Safety Cautions

Read the entire Instruction Manual carefully for important information about safety, handling, installation, operation, maintenance, and parts replacements. This equipment is designed and built in accordance with applicable safety standard in effect on the date of manufacture. Unauthorized modifications will void warranty and can result in severe injury, death and property damage. Do not make any modifications to the equipment. Only qualified persons are to install, operate or service this equipment according to all applicable codes and established safety practices. Use only genuine Toshiba replacement parts and accessories. Improper components could cause the equipment malfunction. Do not install this equipment in areas where unusual service conditions exist. Using this equipment in other than usual service conditions can result in equipment failure. Do not exceed the ratings specified on the equipment nameplate or system accessories. Underrated equipment can fail during operation causing fire, explosion, severe injury, death, and property damage.

TRANSMISSION DISTRIBUTION & INDUSTRIAL SERVICES COMPANY


1-1, SHIBAURA 1-CHOME, MINATO-KU, TOKYO 105-8001, JAPAN PHONE +81-3-3457-4898 FAX +81-3-5444-9169

http://www3.toshiba.co.jp/sic/english/swgr/products.htm

The data given in this catalog are subject to change without notice.

KSP-E2368
2008-11(1.5)

AD 4

Printed in Japan

Type-Form
Vacuum contactor Rated voltage Rated operational current Series Operating mechanism 7.2/3.6kV G : 200A H : 400A No symbol : Non-latched type L : Latched type No symbol : Standard -2 : Upper front terminal

Since the introduction of the first Vacuum Interrupter in 1962, Toshiba has been continuously improving and developing Vacuum Technology. Over 180 thousands Toshiba Vacuum Contactors and Combination Units have been installed, providing reliable services in wide variety of applications worldwide. Consistent with its dedication to the most advanced vacuum technology, Toshiba offers new series of High-voltage vacuum contactors and Vacuum Combination Units with fuses. By adopting an electronics controlled circuit and being designed compactly to ensure reliability, handling ease and safety, the new series of High-voltage Vacuum Contactors and Vacuum Combination Units with fuses are suitable for Motor starters, Transformer feeders and Capacitor switching applications.

Configuration

Series
Fixed type 7.2/3.6kV

Ratings 200A-6.3kA 400A-6.3kA Non-latched type Latched type Non-latched type Latched type Note : Other ratings are available, refer to catalog KSP-E2412.

Standard CV-6GA CV-6GAL CV-6HA CV-6HAL

Special

CV-6HA-2 CV-6HAL-2

Type-Form
Vacuum combination unit Series Rated operational voltage Rated operational current Series Draw-out/in mechanism 3 : 3.3kV 6 : 6.6kV G : 200A H : 400A No symbol : Fixed type M : Manual type D : Handle type No symbol : Non-latched type L : Latched type 1 : Bushing type

No Surge Protection Required


Special main contact materials minimize chopping current. No surge suppressor/arrester is required except for special applications.

Operating mechanism Configuration

Compact and Lightweight


Compact and slim design contactors can be applied to either two-tier motor starters or slim starters per IEC 60470(2000). The Contactors CV-6GA and CV-6HA have the same outline and mounting dimensions, as well as dual voltage ratings (3.6/7.2kV).

Series
Type Ratings Manual type 40kA 40kA 40kA 40kA 40kA 40kA 40kA 40kA Non-latched Latched Non-latched Latched Non-latched Latched 400A Non-latched Latched Non-latched Latched Non-latched Latched Non-latched Latched 400A Non-latched Latched UVA-3GAM UVA-3GAML UVA-3HAM UVA-3HAML UVA-6GAM UVA-6GAML UVA-6HAM UVA-6HAML UVA-3GAM1 UVA-3HAM1 UVA-6GAM1 UVA-6HAM1 Handle type UVA-3GAD UVA-3GADL UVA-3HAD UVA-3HADL UVA-6GAD UVA-6GADL UVA-6HAD UVA-6HADL UVA-3GAD1 UVA-3HAD1 UVA-6GAD1 UVA-6HAD1 Fixed type UVA-3GA UVA-3GAL UVA-3HA UVA-3HAL UVA-6GA UVA-6GAL UVA-6HA UVA-6HAL

Standard

3.3kV

200A 400A

Conformity to Industrial Standard


Conforming to international standards such as IEC, BS, AS and JEM, being certified by class NK and TUV Toshiba Vacuum Contactors can be used widely all over the world.

6.6kV

200A

Excellent Breaking Performance


Since the higher interrupting capacity and short-time withstand capability, Toshiba Vacuum Contactors are appropriate to fuse combination for large capacity load, and to high-speed breaking.

