Configuration Instructions StratixTM 8000 RSLogix 5000 Add-On-Instruction & FactoryTalk View Faceplate

v1.0.0 Initial Release 10 September 2008 v1.0.1 Update 12 September 2008 - added step-by-step detail for AOI setup v1.0.2 Update 30 September 2008 - updated AOI and faceplate setup

Table of Contents
Introduction___________________________________________________________ 3
Stratix 8000 Add-On-Instructions and Faceplates: What are they? _________________ 3 What components are needed?_______________________________________________ 5 Features of using an AOI to communicate to the switch __________________________ 5 Quickstart steps to run the demo _____________________________________________ 6

Install: Stratix 8000 Add-On-Profile _______________________________________ 7


Setting up the Add-On-Profile ________________________________________________ 7

Install: Add-On-Instruction _____________________________________________ 11


Setting up the Add-on Instruction____________________________________________ 11

Install: FactoryTalk View Faceplates _____________________________________ 19


Adding the FactoryTalk View Objects to an Application _________________________ 20

Install: FactoryTalk View Demo Application _______________________________ 22


FactoryTalk View SE_______________________________________________________ 22
About the SE demo _______________________________________________________________ 24

FactoryTalk View ME ______________________________________________________ 25


About the ME demo_______________________________________________________________ 26

Navigating Through the Faceplate _______________________________________ 27 Stratix 8000 AOI Extended Documentation ________________________________ 32 Stratix 8000 Faceplate Extended Documentation___________________________ 36
Home Screen _____________________________________________________________ 36 Port Settings _____________________________________________________________ 37 Port Statistics: Input_______________________________________________________ 38 Port Statistics: Output _____________________________________________________ 39 Trending: Port Utilization and Switch Temperature vs. Time______________________ 40 Trending: Configuration____________________________________________________ 41 Port Fault Status __________________________________________________________ 42

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 2 of 42

Introduction
Stratix 8000 Add-On-Instructions and Faceplates: What are they?
The Stratix 8000 Add-On-Instruction (AOI) provides programmatic access to Stratix 8000 configuration and settings. Additionally, switch status can be monitored both in RSLogix 5000 and FactoryTalk View. The Stratix 8000 faceplate is a pre-configured screen displayed in View SE or View ME that interfaces with the Stratix8000 AOI to provide HMI functionality and integration.

Faceplate

Figure 1: application components

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 3 of 42

The following is list of features that the AOI/faceplate combination provides: Display information about the switch itself Switch hostname IP Address Subnet Mask Default Gateway Temperature Uptime Display individual port status (based on operator selection) inactive, disabled, fault, connected Display individual port fault status (based on operator selection) OK or not connected Threshold exceeded Unauthorized device connected Alarm Relay Active Display diagnostic information on a per-port basis Utilization (%) Threshold Limit (%) Speed Duplex Link Status Auto Negotiation Status Hardware fault status Unauthorized device status Port input counter data In Octets In UCast packets In NUCast packets In Discards In Errors In Unknown Protocols Port output counter data Out Octets Out UCast packets Out NCast packets Out Discards Out Errors Out Unknown Protocols Trend of port utilization and temperature of switch vs. time Port Utilization Switch Temperature Trend range configuration: Utilization MIN and MAX Temperature MIN and MAX Different limits available for each pen

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 4 of 42

What components are needed?


This release of the faceplate package requires the following software pieces to work together:
Version File Name File Location

Stratix 8000 Switch


Stratix IOS (firmware)
Loaded in switch v16.00 or later V1.03.012 Stratix8000ENetSwitch_Rel_Ver_1.03.012.zip AB_1783MS06.L5X (6 port switch) AB_1783MS10.L5X (10 port switch) AB_1783MS14.L5X (14 port switch) AB_1783MS18.L5X (18 port switch) AB_1783MS22.L5X (22 port switch) AB_1783MS26.L5X (26 port switch) Samplecode website

RSLogix
Stratix 8000 Add-On-Profile

Stratix 8000 Add-On-Instructions

v1.00

Samplecode website

FactoryTalk View SE or ME
Stratix 8000 Faceplates SE Global Object Faceplate screens Stratix 8000 Faceplates ME Global Object Faceplate screen

v5.0 or later v1.0 Stratix_8000_SE_v1-0.ggfx popStratix8000.gfx, Main.gfx Stratix_8000_ME_v1-0.ggfx popStratix8000.gfx, Main.gfx Samplecode website

v1.0

Samplecode website

Not required but included in the package for your convenience:


Stratix 8000 demo HMI application for SE Stratix 8000 demo HMI application for ME Sample RSLogix application for 10 port switch
v1.0 v1.0 Stratix8000_SE_demo_v1_0.apa Stratix8000_ME_demo_v1_0.apa Stratix_10port_example.ACD Samplecode website Samplecode website Samplecode website

Features of using an AOI to communicate to the switch


Rockwells Integrated Architecture Switch diagnostic info becomes part of FactoryTalk Live Data SE datalogging, SE/ME trending, Historian SE/ME, alarm history Switch is displayed like any other device on network Operator read-only Not a replacement for CNA, Device Manager, cli, etc Intuitive tag names and switch information No VBA Same interface for View SE and View ME Can easily be distributed as a package Faceplates can be customized

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 5 of 42

Quickstart steps to run the demo


The demo is configured for a 10-port Stratix 8000 switch. The Quickstart instructions are not meant to be a complete step-by-step guide, but instead a high-level indication of the steps required. More details instructions and explanations are found later in this manual.
Please note that a working knowledge of RSLogix 5000 and FactoryTalk View is highly recommended. To setup the demo: 1. Install the Stratix 8000 Add-On-Profile on your machine. 2. Open Stratix_10port_example.ACD and modify to match your controller type and slot number. 3. Add the 10 port switch to your I/O tree and name it Stratix1. You have to name it that for the demo because thats what everything is configured to look at. 4. Set the switchs IP address and set the data connection. 5. In MainTask:MainProgram:MainRoutine, update the message path on the AOI by browsing.

6. Save and download to the controller. 7. Select either the SE or ME view demo application and load to your machine. 8. Make sure the switch is visible in RSLinx Enterprise and set the shortcut Controller to point to your controller. 9. Run your HMI application!

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 6 of 42

Install: Stratix 8000 Add-On-Profile


This manual assumes that your switch has been configured and optimized for EtherNet/IP using Express Setup.

Setting up the Add-On-Profile

Open RS Logix 5000 and create a new application, Select the controller type and where appropriate set the chassis size and correct slot number. If you are using a ControlLogix processor, add an ENBT / EN2T card to the configuration.

When you have done so, or if you are using a CompactLogix processor, right click on the Ethernet network and select New Module

Browse to Communications

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 7 of 42

and scroll down until you find the Stratix 8000 Switch family. Select the appropriate module and click OK:

The New Module window will appear. The next steps will show you how to provide a name and the IP address for your switch. Note that by default, the module definition is configured to be an Input Data connection. You should change this to Data by clicking on the Change button.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 8 of 42

1. Add Switch to my I/O tree and name it Switch1

2. Set the Switch IP address and change the Connection Type to Data. Password is either rockwell or write

When the following window opens, confirm the password:

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 9 of 42

You will return to the main module creation dialog. Click on the Connection tab and note that the RPI is set to a default value of 1000ms. Since the CIP interface to a switch is likely to be used for diagnostic purposes rather than active control, an update once a second is sufficient.

Click OK. You will now see the switch visible in the controller I/O tree.

The switch is functioning properly as a device when there is no yellow X on the I/O tree.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 10 of 42

Install: Add-On-Instruction
Setting up the Add-on Instruction

In your Logix 5000 project, right click on Add-on instruction and select Import Add-On Instruction:

Import the correct add-on instruction for your switch model. In this case, the AB1783MS10T add-on instruction is used as an example. You should select add-on instruction which matches your switch model.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 11 of 42

Note that the Add-on instruction (and a second add-on instruction handling IP address conversion) is now visible in the controller configuration, together with a number of user-defined data types and strings.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 12 of 42

Open the main routine in the controller and click on the Add-On tab.

Click on the AB_1783 button to create an instance of the AB_1783MS add-on instruction.

Populate the AOI as follows, creating the relevant tags in each case. Note that the AOI backing and switch parameters tags can be of either program or controller scope but the Storage and Get_Message tags MUST be set to be controller scoped.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 13 of 42

Right-click on Switch1 and create a new tag.

Right-click on Stratix1 and create a new tag.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 14 of 42

Right-click on Stratix1Storage and create a new tag.

Right-click on S1GetAll and S1GetSgl and create new message tags.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 15 of 42

Click on the symbol to the right of the Get_All_Message tag to open the Message configuration window. Enter the parameters as shown below:

Click on the Communication tab. Click on the Browse button and select the path to your switch.

Return to the Communication Tab of the Message configuration screen and ensure that the Connected and Cache Connections check boxes are ticked.

