RELAY SETTING CALCULATION FOR OVERCURRENT AND VOLTAGE OPERATED RELAYS OF LBDS-9

Subject. Project

Relay Setting Calculation Doc. No. ISP/AREVA-EMC-A/IX/22/16/29/DE/1007J LBDS Package 22 - New Stream 2.5 MT Expansions at IISCO Steel Plant Page- 1

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J

A. Setting of Relays For 33 KV I/C


1.0 BASIC DATA a b d e g h f. g. System voltage in kV Selected CT Ratio = In = Rated current in amps corresponding to CT ratio of 800/1A = Minimum symmetrical 3-Ph S/C current in amps at 33 KV bus = Total load on 33kV bus = Load current = Relay used Setting ranges : I> I>> I>>> TMS = Definite time setting = 2.0 SETTING VALUES 2.1 Proposed Is (IDMT) setting for O/C (51) a. b. c. d. Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Is = Current in amps corresponding to PS = PS*In Proposed TMS setting = IEC SI 1 800 0.550 Standard Inverse 0.1-25In 0.5-40In 0.5-40In 0.025-1.5 0-150 sec 33 800/1 800 11650 34000 594.86 MICOM P127 steps @ 0.01 In @ 0.01 In @ 0.01 In @ 0.025 @ 0.01 sec A A A KVA A

2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 1.75 1400 1.55

2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. b. c. Minimum Isc setting proposed in multiples (M) of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 4.5 3600 0.65

2.4 Time of Operation for Different Fault Current


Current in Amps Multiples of Set Current Equivalent MVA Time of Operation in sec.

Zone of Operation DT zone I>>> DT zone

16000 3600 3600 3600

20 4.5 4.5 4.5

914.52 205.77 205.77 205.77

0.65 0.65
1.55

1.55

Consultant : SATCON

Page 2 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 1400 1400 11650 8000 4800 3200 1600 1520 1440 1400 1360 1280 1200 1120 1040 960 880 1.75 1.75 14.5625 10 6 4 2 1.9 1.8 1.75 1.7 1.6 1.5 1.4 1.3 1.2 1.1 80.02 80.02 665.89 457.26 274.36 182.90 91.45 86.88 82.31 80.02 77.73 73.16 68.59 64.02 59.44 54.87 50.30 1.55 6.84 1.40 1.63 2.11 2.74 5.52 5.96 6.51 6.84 7.22 8.15 9.46 11.40 14.64 21.08 40.36 IDMT zone I> I>>

2.5 Undervoltage protection (27) a. b. c. d. V< in volts = 0.4*Vn (I/C brkr trip) DT setting in sec = V<< in volts = 0.8*Vn (Annunciation, I/C brkr closing circuit interlock) DT setting in sec = 44 2.5 88 2

2.6 Overvoltage protection (59) a. b. V> in volts = 1.1*Vn (For annunciation) DT setting in sec = 121 1

B. Settings of Relays for 33 KV Bus PT


1 RELAY TYPE MICOM P922 110

1.1 Rated PT secondary voltage (Vn) 1.2 Undervoltage protection (27) a. b. c. d. V< in volts = 0.4*Vn (I/C and B/C brkr closing circuit interlock) DT setting in sec = V<< in volts = 0.8*Vn (I/C and B/C brkr closing circuit interlock) DT setting in sec =

44 2.5 88 2

1.3 Overvoltage protection (59) a. b. V>> in volts = 1.1*Vn (For annunciation) DT setting in sec = 121 1

Consultant : SATCON

Page 3 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J

1.4 Residual overvoltage/neutral displacement protection (60) a. b. c. d. V0> in volts = 0.06*Vn (For Alarm) DT setting in sec = V0>> in volts = 0.2*Vn (for tripping of respective I/C) DT setting in sec = 6.6 0.05 20 0.1

C. Settings of Relays For 33 KV Bus Coupler


1.0 BASIC DATA a. b. c. d. e. f. System voltage in kV Selected CT Ratio = In = Rated current in amps corresponding to CT ratio of 1500/1A = Minimum symmetrical 3-Ph S/C current in amps at 11 KV bus = Relay used Setting ranges : IDMT I> DT I>> DT I>>> DT TMS = Definite time setting = 2.0 SETTING VALUES 2.1 Proposed IDMT setting for O/C (51), a. b. c. d. Curve used for IDMT setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = I>1 = Current in amps corresponding to PS = PS*In Proposed TMS setting = IEC SI 1.5 600 0.475 Standard inverse 0.1-4In 0.1-40In 0.1-40In 0.1-40In 0.05-10 0-100 sec 33 400/ 1A 400 11650 MICOM P132 A A

2.2 Proposed I> (DT) setting for O/C (50-1) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 3 1200 1.25

2.3 Proposed I>> (DT) setting for O/C (50-2) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 8.25 3300 0.35 Not used

2.4 Proposed I>>> (DT) setting for O/C (50-3) a. Minimum Isc setting proposed in multiples (M) of In

Consultant : SATCON

Page 4 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

2.5 Time of Operation for Different Fault Current


Current in Amps Multiples of Set Current Equivalent MVA Time of Operation in sec.