Bushing

3.3kV

200A 400A

UVA-3GAML1 UVA-3GADL1 UVA-3HAML1 UVA-3HADL1 UVA-6GAML1 UVA-6GADL1 UVA-6HAML1 UVA-6HADL1

Low Power Consumption


The control device adopts an IC circuit, the control voltage either AC or DC can be easily changed by switches in the electronic circuit board without changing the coil and/or other parts. Since the economizing resistors are eliminated, the power consumption in holding condition has been reduced.

6.6kV

200A

RATINGS AND SPECIFICATIONS


Type From Standard Upper front terminal 6GA 6HA 6HA-2 3.6/7.2kV 200A 300A 6300A- 1s 400A 450A 200A 300A 400A 450A 6300A- 2s CV 6GAL 6HAL 6HAL-2 Latched

RATINGS AND SPECIFICATIONS


Type Non-Latched Form Latched Rated Insulation Voltage Rated Operational Voltage Rated Operational Current Rated Frequency Rated Interrupting Current (With power Fuses) 4000A 3200A 2400A-30s 4000A-12s 6300A-2s 85kA Rated Insulation Level Rated Control Voltage Power Frequency Withstand Voltage Impulse Withstand Voltage Closing Tripping Closing Holding/Tripping 16kV-1min. 45kV 100-110V, 200-220VDC 85% to 110% of the rated control voltage 4.5A(Peak) 0.1A(Average Holding) / 4.0A(Peak Tripping) 65 - 80ms 20 - 30ms Contact arrangement Operational voltage Ratings of Auxiliary Contact Thermal current AC capacity DC capacity Installation Altitude Application Condition Ambient air temperature Relative humidity Vibration Shock Connection Method Position Shutter Provision Control Wire (color and size) Motor (kW) Maximum load Transformer (kVA) Capacitor (kvar) Approx, Weight Withdrawable portion Total Standard 750 1000 1000 70kg 90kg Non-Latched 3NO-2NC, Latched 2NO-2NC Max. 480V, Min. 48V 10A 700VA(PF. 0.35) 60W(L/R 150ms) Floor Mount Installation 1000m or lower -5 to 40OC 45 to 85% Max. 20Hz 1G Max. 30G Main and Earthing circuit ; Automatic connection Control circuit ; Manual plug connection 2 Positions "Connected" and "Disconnected" Insulation shutter provided Yellow, 1.25mm2 1500 2000 2000 70kg 90kg IEC60470 JEM1225 (1986) 1500 2000 2000 75kg 95kg 3000 4000 2000 75kg 95kg 200A Manual type Handle type Manual type Handle type 3GAM 3GAD 3GAML 3GADL 3.6kV 3.3kV 400A 50/60Hz 40kA 22kV-1min. 60kV 200A 3HAM 3HAD 3HAML 3HADL UVA 6GAM 6GAD 6GAML 6GADL 7.2kV 6.6kV 400A 6HAM 6HAD 6HAML 6HADL

Operating Mechanism Rated Voltage (Ur) Rated Operational Current (le) Thermal Current (lth) Rated Frequency Rated Short-time Withstand Current (lk) Rated peak Withstand Current (lp) Short-circuit Making and Breaking Current (Duty) Making Current (100times) AC4 Breaking Current (25times) AC4 Withstand Overload Current 6 times of le - 30s 15 times of le - 1s Coordination with Current-limiting Fuses Cut-off Current (Peak) Rated Insulation Level Power Frequency Withstand Voltage Impulse Withstand Voltage

Non-Latched

50/60Hz 6300A- 2s 6300A- 1s 15.8kA 6300A "O" - 3min. - "CO" -3min. - "CO"

2000A 1600A 1200A-30s 4000A-4s 6300A-1s 55kA

4000A 3200A 2400A-30s 4000A-12s 6300A-2s 85kA

2000A 1600A 1200A-30s 4000A-4s 6300A-1s 55kA

100-110V, 115-120, 200-220, 230-240VAC/100-110,200-220VDC

Allowable Control Voltage Fluctuation Operating Current (at AC100V) Closing Time Opening Time

Prospective Short-circuit Current 40kA 22kV-1min. *1 60kV 300 op. cycles/hr 1200 op. cycles/hr 0.25mill. 2.5mill. 0.25mill. 0.25mill. 100-110, 115-120, 200-220, 230-240VAC/100-110, 200-220VDC 24, 32, 48, 100-110, 200-220VDC 85% to 110% of the rated control voltage 4.5A (Peak) 0.1A (Average) 4.0A (Peak) 65 - 80ms 20 - 30ms 3NO-3NC 2NO-2NC Max. 480V, Min. 48V 10A 700VA (PF. 0.35) 60W (L/R 150ms) Floor Mount Vertical Installation 1000m or lower -5 to 40OC 45 to 85% Max. 20Hz 1G Max. 30G 750/1500 1000/2000 1000/2000 19.0kg 1500/3000 2000/4000 2000/2000 19.5kg 750/1500 1000/2000 1000/2000 19.5kg 1500/3000 2000/4000 2000/2000 20.0kg

