AIR CONDITIONING LOAD ESTIMATE

DATE22 / 05 / 2000..

PROJECT : ........., SRI LANKA

FLOOR : 1st Floor-Office


AREA : 6,779 SQFT

ITEM

AREA OR QUANTITY

SUNGAIN OR FACTOR TEMP.DIFF.

BTU/HR

ESTIMATE FOR

LOCAL TIME SUN TIME

PEAK LOAD

LOCAL TIME SUN TIME

3&4

SOLAR GAIN - GLASS GLASS GLASS GLASS GLASS SKYLIGHT 193.7 SQFT 129.1 SQFT 516.5 SQFT 0 SQFT SQFT SOLAR &TRANS.GAIN-WALLS & ROOF WALL WALL WALL WALL ROOF-SUN POOF-SHADED TRANS. GAIN-EXCEPT WALLS & ROOF ALL-GLASS PARTITION 839.28 SQFT SQFT 0 SQFT 968.4 SQFT CEILING FLOOR 6,779 SQFT 6,779 SQFT 406.728 CFM INTERNAL HEAT PEOPLE 70 PEOPLE 50 HPorKW 5,000 WATTS 245 200 3.4 0.85 0.8 0.85 14,577.50 8,000.00 14,450.00 TEMP RISE DEHUM CFM 200,139.17 SQFT SUB TOTAL SAFETY FACTOR SQFT 3% ROOM SENSIBLE HEAT SUPPLY EAT GAIN SUPPLY SUPPLY DUCT LEAK.LOSS 1355.76 16.2 0.2 DUCT FAN 5,003.48 205,142.65 8 (1 - BF) X (Trm - Tadp) ADP INDICATED ADP 16.2 41.2 11.2 16.2 16.2 16.2 16.2 1.13 0.3 0.3 0.3 0.31 0.52 1.08 15,363.86 0.00 0.00 4,706.42 34,043.13 57,104.61 7,116.11 ESHF EFFECTIVE SENS HEAT FACTOR = CFM OUTDOOR AIR THROUGH APPARATUS APPERATUS DEW POINTS EFFECTIVE ROOM SENS.HEAT EFFECTIVE ROOM TOTAL .HEAT = 597.18 SQFT 661.74 SQFT 613.32 SQFT 0 SQFT SQFT

4.00PM 164 164 15 69


0.54 0.54 0.54 0.54 17,152.30 11,434.87 4,183.49 0.00 2 HOURS OF OPERATION CONDITIONS OUT DOOR(OA) ROOM(RM) DIFFERENCE DB 91.4 75.2 16.2 70 PEOPLE 6,779 SQFT WB 82.4 64 18.4 55% %RH DP GR/LB 155 70 85 630.00 1355.76 1355.76

W E N S 5 W E N S

OUT DOOR AIR


0.34 0.34 0.34 0.34 0.51 3,654.74 5,849.78 2,502.35 0.00 0.00

18 26 12 24
41

VENTILATION

9 CFM/PERSON 0.2 CFM/SQFT CFM VENTILATION

INFILTRATION SWINGING
REVOLVING DOORS PEOPLE DOORS FEET CFM/PERSON CFM/DOOR CFM/FT CFM INFILTRATION 406.728

OPEN DOORS EXHAUST FAN CRACK

1355.76

INFILTRATION

0.816

RSHF
54 F =

0.852 GSHF
SELECTED ADP 18.02 F 54 F

0.737

3&7

POWER LIGHTS

DEHHUMIDIFIED AIR QUANTITY

APPLIANCES.ETC. ADDITIONAL HEAT GAINS


SUB TOTAL

EFFECTIVE ROOM SENS HEAT 1.08 X TEMP RISE ROOM SENS. HEAT 1.08 X CFM DA ROOM SENS. HEAT 1.08 X F des diff
CFM SA CFM DA

10,785

CFMDA

2&3

STORAGE

OUT LET TEMP DIFF

=
205,142.65 18.38

17.61 F (RM OUTLET AIR)

SUPPLY AIR QUANTITY

SUPPLY CFM

11,160 CFMSA

BY PASS CFM
1.08 4,744.08 209,886.72 23,508.88 12,197.50 0.00 EDB LDB

375.6

CFMBA

8 6

OUTDOOR AIR

RESULTING ENT &LVG CONDITIONS AT APPARATUS 77.17 F 57.5 F FROM PSYCH CHART EWB = NOTES 67 F LWB = 57 F

EFFCTIVE ROOM SENSIBLE HEAT LATENT HEAT INFILTRATION PEOPLE 406.728 CFM PEOPLE X 70 PEOPLE 85 205 0.68 0.85

3&7

STEAM

lb/hr

1050

APPLIANCES ETC.
ADDITIONAL HEAT GAINS

VAPORTRANS. SAFETY FACTOR h

SQFTXI/100X

GR/LBX

CHECK FIGURES a) b) CFM/TR SQFT/TR CFM/SQFT = SELECT MODAL = = 450 273 1.65

SUB TOTAL

7
SUPPLY DUCT LEAKAGE LOSS OUTDOOR AIR CFM X GRABL X 1355.76 CFM

ROOM LATENT HEAT BF X 0.68 85 0.102

35,706.38 11,754.44 47,460.82

c)

EFFIECTIVE ROOM LATENT HEAT

EFFECTIVE ROOM TOTAL HEAT OUT DOOR AIR HEAT SENSIBLE: LATENT: 630.00 CFM 630.00 CFM SUB TOTAL GRAND TOTAL HEAT 16.2 85 0.918 0.578

257,347.54
9,369.11 30,951.90 40,321.01 297,668.55 ACTUAL CAPACITY TR CFM

RETURN DUCT HEAT GAIN

DUCT

RETURN DUCT HP LEAK. GAIN PUMP1

DEHUM & PIPE LOSS

24.8 273.28 sq.ft/TR

PREPARED BY: Indrajeewa CHECKED BY : Ramon