August 1999 P/N 76-100016-001

PEGAsys

Intelligent Suppression-Control and Fire-Alarm System

Installation, Operation, and Maintenance Manual


UL Listing File No. S2422 Factory Mutual Approval J.I. No. OB2A6.AY

LISTED

Fire Systems

PEGAsys
Intelligent Suppression-Control and Fire-Alarm System

Installation, Operation, And Maintenance Manual

Document No. PEGAsys August 1999

This Manual Is To Be Used By Trained Distributors Only

FOREWORD
This manual is intended to clearly and accurately reflect the PEGAsys Fire Alarm/Suppression Control System. This publication describes the operation, installation and maintenance of the PEGAsys Fire Alarm/Suppression Control System, P/Ns 76-100000-501 for Single-Loop System and 76-100000-600 for Multi-Loop System.

TERMS AND ABBREVIATIONS


ADA AI AO BPM CCM CCP EDP EOC FCP GUI I/O ID IRI NC Americans with Disabilities Act Addressable Contact Input Device Addressable Relay Output Device Beats Per Minute Central Control Module Central Control Panel Electronic Data Processing Event Output Control Fire Control Panel Graphical User Interface Input/Output Identification Industrial Risk Insurers Normally Closed NO NR NYC P/N PAS PC PCS Normally Open Not Registered New York City Part Number Positive Alarm Sequence Personnel Computer PEGAsys Configuration Software

PC Line Power/Communication Line (RX/TX Loop) PS RCU RTC RX/TX UL VDC Power Supply Remote Control Unit Real Time Clock Receive Transmit Underwriter Laboratories Voltage Direct Current

ACCEPTANCES, APPROVALS, AND CERTIFICATIONS PEGAsys Single-Loop System (P/N 76-100000-501)


UL: Underwriters Laboratories Listing File Number S2422. FM: Factory Mutual Engineering Corp. (Factory Mutual System) Approval J.I. Number 3005511 CSFM: Pending. NYC: Pending.

PEGAsys Multi-Loop System (P/N 76-100000-600)


UL: Underwriters Laboratories Listing File Number S2422. FM: Factory Mutual Engineering Corp. (Factory Mutual System) Approval J.I. Number 3005511 CSFM: Pending. NYC: Pending.

(THIS PAGE IS INTENTIONALLY LEFT BLANK)

ii

TABLE OF CONTENTS
Forward ......................................................................................................................................................... i Terms and Abbreviations ................................................................................................................................ i Appendices ................................................................................................................................................... vi List of Illustrations .......................................................................................................................................... vii List of Tables ................................................................................................................................................. ix Safety Summary ............................................................................................................................................ x PARAGRAPH
1 1-1 1-1.1 1-1.2 1-2 1-2.1 1-2.2 1-2.3 1-2.4 1-2.5 1-2.6 1-2.7 1-2.7.1 1-2.7.2 1-2.7.3 1-2.7.4 1-2.8 1-2.9 1-2.9.1 1-2.9.2 1-2.9.3 1-2.10 1-2.11 1-2.12 1-2.13 1-2.14 1-3 2 2-1 2-1.1 2-2 2-2.1 2-2.2 2-2.3 2-3 2-3.1 2-3.2 2-3.3 2-4 2-5 2-5.1 2-5.2 2-5.3 2-5.4 2-5.4.1 2-5.4.2 2-5.4.3 2-5.4.4 2-6 2-6.1 2-6.2 2-6.2.1 2-6.2.2

TITLE

PAGE

GENERAL INFORMATION ................................................................................................................................................ 1-1 Introduction ..................................................................................................................................................................... 1-1 System Description ........................................................................................................................................................ 1-1 System Components ..................................................................................................................................................... 1-1 Component Description ................................................................................................................................................. 1-1 Central Control Module (CCM) ....................................................................................................................................... 1-1 Display Module ............................................................................................................................................................... 1-1 Receiver/Transmitter Module (RX/TX) ............................................................................................................................ 1-2 Power Supply/Charger Assembly .................................................................................................................................. 1-2 Basic Motherboard ......................................................................................................................................................... 1-2 Multi-Loop Motherboard ................................................................................................................................................. 1-3 Input/Output Modules ..................................................................................................................................................... 1-3 Signal Output Module ..................................................................................................................................................... 1-3 Relay Output Module ...................................................................................................................................................... 1-3 Agent Release Output Module ....................................................................................................................................... 1-4 City Tie Module ............................................................................................................................................................... 1-4 Standby Batteries ............................................................................................................................................................ 1-4 Intelligent Loop Devices ................................................................................................................................................. 1-4 SmartOneTM Ionization Detectors ................................................................................................................................... 1-4 SmartOne Photoelectric Detectors ................................................................................................................................ 1-5 SmartOne Heat Detectors ............................................................................................................................................. 1-5 SmartOne Detector Bases ............................................................................................................................................ 1-5 Addressable Contact Input Devices .............................................................................................................................. 1-5 Addressable Relay Output Devices ............................................................................................................................... 1-5 Model DH-2000 Air Duct Housing .................................................................................................................................. 1-5 Loop Isolator Devices .................................................................................................................................................... 1-6 System Specification ...................................................................................................................................................... 1-6 OPERATION .................................................................................................................................................................... 2-1 Introduction ..................................................................................................................................................................... 2-1 Mode of Operation .......................................................................................................................................................... 2-1 Control and Indicators .................................................................................................................................................... 2-1 LCD Display ................................................................................................................................................................... 2-1 Audible Device ................................................................................................................................................................ 2-2 Control and Indicator Description .................................................................................................................................. 2-2 System Security .............................................................................................................................................................. 2-2 Levels of Security ............................................................................................................................................................ 2-2 Default Passwords ......................................................................................................................................................... 2-2 Entering Passwords ...................................................................................................................................................... 2-2 System Power-Up .......................................................................................................................................................... 2-2 System Menus ................................................................................................................................................................ 2-4 Menu Structure ................................................................................................................................................................ 2-4 Accessing the System Menus ........................................................................................................................................ 2-4 Exiting the System Menus .............................................................................................................................................. 2-4 Menu Functions .............................................................................................................................................................. 2-4 Isolate Menu Function .................................................................................................................................................... 2-4 List Menu Function ......................................................................................................................................................... 2-4 Set Menu Function .......................................................................................................................................................... 2-4 Test Menu Function ........................................................................................................................................................ 2-4 Modes of Operation ........................................................................................................................................................ 2-5 Normal Standby Mode .................................................................................................................................................... 2-5 Active Alarm Mode ........................................................................................................................................................... 2-5 Alarm Mode Indications .................................................................................................................................................. 2-5 Alarm Mode User Action ................................................................................................................................................. 2-5
iii

TABLE OF CONTENTS (CONT.)