Switching frequency (AC3) Mechanical Life Electrical Life (AC3) Closing Rated Control Voltage Tripping Allowable Control Voltage Fluctuation Endurance Operating Current (at 100V) Closing Time Opening Time Contact arrangement Operational voltage Thermal Current AC Capacity DC Capacity Installation Altitude Ambient air temperature Relative humidity Vibration Shock Motor (kW) Transformer (kVA) Capacitor (kvar) Closing Holding/Tripping

Ratings of Auxiliary Contact

Application Condition

Maximum Load Weight Standard *2

IEC60470 (2000) JEM1167 (1990)

*1 : Special withstand voltage (32kV-1min.) will be supplied by request. *2 : CE marking can be available by request.

APPLICATION AND SELECTION OPERATING COIL EXCITATION


Non-Latched
(Continuous Excitation)

NOTICE FOR APPLICATION CAPACITOR APPLICATION


The current limiting fuses shall be combined for capacitor switching application. The series reactor shall be connected, especially back-to-back application. Service life of capacitor switching The switching, opening and closing, of capacitor produces severe condition for contactor, such as high frequency inrush current and interpole recovery voltage higher than twice of normal voltage. The criteria of maximum number of capacitor switching are shown in the figure below. The vacuum interrupters should be replaced when the number of switching operations reached to point shown in figure.

Mainly applied to frequent switching operation such as motor.

Latched
(Instantaneous Excitation)

Mainly applied to non-frequent switching operation and/or to the important load which require to be contact closed even by power loss.

PROTECTION COORDINATION
The protection coordination with upper/lower stream relay shall be evaluated by considering total system and load characteristics. The single-phase protection shall be performed which may be occurred by power fuses. (Apply 2E-relay or fuse blown detection which is provided on combination unit as standard.)
100

APPLICATION GUIDE TO SURGE


table.
Switching Life (Thousand Op.)

No surge protection is required except for special application, however the insulation coordination shall be evaluated by following

50 40 30

Load

Protection

Notice The surge suppressor shall be installed for machine rated at 55kW or below, and/or be subject to inching operation. The surge suppressor shall be installed between starting

20

Rotating Machine

Not required

contactor and autotransformer for machine started by autotransformer. The suppressor shall be installed for machine which has inferior insulation.

10

20

30

50

100

200

300

400

Dry-type Transformer

Not required

The surge arrester shall be installed for transformer rated at 150kVA or below and exciting inrush is interrupted. The installation of suppressor and insulation coordination shall

S witc h in g Cu r r e n t ( A )

Fig. 1 Capacitor Switching Life (with 6% reactor)

Oil-immersed Transformer

Not required

be evaluated when the low surge level apparatus are connected on secondary circuit of transformer.

Capacitor

Not required

Refer to the clause for capacitor application.

TERMINAL CONNECTION
Either terminals, upper or lower, can be used for power or load side on contactor. The upper terminals shall be connected to power side on combination unit for the protection coordination.

The surge suppressor is composed of capacitor and series resistor, and is one of the most excellent protection mediums. The device features suppression as well as a decrease of surge generation. Particularly being free from limitation on the number of operating times, this device is suitable for protecting motors and transformer required performing frequent operations. The surge arrester has no effect of suppressing the surge generation, this suppresses overvoltage to within a fixed level.

CONTROL TRANSFORMER
The contactor can be operated with following burden of control transformer.

Type Form (Contactor) CV-6GA(L), 6HA(L)

Control Transformer 400VA or more

VT 100VA 10P10

OUTLINE DIMENSIONS
30 13 30 69 115 368 115 69 30 31
RECOMMENDED PARTITION DISTANCE

OPERATING CIRCUITS
202 2 15

Non-latched type High-Voltage Vacuum Contactors


P or R

The typical operating circuit is shown in Fig. 4 indicating type CV-6GA/6HA contactor.
*1

E E E

OFF

REMOTE SWITCH *2 4 VMC 16 15 3 1 4 5 DU 26 25 52CC 2E-RY 6 2 52CC 24 23 22 21 14 13 12 11

ON

FRONT COVER

30 6

Make sure to use the "NO" contacts of quick operating relay (4) self-holding circuit. Do not use the "NO" auxiliary contacts of vacuum contactor, this may cause the welding of main contacts when the start (ON) button is pushed incompletely. (refer to the marked 1 in figure) Make sure to switch the closing coil on DC side. Should
100-110VAC/DC 200-220VAC/DC

