEI * fraction2C 5. BLk0 MEI = BLK1 MEI +BLK2 MEE 6.BLk0 CEI = BLK1 CEI+ BLK2 CEI MVar Export 1. BLK1 MVE =GT1 MVE + ST MVE * fraction1M 2. BLK2 MVE =GT2 MVE + ST MVE * fraction2M 3. BLk1 CVE =GT1 CVE + ST CVE * fraction1C 4. BLK2 CVE =GT2 CVE + ST CVE * fraction2C 5. BLk0 MVE = BLK1 MVE +BLk2 MVE 6. BLk0 CVE = BLK1 CVE+ BLk2 CVE

MVar Import 1. BLK1 MVI =GT1 MVI + ST MVI * fraction1M 2. BLK2 MVI =GT2 MVI+ ST MVI * fraction2M 3. BLk1 MVI =GT1 MVI+ ST MVI * fraction1C 4. BLK2 MVI =GT2 MVI + ST MVI * fraction2C

Page 17 of 170

(10)

5. BLk0 MVI = BLK1 MVI +BLK2 MVI 6.BLk0 CVI = BLK1 CVI+ BLK2 CVI

Time Synchronize
There are two combo boxes available for the Time Synchronize. The Time Sync Meter is used to Set Meter time from the PC time. The Time Sync PC is used to set PC time from the Meter Time. The GPS clock time is taken as a reference time in the Main metering station PC and the all the EDMI Meters Viz Block1-Main, Block 2-Main, Block0-Main / Block1-Check, Block2-Check, Block0-Check are set. If the Time Sync Meter Mode is selected automatic than the Time Synchronize will take place once in a day at 23:00 Hours and all the MK6 Meters are sync with PC. If the Mode is selected in Manual, the time Sync of Meter is done manually at any time. Please note that The Time Sync will occur only if the Drift between the PC and MK6 meters is less then 5 Min. If the Time Sync PC Manual Mode is selected the PC time is synchronized with MK6 Meter. In this case the Block1 Main meter time as set by MSSL will be taken as reference and the PC time will be Set. Time Sync PC Automatic is not implemented. Please note that the Time Sync only affects the Polling time of the EDC software and the Polling time of the EDMI meters but the processed Meter Data are stamped with the FAG time as available in the text file.

Auditing
There are three folders contains data for Data Auditing Raw Data Processed - This folder contains the Text Files as furnished by L&G. To disable the Backing up of processed Raw Data as furnished by the EDC the RAW Data backup feature can be disabled in the setup. Data - This Folder contains a sub folder for Each Day. The Sub folders contains the Data file of the Raw Data and Calculated Block Data as processed by MPS Data Log - This Folder contains a Single file named as Main-DDMMYYYY.log or Check_DDMMYYYY.log and this file all the Raw Data and Block Data values in a single File.