PARAGRAPH
2-6.3 2-6.3.1 2-6.3.2 2-6.4 2-6.4.1 2-6.4.2 2-7 2-8 2-8.1 2-8.1.1 2-8.2 2-8.2.1 2-8.2.2 2-8.3 2-8.3.1 2-8.3.2 2-8.3.3 2-8.3.4 2-8.3.5 2-8.4 2-8.5 2-8.5.1 2-8.6 2-8.7 2-8.7.1 2-8.7.2 2-8.7.3 2-8.7.4 2-8.7.5 3 3-1 3-2 3-3 3-3.1 3-3.2 3-3.3 3-3.4 3-3.5 3-3.6 3-3.7 3-3.8 3-3.9 3-3.10 3-3.11 3-3.12 3-3.13 3-3.14 3-3.15 3-3.16 3-3.17 4 4-1 4-2 4-3 4-3.1 4-3.2 4-3.3 4-3.4

TITLE

PAGE

Active Supervisory Trouble Mode ................................................................................................................................. 2-10 Supervisory Trouble Mode Indication ........................................................................................................................... 2-10 Supervisory Trouble Mode User Action ........................................................................................................................ 2-10 Active Trouble Mode ...................................................................................................................................................... 2-11 Trouble Mode Indications .............................................................................................................................................. 2-11 Trouble Mode User Action ............................................................................................................................................. 2-11 Printing Operation ......................................................................................................................................................... 2-11 System Programming ................................................................................................................................................... 2-11 EOC Programming ........................................................................................................................................................ 2-11 Listing EOC Programming ........................................................................................................................................... 2-12 RTC Programming ....................................................................................................................................................... 2-12 Listing RTC Programming ........................................................................................................................................... 2-12 Enable/Disable RTC Program Line Numbers ............................................................................................................ 2-12 Types of Inputs and Outputs ........................................................................................................................................ 2-12 System Inputs ............................................................................................................................................................... 2-12 Remote Control Unit (RCU) ......................................................................................................................................... 2-12 RX/TX Loops ................................................................................................................................................................. 2-12 System Outputs ............................................................................................................................................................ 2-13 System I/O Modules ..................................................................................................................................................... 2-13 Addressing I/O Modules ............................................................................................................................................... 2-13 Registering I/O Module Assignments .......................................................................................................................... 2-13 Listing I/O Module Assignment .................................................................................................................................... 2-13 Addressing RCUs ....................................................................................................................................................... 2-13 Registering RCUs ....................................................................................................................................................... 2-14 Detector Registration ................................................................................................................................................... 2-14 Addressable Contact Monitor Registration .................................................................................................................. 2-14 Remote Relay Registration .......................................................................................................................................... 2-15 Listing all Registered RCUs ....................................................................................................................................... 2-15 Un-registering RCUs .................................................................................................................................................. 2-15 FUNCTIONAL DESCRIPTION .......................................................................................................................................... 3-1 Introduction ..................................................................................................................................................................... 3-1 Overall Block Diagram Description ................................................................................................................................ 3-1 Functional Descriptions ................................................................................................................................................. 3-2 Central Control Module .................................................................................................................................................. 3-2 Receiver/Transmitter (RX/TX) Module ............................................................................................................................ 3-3 Power Supply/Charger Assembly, Revision A ................................................................................................................ 3-4 Power Supply/Charger Assembly, Revision C ............................................................................................................... 3-5 Multi-Loop I/O Motherboard ............................................................................................................................................ 3-6 Signal Output Module ..................................................................................................................................................... 3-7 Relay Output Module ...................................................................................................................................................... 3-8 Agent Release Module ................................................................................................................................................... 3-9 City Tie Module ............................................................................................................................................................. 3-10 Field Devices ................................................................................................................................................................. 3-11 SmartOne Ionization Detectors .................................................................................................................................... 3-11 SmartOne Photoelectric Detectors ............................................................................................................................... 3-11 SmartOne Heat Detectors ............................................................................................................................................ 3-11 Addressable Contact Input Devices ............................................................................................................................. 3-11 Addressable Relay Output Devices ............................................................................................................................. 3-12 Model DH-2000 Air Duct Housing ................................................................................................................................ 3-12 Loop Isolator Devices .................................................................................................................................................. 3-12 MAINTENANCE PROCEDURE ......................................................................................................................................... 4-1 Introduction ..................................................................................................................................................................... 4-1 Scheduled Maintenance ................................................................................................................................................ 4-1 Maintenance Procedures ............................................................................................................................................... 4-1 Lamp Test ....................................................................................................................................................................... 4-1 Loop Device Test ............................................................................................................................................................ 4-1 Battery Test ..................................................................................................................................................................... 4-1 Walk Test ........................................................................................................................................................................ 4-2

iv

TABLE OF CONTENTS (CONT.)


PARAGRAPH
4-3.4.1 4-3.4.2 4-3.5 4-3.5.1 4-4 4-4.1 4-4.2 4-5 4-5.1 4-6 4-6.1 5 5-1 5-2 5-2.1 5-2.2 5-3 5-4 5-4.1 5-4.2 5-4.3 5-4.4 6 6-1 7 7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-7.1 7-7.2 7-7.3 7-7.4 7-7.6 7-7.7 7-7.8. 7-8 7-9 7-9.1 7-9.2 7-10 7-10.1 7-11 7-12 7-13 7-14 7-14.1 7-15 7-16 7-17 7-18 7-18.1 7-18.2