Zone of Operation DT zone I>> DT zone I>

8000 3300 3300 1200 1200 11650 6000 3000 1800 1200 1140 1080 1020 960 900 840 780 720 660

20 8.25 8.25 3 3 19.417 10 5 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1

457.26 188.62 188.62 68.59 68.59 665.88 342.95 171.47 102.88 68.59 65.16 61.73 58.30 54.87 51.44 48.01 44.58 41.15 37.72

0.35 0.35 1.25 1.25 4.76 1.09 1.41 2.03 2.99 4.76 5.15 5.62 6.23 7.04 8.17 9.85 12.64 18.20 34.85

IDMT zone

2.6 25 Check Synchronisation a. b. c. d. e. Phase angle setting Vdiff setting in volts Slip frequency setting in Hz Dead Bus Charging Voltage setting in volts Live Bus Voltage setting in volts 15 5.5 0.1 20 32 > 20% > 30%
o

5%

D. Settings of Relays For 33 KV Transformer Feeder


1.0 BASIC DATA a. b. c. d. e. f. System voltage Selected CT Ratio = In = Rated current in amps corresponding to CT ratio of 250/1A = Minimum symmetrical 3-Ph S/C current in amps at 33 KV bus = Reflected current on 33 KV side due to fault at 6.6kV side of trafo and minimum fault level condition = Rated primary current in amps of 31.5 MVA Transformer = 33 600/1 600 11650 2256 551 kV A A A A A

Consultant : SATCON

Page 5 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J

g. h.

Relay used Setting ranges : I> I>> I>>> TMS = Definite time setting =

MICOM P122 steps 0.1-25In 0.5-40In 0.5-40In 0.025-1.5 0-150 sec @ 0.01 In @ 0.01 In @ 0.01 In @ 0.025 @ 0.01 sec

2.0 SETTING VALUES 2.1 Proposed Is (IDMT) setting for O/C (51), I> a. b. c. d. Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Is = Current in amps corresponding to PS = PS*In Proposed TMS setting = IEC SI 1 600 0.325 Standard inverse

2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 1.5 900 0.95

2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. b. c. Minimum Isc setting proposed in multiples (M) of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 5 3000 0.05

2.4 Time of Operation for Different Fault Current


Current in Amps Multiples of Set Current Equivalent MVA Time of Operation in sec.

Zone of Operation DT Zone (I>>>)

12000 3000 3000 3000 900 900 11650 6000 4200 3000 2256

20 5 5 5 1.5 1.5 19.42 10.00 7.00 5.00 3.76

685.89 171.47 171.47 171.47 51.44 51.44 665.89 342.95 240.06 171.47 128.95

0.05 0.05 0.95 0.95 0.95 5.59 0.74 0.97 1.15 1.39 1.70

DT Zone (I>>)

Consultant : SATCON

Page 6 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 1200 1140 1080 1020 960 900 840 780 720 660 2.00 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 68.59 65.16 61.73 58.30 54.87 51.44 48.01 44.58 41.15 37.72 3.26 3.52 3.85 4.26 4.82 5.59 6.74 8.65 12.46 23.85 IDMT zone I>

E. Settings of Relays for 6.6 KV I/C From 25/31.5 MVA Trafo


1.0 BASIC DATA a. b. c. d. e. f. g. h. System voltage Selected CT Ratio = In = Rated current in amps corresponding to CT ratio of 250/1A = Minimum symmetrical 3-Ph S/C current in amps at 6.6 KV bus = Reflected current on 33 KV side due to fault on 6.6kV side of trafo and minimum fault level condition = Rated primary current (at 6.6kV) in amps of 31.5 MVA Transformer = Relay used Setting ranges for overcurrent relays : I> (IDMT) I>> (DT-1) I>>> (DT-2) TMS = Definite time setting = 2.0 SETTING VALUES 2.1 Proposed IDMT setting for O/C (51), a. b. c. d. Curve used for IDMT setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = I>1 = Current in amps corresponding to PS = PS*In Proposed TMS setting = IEC SI 0.9 2700 0.275 Standard inverse 0.1-4 In 0.1-30 In 0.1-30 In 0.05 - 10 0-100 sec 6.6 3000/1 3000 11280 2256 2756 MICOM P632 kV A A A A A

2.2 Proposed I> (DT) setting for O/C (50-1) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = 1.5 4500 0.65 Not used

2.3 Proposed I>> (DT) setting for O/C (50-2) a. Minimum Isc setting proposed in multiples M of In b. Isc Current in amps corresponding to Isc setting = M*In

Consultant : SATCON

Page 7 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c. Proposed DT time in sec =

2.4 Time of Operation for Different Fault Current


Current in Amps Multiples of Set Current Equivalent MVA Time of Operation in sec.