COS START INTERLOCK STOP INTERLOCK

INTERRUPTERS

10
INDICATOR

MAIN CIRCUIT TERMINALS 12 DIA-6 HOLES

124

GL

RL

400

4 N or T

371

OFF ON

TRIP LEVER TRIPPING HOLE (DIA 9) AUXILIARY SWITCH

30
MAIN CIRCUIT TERMINALS

the coil be switched on AC side, a discharging circuit will be formed by rectifiers against coil, resulting in prolonged opening time and lowered breaking performance. (refer to the marked 2 in figure)

180

DIA 15

(REAR) + 345-1 166 179 10 195 219 10 + 195-1 166 134 300 + 1 (FRONT)
DETAIL OF MOUNTING HOLES (TOP VIEW)

VMC 52CC DU 4

: Vacuum contactor : Closing coil : Drive unit : Control relay

128

217

87654321

Fig. 4 Non-latched type operating circuit

13 18
EARTHING TERMINAL (M8 BOLT) CONTROL TERMINAL

300 373

60 21
MOUNTING HOLES

11 DIA - 4 HOLES

COUNTER (OPTION)

LATCH MECHANISM (FOR LATCHED TYPE)

Latched type High-Voltage Vacuum Contactors


The typical operating circuit is shown in Fig. 5 specifying type CV-6GAL/6HAL contactor. The electrical trip free circuit must be furnished in control A stable DC power source such as battery is
100-110VDC 200-220VDC P E ON E

REMOTE SWITCH

OFF

2E-RY

Fig. 2 Types CV-6GA ( L ) /CV-6HA ( L )

circuit. (outside of contactor)


RECOMMENDED PARTITION DISTANCE

COS START INTERLOCK

4 3 1 4 5

11

15

14

VMC 13 12

16 DU 26 D 6 GL 2 7 RL 52CC 52CC 21 52TC 25 24 23 22

30 13 30 69 115

368 115 69

30 31

60 2 15

202 13

recommended for control circuit. If the DC power source is not available, employ the AC closing and capacitor trip device for tripping. Make sure to use the "NO" auxiliary contacts (11-21) of vacuum contactor in trip circuit, and "NC" auxiliary contacts (16-26) of vacuum contactor for control relay
MAIN CIRCUIT TERMINALS 12 DIA-3 HOLES

MAIN CIRCUIT TERMINALS FRONT COVER INTERRUPTERS

30 6

VMC : Vacuum contactor 52CC : Closing coil 52TC : Trip coil DU : Drive unit 4 : Control relay

circuit.

Fig. 5 Latched type operating circuit

M10 SCREW

10
INDICATOR

124

30 371 6

400

OFF ON

TRIP LEVER (FOR LATCHED TYPE) TRIPPING HOLE (DIA 9) AUXILIARY SWITCH

180

128 DIA-15

217

(REAR) + 345 -1 166 + 195- 1 179

87654321

3 4 1 2

10 300 373 60 21
MOUNTING HOLES

166 134 + 300 -1 (FRONT)

11 DIA-4 HOLES

5
52 CC

TIMER

13 18
EARTHING TERMINAL (M8 BOLT) CONTROL TERMINAL

10

195 215

10

OSCILLATION

6
SWITCHING

POWER

LATCH MECHANISM (FOR LATCHED TYPE)

DETAIL OF MOUNTING HOLES (TOP VIEW)

Fig. 3 Types CV-6HA ( L ) -2 Fig. 6 Configuration of Drive -Unit

OUTLINE DIMENSIONS
REQUIRED MINIMUM INSULATION DISTANCE LIFTING HOLES INSULATION SHUTTER (20 DIA-2 HOLES) CONNECTED POSITION

RECOMMENDED PARTITION DISTANCE DISCONNECTED POSITION

REQUIRED MINIMUM INSULATION DISTANCE. CONNECTED POSITION

INSULATION SHUTTER POWER SOURCE TERMINALS 13 DIA-3 HOLES

LIFTING HOLES (20 DIA-2 HOLES)

RECOMMENDED PARTITION DISTANCE DISCONNECTED POSITION

10 466 125 125 30 12


METAL COVER HANDLE CONTROL CONNECTOR

115

125

125

115

10 10

100

588

10

115

125

125

115

10 10

100

555

139

116 90 5

POWER SOURCE PRIMARY CONDUCTORS 3-M12 SCREWS, DEPTH 20

12
METAL COVER

130

130 DIA 36 107 45 45 107 107 45 45 107

15 6 (PF)

(PF)
INDICATOR

METAL PARTITION

605

535

CONTROL CONNECTOR

535

293

COUNTER (OPTION)

33 15 148 60

COUNTER (OPTION)

535

(VMC) 6

505

INDICATOR

154

HANDLE

(VMC) 33

METAL PARTITION

293

257

186

186 114

104 124

19

148 60

114

104

124

LOCK LEVER MOUNTING HOLES

20

41 103 155 145 191 192 210 210 246 246

130
MANUAL TRIP LEVER (LATCHED TYPE)

412 472
LOAD TERMINALS 13 DIA-3 HOLES EARTHING TERMINAL (8mm 2 )