TITLE

PAGE

Walk Testing Detectors .................................................................................................................................................. 4-2 Walk Test Procedure ...................................................................................................................................................... 4-2 Alarm Simulation Test (AST) .......................................................................................................................................... 4-2 AST Procedure ............................................................................................................................................................... 4-3 Disarming and Rearming Release Circuits .................................................................................................................. 4-3 Disarming Release Circuits .......................................................................................................................................... 4-3 Arming Release Circuits ................................................................................................................................................ 4-3 Power-Down System ...................................................................................................................................................... 4-3 Power-Down Procedure ................................................................................................................................................. 4-3 Power-Up System .......................................................................................................................................................... 4-4 Power-Up Procedure ...................................................................................................................................................... 4-4 TROUBLESHOOTING AND CORRECTIVE MAINTENANCE ............................................................................................. 5-1 Introduction ..................................................................................................................................................................... 5-1 Standard Fault Isolation Techniques ............................................................................................................................. 5-1 Visual Inspection ............................................................................................................................................................ 5-1 Power Checks ................................................................................................................................................................ 5-1 Troubleshooting ............................................................................................................................................................. 5-1 Removal and Replacement ........................................................................................................................................... 5-2 Required Tools ............................................................................................................................................................... 5-2 Central Control Module .................................................................................................................................................. 5-2 RX/TX Module ................................................................................................................................................................. 5-2 Field Devices .................................................................................................................................................................. 5-3 PARTS LIST .................................................................................................................................................................... 6-1 Introduction ..................................................................................................................................................................... 6-1 INSTALLATION ................................................................................................................................................................ 7-1 Introduction ..................................................................................................................................................................... 7-1 Materials Required For Installation ................................................................................................................................ 7-1 Installation Procedure For Central Control Panel ......................................................................................................... 7-1 Installation Procedure For Expansion Enclosures ........................................................................................................ 7-1 Installation Procedure For I/O Motherboard ................................................................................................................... 7-2 Installation Procedure For Rx/Tx Module (Multi-Loop Only) ........................................................................................... 7-2 Installation of I/O Modules .............................................................................................................................................. 7-3 Signal Audible Output Module ........................................................................................................................................ 7-3 Relay Output Module ...................................................................................................................................................... 7-4 Agent Release Module ................................................................................................................................................... 7-4 City-Tie Output Module ................................................................................................................................................... 7-4 Power Supply/Charger Assembly .................................................................................................................................. 7-4 Power Supply/Charger Assembly, Expansion Enclosure .............................................................................................. 7-4 Power Supply Communication Connections ................................................................................................................ 7-6 Connecting AC Power .................................................................................................................................................... 7-6 Install And Connect DC Power ....................................................................................................................................... 7-6 Battery Enclosure ........................................................................................................................................................... 7-6 Batteries ......................................................................................................................................................................... 7-6 Field Device Connection To RX/TX Module .................................................................................................................... 7-7 Wiring the RX/TX PC Line ............................................................................................................................................... 7-7 Output Signal Connection .............................................................................................................................................. 7-9 External Power Failure Indicator Connection .............................................................................................................. 7-10 Detector Installation ..................................................................................................................................................... 7-10 Setting and Adjusting Smoke & Heat Detector Sensitivities ........................................................................................ 7-10 Setting and Adjusting Smoke and Heat Detector Sensitivity Procedure ..................................................................... 7-10 Addressable Contact Input Device Installation ............................................................................................................. 7-11 Addressable Relay Output Device Installation ............................................................................................................. 7-11 Installation Checkout ..................................................................................................................................................... 7-11 Connection of Peripherals ............................................................................................................................................ 7-11 Connecting a Terminal or Personal Computer ............................................................................................................ 7-11 Connecting a Printer ..................................................................................................................................................... 7-11

APPENDICES
APPENDIX
A B C D E F G H I J K L M N O

TITLE

PAGE

POWER SUPPLY REQUIREMENTS .............................................................................................................................. A-1 SYSTEM EXPANSION .................................................................................................................................................... B-1 RELEASING APPLICATIONS ......................................................................................................................................... C-1 NOT USED .................................................................................................................................................................... D-1 FACTORY MUTUAL SPRINKLER REQUIREMENTS .................................................................................................... E-1 GLOSSARY ..................................................................................................................................................................... F-1 DISPLAY ABBREVIATIONS ............................................................................................................................................ G-1 INDEX ............................................................................................................................................................................ H-1 SYSTEM DRAWINGS ...................................................................................................................................................... I-1 PEGAsys NETWORK INTERFACE CARD ...................................................................................................................... J-1 ADDRESSABLE SIGNAL/SOUNDER ............................................................................................................................ K-1 REMOTE DISPLAY CONTROL MODULE AND REMOTE DISPLAY MODULE ............................................................... L-1 ADDRESSABLE ALARMLINE MODULE ........................................................................................................................ M-1 NETWORKABLE CENTRAL CONTROL MODULE (NCCM) ......................................................................................... N-1 CENTRAL STATION OPERATION .................................................................................................................................. O-1

vi

LIST OF ILLUSTRATIONS
FIGURE
1-1 1-2 1-3 1-4 1-5 1-6 1-7 1-8 1-9 1-10 1-11 1-12 1-13 1-14 1-15 1-16 1-17 1-18 1-19 1-20 1-21 2-1 2-2 2-3 3-1 3-2 3-3 3-4 3-5 3-6 3-7 3-8 3-9 3-10 3-11 3-12 3-13 3-14 3-15 3-16 3-17 3-18 5-1 5-2 7-1 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10 7-11 7-12 7-13