60000 4500 4500 27000 24300 18900 10800 11280 8100 5400 5130 4860 4590 4500 4320 4050 3780 3510 3240 2970

20 1.5 1.5 10 9 7 4 4.1777 3 2 1.9 1.8 1.7 1.6666 1.6 1.5 1.4 1.3 1.2 1.1

685.89 51.44 51.44 308.65 277.79 216.06 123.46 128.95 92.60 61.73 58.64 55.56 52.47 51.44 49.38 46.30 43.21 40.12 37.04 33.95

0.65 0.65 3.75 0.82 0.86 0.97 1.37 1.33 1.73 2.76 2.98 3.26 3.61 3.75 4.08 4.73 5.70 7.32 10.54 20.18

Zone of Operation DT zone I>>

IDMT zone I>

2.5 Undervoltage protection (27) a. b. c. d. V< in volts = 0.4*Vn (I/C brkr trip) DT setting in sec = V<< in volts = 0.8*Vn (Annunciation, I/C brkr closing circuit interlock) DT setting in sec = 44 2.5 88 2

2.6 Overvoltage protection (59) a. b. V> in volts = 1.1*Vn (For annunciation) DT setting in sec = 121 1 Available range 0.3 0.8 2756 551 27556 55112 0.1-2.5 x I ref 5-30 x I ref 5-30 x I ref 0.2-0.5 0.4-1.5

2.7 Transformer Differential Protection (87T) a. b. c. d. e. f. m1 m2 I ref = Trafo full load current in amps on 31.5 MVA base (FLC) Idiff> in amps = 0.2 x I ref Idiff>> in amps = 10 x I ref Idiff>>> in amps = 20 x I ref

Consultant : SATCON

Page 8 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J g. h. IRm2 in amps = 4 x I ref Rush I in amps = 0.2 x I ref 11022 551 1.5-10 x I ref 0.1-0.5 x I ref

F. Settings of Relays for 6.6 KV Bus Coupler


1.0 BASIC DATA a. System voltage in kV b. c. d. e. f. Selected CT Ratio = In = Rated current in amps corresponding to CT ratio of 1500/1A = Minimum symmetrical 3-Ph S/C current in amps at 11 KV bus = Relay used Setting ranges : IDMT I> DT I>> DT I>>> DT TMS = Definite time setting = 2.0 SETTING VALUES 2.1 a. b. c. d. Proposed IDMT setting for O/C (51), Curve used for IDMT setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = I>1 = Current in amps corresponding to PS = PS*In Proposed TMS setting = 0.1-4In 0.1-40In 0.1-40In 0.1-40In 0.05-10 0-100 sec 6.6 1500/ 1A 1500 11280 MICOM P132 A A

IEC SI 1 1500 0.275

Standard inverse

2.2 Proposed I> (DT) setting for O/C (50-1) a. Minimum Isc setting proposed in multiples M of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

1.5 2250 1.3

2.3 Proposed I>> (DT) setting for O/C (50-2) a. Minimum Isc setting proposed in multiples M of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

3 4500 0.35 Not used

2.4 Proposed I>>> (DT) setting for O/C (50-3) a. Minimum Isc setting proposed in multiples (M) of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

2.5 Time of Operation for Different Fault Current


Current in Amps Multiples of Set Current Equivalent MVA Time of Operation in sec.

30000 Consultant : SATCON

20

342.95

0.35

Zone of Operation DT zone Page 9 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 4500 4500 2250 2250 11280 4500 3750 3000 2850 2700 2550 2400 2250 2100 1950 1800 1650 3 3 1.5 1.5 7.520 3 2.5 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 51.44 51.44 25.72 25.72 128.95 51.44 42.87 34.29 32.58 30.87 29.15 27.44 25.72 24.01 22.29 20.58 18.86 0.35 1.30 1.30 4.73 0.93 1.73 2.08 2.76 2.98 3.26 3.61 4.08 4.73 5.70 7.32 10.54 20.18 IDMT zone I>> DT zone I>

2.6 25 Check Synchronisation a. b. c. d. e. Phase angle setting Vdiff setting in volts Slip frequency setting in Hz Dead Bus Charging Voltage setting in volts Live Bus Voltage setting in volts 15o 5.5 0.1 20 32 > 20% > 30% 5%

G. Settings of Relays for 6.6 KV O/G Fdr to Capacitor bank


1.0 BASIC DATA a System voltage in kV b d e g h f. g. Selected CT Ratio = In = Rated current in amps corresponding to CT ratio of 125/1A = Minimum symmetrical 3-Ph S/C current in amps at 6.6 KV bus = Capacitor bank rating = Load current = Relay used Setting ranges : I> I>> I>>> TMS = Definite time setting = 2.0 SETTING VALUES 0.1-25In 0.5-40In 0.5-40In 0.025-1.5 0-150 sec 6.6 125/1 125 11280 250 21.87 MICOM P127 steps @ 0.01 In @ 0.01 In @ 0.01 In @ 0.025 @ 0.01 sec A A A KVAR A

Consultant : SATCON

Page 10 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 2.1 Proposed Is (IDMT) setting for O/C (51) a. Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] b. c. d. Plug setting (PS) proposed = Is = Current in amps corresponding to PS = PS*In Proposed TMS setting =

IEC SI 0.225 28.125 0.200

Standard Inverse

2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. Minimum Isc setting proposed in multiples M of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

4 500 0.05 Not used

2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. Minimum Isc setting proposed in multiples (M) of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

2.4 Time of Operation for Different Fault Current


Current in Amps Multiples of Set Current Equivalent MVA Time of Operation in sec.