Click OK to close the window.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 16 of 42

Click on the symbol to the right of the Get_Single_Message tag to open the Message configuration window. Enter the parameters as shown below:

Click on the Communication tab. Click on the Browse button and select the path to your switch.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 17 of 42

Return to the Communication Tab of the Message configuration screen and ensure that the Connected and Cache Connections check boxes are ticked.

Click OK to close the window.

Download your program to the controller.

Note: By default, the Add-on instruction is configured to allow control of the port status from the Faceplate. If you wish to remove this functionality, the button can be deleted from the global object. Alternatively, the bit controlling the visibility setting can be changed in the first rung of the add-on instruction. This will turn of the Set_ShowDisableButton bit on the first scan. Note that changing the add-on instruction will affect all instances of the switch. Alternatively, this bit can be turned on or off programmatically.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 18 of 42

Install: FactoryTalk View Faceplates


This section describes how to import the faceplate files into an existing View SE or View ME application. There is no need to follow this section if you use the Stratix 8000 SE or ME demo HMI application. The faceplate global object files contains 2 objects the faceplate object (shown in the graphic below on the left) and an overview read-only graphic that shows switch status (shown in the graphic below on the right).

The global object contains 2 tag placeholders that need to be set at runtime by passing a parameter file using /P or by passing tags using /T with the Display command. #1 = complete path to the Switch_Parameters parameter of the AOI.

#2 = RSLinx shortcut name defined in your View application (without brackets) In the demo application, youll see that #1 and #2 are defined as such:

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 19 of 42

Adding the FactoryTalk View Objects to an Application

1. Drag the .ggfx global object file to your FactoryTalk View application.

Drag the SE object into your SE application. Drag the ME object into your ME application.

2. You will now need a new screen which uses the global object as a template. Drag the .gfx screen file to your FactoryTalk View application.

The popStratix8000.gfx screen uses the respective SE or ME global object as a template. The Main.gfx file is not necessary, but it shows you how to call the faceplate popStratix8000 from a button. Using View ME In View ME, you will create a button on your screen that has a command similar to the following defined as a release action:

Youll need to create a parameter file as well called Stratix8000.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 20 of 42

The contents of the parameter file should look like this:

#1 = complete path to the Switch_Parameters parameter of the AOI and #2 = RSLinx shortcut name defined in your View application (without brackets)

Using View SE

In View SE, you will create a button on your screen similar to the following defined as a release action:

that has a command

Display popStratix8000 /T::[Controller]Program:MainProgram.stratix1,Controller

where ::[Controller]Program:MainProgram.stratix1 is the runtime substitution for #1 and Controller is the substitution for #2. Modify the command with your controller shortcut name and your switch parameters tag! You may also use the /P option and configure a parameter file as in View ME.
Display popStratix8000 /PStartix8000

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 21 of 42

Install: FactoryTalk View Demo Application


This section contains.

FactoryTalk View SE
1. Double-click the file Stratix8000_SE_demo_v1_0.apa and the FactoryTalk View application manager will create a new standalone View SE application. Assign the Linx topic to your controller. Note: Please keep the [Controller] shortcut name.

2.

3.

In Studio, before you run the application, open the Properties of the TagAandE server. Verify both tabs and close the Properties window. There wont be a need to change anything, but you still should open this window.

4.

On the Main Display, there are 3 buttons. You will have to configure the last 2 buttons to get them to work.

5.

On the Switch Ladder Code button, delete whats there and add this command with this syntax:
OpenRSLogix5000 "C:\Stratix8000\L32E_S8K_Faceplate_Full.ACD" MainProgram MainRoutine

where
"C:\Stratix8000\L32E_S8K_Faceplate_Full.ACD"

is replaced with the path to your ACD file. 6. On the Switch Webpage button, replace the IP address with your switchs IP address.

AppStart http://192.168.1.5

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 22 of 42

Run the SE Application: Client setup


Main is the startup screen.

Suggested window properties:

Rest of the config can be default.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 23 of 42

About the SE demo


Main.gfx

Stratix8000 read-only general status display.

Button to launch Stratix8000 website. Button to open Logix5000 to show Stratix8000 AOI (if configured) Button to call Stratix8000 faceplate Tag-Based Alarm and Events to show how port status can be captured,displayed to operator, and displayed in A&E History (if configured).