LOCK LEVER MOUNTING HOLES

38

527 800
13 DIA-4 MOUNTING HOLES

235

20

41 103 145 155 191 192 210 247 210 247

MANUAL TRIP LEVER (LATCHED TYPE)

38

527 810
13DIA-4MOUNTING HOLES

130 235 (VT)

METAL PARTITION

19

204

30

18 91

264

18 48

DIA 25

10
LOAD PRIMARY CONDUCTORS 3-M12 SCREWS, DEPTH 20

412 472 489


EARTHING TERMINAL (8mm 2 )

(VT)

20

20

Fig. 7 Types UVA-3GAM(L)/UVA-3HAM(L) UVA-6GAM(L)/UVA-6HAM(L)

Fig. 9 Types UVA-3GAM(L)1/UVA-3HAM(L)1 UVA-6GAM(L)1/UVA-6HAM(L)1

REQUIRED MINIMUM INSULATION DISTANCE INSULATION SHUTTER RECOMMENDED PARTITION DISCONNECTED DISTANCE POSITION CONNECTED POSITION LIFTING HOLES (20 DIA-2 HOLES)

10
METAL COVER

115

125

125

115

10

100

555

139

POWER SOURCE TERMINALS 13 DIA-3 HOLES

10
METAL COVER

115

125

125

115

10

RECOMMENDED PARTITION DISTANCE DISCONNECTED POSITION

100

REQUIRED MINIMUM INSULATION DISTANCE LIFTING HOLES (20 DIA-2 HOLES) INSULATION SHUTTER CONNECTED POSITION

588

116 90

POWER SOURCE PRIMARY CONDUCTORS 3-M12 SCREWS, DEPTH 20

10

10

12 125

466 125 30

12

130 5

130 DIA 36

HANDLE CONTROL CONNECTOR

INDICATOR COUNTER (OPTION)

(PF)

15

HANDLE CONTROL CONNECTOR

INDICATOR

(PF)

METAL PARTITION

154

605

605

535

535

535

(VMC) 139 6

COUNTER (OPTION)

(VMC) 139

METAL PARTITION

293

293

257

186 114

164 170

186 114

124

164 170

124

104

20

19

104

20

19

MOUNTING HOLES

20

145 191 210 252

103 155 192 210 328

130
DRAWOUT MECHANISM

8 25

38

527 808

235 (VT)

LOAD TERMINALS 13 DIA-3 HOLES DRAWOUT MECHANISM

412 472
EARTHING TERMINAL (8mm 2 )

MOUNTING HOLES

20

20

MANUAL TRIP LEVER (LATCHED TYPE)

13 DIA-4 MOUNTING HOLES

145 191 210 252

103 155 192 210 328

130
DRAWOUT MECHANISM

8 25

38

527 808
13 DIA-4 MOUNTING HOLES

235

METAL PARTITION

204

15

30

18 91

264

18 48

DIA 25

10 (VT)
LOAD PRIMARY CONDUCTORS 3-M12 SCREWS, DEPTH 20

412 472 489


EARTHING TERMINAL (8mm 2 )

20

MANUAL TRIP LEVER (LATCHED TYPE)

Fig. 8 Types UVA-3GAD(L)/UVA-3HAD(L) UVA-6GAD(L)/UVA-6HAD(L)

Fig. 10 Types UVA-3GAD(L)1/UVA-3HAD(L)1 UVA-6GAD(L)1/UVA-6HAD(L)1

10

OPERATING CIRCUITS
Test R AC T L5 2E-RY E OFF STOP INTERLOCK E E 4 Normal Service Main Power Supply R S T
T1 T13 T12 T2 T14 T5 T17 T18 T6 T7 T8 T10 T3 T11 T4 4

INTERLOCKS
L4 LS2

The electrical and mechanical interlocks are provided on Combination unit as described below to prevent misoperation and to ensure high safety. The unit can not be withdrawn from the "CONNECTED" position, while the contactor is "ON". The unit can not be inserted into the "CONNECTED" position, while the contactor is "ON". The contactor can not be closed, unless the unit is either in the "CONNECTED" or "DISCONNECTED" position. The cubicle door can not be opened, unless the unit is in the "DISCONNECTED" position. (note) The unit can not be inserted into the "CONNECTED" position, unless the cubicle door is closed. (note) The operating handle can not be extracted, unless the unit is either in the "CONNECTED" or "DISCONNECTED" position. The contactor is "OFF" by inserting the operating handle. (Refer to Notes on page 11.) The unit can be padlocked at the "CONNECTED" and "DISCONNECTED" position.