2500 500 500 500 281 169 113 56 53 51 48 45 42 39 37 34 31

20 4 4 17.7777 10 6 4 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1

28.58 5.72 5.72 5.72 3.22 1.93 1.29 0.64 0.61 0.58 0.55 0.51 0.48 0.45 0.42 0.39 0.35

0.05 0.05 0.47 0.47 0.59 0.77 1.00 2.01 2.17 2.37 2.62 2.96 3.44 4.15 5.32 7.66 14.67

Zone of Operation DT zone I>>

IDMT zone I>

2.5 Undervoltage protection (27) a. U< in volts = 0.8*Vn (For tripping) b. DT setting in sec =

88 1.00

Bus PT supply =110V

2.6 Residual overvoltage/neutral displacement protection (60) a. Ue> in volts = 0.06*Vn (For Alarm) b. DT setting in sec =

6.6 0.05

Bus PT supply =110V

Consultant : SATCON

Page 11 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c. d. Ue>> in volts = 0.2*Vn (For tripping) DT setting in sec = 22 0.1

H. Settings of Relays for 6.6 KV O/G Fdr to 1600 KVA Transformer


1.0 BASIC DATA a. b. c. d. e. f. g. h. System voltage Selected CT Ratio = In = Rated current in amps corresponding to CT ratio of 250/1A = Minimum symmetrical 3-Ph S/C current in amps at 6.6 KV bus = Reflected current on 6.6 KV side due to fault on 415V side of trafo and minimum fault level condition = Rated primary current in amps of 1600 KVA Transformer = Relay used Setting ranges : I> I>> I>>> TMS = Definite time setting = 2.0 SETTING VALUES 2.1 Proposed Is (IDMT) setting for O/C (51), I> a. Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] b. c. d. Plug setting (PS) proposed = Is = Current in amps corresponding to PS = PS*In Proposed TMS setting = 0.1-25In 0.5-40In 0.5-40In 0.025-1.5 0-150 sec 6.6 250/1 250 11280 2165 140 MICOM P122 steps @ 0.01 In @ 0.01 In @ 0.01 In @ 0.025 @ 0.01 sec kV A A A A A

IEC SI 0.75 187.5 0.375

Standard inverse

2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. Minimum Isc setting proposed in multiples M of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

0.9 225 1

2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. Minimum Isc setting proposed in multiples (M) of In b. c. Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

11.5 2875 0.05

2.4 Time of Operation for Different Fault Current


Current in Amps Multiples of Set Current Equivalent MVA Time of Operation in sec.

5000 2875 2875

20 11.5 11.5

57.16 32.87 32.87

0.05 0.05 1.00

Zone of Operation DT Zone (I>>>)

Consultant : SATCON

Page 12 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 2875 225 225 11280 2165 1688 938 375 356 338 319 300 281 263 244 225 206 11.5 0.9 0.9 60.16 11.55 9.00 5.00 2.00 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 32.87 2.57 2.57 128.95 24.75 19.29 10.72 4.29 4.07 3.86 3.64 3.43 3.22 3.00 2.79 2.57 2.36 1.00 1.00 14.37 0.61 1.05 1.17 1.60 3.76 4.06 4.44 4.92 5.56 6.45 7.78 9.98 14.37 27.52 IDMT zone I> DT Zone (I>>)

I. Settings of Relays for 6.6 KV Bus PT


1 RELAY TYPE MICOM P922 110

1.1 Rated PT secondary voltage (Vn) 1.2 Undervoltage protection (27) a. b. c. d. V< in volts = 0.4*Vn (I/C and B/C brkr closing circuit interlock) DT setting in sec = V<< in volts = 0.8*Vn (I/C and B/C brkr closing circuit interlock, u/v trip of motor feeders) DT setting in sec =

44 2.5 88 2

1.3 Overvoltage protection (59) a. b. V> in volts = 1.1*Vn (For annunciation and tripping of capacitor feeders) DT setting in sec = 121 1

1.4 Residual overvoltage/neutral displacement protection (60) a. b. c. d. V0> in volts = 0.06*Vn (For Alarm) DT setting in sec = V0>> in volts = 0.2*Vn (for tripping of respective I/C) DT setting in sec = 6.6 0.05 20 0.1