TITLE

PAGE

PEGAsys System Overall Diagram ................................................................................................................................ 1-0 Central Control Module (CCM) ....................................................................................................................................... 1-2 Display Module Assembly .............................................................................................................................................. 1-2 Receiver/Transmitter Module (RX/TX) ............................................................................................................................ 1-2 Power Supply/Charger Assembly .................................................................................................................................. 1-2 Basic I/O Motherboard .................................................................................................................................................... 1-3 Multi-Loop I/O Motherboard ............................................................................................................................................ 1-3 Signal Output Module ..................................................................................................................................................... 1-3 Relay Output Module ...................................................................................................................................................... 1-4 Agent Release Output Module ....................................................................................................................................... 1-4 City-Tie Module ............................................................................................................................................................... 1-4 Battery Enclosure ........................................................................................................................................................... 1-4 SmartOneTM Detection Device ....................................................................................................................................... 1-4 4-inch Detector Base ...................................................................................................................................................... 1-5 6-inch Detector Base ...................................................................................................................................................... 1-5 Addressable Contact Input Device ................................................................................................................................. 1-5 Addressable Relay Output Device ................................................................................................................................. 1-5 Air Duct Housing ............................................................................................................................................................ 1-5 Loop Isolator, Stand-Alone ............................................................................................................................................. 1-6 Loop Isolator, RX/TX Mount ............................................................................................................................................ 1-6 Loop Isolator, 6 Detector Base Mount ........................................................................................................................... 1-6 System Front Panel ........................................................................................................................................................ 2-1 Level One Menu Structure .............................................................................................................................................. 2-6 Level Two Menu Structure ............................................................................................................................................... 2-7 Overall Block Diagram, Single-Loop System ................................................................................................................ 3-1 Overall Block Diagram, Multi-Loop System ................................................................................................................... 3-1 Central Control Module, Details ..................................................................................................................................... 3-2 Receiver/Transmitter Module, Details ........................................................................................................................... 3-3 Obsolete Power Supply/Charger Assembly, Revision A, Details .................................................................................. 3-4 Power Supply/Charger Assembly, Revision C, Details ................................................................................................. 3-5 Multi-Loop I/O Motherboard, Details .............................................................................................................................. 3-6 Signal Output Module, Details ....................................................................................................................................... 3-7 Relay Output Module, Details ......................................................................................................................................... 3-8 Agent Release Output Module, Details .......................................................................................................................... 3-9 City Tie Module, Details ................................................................................................................................................ 3-10 Typical Detector ............................................................................................................................................................. 3-11 Addressable Contact Input Device ............................................................................................................................... 3-12 Addressable Relay Output Device ............................................................................................................................... 3-12 DH-2000 Air Duct Housing ........................................................................................................................................... 3-12 Loop Isolator, RX/TX Mount .......................................................................................................................................... 3-13 Loop Isolator, Stand-Alone ........................................................................................................................................... 3-13 Loop Isolator, 6 Detector Base Mount ......................................................................................................................... 3-13 Installation for Single Loop ............................................................................................................................................ 5-2 Installation for Multi-Loop ............................................................................................................................................... 5-2 CCP Installation Drawing ............................................................................................................................................... 7-1 Back Plate, I/O Motherboard & 4 P.S. .............................................................................................................................. 7-2 Back Plate, 8 P.S. ............................................................................................................................................................ 7-2 Back Plate, 2 I/O Motherboard ........................................................................................................................................ 7-2 Installation for Multi-Loop ............................................................................................................................................... 7-3 Power Supply/Charger (Rev A), Wiring Diagram ........................................................................................................... 7-4 Power Supply/Charger (Rev C), Wiring Diagram .......................................................................................................... 7-5 Power Supply/Charger (Rev A), Wiring Diagram for Expansion Enclosure .................................................................. 7-5 Power Supply/Charger (Rev C), Wiring Diagram for Expansion Enclosure ................................................................. 7-5 Battery Enclosure ........................................................................................................................................................... 7-7 Conduit to CCP ............................................................................................................................................................... 7-7 Shielded Wire to CCP .................................................................................................................................................... 7-7 Style 4, RX/TX PC Line Connections .............................................................................................................................. 7-8
vii

LIST OF ILLUSTRATIONS (CONT.)


FIGURE
7-14 7-15 7-16 7-17

TITLE

PAGE

Style 6, RX/TX PC Line Connections .............................................................................................................................. 7-8 Style 6, RX/TX PC Line Connections with Loop Isolators .............................................................................................. 7-9 Style 7, RX/TX PC Line Connection ................................................................................................................................ 7-9 CCM Printer Port ........................................................................................................................................................... 7-12

viii

LIST OF TABLES
TABLES
1-1 2-1 2-2 2-3 2-4 2-5 3-1 3-2 5-1 5-2 6-1 7-1 7-2 7-3

TITLE

PAGE

System Specification ...................................................................................................................................................... 1-6 Controls and Indicators .................................................................................................................................................. 2-3 Isolate Menu Function .................................................................................................................................................... 2-8 List Menu Function ......................................................................................................................................................... 2-8 Set Menu Function .......................................................................................................................................................... 2-9 Test Menu Function ...................................................................................................................................................... 2-10 Multi-Loop I/O Motherboard Connectors ........................................................................................................................ 3-6 Approved Release Output Devices ................................................................................................................................ 3-9 Troubleshooting Index ................................................................................................................................................... 5-1 RX/TX Configuration Selection ....................................................................................................................................... 5-3 PEGAsys System Parts List ........................................................................................................................................... 6-1 RX/TX Configuration Selection ....................................................................................................................................... 7-3 Aux. Power Supply Module Connections to Rev. A ......................................................................................................... 7-5 Aux. Power Supply Module Connections to Rev. C ........................................................................................................ 7-5

ix

SAFETY SUMMARY
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability:
Warning - Several different sources of power can be connected to this fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA - 1996 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0 to 49 C and at a relative humidity of 85% RH (non-condensing) @ 30C. However, the useful life of the systems standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 60-80F. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. The use of overhead or outside aerial wiring is not recommended due to the increased susceptibility to nearby lightning strikes. Consult with the Applications Engineering Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides. Before making modifications, verify that they will not interfere with battery and printed circuit board location. Do not over tighten screw terminals, over tightening may damage threads, resulting in reduced terminal contact pressure and difficult with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the Instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. PEGAsys operation and reliability depend upon proper installation.

Fire Alarm System Limitations

While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance!

An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification-capability can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. A fire alarm system will not operate without electrical power. If AC power fails, the system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.

Auxiliary Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections should be kept.

GENERAL SAFETY NOTICES

The following must be observed to maintain personnel safety.

The following general safety notices supplement specific warnings and cautions appearing in the manual. The safety precautions in this section must be understood and applied during operation and maintenance. This manual is to be used by trained distributors/technicians. The entire manual should be read and fully understood prior to installation. TEST EQUIPMENT Make certain test equipment is in good operating condition. Do not touch live equipment or personnel working on live equipment while holding a test meter. Some types of measuring devices should not be grounded; these devices should not be held when taking measurements. FIRST AID Any injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately. GENERAL PRECAUTIONS The following general safety precautions are to be observed at all times: 1. 2. 3. 4. 5. All electrical components associated with equipment shall be installed and grounded in accordance with NEC, NFPA and local regulation requirements. Special precautionary measures are essential to prevent applying power to equipment at any time maintenance work is in progress. Before working on electrical equipment, use a voltmeter to ensure that system is not energized. When working near electricity, do not use metal rules, flashlights, metallic pencils, or any other objects having exposed conductive material. When connecting a meter to terminals for measurement, use range higher than expected voltage.

xi

Intelligent Suppression Control/Fire Alarm System

PEGAsys

CHAPTER 1 GENERAL INFORMATION


In multi-loop form the PEGAsys ML panel (P/N 76-100000-600) consists of a CCM, one power-supply assembly, one RX/TX module and one multi-loop motherboard mounted in the enclosure. The unique multi-loop motherboard provides the ability to connect up to eight RX/TX modules to the system allowing a full 2040 addressable points to be connected to the PEGAsys ML system. Auxiliary enclosures are available to allow the system to be expanded. The auxiliary enclosure has the same dimensions as that of the main enclosure with the absence of the window in the door. There are optional back planes which install in the expansion enclosure. This allows the number of I/O modules and system power supplies to be expanded. To allow for maximum system flexibility expansion enclosure(s) and backplane(s) can be added to the system. Refer to Appendix B for further system expansion details.