How to furnish the front door with interlocks When performing interlocks between the handle operation type unit and front door, conduct the design by adopting following steps, referring to Fig. 13. Preparation of small door Provide the front door with a small door for handle operation. (approx. size 95X200) Interlock to prevent door opening at connected position The interlock pin in the connected position is at "B" position. Attach a stopper for the interlock pin to door so that the interlock pin can be clasped and the door can not be opened. The stopper may be installed with screws for emergency door open by removing screws. Interlock to prevent handle operation at door opening Provide a rod on door side for interlock lever release and adjust the length of rod. Provide the small hole (approx. 12X22) at location of ON-OFF indication for confirmation of unit position.

L4
E ON COS START INTERLOCK
T1

LS2

L5 L8

T2

T3

T4

T5

T6

T7

T8

T10 T12 T11

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

T13 T15 T17 T19 T21 T23 T14 T16 T18 T20 T22 T24 AUS
(CONTROL CONNECTOR HOUSING)

PF

F VT F1

DU

16

15 14

13 12 11

LS3 LS4
NOTE 1. LS1 is ON at the position of both connected and disconnected. 2. LS2 provided only on handle operation type, but not connected to connector housing, is OPERATE by inserting the handle. Make sure to open the contactor by handle insertion. 3. LS3 operates only at the connected position. 4. LS4 indicates fuse blown. (Fuse blown detector)

LS1
5 52CC 52CC 26 25 24 23 22 21

52

U V W Load

T19

T20

T21 T15 T22

T23

T24 T16

8 - 10

Fig. 11 Non-latched type (AC operation)


P DC N

(Note) The f r ont door must be adj ust ed w hen t he i nt er l ocks ar e em pl oyed.
Parts Position Interlock Position "A" "B" Shaft Position "B" "C" Name Plate Inserting Arm Position for ON-OFF Direction of Indicator Handle "D" "E" OFF ON "B" "C"

Symbol marked

indicate for handle operation type

8 Stopper 2 Interlock Pin (DIA 8)

E ON E COS START INTERLOCK 2EX

L4 E E OFF 2EX L8

LS2

2E

Disconnected Position Connected Position

Small Door 95 53 8 Hole 1 Rod Shutting The Door Cancels The Interlock 2 Interlock Pin

23

Draw-out Position

3 Shaft 5 Interlock Lever 1 Rod 9 Rod Support 6 Arm 32 "C" "D" 5 Interlock Lever "E"

2EX

18

4 4

4 Name Plate for ON-OFF Indication 2 Interlock Pin 1 Rod Depressing Position 20

R S T

T1 T13 T12

T3 T15

T2 T14

T6

T18

T4

T16

T7 T8

T10

T11

T5

10

Main Power Supply

F VT F1

81

68

5 52 D 6 U V W Load
52CC 52CC

26

21 52TC

25 24

23 22

65

LS4

28 113
T19 T21 T20 T22 T23 T24 T17

3 Shaft 7 Lock Lever Cubicle Door 7

81 68 65

DU

16

11

13 12

LS1

LS3

104

PF

AUS 15 14

200

"B"

"A" 74 101

32

Mounting Hole of Combination Unit

Mounting Hole of Combination Unit

Fig. 12 Latched type (shunt trip)

Fig. 13 Withdraw mechanism and hole for handle operation type

11

12

OUTLINE DIMENSIONS Double Barrel Fuses


RECOMMENDED PARTITION DISTANCE DISCONNECTED POSITION REQUIRED MINIMUM INSULATION DISTANCE CONNECTED POSITION POWER FUSE (DOUBLE BARREL)

OUTLINE DIMENSIONS Fused Contactors


Type Form
139

Non-latched type Latched type

UVA-3GA UVA-3GAL 3.3 200 40

UVA-3HA UVA-3HAL

UVA-6GA UVA-6GAL 6.6

UVA-6HA UVA-6HAL

10

115

125

125

115

10 10

100

555

Rated operational voltage (kV) Rated operational current (A)


POWER SOURCE TERMINALS

400

200 40

400

Rated interrupting current (kA)

(PF)
METAL COVER

15 6 (PF) B
10 115 125 125 115 10
RECOMMENDED PARTITION DISTANCE

REQUIRED MINIMUM INSULATION DISTANCE

LIFTING HOLES (20 DIA-2 HOLES)

(VMC) 6

154

543

POWER SOURCE TERMINALS (13 DIA-3 HOLES)

535

9 10 125

466 125 30

293

257

15

METAL COVER INDICATOR

605

LOAD TERMINALS
535

(VMC)

154 535

15

(PF)

POWER FUSE RATED FPG1-C50A FPG1-C60A FPC3-M250A / C175A

FUSE SIZE 50DIA 85DIA

A 575 627

B 645

CONTROL CONNECTOR

COUNTER (OPTION)