J. Settings of Relays for IC & BC at 415V PCC


1.0 BASIC DATA Consultant : SATCON Page 13 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J a. b. c. d. e. f. System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 415V bus during 3phase fault = In = Rated primary current in amps corresponding to selected CT ratio Relay used Setting ranges : I> inverse I> definite time I>> definite time TMS = Definite time setting for I> = Definite time setting for I>> = g. h. i. j. k. l. n. Transformer rating = Voltage ratio = Transformer full load current, HV = Transformer full load current, LV = Transformer vector group = Transformer % impedance = Through fault current at HV side = 0.5 - 2.5 In 0.5 - 5.0 In 0.5 - 40.0 In and infinity 0.05 - 1.0 0.05 - 300s 0.04 - 300s 1600 6600/433 140 2133 Dyn11 6.25% 33007 2165.46 A (From ETAP output) A kVA V A A 0.415 3000/5 33007 3000 SPAJ 140C kV A A A (ABB)

m. Through fault current at LV side =

2.0 SETTING VALUES 2.1 Proposed I> (IDMT) setting for O/C (51), a. b. c. d. Curve used for I> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = I> = Current in amps corresponding to PS = PS*In Proposed TMS setting = IEC SI 0.85 2550 0.275 1.1 3300 0.7 (Assumed) Standard inverse

2.2 Proposed I> (DT) setting for O/C (50) a. b. c. Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

2.3 Proposed I>> (DT) setting for O/C (50) a. b. c. Minimum Isc setting proposed in multiples (M) of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =

Not used

2.4 Time of Operation for Different Fault Current

Consultant : SATCON

Page 14 of 15

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
CURRENT IN AMPS (I) I = MxIs MULTIPLES OF SET CURRENT (M) M EQUIVALENT TIME OF OPERATIOM MVA (sec) MVA sec

ZONE OF OPERATION

60000 3300 3300 33007 25500 22950 20400 17850 15300 12750 10200 7650 5100 4845 4590 4335 4080 3825 3570 3315 3300 3060 2805

20 1.1 1.1 12.9439 10 9 8 7 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.29411 1.2 1.1

43.13 2.37 2.37 23.73 18.33 16.50 14.66 12.83 11.00 9.16 7.33 5.50 3.67 3.48 3.30 3.12 2.93 2.75 2.57 2.38 2.37 2.20 2.02

0.7 0.7 7.45 0.73 0.82 0.86 0.91 0.97 1.06 1.18 1.37 1.73 2.76 2.98 3.26 3.61 4.08 4.73 5.70 7.32 7.45 10.54 20.18

DT Zone (I>>)

IDMT Zone (I>)

2.5 Undervoltage protection (27) at incomer a. Relay used


b. c. d. e. Available setting = Time = Selected setting = Purpose

VAGM22 40-80 Inst. 40 Tripping & Annc. % %

2.6 Overvoltage protection (59) at incomer a. b. c. d. e. Relay used Available setting = Time = Selected setting = Purpose VAGM22 110-140 Inst. 110 Tripping % %

Consultant : SATCON

Page 15 of 15

OVERCURRENT COORDINATION CHART FOR LBDS-9

10

TIME IN SECONDS

0.1

0.01 1.00 33kV INCOMER 6.6KV BUS COUPLER 10.00 33KV BUS COUPLER 6.6KV TRAFO FDR LTPCC

MVA
33KV TRAFO FDR

100.00 6.6KV INCOMER

1000.00

415V PCC INCOMER

CONSORTIUM

RELAY SETTING CALCULATION FOR EARTH FAULT RELAYS OF LBDS-9

Subject. Project

Relay Setting Calculation Doc. No. ISP/AREVA-EMC-A/IX/22/16/29/DE/1007J LBDS Package 22 - New Stream 2.5 MT Expansions at IISCO Steel Plant Page- 1

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J A. 1.0 a. b. c. d. e. f. 33kV INCOMER BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 2.0 2.1 a. b. c. d. 2.2 a. b. c. 2.3 SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec

33 800/1 400 800 MICOM P127 0.1 - 1.0 In 0.1 - 8 In 0.025 - 1.5 0 - 150 sec

kV A A A

@ 0.005 In (Inverse time) @ 0.005 In (Definite time) @ 0.025 @ 0.01 sec

IEC SI 0.15 120 0.15

Standard inverse

0.25 200 0.7

ZONE OF OPERATION

16000 200 200 2400 1800 1200 1080 960 840 720 600 480 400 360 240

20 0.25 0.25 20 15 10 9 8 7 6 5 4 3.3333 3 2

914.52 11.43 11.43 137.18 102.88 68.59 61.73 54.87 48.01 41.15 34.29 27.44 22.86 20.58 13.72

0.7 0.7 2.05 0.34 0.38 0.45 0.47 0.49 0.53 0.58 0.64 0.75 0.86 0.95 1.50

DT Zone (Ie>>)

IDMT Zone (Ie>)

Consultant : SATCON

Page 2 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 228 216 204 200 192 180 168 156 144 132 1.9 1.8 1.7 1.6666 1.6 1.5 1.4 1.3 1.2 1.1 13.03 12.35 11.66 11.43 10.97 10.29 9.60 8.92 8.23 7.54 1.63 1.78 1.97 2.05 2.22 2.58 3.11 3.99 5.75 11.01

B. 1.0 a. b. c. d.

33kV BUS COUPLER BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.01 - 4.0 In 0.002 - 8.0 In 0.05 - 10 0 - 100 sec (Inverse time) (Definite time) 33 400/1 400 400 kV A A A

e. f.

