Baghdad on 28/7/ 2012 No: 25 To-M/S: Tagreed Company S/Repair Offer Dear Sir, After our staff inspect

your Gensets on 30/5/2012 an accordingly regard the gen sets model C1400-D5 , and according to more photos clarified that the gensets working too long time we Found the following: 1- A0K537300 ESN: 3315748 A- Control assembly of HMI was lost B- Radiator Very dirty need to clean it or replaced C- Replaced Anti freeze coolant D- Replaced All filters E- The engine not running so it need another inspection when HMI available 2- B04K404860 ESN :33155749 A- Replace Antifreeze Coolant B- Replace injectors C- Replace all filters and lubricant D- Clean Radiator or replaced if it's necessary E- Rebuilt engine (overhaul) Evaluation: Due to depreciation and also not having hourly services done for this generator in past, this generator cannot properly work unless complete repair be done for it, I should add even when all the repair be completed at the most it is has less than 50% of it is normal work, due to radiator problem and considering the hot weather situationat this please you can use this generator with very low potency if you keep using water to cool the radiator.

Hay Al-Wahda, No 2, St. 38, Dis. 904 Elwiah, Baghdad, Iraq Baghdad: Al-Kut: Erbil: Amman +964 1 719 0020 +964 780 196 4084 +964 770 442 5027 +964 66 255 1888 +962 6 593 8850

-
+ + + + +

: : : :

Email: micta@al-bunnia.com Website:http://micta.al-bunnia.com

This complex because one of its generators is unusable and the second generator is depreciation and can work with very low potency needs to have a backup generator (over one MG power)to be able to supply power for four blocks

3- B04K417510 ESN: 33156123 A- Need to Replace Rear engine Oil Seal B- Need to Replace injectors C- Repair fuel pumps D- Need Engine belts E- Need to Replace all Engine filters F- Need to Replace coolant G- Clean radiator or replace it. H- Rebuilt engine (overhaul) Evaluation: this generator cannot properly work unless complete repair be done for it, I should add even when all the repair be completed at the most it is has less than 45% of it is normal work, due to radiator problem and it coolant considering the hot weather situation at this please you can use this generator with very low potency if you keep using water to cool the radiator. Other issue regarding this generator is fuel usage; due tocondition of this generator it will use 2.5 times as much as a normal generator.

4- B05K546380 ESN: 25299011 A- Engine Need to Rebuild B- Need to Replace coolant and radiator C- Replace injectors, and repair fuel pumps

Evaluation:

This generator is very depreciation and it is not reliable and cannot be used during some hours of day. Due to radiator problem and coolant and considering the weather situation when this generator is being used it must be cool done with water while it is running (all the time)

5- B04k399430 ESN: 25290324 A- Engine need to Rebuild B- Replace radiator and coolant 6- B05K546390 ESN : 25296966 A- Engine need to Rebuild B- Replace coolant and radiator Evaluation: This generator cannot be used because of oil pressure problem, oil pressure is very low and engine needs to be rebuilt. This complex because one of its generators is unusable and the second generator is depreciation and can work with very low potency needs to have a backup generator (over one MG power) to be able to supply power for four blocks. 7- B05K553670 ESN : 25296826 A- Baseboard and all PCC lost B- All genset harness lost engine and Alternator C- Tensier belt lost D- Fuel pipes lost and broken E- Shock observer base lost F- DC engine alternator lost G- Belts lost H- Oil hose behind starter lost I- The engine not running so it need another inspection when parts lost available

Evaluation: This generator condition is much unknown and only can be evaluated after all repairsthat needed be done, first the repair has to be done and then start the generator and check the systems and make evaluation. 8- FO4K427040 ESN: 33156254 A- Engine Need to Rebuild B- Replace radiator and coolant ( radiator damage there is a holes in radiator) C- Replace injectors and repair pumps Evaluation: First the engine needs to be rebuild, right now this generator works with less than 50% capacity and potency. Section 3 has two generators one is broken and not working and the second one has unknown condition and has a lots of destructions, considering both generators condition this section has to have a big generator ( 1.5 MG capacity power) as a backup generator to be able to supports all four blocks. 9- B05K548350 ESN: 25299433 A- Base board and HMI lost B- Alternator and engine harness lost C- All fuel hoses lost D- DC alternator lost E- Engine belt consumed F- Injector must be replace G- The engine not run so it need another inspection when genset running.