Note: everytime the faceplate is initially displayed, it is forced to show the Home display through the use of a display command on popStratix8000.gfx.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 24 of 42

FactoryTalk View ME
1. Double-click the file Stratix8000_ME_demo_v1_0.apa and the FactoryTalk View application manager will create a new standalone View ME application. Assign the Linx topic to your controller, both local and target. Note: Please keep the [Controller] shortcut name.

2.

3. Create a runtime application and transfer to your Panelview station using the Transfer Utility.

or run a Test Application

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 25 of 42

About the ME demo Screen size is 640x480 and tested on a PanelviewPlus1000.


Main.gfx

Stratix8000 read-only general status display.

Button to call Stratix8000 faceplate

Note: everytime the faceplate is initially displayed, it is forced to show the Home display through the use of a display macro on popStratix8000.gfx.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 26 of 42

Navigating Through the Faceplate


What follows is a brief dialogue to guide you through the navigation of the SE or ME faceplate.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 27 of 42

Click on the button to launch the switch display. The home screen will appear. Note that the display will automatically detect the type of device connected and modify the display accordingly for example you will see either a six port or a 10 port base unit. Similarly, expansion modules will also be shown if they are present.

Note that the colour scheme is similar to that used with the Device Manager active ports are shown green whereas disabled ports are a dark brown colour. Further information can be obtained by clicking on the button, which brings up context sensitive help for each screen.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 28 of 42

Close the help by clicking the

button. button.

You can always return to the home screen by clicking the

To select a port in View SE, click on the port itself. To select a port in ViewME, click on the multi-list selector Up/Down arrows. The selected port is highlighted in yellow. For example, here port Fa1/3 has been selected.

Click on the Disable button to turn off that port. If a port is disabled, the colour of that port will change to brown. Click on the button to show information about the incoming traffic for the selected port.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 29 of 42

Change the selected port setting and note the differences between active and inactive ports. Click on the button to show information about the outgoing traffic for the selected port.

to display the trend object. This shows the utilisation of the Click on the trend button selected port (in blue) and CPU temperature (in red). The y-axis scale can be changed by clicking on the Next Pen button. Data which is currently being displayed is indicated by the green rectangle. In this case, it shows that the active trend of the port utilisation for port Fa1/3.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 30 of 42

Now click on the Trend settings button to modify the display parameters. Enter new values, as shown below. In each case, remember to press the enter key after entering the value in the respective fields.

again to view the modified graph. Click Next Pen if the Click on the trend button Temperature selection is not active. You should see a graph similar to that shown below. or red (alarm active) . Click on the alarm button, which may be grey (no alarm active) This screen will indicate if an unauthorised device is connected to the switch, if bandwidth has been exceeded on any of the ports or if the alarm relay contact has been triggered.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 31 of 42

Stratix 8000 AOI Extended Documentation


Introduction The Faceplate for the Stratix 8000 family of switches provides a mechanism for users to obtain diagnostic information from hardware for display in a FactoryTalk View project. Functionality has been implemented in two parts an add-on instruction (AOI) which is integrated into a controller file and a global object which is used in the Factory Talk Project. Operating Philosophy The Stratix 8000 AOI package consists of a number of variants, each corresponding to a variant of the Stratix 8000 family. This owes to the fact that the input structure for each variant is different. The principal functions of the AOI are to copy data from the input image into a user-defined data type (UDT) and to periodically poll appropriate CIP objects as required by the users selection. Similarly, where output control is permitted, the AOI copies the port enable / disable options selected by the user to the output image of the AOI. In contrast, there is one global object for the complete range of variants. The global object uses a value set in the AOI to determine the base unit and expansion module variants for display. The global object consists of a number of layered screens. Each is displayed depending on the users selection. The operating principle behind the code is to send an explicit message to the appropriate CIP object in the device whenever this is requested by the user. Where possible, the Get Attribute All service is used to read all attributes from an object. Since vendor-specific attributes cannot be read by the get attribute all service, a second message instruction, configured to use the Get Attribute Single service. The selection of a particular screen sets the tag Switch_Parameters.HMI.Set_FaceplateAnimation to a unique value. This value in turn is used to determine which CIP objects are polled. This is done using a tag called MessageNumber. Each value of the MessageNumber tag corresponds to the polling of a different CIP object. This is achieved by setting a value for class, instance and attribute for each value of MessageNumber and calling the appropriate MSG instruction. On completion of the MSG, the data is copied into the relevant part of the UDT. Software Description The following section provides a rung-by-rung description of the code. Rung numbers refer to the 10-port variant, called 1783MS10. Rung 0: A placeholder rung to facilitate inclusion of the AOI description Rung 1: This rung initialises the add-on instruction on the first scan. The operations completed are setting the pre-set values of the MessageTimer, InitialTimer and Message Counter. Changing the value of the MessageTimer preset will vary the frequency of sending an explicit message to the switch. By default, this is set to 1 second. For a faster poll, this value should be reduced. Conversely, for a slower poll, the value should be increased. MessageCounter defines the number of messages which can be sent to the switch. This value should not be changed unless data from addition CIP objects or attributes is required. InitialTimer introduces a delay in sending the first message. This is designed to avoid multiple messages being sent at the same time at startup. Associated with this is the Startup bit which is latched on during the first scan, and unlatched later in the program. In rung 1, the initial values for the trend axes are also defined. By default, the temperature and utilisation values are set to a minimum of 0 and a maximum of 100. These can be adjusted when the Faceplate is running. Also switched on (latched) in this rung is the bit used to determine whether the port enable / disable button is visible in the FactoryTalk View project. By default, the button is visible. To make it invisible, this operand should be changed from Latch (OTL) to Unlatch (OTU). Rung 2: Sets the InitialTimer running if the Startup bit is set Rung 3: If the value of the initial timer is greater that 250mS, unlatch the startup bit and set the InitialDelay bit to enable the first explicit message Rung 4: Copies the input image to a temporary array. This step is needed as the inputs are only available as BOOLs. In copying this data, each BOOL is mapped to a DINT for ease of data handling elsewhere in the AOI. Rung 5: Copies each of the DINTs in the input array to the Input part of the Switch UDT. The Switch_Parameters.Inputs part of this UDT has a structure which is common for all members of the Stratix 8000 family which allows the same graphics to be used for all variants. This rung ensures that all inputs are mapped to the correct location.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 32 of 42