MICOM P132

2.0 2.1 a. b. c. d. 2.2 a. b. c. 2.3

SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec

IEC SI 0.2 80 0.125

Standard inverse

0.4 160 0.4

ZONE OF OPERATION

8000 160 160

20 0.4 0.4

457.26 9.15 9.15

0.4 0.4 1.25

DT Zone (Ie>>)

Consultant : SATCON

Page 3 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J

800 720 640 560 480 400 240 160 152 144 136 128 120 112 104 96 88

10 9 8 7 6 5 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1

45.73 41.15 36.58 32.01 27.44 22.86 13.72 9.15 8.69 8.23 7.77 7.32 6.86 6.40 5.94 5.49 5.03

0.37 0.39 0.41 0.44 0.48 0.53 0.79 1.25 1.35 1.48 1.64 1.85 2.15 2.59 3.33 4.79 9.17 IDMT Zone (Ie>)

C. 1.0 a. b. c. d.

33kV TRANSFORMER FEEDER FOR 25/31.5 MVA TRAFO BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.1 - 1.0 In 0.1 - 8 In 0.025 - 1.5 0 - 150 sec @ 0.005 In (Inverse time) @ 0.005 In (Definite time) @ 0.025 @ 0.01 sec 33 600/1 400 600 kV A A A

e. f.

MICOM P122

2.0 2.1 a. b. c. d. 2.2 a. b. c. 2.3

SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current 0.2 120 0.1 IEC SI 0.1 60 0.05 Standard inverse

Consultant : SATCON

Page 4 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J

CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M

EQUIVALENT MVA MVA

TIME OF OPERATIOM (sec) sec

ZONE OF OPERATION

12000 120 120 1200 900 600 540 480 420 400 360 300 240 180 120 114 108 102 96 90 84 78 72 66 D. 1.0 a. b. c. d.

20 0.2 0.2 20 15 10 9 8 7 6.6666 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1

685.89 6.86 6.86 68.59 51.44 34.29 30.87 27.44 24.01 22.86 20.58 17.15 13.72 10.29 6.86 6.52 6.17 5.83 5.49 5.14 4.80 4.46 4.12 3.77

0.1 0.1 0.50 0.11 0.13 0.15 0.16 0.16 0.18 0.18 0.19 0.21 0.25 0.32 0.50 0.54 0.59 0.66 0.74 0.86 1.04 1.33 1.92 3.67

DT Zone (Ie>>)

IDMT Zone (Ie>)

6.6KV INCOMER FROM 25/31.5 MVA TRAFO BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 415V bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.1 - 0.8 In 0.1 - 8 In 0.05 - 10 0 - 100 sec (Inverse time) (Definite time) 6.6 3000/1 600 3000 kV A A A

e. f.

MICOM P632

2.0 2.1

SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N),

Consultant : SATCON

Page 5 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J a. b. c. d. 2.2 a. b. c. 2.3 Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec

IEC SI 0.1 300 0.075

Standard inverse

0.12 360 0.7

ZONE OF OPERATION

60000 360 360 3000 2700 2400 2100 1800 1500 1200 900 600 570 540 510 480 450 420 390 375 360 330 2.4 a. b.

20 0.12 0.12 10 9 8 7 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.25 1.2 1.1

685.89 4.12 4.12 34.29 30.87 27.44 24.01 20.58 17.15 13.72 10.29 6.86 6.52 6.17 5.83 5.49 5.14 4.80 4.46 4.29 4.12 3.77

0.7 0.7 2.87 0.22 0.23 0.25 0.26 0.29 0.32 0.37 0.47 0.75 0.81 0.89 0.98 1.11 1.29 1.56 2.00 2.35 2.87 5.50

DT Zone (Ie>>)

IDMT Zone (Ie>)

REF (64R) [Biasing by residual current] Instantaneous Idiff> in amps = 0.1*FLC m= 300 1.005 (fixed slope)

E. 1.0 a. b.

BACK UP E/F (51G) AT 25/31.5 MVA TRAFO NEUTRAL


BASIC DATA System voltage in kV Selected CT Ratio = 0.415 600/1 kV A

Consultant : SATCON

Page 6 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c. d. Symmetrical S/C current in amps at 415V bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> TMS = 2.0 2.1 a b c d 2.2 SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51G), Curve used for Ie>1 (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec

36950 600

A (Based on ETAP fault calculation) A

e. f.

MICOM P111 0.01 - 1.0 In 0.025 - 1.2

(Inverse time)

IEC SI 0.55 330 0.1

Standard inverse

ZONE OF OPERATION

6600 4950 3300 2970 2640 2310 1980 1650 1320 990 660 627 600 594 561 528 495 462 429 396 363

20 15 10 9 8 7 6 5 4 3 2 1.9 1.8181 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1

75.45 56.59 37.72 33.95 30.18 26.41 22.63 18.86 15.09 11.32 7.54 7.17 6.86 6.79 6.41 6.04 5.66 5.28 4.90 4.53 4.15

0.23 0.25 0.30 0.31 0.33 0.35 0.38 0.43 0.50 0.63 1.00 1.08 1.16 1.18 1.31 1.48 1.72 2.07 2.66 3.83 7.34 IDMT Zone (Ie>)

F. 1.0 a.

6.6kV BUS COUPLER BASIC DATA System voltage in kV 6.6 kV

Consultant : SATCON

Page 7 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J b. c. d. Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 2.0 2.1 a. b. c. d. 2.2 a. b. c. 2.3 SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec

1500/1 600 1500

A A A

e. f.