Evaluation: Cannot start this generator to be check unless all the parts of this generator be replaced. 10- B04K399400 ESN: 33155617 A- Engine need to Rebuild B- Replace coolant and radiator

Evaluation: In the best situation efficiency of this generator is 50%, due to weathercondition and very high heat and also destruction of this generator, water temperature of this generator goes up as high as 95 degrees which is not good and radiator has to be cool don with pouring water on it. This complex because one of its generators is unusable and the second generator can work with very low potency needs to have a backup generator (over one MG power) to be able to supply power for four blocks

11ABCDE-

CO4K416930 ESN: 33156003 Base board and HMI lost Replace coolant antifreeze Replace engine belts Replace radiator The engine not running soit need another inspection when lost parts are available.

Evaluation: Cannot start and check this generator unless all the parts of this generator be replaced. After replacing the part it need to be inspected. 12- AKSA ID (A05D388065) ESN: 33159241 A- Engine Need to Rebuild B- Replace radiator and coolant. Evaluation: Considering this generator is not Cummins made and was assembled at Turkey, cooling system of this generator is not designed for hot weather condition, it has designed for weather less than 50 degree, considering this

fact and also effete of this generator you cannot count on this generator a normal generator and has a very low rank. This complex because one of its generators is unusable and the second generator can work with very low potency needs to have a backup generator (over one MG power) to be able to supply power for four blocks

13- A04K390790 ESN: 33155292 A- The engine running with deep sea electronic control and the better replace it with Cummins control B- Rebuild engine C- Replace coolant and replace radiator. Evaluation: Depreciation of this generator is very high and because of this reason it cannot work properly and drop dead stagger, the entire repair needs to be immediately. Cooling system is very depreciation and radiator would find a hole after working for little while and repair man has to fix it to be able to cover some of the resident's needs. Since this generator engine running with deep sea electronic control it does not have some of the control system on it and efficiency of this generator in some hours during a day drops under 40% and it's not a reliable generator. Oil and fuel usage of this generator is very high. 14- B05K554350 ESN: 25299238 A- The genset running with Deep Sea Electronic and the better to change to Cummins PCC B- Replace coolant and clean radiator or replace it C- Rebuild engine D- Replace injectors E- Repair fuel pump Evaluation:

Depreciation of this generator is very high and because of this reason it cannot work properly and drop dead stagger, the entire repair needs to be immediately. Cooling system is very depreciation and radiator would find a hole after working for little while and repair man has to fix it to be able to cover some of the resident's needs. Since this generator engine running with deep sea electronic control it does not have some of the control system on it and efficiency of this generator in some hours during a day drops under 40% and it's not a reliable generator. Oil and fuel usage of this generator is very high. To be able to cover the residents power needs must have a big generator (1.5 MG capacity power) as a backup generator. Outcome: 1- Work hour of these generators as of right now is between 12000 to 18000 hours, usually you have to have the engine and alternator overhaul when the work hours get at this point which has not been done for these generators, this might cause problems and it could make a generator out of order any time. 2- Our suggestion is to replace the generators that need to be over haul. 3- We inspected 14 generators, 5 generators has engine problems or missing some parts are out of order and cannot be used, seven generator need to have engine over haul and their efficiency and potency is very low, most of them with less than 50% potency although their fuel and oil usage is very high, two generator because of radiator problem can be used only in some hours of a day or night. This generator water temperature goes very high beside high usage of fuel and oil burningadding hot weathercondition and system has to be cool done by pouring water on radiator, the amount of water needed for cooling all these generators is at least 12000 LT. per day. 4- Due to lack of proper hourly, monthly services fuel usage of these generators are very high. 5- Financially the cost for repair these generators would be very high and considering the restriction and limitations of part in Iraq it would take some time before the repair be completed.

6- Finally after all the repairs and fixing all the generators each section has to have a generator as a back up to be sure.

Eng. Kassim Rasheed MICTA Service Manager