15 257

30

Fig. 14 Types UVA-3GAM(L)/UVA-3HAM(L) UVA-6GAM(L)/UVA-6HAM(L)


MOUNTING HOLES

19

190 191 436

103 190 192

104

697

114

124

294

12
MANUAL TRIP LEVER (LATCHED TYPE)

455 479
12 DIA-4 MOUNTING HOLES

55

LOAD TERMINALS (13 DIA-3 HOLES)

EARTHING TERMINAL (8mm 2 )

(VT)

Earthing Switch
INSULATION SHUTTER

Fig. 16 Types UVA-3GA(L)/UVA-3HA(L) UVA-6GA(L)/UVA-6HA(L)


3 136 12 466 12

MOVABLE UNIT

DRAWOUT MECHANISM

45

182

535

65

20

130 25 808 907


EARTHING MECHANISM

175

74

EARTHING CLIPS

42
DRAWOUT MECHANISM

472
EARTHING WIRE EARTHING TERMINAL (8mm 2 )

Fig. 15 Earthing Switch Configuration

13

14

: Provided as Standard

: Option upon request

: Supplied

: Not supplied

Contactor Name of parts Counter Position switch Blown fuse detector VT (1unit) Additional VT Insulation barrier Insulation fuse barrier Shutter padlock provision Position padlock provision Earthing switch LS3 LS7 LS4 CV

Combination Units Manual type Handle type Fixed type Option Connected position (1NO-1NC) Disconnected position (1NO) 1NO Provided only on Non-latched Max. 2VT Partition between power and load terminals For the earthing side Padlock not provided Padlock not provided For load side cable
WIRE

Contactor Remarks Name of parts Control wire Control test wire Operating handle LC9 Capacitor trip device CR Surge suppressor Mechanical interlock LC10 CIT-10Q CV

Combination Units Manual type Handle type Fixed type Remarks With plug (2mm2 X 2m) With plug and socket (2mm2 X 2m) For Handle type For Latched type 100/110VAC for 100-110V coil 200/220VAC for 200-220V coil 100/200VAC for 100-110V coil

NV60K304T1 (See Page 5) (See Fig. 20)

CONNECTOR

DIA 27

DIA 6 HOLE

INSERT SIDE 10X20.5 HOLE 49

66

70 86

400 2000 46
24

4.5

44

Fig. 18 Control wire : Supplied : Not supplied

Fig. 19 Operating handle

Contactor Name of parts Wipe gauge Trip rod Connector housing and pins as loose parts CV

Combination Units Manual type Handle type Fixed type Remarks

Capacitor trip device


For checking contact wear For latched type only Crimping tool No.720725-1 Tyco Electronics AMP. CO.
The capacitor trip device will be used for latched contactor when DC power source is not available. The device charges from AC power, and supplies DC power to the trip coil at trip command. The alarm contact is provided on CIT-10Q.

Mechanical interlock
The mechanical interlock shall be used in the reversing starter to prevent mechanically from closing the forward and reverse contactors simultaneously.
CV-6GA,6HA CV-6GAL,6HAL

Wipe gauge
The wipe gauge can be used for checking contact wear of vacuum interrupters. Refer to the instruction manual for using this gauge. Wipe gauge
28 t 0.5 120

The following vertical pitch interlocks are available for CV6 series contactors.
SHAFT (VMC) VMC : OFF
8.8

Vertical pitch 450mm and 550mm

Trip rod
The trip rod may be used for manual tripping for latched contactor and combination unit, however this operation shall be maintenance purpose or emergency case only.

Trip rod
DIA 7
PITCH BETWEEN CONTACTORS

60
P

OFF ON

Housing (Pins)
HOUSING

VMC : OFF

Connector housing and pins as loose parts


These parts are for the connection of control circuit in combination unit.
46 66 70 86
MOUNTING HOLES 11 DIA -4 HOLES 10

136 195 257 10 45

128

13 300 426 45

24

Fig. 20 Outline of mechanical interlock

Fig. 17 Standard accessories 15 16

400

Motor application
3.3kV Power fuse Current (A) Type Vacuum Contactor (A) Standard value of load current (A) 10 11.7 13.8 18.8 22.1 26.7 32.5 38.5 48 74.1 92.1 102.6 140.9 171.9 178 195.1 216.2 267 320.3 Applicable motor (kW) 37 45 55 75 90 110 132 160 200 315 400 450 630 750 800 900 1000 1250 1500 1750 2000 2500 3000 Standard value of load current (A) 4.8 5.6 6.6 9.1 10.5 12.8 15.1 18.4 23.7 36.9 46.1 51.3 70.6 82.1 89 97.6 108.1 134.4 160.2 194 217 270 322 6.6kV Vacuum Contactor (A) Power fuse Type Current (A)

Inquiry No. : Quantity :

P/O No. :

