Switchgear and Substations

3.2 Medium-Voltage Switchgear

8DJH

Rated Voltage Frequency Short-duration power-frequency withstand voltage Lightning impulse withstand voltage Normal current for ring-main feeders Normal current for busbar Normal current for circuit-breaker feeders Normal current for transformer feeders Short-time withstand current, 1 s Short-time withstand current, 3 s Short-circuit making current for ring-main feeders for circuit-breaker feeders for transformer feeders Short-time withstand current, 1 s Short-time withstand current, 3 s Short-circuit making current for ring-main feeders for circuit-breaker feeders for transformer feeders
* 42 kV according to some national requirements

kV Hz kV kV A max. A A A max. kA max. kA 50 Hz max. kA max. kA max. kA max. kA max. kA max. kA 60 Hz max. kA max. kA max. kA max. kA

7.2 50/60 20 60 630

12 50/60 28* 75

15 50/60 36 95

17.5 50/60 38 95

24 50/60 50 125

400 or 630 250 or 630 200** 25 20 63 63 63 63 21 21 55 55 55 55 25 20 63 63 63 63 21 21 55 55 55 55 25 20 63 63 63 63 21 21 55 55 55 55 25 20 63 63 63 63 21 21 55 55 55 55 20 20 50 50 50 50 20 20 52 52 52 52

Peak withstand current

Fig. 3.2-21: 8DJH block type

The gas-insulated mediumvoltage switchgear type 8DJH is used for power distribution in secondary distribution systems up to 24 kV. Ring-main feeders, circuit-breaker feeders and transformer feeders are all part of a comprehensive product range to satisfy all requirements with the highest level of operational reliability also for extreme ambient conditions. Performance features Design veried according to IEC 62271-200 Sealed pressure system with SF6 lling for the entire service life Safe-to-touch enclosure and standardized connections for plug-in cable terminations 3-pole, gas-insulated switchgear vessel for switching devices and busbar Panel blocks and single panels available Switching devices: threeposition load-break switch (ON OFF EARTH), switchfuse combination for distribution transformer protection, vacuum circuitbreaker with three-position disconnector, earthing switch Earthing function of switching devices generally make-proof

Peak withstand current

** Depending on HV HRC fuse-link

Table 3.2-20: Technical data of 8DJH

Dimensions Width W Number of feeders (in extracts) 2 feeders (e.g., RR) 3 feeders (e.g., RRT) 4 feeders (e.g., 3R + 1T) Panels without low-voltage compartment Panels with low-voltage compartment (option) Switchgear with pressure absorber (option) Standard switchgear Switchgear with pressure absorber (option)

Dimensions in mm 620 1,050 1,360 1,200/1,400/1,700 1,4002,600 1,8002,600 775 890

Height

Depth

Fig. 3.2-22: Dimensions of 8DJH block types

Siemens Energy Sector Power Engineering Guide Edition 7.0

109