Rung 6: This rung reads each ports utilisation value and maps it the UDT corresponding to that ports Ethernet Link object. This serves two purposes it reduces the need to send an explicit message to read the bandwidth from attribute 100 of the Ethernet Link object and also allows the global object to read all of the display data to be read from the UDT directly. Rung 7: The screens in the global object are defined such that the screens themselves have a value between 0 and 9, with the respective help screens having a value 10+ that for the screen itself. With the current implementation of the global object, only screens 0 to 6 require any explicit messaging. Rung 7 controls a MessageTimer the preset for which is set on the first scan to poll CIP objects at a regular interval. The MessageTimer however will only count up if a screen is selected which requires the display of data obtained by explicit messaging. The timer will also only count up if the two MSG instructions used in the AOI are not currently enabled. The DN bit of the timer is included in the rung to ensure that it self-resets. The counter is also dependent on the InitialDelay bit being set. Rung 8: Rung 8 triggers a counter which increments whenever the MessageTimer is complete. This provides a value which increments every second. The counter is self-resetting on completion. Rung 9: Stratix 8000 switches have multiple instances of the Ethernet Link object. Information such as port speed, duplex status and port statistics are obtained from the appropropriate instance of the Ethernet Link object. The instance to be polled is determined by the port selected by the user. Rung 9 checks that the input from the user is non-zero and copies the value to the Selected_EthernetLink_Instance variable. Rung 10: Rung 10 determines which objects are to be polled depending on the selected screens. This is set up as follows: Set_FaceplateAnimation 0 2 MessageNumber(s) 10 4 5 6 7 8 9 10 4 10 4 10 1 10 1 2 10 10

3 4 5 6

7 Rung 11: Resets the Message Counter when necessary

Rung 12: Triggers the Get Attribute All Message whenever the MessageTimer is done. The class, attribute and instance parameters are set up as follows: For all objects except for initial message: Attribute = 0 Message Number 0 (First Message) 1 2 3 4 Class / Object 246 Ethernet Link 863 Switch Parameter 245 TCP/IP 246 Ethernet Link 246 Ethernet Link Instance 0 1 1 0 Selected_EthernetLink_Instance Data (Main) Number of Instances (Ports) Temperature Uptime IP Address Hostname Number of Instances (Ports) Port settings Counters

The results of the message operation are copied into the Storage SINT array.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 33 of 42

Rung 13: Triggers Get Attribute Single Message whenever the MessageTimer is done. The class, attribute and instance parameters are set up as follows: Message Number 5 6 7 8 9 10 Class / Object 246 Ethernet Link 246 Ethernet Link 246 Ethernet Link 246 Ethernet Link 246 Ethernet Link 246 Ethernet Link Instance Selected_EthernetLink_Instance Selected_EthernetLink_Instance Selected_EthernetLink_Instance Selected_EthernetLink_Instance Selected_EthernetLink_Instance 0 Attribute 108 109 110 111 112 105 Data (Main) Applied Smartport VLANs assigned Broadcast Threshold Unicast Threshold Multicast Threshold Disabled Ports