Designation and type form

UVA
Use this sheet for confirmation on each rating and specification

M25

Type
M25 FPG1-6X75N

UVA 6 : 6.6kV G : 200A M : Manual type No symbol : Non Latched type Operating voltage Closing voltage Latched type Tripping voltage 3 : 3.3kV H : 400A A D : Handle type L : Latched type 6.3kA (without power fuse) AC/DC100-110V others (specify : AC/DC100-110V others (specify : DC100-110V others (specify : Without power fuse T40 C25 T50 C40 M25 M200 T225 C150 Quantity (set No.) M150 T175 FPC3 (6.6kV) Quantity (set No.) C100 M200 T225 C150 M250 T60 C50 M40 M250 T75 C60 M50 M300 M350 T350 C275 2 X M250 2 X C50 2 X C60 AC/DC200-220V V) AC/DC200-220V V) DC200-220V V) ).

M50

FPC3-3X25N 200

Rated operational voltage Rated operational current Series

M100 M200 M250 M300 M350 FPC3-3X25N 400 FPC3-3G25N

200

M50

Draw-out/in mechanism
FPC3-6X75N M150

1 Bushing type

Operating mechanism
FPC3-6G75N M200

Rated interrupting current


FPC3-6X75N 400 FPC3-6H75N M400 M250

40kA (with power fuse)

Non Latched type Rated control voltage

Notes 1. Full-load current represents the average value of Toshiba Motors (2, 4, 6 poles). Check the motor characteristics. 2. The standard for power fuse selection is : full-load current X 6, 5 second-2 times.

Transformer application
3.3kV Power fuse Current (A) Type Vacuum Contactor (A) Standard value of load current (A) 5.3 8.8 13.2 17.5 26.3 35 43.8 54.5 70 87.5 109 131.2 175 218.7 263 350 Applicable transformer (kVA) 30 50 75 100 150 200 250 300 400 500 600 750 1000 (1250) 1500 2000 2500 3000 4000 0.1 second. Standard value of load current (A) 2.7 4.4 6.6 8.8 13.2 17.5 21.9 26.3 35 43.8 54.5 65.7 87.5 109.4 131.2 175 218.7 263 350 6.6kV Vacuum Contactor (A) Power fuse Type Current (A)

Refer to Fuse selection table. Quantity (set No.) shall be scribed in parentheses ( Three-phase FPG1 (3.3/6.6kV)
T20

Single-phase T20 C15 T30 C20

T20 T30 T50 T60 T75 T150 T225 M250 M300 T350 2 X M250 FPG1-6X75N 200 FPC3-3X25N FPC3-3G25N

Quantity (set No.) M25 T50 FPC3 (3.3kV) C40 Power fuse selection

M50 T100 C75

M100 T150 C100

FPG1-6X75N T30 200 T50 T75 FPC3-6X75N FPC3-6G75N FPC3-6X75N 400 FPC3-6H75N T175 T225 M250 T400

C175

C200

2 X C175

FPC3-3X25N

C175

M400 T400

400

1 X VT 2 X VT Not required LS3 Connected position switch Disconnected position switch Blown fuse detector Insulation barrier between fuses Insulation fixing barrier Insulation shutter Connector housing and pins as loose parts Counter Insulation barrier (Partition between power and load terminals) Insulation fuse barrier for the earth (Phase to earth) Shutter padlock provision Position padlock provision Earthing switch for load side cable Please refer to page 16 to specify the quantities each LS7 LS4 Standard accessories 3300/110V 6600/110V Others (specify : 3300/220V 6600/220V V) UVA type : standard UVA type : option UVA type : standard

Notes 1. The standard for power fuse selection is : full-load current 2. 2 X M : double barrel/phase.

X 10,

VT
6.6kV Applicable capacitor (kvar) 30 50 75 100 150 200 250 300 400 500 600 800 1000 1250 1500 2000

Capacitor application (with series reactor)


3.3kV Power fuse Current (A) C15 C40 C50 C60 2 X C50 2 X C60 C150 C175 C200 C275 2 X C175 FPC3-3G25N FPG1-6X75N 200 Type Vacuum Contactor (A) Standard value of load current (A) 5.3 8.8 13.2 17.5 26.3 35 43.8 55.6 74.2 93 111 148 185 232 278 372 Standard value of load current (A) 2.7 4.4 6.6 8.8 13.2 17.5 21.9 28 37 46.4 55.6 74.2 97 116 139 185 Vacuum Contactor (A) Power fuse Type Current (A)

Limit switch

C15

FPG1-6X75N 200

C40 C50 C60 2 X C50 2 X C60 C150

Options

FPC3-3X25N

400

FPC3-6X75N

C175

Notes 1. The standard for power fuse selection is : full-load current X 5, 0.1 second. 2. 2 X C : double barrel/phase.