1-1

INTRODUCTION

This manual contains the operation, maintenance, troubleshooting, parts listing, and installation information necessary to support the PEGAsys Intelligent Suppression Control and Fire Alarm System. NOTE: This manual is to be used by trained distributors only. The entire manual should be read and fully understood prior to installation.

1-1.1

System Description

PEGAsys is a fire alarm/suppression control system which can be used for local, auxiliary, remote protective signaling and releasing device service. The system is a microprocessor based design for use with intelligent detectors and loop devices. The system utilizes distributed intelligent field devices. These devices are typically smoke detectors, contact input devices relay outputs and signal output modules which represent a single fire alarm initiation/indicating zone. Each device contains its own data transceiver, micro controller, 4k of memory and applicable algorithms which allows each device to operate independent of the control system. These unique devices have the ability to analyze information, make decisions and store information within themselves. They communicate with the PEGAsys system using the BIP protocol which utilizes a two-wire (Style 4), four wire (Style 6) or isolated (Style 7) multiplex trunk. The PEGAsys can support up to 255 device addresses per loop with a maximum of 8 loops for a total of 2040 Intelligent device points per system. The PEGAsys is capable of controlling a wide variety of auxiliary devices, such as relays, audible visual indicating signal devices and agent/sprinkler release systems. The system also supports the use of serial printers which provide hard copy of system status information.

1-2

COMPONENT DESCRIPTION

The following paragraphs give a brief description of each components used in the PEGAsys system. For functional descriptions of each component see Chapter 3 of this manual.

1-2.1

Central Control Module (CCM)

The CCM assembly is the heart of the system and is comprised of two PCB assemblies, the display module and the main processor module. The CCM controls the operation and supervision of all the system modules and software within the PEGAsys system. It receives loop device data from the RX/TX module, processes the data based on pre-programmed instructions and transmits output commands to the output modules, field devices, and display module(s).

1-2.2

Display Module

1-1.2

System Components

The system is comprised of three major components as shown in Figure 1-1: the Central Control Panel (CCP) communicates with the field devices and drives output devices such as alarm signals that communicate with central stations and various types of control equipment. A display panel located on the CCP provides system status LEDs, Control Switches and a 80-character LCD for alphanumeric display of system status information. The single-loop PEGAsys Central Control Panel (P/N 76100000-501) consists of the Central Control Module (CCM) assembly, one receiver/transmitter (RX/TX) module and one power supply assembly. Optionally the system can add a motherboard assembly which allow the installation of optional output modules. An auxiliary power supply module can be added which increases the base system power supply capacity to 8.0 amps at 24 VDC.

The display module assembly, attached to the main processor PCB, provides the system with the operator interface for control switches, system status LEDs, system trouble/alarm buzzer, a 80-character (2 x 40) LCD display and an integral numeric keypad. The keypad is used for entering the security password and navigating through the user menus. The system buzzer provides two distinctly different signaling patterns for audible warning of system alarms and troubles.

76-100016-001

1-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System Battery charging and supervision AC power supervision 24 VDC supervision Battery load test 24 VDC ground fault detection (+/-) Auxiliary 24 VDC outputs

Display Reset Switch

Loop Isolator for Style 7

Figure 1-4. Receiver/Transmitter Module (RX/TX) Figure 1-2. Central Control Module (CCM)

System Status

POWER ON GROUND FAULT

ALARM PREALARM

TROUBLE CPU ERROR

SUPERVISORY SILENCE

ACKLDGE SCROLL

SILENCE DRILL

RESET

1 6

2 7

3 8

4 9

5 0

Figure 1-3. Display Module Assembly

1-2.3

Receiver/Transmitter Module (RX/TX)

The RX/TX functions as the hardware & software interface between the field devices and the CCM. The RX/TX receives control requests from the CCM and establishes communications with the field devices. The RX/TX receives status changes from the field devices and reports these changes to the CCM. The RX/TX shown in Figure 1-4 is capable of communicating with up to 255 intelligent devices and complies with the wiring requirements of NFPA Style 4, 6 & 7 (with the use of the loop isolator device). Style 4 initiation circuit wiring will permit T tapping, or branch circuitry.

Figure 1-5. Power Supply/Charger Assembly

1-2.4

Power Supply/Charger Assembly

1-2.5

Basic Motherboard

The power supply/charger assembly (P/N 76-100009-010) is comprised of a printed circuit board (PCB) assembly and a AC/ DC switching power supply unit. The switching power supply unit provides 4 amps of 24 VDC from the 120/240 VAC input power. The PCB assembly is a microprocessor based unit which provides the system with:

The basic I/O motherboard assembly (P/N 76-100007-001) is an assembly which can accept up to 8 I/O module circuit board assemblies. The motherboard is mounted to the back of the system enclosure and /or the auxiliary enclosures. It distributes the system 24 VDC power and I/O bus communications to the I/ O modules. The I/O bus communications are provided by a RJ12 (flat phone cable) style connection. The 24 VDC is provided by the system power supply via a 2-conductor wiring harness.

August 1999

1-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System The I/O motherboard mounts to standoffs on the back of the main and expansion enclosures with screws provided. 1-2.7.1 SIGNAL OUTPUT MODULE

PEGAsys
The PEGAsys panel has the capacity for a maximum of (8) Alarm Sounder/Signal Output cards, thus providing 32 possible signal circuits. Each Alarm Sounder/Signal Output card, Figure 18, is equipped with supervised 24 VDC outputs which can operate as Style Y or Style Z indicating circuits.

Figure 1-6. Basic I/O Motherboard

1-2.6

Multi-Loop Motherboard
76-100003-001

The multi-loop I/O motherboard assembly (P/N 76-100017-001) is an assembly which can accept up to 8 RX/TX modules and provide connections for up to 7 I/O module circuit board assemblies. The ML motherboard is mounted to standoffs on the back of the main system enclosure. It distributes system 24 VDC power, CCM-RX/TX communications for up to 8 RX/TX modules and I/O bus communications to the I/O modules. The I/O bus communications are provided by a RJ-12 (flat phone cable) style connection. A single RJ-12 connection connects the ML motherboard to the CCM for RX/TX communications. The 24 VDC is provided by the system power supply via a 2conductor wiring harness.