The results of the message operation are copied into the Storage SINT array. Rung 14 & Rung 15: Generate a bit when the respective message is done. These rungs allow the respective bit to be used in subsequent rungs instead of using the respective .DN bit and a ONS elsewhere in the program. Rung 16: Copies the result of the Get Attribute All message into the appropriate part of the UDT. The value of the MessageNumber determines to which variable the results are copied. Rung 16 translates the results corresponding to messages 1 to 4. Rung 17: Copies the results of the Get Attribute Single message into the appropriate part of the UDT. The value of the MessageNumber determines to which variable the results are copied. Rung 17 translates the results corresponding to messages 5 to 10. Rung 18: Copies the disabled_ports value obtained by message 10 to HMI.Val_Disabled_Ports for display Rung 19: When the switch information screen is selected, the IP address, subnet mask and default gateway are read from the TCP/IP object. This rung converts this information into dotted-decimal from by calling the IP_Address_to_String AOI for each conversion. The result is placed in the HMI part of the UDT. Rungs 20 and 21: The trend object allows the operator to change the axes for the two parameters which can be displayed: temperature and port utilisation. These two runs copy the values which have been set by the user to the variables used by the trend object for display. Rung 22: Copies port settings and counters for the selected port for display. The information copied here includes speed and duplex settings for the port, the applied smartport as well as the port counters themselves. Rung 23: If the trend object is selected (animation 6) copy the value of the temperature read from the switch parameter object to the tag read by the trend object. Rung 24: Copies the switch hostname and uptime to the HMI part of the UDT for display. This rung does a comparison between the current value in the UDT and that obtained in the TCPIP object. If there is a difference, the destination string is cleaned before the new data is copied. This ensures that the FTView screen displays the information correctly. Rung 25: Captures whenever the port disable button is pressed and increments the value stored in the button_counter array. Each element of the array corresponds to one of the ports. The appropriate element is determined by the value of HMI.Set_SelectedPort Rung 26: If the stored value is 1, latch on the output bit for the selected port in order to disable it. Rung 27: If the stored value is 0, unlatch the output bit for the selected port in order to enable it. Rung 28: Monitor the value of the button counter and reset it to 0 if it is 2 ensures that the only possible values are 0 and 1 Rung 29: Map the value of button_counter for the selected port to the tag HMI.Val_EnableButton to ensure that the button displays enable when the port is disabled and disable when the port is enabled. Rung 30: Copies the output word used internally by the port control rungs to the actual output

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 34 of 42

Rungs 31 & 32: Map the values set on the trend configuration screen to the axes values used in the trend object depending on the button selected by the user. Clicking utilization sets the value of Set_TrendNextPenOper to 0 whereas clicking temperature sets this value to 1 Rung 33: Maps the error bits of the messages to the error bit of the AOI to provide visual indication of an error condition in the AOI.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 35 of 42

Stratix 8000 Faceplate Extended Documentation


The following section shows all screens together with their corresponding Faceplate Animation values (in the left column) Home Screen
Navigation (default)

Faceplate

Shows switch name, network information, temperature, uptime, and number of active multi-cast groups. Additionally, general port status is displayed.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 36 of 42

Port Settings
Navigation

Faceplate

Shows individual port settings Port selected from the arrowed selector (View ME) or by clicking on port graphic (View SE).

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 37 of 42

Port Statistics: Input

Navigation

Faceplate

Shows additional port diagnostics Port selected by clicking on desired port on switch graphic.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 38 of 42

Port Statistics: Output

Navigation

Faceplate

Shows additional port diagnostics Port selected by clicking on desired port on switch graphic.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 39 of 42

Trending: Port Utilization and Switch Temperature vs. Time

Navigation

Faceplate

Show port utilization trend (real-time only) Port selected from the arrows. Graph starts fresh at each new port selection. Shows temperature of switch

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 40 of 42

Trending: Configuration

Navigation

Faceplate

Trend range configuration

After changing legend limits, select them for display by clicking on the pen legend on the trending screen.

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 41 of 42

Port Fault Status

Navigation

Faceplate

Show individual port fault status

9/30/2008

Stratix 8000 AOI & Global Object Manual

Page 42 of 42