MICOM P132 0.01 - 4.0 In 0.002 - 8.0 In 0.05 - 10 0 - 100 sec

(Inverse time) (Definite time)

IEC SI 0.09 135 0.1

Standard inverse

0.15 225 0.4

ZONE OF OPERATION

30000 225 225 1350 1215 1080 945 810 675 600 405 270 257 243 225 216 203 189

20 0.15 0.15 10 9 8 7 6 5 4.4444 3 2 1.9 1.8 1.66666 1.6 1.5 1.4

342.95 2.57 2.57 15.43 13.89 12.35 10.80 9.26 7.72 6.86 4.63 3.09 2.93 2.78 2.57 2.47 2.31 2.16

0.4 0.4 1.36 0.30 0.31 0.33 0.35 0.38 0.43 0.46 0.63 1.00 1.08 1.18 1.36 1.48 1.72 2.07

DT Zone (Ie>>)

IDMT Zone (Ie>)

Consultant : SATCON

Page 8 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 176 162 149 1.3 1.2 1.1 2.01 1.85 1.70 2.66 3.83 7.34

G. 1.0 a. b. c. d.

6.6kV TRANSFORMER FEEDER FOR LTPCC BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 6.6kV bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.1 - 1.0 In 0.1 - 8 In 0.025 - 1.5 0 - 150 sec @ 0.005 In (Inverse time) @ 0.005 In (Definite time) @ 0.025 @ 0.01 sec 6.6 250/1 600 250 kV A A A

e. f.

MICOM P122

2.0 2.1 a. b. c. d. 2.2 a. b. c. 2.3

SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec

IEC SI 0.1 25 0.075

Standard inverse

0.2 50 0.1

ZONE OF OPERATION

5000 50 50 600 375 250 225 200 175 150

20 0.2 0.2 24 15 10 9 8 7 6

57.16 0.57 0.57 6.86 4.29 2.86 2.57 2.29 2.00 1.71

0.1 0.1 0.75 0.16 0.19 0.22 0.23 0.25 0.26 0.29

DT Zone (Ie>>)

IDMT Zone

Consultant : SATCON

Page 9 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 125 100 75 50 48 45 43 40 38 35 33 30 28 H. 1.0 a. b. c. d. 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 1.43 1.14 0.86 0.57 0.54 0.51 0.49 0.46 0.43 0.40 0.37 0.34 0.31 0.32 0.37 0.47 0.75 0.81 0.89 0.98 1.11 1.29 1.56 2.00 2.87 5.50 (Ie>)

415V INCOMER AND BUS COUPLER BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 415V bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> Ie>> TMS = Definite time setting = 0.1 - 0.8 In 0.1 - 10 In 0.05 - 1.0 0.05 - 300 sec (Inverse time) (Definite time) 0.415 3000/5 36950 3000 kV A A (Based on ETAP fault calculation) A

e. f.

SPAJ 140C

2.0 2.1 a. b. c. d. 2.2 a. b. c. 2.3

SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51N), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Proposed Ie>> (DT) setting for E/F (50N) Minimum Isc setting proposed in multiples M of In Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec = Time of Operation for Different Fault Current
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec

IEC SI 0.1 300 0.525

Standard inverse

0.12 360 0.7

ZONE OF OPERATION DT Zone

60000

20

43.13

0.7

Consultant : SATCON

Page 10 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 360 360 36950 4500 3000 2700 2400 2100 1800 1500 1200 900 600 570 540 510 480 450 420 390 375 360 330 0.12 0.12 123.1666 15 10 9 8 7 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.25 1.2 1.1 0.26 0.26 26.56 3.23 2.16 1.94 1.73 1.51 1.29 1.08 0.86 0.65 0.43 0.41 0.39 0.37 0.35 0.32 0.30 0.28 0.27 0.26 0.24 0.7 20.12 0.73 1.32 1.56 1.64 1.73 1.85 2.01 2.25 2.61 3.31 5.27 5.69 6.22 6.89 7.78 9.03 10.89 13.97 16.43 20.12 38.52 IDMT Zone (Ie>) (Ie>>)

J. 1.0 a. b. c. d.

BACK UP E/F (51G) AT 1.6 MVA TRAFO NEUTRAL


BASIC DATA System voltage in kV Selected CT Ratio = Symmetrical S/C current in amps at 415V bus during SLG fault = Rated primary current in amps corresponding to selected CT ratio, In = Relay used Setting ranges : Ie> TMS = 0.2 - 0.8 In 0.1 - 1.0 (Inverse time) 0.415 500/5 36950 500 kV A A (Based on ETAP fault calculation) A

e. f.

