We touch your electricity everyday!

* Compact & Drawout Design * Versatile & Programmable Relay * Rated 1A/5A - 50/60 Hz Site Selectable * Wide Range Auxiliary Supply

CSENEX-I
Current Protection & Monitoring System
Application

The CSENEX-I relays have been designed for controlling, protecting and monitoring industrial, utility distribution networks and substations. They can also be used as backup protection scheme for feeders, transformers and generators against over current.

Main Features:

1A & 5A Rated CT input (programmable) Drawout with self CT shorting SCADA communication (local & remote) Wide auxiliary supply range DI / DO matrix programmability Event record Fault record

Series

Protection & Control Over current Sensitive earth fault Auto re-closer - Multi shot Negative phase sequence Trip circuit supervision Circuit breaker failure protection Short circuit Residual over voltage
(Neutral displacement)

Metering & Monitoring Phase current Negative phase sequence Earth current Communication Modbus RTU on RS-485

Broken conductor Inrush blocking

Electronic Division
Unit - Protection & Control

We touch your electricity everyday!


Model Selection Chart
Function CT inputs PT inputs Over current/ Earth Fault ANSI 50/51 50N/51N 50SN/51SN Neutral displacement CBFP Unbalance Trip circuit Inrush blocking Broken conductor Auto Re-closer Digital input Digital output Fault record Event record Selection of 1/5A Enclosure type 59N 50BF 46 74TC 51H 46BC 79 x x x x x x x 4 10 x S it e selectable Draw out with CT shorting
(112x145x145)

NEX-I 200 4 x

NEX-I 201 4 x x x x 4 4 10 50 Site selectable Draw out w i t h CT shorting


(112x145x145)

NEX-I 202 4 x x 6 4 10 50 Site selectable Draw out with CT shorting


(112x145x145)

NEX-I 203 4 1 x 6 4 10 50 Site selectable Drawout with CT shorting


(112x145x145)

Enclosure size (WxHxD) Front comm. Rear comm. (RS -485)

Technical Data Auxiliary voltage Uaux Rated phase current Ip -current measuring range Rated neutral current In Thermal withstand capability in current circuit 24-260V AC/DC 1A & 5A (site selectable) 30xIp 1A & 5A (site selectable) At Ip=1A Continuous=4xIp for 10 Sec=30xIp for 1 Sec=100xIp Rated frequency Fn Digital inputs (external voltage) Trip contacts 50/60 Hz 6 programmable 4 programmable

Records Event recorder Fault recorder Tests and Environment 50 (non volatile memory with time stamp) 10 (non volatile memory with time stamp) IEC 60255 / 60068

(EMC Emission / Emmunity / Mechanical / EMI) Operating temperature Degree of protection Weight Dimension (WxHxD) 700C IP54 1.0 kg 125.0x156.0x158.5 mm

C&S Electric Limited


(Protection & Control Division)
44, Okhla Industrial Estate, New Delhi -110 020 (INDIA) Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413 E-mail: cspc@cselectric.co.in
Issue Date : 21.07.11 Rev. No. : 07 Rev. Date : 07.12.11

Branch Offices :
Ahmedabad:+91 79 30074534/35/36 Fax:+91 79 30074519 Bangalore:+91 80 3057 0372/73, 3057 0347 Fax:+91 2558 4839 Bhubaneswar:+91 674 2507265 Fax:+91 674 2507265 Chennai:+91 44 3918 0531-35 Fax:+91 44 39180514 Cochin:+91 0484 3071717 Fax: +91 0484 3071716 Delhi:+91 11 30838822-25 Fax:+91 11 30838826 Hyderabad:+91 40 3918 2496/97 Fax:+91 40 3910 3631 Kolkata:+91 33 22275850/51 Fax: +91 33 2227 5849 Mumbai:+91 22 30487146/47/48 Fax:+91 22 2412 6631 Pune:+91 20 30283244/45 Fax:+91 20 30283244