Figure 1-8. Signal Output Module Figure 1-7. Multi-Loop I/O Motherboard 1-2.7.2 RELAY OUTPUT MODULE The PEGAsys panel has the capacity for a maximum of 8 Auxiliary Relay Output cards, allowing up to 32 relays. Each Auxiliary Relay Output card is equipped with four (4), Form C, dry-contact relay outputs. The ability to isolate an individual relay output is provided through the system operator menu.

1-2.7

Input/Output Modules

The optional input/output modules allow the PEGAsys system to interface with external auxiliary devices. These auxiliary devices can be audible/visual signal devices, HVAC systems, elevator recall, power shut down, remote annunciators, agent/ sprinkler release system and any other control type input or output which may need to be interfaced to the system. The input and output modules plug into the motherboard assembly located on the back plate of the system enclosure. Each I/O module occupies one slot in the motherboard assembly which has 8 slots available. The I/O modules and the CCM communicate over the RS-485 based I/O bus, which uses a 6-conductor phone type cable to connect the CCM to the motherboard. The PEGAsys single-loop panel has the ability to support a maximum of 16 I/O modules, in any combination. However, no more than 8 of any one type of module can be used. If using a City-Tie module, the limit is one per system. The PEGAsys multi-Loop panel has the ability to support a maximum of 23 I/O modules, in any combination, on the system. However, no more than 8 of any one type module can be used. If using a City-Tie module, the limit is one per system. The following paragraphs describe each available I/O module in greater detail.
76-100016-001 1-3

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

76-100002-001

Figure 1-11. City Tie Module

1-2.8
Figure 1-9. Relay Output Module 1-2.7.3 AGENT RELEASE OUTPUT MODULE The PEGAsys panel has the capacity for a maximum of 8 agent release output modules, providing up to 8 release circuits and 24 maximum signal outputs on those modules.

Standby Batteries

Space is provided within the central control panel enclosure for up to two (2) 12-V, 17 Amp Hour, sealed lead-acid batteries used for 24, 60 or 90 hour standby operation. If additional batteries are required, an optional battery enclosure is available. The enclosure (Figure 1-12) is a heavy duty steel cabinet which can house up to two 40AH batteries. For installation information see Paragraph 7-9.1.

FIRE ALARM SYSTEM STANDBY BATTERIES

KIDDE

Figure 1-12. Battery Enclosure

1-2.9

Intelligent Loop Devices

The SmartOneTM Series of Intelligent Fire Alarm devices provide the PEGAsys control system with smoke and heat detection and necessary monitoring and control functions required by todays advanced fire alarm systems. The following paragraphs describe each available intelligent detection device. Figure 1-10. Agent Release Output Module 1-2.7.4 CITY-TIE MODULE The City-Tie (Notification) Module will provide connection and operation for local energy, shunt type master box and reverse polarity styles of output.

Figure 1-13. SmartOne Detection Device 1-2.9.1 SmartOne IONIZATION DETECTORS The SmartOne Ionization smoke detectors provide true distributed-intelligence, addressable microprocessor-based smoke detection to the PEGAsys system.

August 1999

1-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System 1-2.9.2 SmartOne PHOTOELECTRIC DETECTORS The SmartOne Photoelectric smoke detectors provide true distributed-intelligence, addressable microprocessor-based smoke detection to the PEGAsys system. 1-2.9.3 SmartOne HEAT DETECTORS The SmartOne Thermistor heat detectors provide true distributed-intelligence, addressable, microprocessor-based heat detection to the PEGAsys system.

PEGAsys

1-2.10 SmartOne Detector Bases


The SmartOne series of detection devices all use universal mounting bases which are available in three styles. The 4SB is a European-Style 4-inch base whose outside diameter matches that of the low profile SmartOne detectors, which when combined, provides a very attractive unit. The 4SB, shown in Figure 1-14, mounts to standard 3, 3.5-inch, or 100-mm electrical boxes with ease. Figure 1-16. Addressable Contact Input Device

1-2.12 Addressable Relay Output Devices


The addressable relay output device (P/N 70-408004-001) provides the PEGAsys system with a Form-C dry-contact interface for remote control applications.

Figure 1-14. Four-inch Detector Base The 6SB model, shown above, is a traditional style detector base with an integral trim ring which provides coverage for any inconsistencies between the electrical box and ceiling material. The 6SB mounts to standard 3, 3.5 and 4 inch electrical boxes with ease. Figure 1-17. Addressable Relay Output Device

1-2.13 Model DH-2000 Air Duct Housing


The DH-2000 air duct housing is designed for detecting particles of combustion products in air-handling systems.

Figure 1-15. 6-inch Detector Base

1-2.11 Addressable Contact Input Devices


The SmartOne Contact Monitor (P/N 70-407008-00X) allows an installer the ability to interface typical NO/NC fire alarm devices, such as water flow and tamper switches to the PEGAsys system. The contact monitor is also used to interface to the manual alarm, manual release and abort stations. Figure 1-18. Air Duct Housing

76-100016-001

1-5

August 1999

PEGAsys
1-2.14 Loop Isolator Devices
The SmartOne series of loop devices, shown in Figures 1-19 through 1-21, offer optional loop isolation which protects the loop from wire to wire short conditions (NFPA Style 7.0).

Intelligent Suppression Control/Fire Alarm System Table 1-1. System Specifications


IT E M P o w er S u p p ly *P o we r Re q ui re me nt: P.S . Inp ut (P e r Mo d ule ) P.S . Outp ut (P e r Mo d ule ) B a t. C ha rg e r Outp ut: A ux. Outp uts: (2) CCM S i g na l Outp ut: Re le a se Outp ut: 24 V D C , 2 A mp s 24 V D C , 2 A mp s 1 A mp @ 30 V D C 1 A mp @ 30 V D C 120/220 V, 50/60 Hz 120 VA C , 1.9 A mp s 220 VA C , .95 A mp s 24 V D C , 4 A mp s 26.4 V D C , 3A mp s 24 V D C , 1.5 A mp s e a ch C H AR AC T E R IS T IC S

Figure 1-19. Loop Isolator, Stand-Alone


SHORT-1 SHORT-2 J1 DS2 DS1
R

Re la y C o nta ct Ra ti ng : Tro ub le Re la y Ra ti ng : R X T X M o d u le Ma x. Vo lta g e : Mi n. Vo lta g e : Ma x. Li ne C a p a ci ta nce : Ma x. Li ne Re si sta nce : Ma x. A d d re ssa b le D e vi ce s: R elease M o d u le Re le a se Outp ut S i g na l Outp ut Re le a se Outp ut Typ e : S ig n al Au d ib le M o d u le S i g na l Outp uts: R elay M o d u le

26.4 V D C 19.0 V D C 1.0 uF 26 Ohms 255 p e r RX TX

LOOP ISOLATOR RX/TX

Underwriters Laboratories Inc.


