HARTTemp_V2.

05Fast Start

------SENSE Instruments Co., Ltd.

is always smart

Main Content

Electrical Connection Setup and Install


1. System Requirements 2. COM Ports Setup 3. Software Install

3. Parameter Setup 4. HART Information 5. Calibrate 6. Picture Monitor

Others Contact Information

Software Operation
1. Overview 2. D/A Trim and Loop Current Test

is always smart

Electrical Connection

Note: The measurement circuit must have a load of at least 250ohm.

is always smart

Setup and Install


1. System Requirements
Windows 95/98/2000/ME/XP and updates CPU: Min. 350MHz RAM: Windows 95/98/ME: 64MB and greater Windows 2000/XP: 128MB CD-ROM drive Free serial interface Screen resolution: 800X600 pixel and higher Mouse Modem: HARTTalker

is always smart 2. COM Ports Setup


If you use Windows 2000 and Windows XP, You should setup COM before you run HARTTran Steps: Click Start-Settings-Control Panel-System-Hardware-Device Manager-Ports (COM&LPT)Communication Port (COMs) -Port Settings-Advanced then cancel Use FIFO buffer. Now restart the PC.

3. Software Install
Please insert CD into the Drive, then copy all files of HARTTemp_V1.03 package, run HARTTemp_V1.03.

is always smart

Software Operation
1. Overview
Main Menu Bar

Menu Icon Bar

Status Bar

Info Bar

is always smart

2. D/A Trim and Loop Current Test


Please do D/A trim at first. The purpose of it is making the transmitter output value is the same as standard current meter. Step 1: Connect standard current meter into loop power circuit then power the transmitter. Step 2: Please click 1st [Get] button, and input current meter value into [1st current]. Step 3: Click 2nd [Get] button, and current meter value into [2nd current]. Step 4: Click [Update] button.

Step 5: You can use [loop test] to test the D/A trim result.

is always smart

3. Parameter Setup
The following parameter can be used as your requirements. Then click [Update] button Type: Entry of sensor used Zero: For limits see the temperature transmitter datasheet Full: For limits see the temperature transmitter datasheet Unit: Enter engineering limits Offset: Entry of zero point correction Wire: Entry of RTD connection mode, only for RTD Filter: constant current, From 0 to 160uA Self Stability: 4mA and 20mA output are locked between Damp Time: Input: 0 to 100 seconds, 0.1 step Display Mode: only for the temperature transmitter with digital display Decimal: only for the temperature transmitter with digital display 02%FS.

Note: The difference between [Self Stability] and [Filter] is 2 point(4mA and 20mA) stable for [Self Stability], all range is stable for [Filter]

is always smart

4. HART Information
A. User Information
Date: the date of programming Tag: 8 characters Descriptor: 16 characters Message: 32 characters

B. Short Address
You can change the Roll Address from 0 to 15.

C. Long Address
Device ID, 6 digital

Note: If multi drop configuration, all transmitter in loop have unique addressed.

is always smart 5. Calibrate


This item is suitable for the local field. Step1: Input lower the range value(4mA) Step2: Click [Calibration to 4mA] Step3: Input upper range value(20mA) Step4: Click [Calibration to 20mA]

is always smart 6. Picture Monitor


The actual measured data can be displayed in real time. You can monitor the process variable, current, and % range as a graph at the same time. You also can choose freely to monitor one of them via Menu Icon Bar. Additionally, you can save the monitor data to computer and view history data.

Note: The monitor period can be selected from 2sec. to 30 minutes.

is always smart

Others
Language Translation: This is a very useful tool for you if your native language is not English.
Step 1: Open the file (English.ini), then save as the new language file.
Step 2: Translate the reference language into your own language Step 3: Click [Save] button, and close the file. Step 4: Then you go to the Main Menu Bar, click [Environment], choose your own language.

is always smart

Contact Information
SENSE Instruments CO., Ltd. Phone: +86-21-58540878 Fax: +86-21-58993196 Email: sense.oversea@sen-tec.com Web: www.sen-tec.com Please do not hesitate to ask if there is anything else we can do for you.

is always smart

THE END