CDG 11

(3 sec version)

2.0 2.1 a b c d 2.2

SETTING VALUES Proposed Ie> (IDMT) setting for E/F (51G), Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = Ie> = Current in amps corresponding to PS = PS*In Proposed TMS setting = Time of Operation for Different Fault Current IEC SI 0.6 300 0.75 Standard inverse

Consultant : SATCON

Page 11 of 12

SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M EQUIVALENT MVA MVA TIME OF OPERATIOM (sec) sec

ZONE OF OPERATION

36950 4500 3000 2700 2400 2100 1800 1500 1200 900 600 570 540 510 480 450 420 390 360 330

123.1666 15 10 9 8 7 6 5 4 3 2 1.9 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1

26.56 3.23 2.16 1.94 1.73 1.51 1.29 1.08 0.86 0.65 0.43 0.41 0.39 0.37 0.35 0.32 0.30 0.28 0.26 0.24

1.04 1.89 2.23 2.34 2.47 2.65 2.88 3.21 3.73 4.73 7.52 8.13 8.88 9.84 11.12 12.90 15.55 19.96 28.74 55.03 IDMT Zone (Ie>)

Consultant : SATCON

Page 12 of 12

EARTH FAULT PROTECTION COORDINATION CURVES FOR 415V

100

10

TIME IN SEC

0.1 0.10 1.00 415V Incomer

MVA
Back Up 51G

10.00 SLGF fault Current 36950A

SLG Fault Current = 36950A

100.00

Consultant : SATCON

EARTH FAULT PROTECTION COORDINATION CURVES FOR 6.6KV

10

TIME IN SEC

0.1 0.10 6.6kV TRAFO FDR 1.00 6.6KV BUS COUPLER 10.00 6.6KV INCOMER

600A SLG

MVA

100.00 600A SLG FAULT

1000.00

51G at 6.6kV NEUTRAL

Consultant : SATCON

EARTH FAULT PROTECTION COORDINATION CURVES FOR 33KV

100

10

TIME IN SEC

0.1 1.00 33kV TRAFO FDR 10.00

400A SLG Fault Current

MVA
33KV BUS COUPLER

100.00 400A SLG FAULT 33KV INCOMER

1000.00

Consultant : SATCON

Project: Location: Contract: Engineer: Filename:

ISP MODERNISATION BURNPUR AREVA SATCON LBDS9LT

ETAP
7.0.0C

Page: Date: SN:

1 07-08-2011 SATCON2007 Base Normal

Study Case: SC

Revision: Config.:

SHORT CIRCUIT CALCULATION AT LT BUS

Short-Circuit Summary Report


3-Phase, LG, LL, LLG Fault Currents Bus
ID LV SWBD kV 0.433 I"k 33.007

3-Phase Fault
ip 79.775 Ik 33.007 I"k

Line-to-Ground Fault
ip 89.314 Ib 36.954 Ik 36.954 I"k 28.585

Line-to-Line Fault
ip 69.087 Ib 28.585 Ik 28.585 I"k

*Line-to-Line-to-Ground
ip 86.248 Ib 35.685 Ik 35.685

36.954

35.685

All fault currents are in rms kA. Current ip is calculated using Method C. * LLG fault current is the larger of the two faulted line currents.

Project: Location: Contract: Engineer: Filename:

ISP MODERNISATION BURNPUR AREVA SATCON LBDS9LT

ETAP
7.0.0C

Page: Date: SN:

2 07-08-2011 SATCON2007 Base Normal

Study Case: SC

Revision: Config.:

SHORT CIRCUIT CALCULATION AT LT BUS

Sequence Impedance Summary Report


Bus
ID LV SWBD kV 0.433

Positive Seq. Imp. (ohm)


Resistance 0.00093 Reactance 0.00790 Impedance 0.00795

Negative Seq. Imp. (ohm)


Resistance 0.00093 Reactance 0.00790 Impedance 0.00795

Zero Seq. Imp. (ohm)


Resistance 0.00075 Reactance 0.00535 Impedance 0.00541

Fault Zf (ohm)
Resistance 0.00000 Reactance 0.00000 Impedance 0.00000

One-Line Diagram - OLV1 (Short-Circuit Analysis - 3 PHASE FAULT)

6.6KV BUS 129 MVAsc

MV SWBD 6.6 kV

2.17
V 28 k 5.

DS

T1 1.6 MVA 6.6/0.433 kV 6.25 %Z

LV SWBD 0.433 kV

33.01
33.0 kA

LV LOAD 1.2 MVA


page 1 10:37:45 Aug 07, 2011 Project File: LBDS9LT

One-Line Diagram - OLV1 (Short-Circuit Analysis - SLG FAULT)

6.6KV BUS 129 MVAsc

MV SWBD 6.6 kV
V 81 k 3.

DS

T1 1.6 MVA 6.6/0.433 kV 6.25 %Z


V 23 k 0.

LV SWBD 0.433 kV

36.95
36.9 5 kA

LV LOAD 1.2 MVA


page 1 10:38:58 Aug 07, 2011 Project File: LBDS9LT