LISTED

REFER TO INSTALLATION MANUAL P/N 76-100016-001 FOR MODULE INSTALL. PROCEDURES

KIDDE-FENWAL, INC.
ASHLAND, MA 01721

Figure 1-20. Loop Isolator, RX/TX Mount

2 A mp s @ 24 V D C 2 A mp s @ 24 V D C e a ch C a p a b le o f re le a si ng so le no i d s (sup p re ssi o n a nd sp ri nkle r)

(4) style " Y" o r (2) style " Z" 2 A mp s @ 24 V D C e a ch

Figure 1-21. Loop Isolator, 6" Detector Base Mount

C o nta ct Ra ti ng : C ity T ie M o d u le

(4) Fo rm C C o nta cts, 2 A mp s @ 30 V D C o r 1 A mp @ 120 VA C

1-3

SYSTEM SPECIFICATION

S hunt C o nta ct: Lo ca l E ne rg y Outp ut: Lo ca l E ne rg y S up e rvi so ry: Lo ca l E ne rg y Lo a d :

System power specifications are outlined in Table 1-1.

5 A mp s @ 24 V D C , Re si sti ve 500 mA ma x. @ 24 V D C , C urre nt Li m. 11 mA Ma ste r B o x Tri p C urre nt 0.25 A mp s. typ i ca l

*Refer to Appendix A for total system power and AC branch circuit requirements.
August 1999 1-6 76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

CHAPTER 2 OPERATION
When an Alarm returns to a normal state (Alarm Off), the buzzer will sound in a pulsed fashion, the alarm off condition must be acknowledged to silence the buzzer. During the Trouble Off condition, the audible device provides no sound. The following summarizes the buzzer operation: Alarm condition is indicated by a continuous ON signal, Alarm OFF is indicated by a second ON second OFF signal, Trouble condition is indicated by a 1 second ON and 1 second OFF continuous beeping,

2-1

INTRODUCTION

This chapter describes the PEGAsys system controls and indicators located on the display panel. It also describes the operating procedures and menu system.

2-2.1

Modes of Operation

There are two modes of PEGAsys system operation: In the default operation the panel will be set to latch all alarm inputs on the system. The latching operation will not allow the loop input devices to generate an "alarm off" signal that would possibly interrupt a discharge time delay sequence. To return the panel to normal the "RESET" button will need to be pushed. The second mode of operation is non-latching. This option can be enabled, using the PCS (PEGAsys Configuration Software) to define if a loop device input is to be non-latching. The non-latching operation will allow the loop input devices to generate an "Alarm Off" signal to the panel. When this signal is received the panel would interrupt the discharge time delay sequence of operation. However, all outputs that had been activated previous to the "Alarm Off" signal will remain on and latched until the panel is reset.

Every individual change of status must be individually acknowledged by pressing the ACKLDGE (acknowledge) pushbutton to silence the Audible device.

2-2

CONTROLS AND INDICATORS

The control and indicators of the PEGAsys system are located on the display panel, shown in Figure 2-1. The display panel is mounted on top of the CCM. To gain access to the CCM, the panel door must be open. Table 2-1 lists controls and indicators for the display unit, giving name and functional description.

The advantage of offering a latching or non-latching operation per loop input device, allows the installer/designer to customize the system. This allows the inter mixing of latching and nonlatching devices to protect critical areas where both type may be specified

2-2.1

LCD Display

The display panel contains an 80-character (2X40) alphanumeric display. This LCD display is used to present system status. In the procedure section of this chapter there will be several

System Status

POWER ON GROUND FAULT

ALARM PREALARM

TROUBLE CPU ERROR

SUPERVISORY SILENCE

ACKLDGE SCROLL

SILENCE DRILL

RESET

1 6

2 7

3 8

4 9

5 0

Figure 2-1. System Front Panel


76-100016-001 2-1 August 1999

PEGAsys
simulated LCD display readouts. The LCD display readouts will be used to aid users in the operation of the system. c.

Intelligent Suppression Control/Fire Alarm System Type in three or four digit password into keypad. Ensure a pound sign (#) appears for each key pressed.

2-2.2

Audible Device

NOTE: Use the default password, if a new password has not been set. d. Press the return () key. Verify that the display reads:

The Display Panel also contains an audible device which generates two separate audible tones, one for alarms and one for troubles. This device sounds continuously when a new alarm condition is received until the condition is acknowledged. It also sounds intermittently when a trouble, supervisory, or pre-alarm condition is received until the condition is acknowledged.

1:ISOLATE 3:SET

2:LIST 4:TEST

2-2.3

Control and Indicator Description

2-4

SYSTEM POWER-UP

Refer to Table 2-1 for complete description of controls and indicators.

The following step-by-step procedure is for initial power-up of the CCP. a. Perform the installation check-out procedure in Chapter 7 of this manual. Set the circuit breaker for the CCP power to ON. Verify that the display reads "Main Processor Power On" and that the CPU ERROR indicator is lit. Ensure that the audible device is buzzing continuously. Press the display module reset switch. Verify that the CPU ERROR indicator is extinguished and the audible device is silenced. Verify that the display reads as follows:

2-3

SYSTEM SECURITY

b.

The PEGAsys system provides three distinct levels of program protection, as required by UL Standard 864. The user can only access the system by entering a valid password. Typical valid passwords consist of three or four characters but may be up to eight characters in length.

c.

2-3.1

Levels of Security

d.

The three security levels are: Level One, Level Two, and System Manufacturer. The highest security level is reserved for the system manufacturer. System owner is level one, system installer is level two. Passwords consist of numeric characters (0 - 9) which allows access from the integral keypad of the CCM. Alphanumeric characters can only be used with the PCS program and if used they will lock out any possible entry using the CCM keypad to gain entrance to the menus. If alphanumeric passwords are necessary for a particular application, it is recommended that the Level One password be numeric and the Level Two password be alphanumeric so as to allow the user to retrieve system information (system information lists) and also prevent a user from changing any programmed system parameters.

MAIN PROCESSOR POWER ON


e. After ten seconds, verify that the display reads as follows:

RXTX NON-MONITORING TROUBLE ON RXTX1


NOTE: For multi-loop systems only. The above and below RX/ TX messages will repeat themselves for each RX/TX module installed in the system. The above message will be displayed while the system is initializing itself. This initialization can take up to 90 seconds. To clear the below RX/TX message use the AutoLearn function from the menu function or upload the configuration from the PCS program. If using PCS software, verify that the correct number of RX/TX loops are enabled in the Loops Topic of the configuration file prior to uploading.

2-3.2

Default Passwords

The PEGAsys system provides protection from unauthorized entry to the system menus by utilizing two levels of default passwords, level one and level two. This feature provides two separate passwords which increases the security of the system. Default passwords are set when the system is shipped from Kidde. These default passwords are: Level One = 987 Level Two = 1865 These default passwords are valid until other passwords are programmed into the system.

RX/TX 1 NOT REGISTERED ON RX/TX LOOP 1


f. g. h. Verify that the POWER ON and TROUBLE indicators are lit. Connect the backup batteries to the CCP in accordance to the procedure in Chapter 7. Press the ACKLDGE pushbutton. After approximately one minute the display will momentarily read :

RXTX NON-MONITORING TROUBLE OFF


i. Verify the display reads the incorrect time and date. Set time and date as follows: (1) Press 0 (zero) key. Verify that the display reads: j.

2-3.3
a. b.

Entering Passwords

The password entry procedure is listed below: Verify that the system status is displayed. Press 0 (zero) key. Verify that the display reads:

PLEASE ENTER PASSWORD


(2) Type in the default 1st level password (987). (3) Press the return () key. Verify that the display reads:
2-2 76-100016-001

PLEASE ENTER PASSWORD


August 1999

Intelligent Suppression Control/Fire Alarm System Table 2-1. Control and Indicators

PEGAsys

LED POWER ON

FUNCTION When illuminated, indicates that the system is receiving AC input power. When off, indicates an AC input power failure has occurred (trouble condition) and the system has switched to a battery standby condition. When illuminated, indicates an alarm condition has been reported by an input device. When illuminated, indicates a trouble condition exists in the system. When illuminated, indicates a supervisory condition has been reported by a system-input device programmed for supervisory input. When illuminated, indicates a ground fault has been detected on the 24 VDC line by the power supply monitor. The LCD will display either + / -. When illuminated, indicates a smoke or heat detector has sensed a level of smoke or heat which exceeds the pre-alarm setpoint. When illuminated, indicates CCM software has failed. The system defaults to Zone Alarm / General Signal status. When illuminated, indicates the Signal/Audible outputs have been silenced.

ALARM TROUBLE SUPERVISORY GROUND FAULT PRE-ALARM CPU ERROR SILENCE SWITCH

FUNCTION When pressed after an Alarm ON (Alarm OFF if input device is set for nonlatching) Trouble, supervisory, or pre-alarm ON condition has occured, it silences the panel's audible buzzer. The "ALARM", "TROUBLE", "SUPERVISORY", or "PRE-ALARM" LED indicator glows steady to indicate that the condition has been acknowledged. Subsequent conditions will cause the panel to resound the above sequence. When pressed after acknowledging current Alarm, it silences the system signal outputs which have been programmed as silenceable. The "SILENCE" indicator illuminates to indicate that the signal outputs have been silenced. Pressing the "SILENCE" switch does not effect the Relay Output status. When pressed after all active alarms have been acknowledged and cleared, the system: Resets auxiliary 24 VDC outputs used to power 4 wire detectors Resets all latched alarm conditions. Returns all relays to their normal state. Displays "System Reset" on the visual display. Turns the "ALARM" and "ZONE ALARM" indicators off. When pressed during an active alarm, trouble, or supervisory condition, will cause the LCD to scroll through the active event buffer(s). The Alarm condition will not allow supervisory or troubles to be viewed. Supervisory condition will not allow the troubles buffer to be viewed. When pressed and held for five seconds, the system will activate all signal outputs which have been programmed for drill activation. Use to enter password and system information into the menu system. Use to exit the menu system and to correct wrong entries. Used as the Enter key when using the menu system.
2-3 August 1999

ACKNOWLEDGE

SILENCE

RESET

SCROLL

DRILL NUMERIC KEYPAD (1-0) BACKSPACE RETURN


76-100016-001

PEGAsys
1:ISOLATE 3:SET 2:LIST 4:TEST 2-5.3
a.

Intelligent Suppression Control/Fire Alarm System

Exiting the System Menus

(4) Type in 3111 on the keypad. Verify that the display reads:

To exit the system's menus, perform the following steps: Press the backspace key as many times necessary to reach the top level menu, shown in the top of the next column:

SYSTEM TIME (AM/PM) ENTER THE TIME _ _ : _ _ (HH:MM)


(5) Type in the time (HH=hours 0-12 and then MM=minutes 0-59). Press the return key. Verify that the display reads: b.

1:ISOLATE 3:SET

2:LIST 4:TEST

SYSTEM TIME (AM/PM) 1:AM 2:PM


(6) Type in appropriate selection (1 for AM or 2 for PM). NOTE: If there has been a mistake in the entered data, press the backspace key as many times as required to get to the mistake, then re-enter data from that point. k. The power-up procedure is complete at this point. The system is now ready for loop device registration and programming which is covered in this chapter.

Press the backspace key. Verify that the system returns to standby. The display should read:

SYSTEM STATUS NORMAL HH:MM MM-DD YR 40 CHARACTER CUSTOM MESSAGE


NOTE: When exiting the system menus, if the system is normal the display panel should show the time and date as shown in the above step.

2-5.4

Menu Functions

2-5

SYSTEM MENUS

PEGAsys has a built-in menu structure. This menu structure has been implemented to aid users with system operating functions. The following paragraphs describe the menu structure, accessing the menu, exiting the menu and menu functions. Figure 2-2 shows the system's Level One menu structure. Figure 2-3 shows the system's Level Two menu structure.

Tables 2-2 through 2-5 list and provide a brief description of all functions that you can perform using the PEGAsys systems menus. In addition, the tables provide the security access level and a keystroke formula for each function. The keystroke formula is a sequence of numbers you enter via the systems keypad to access a particular function. These formulas provide the path from the main menu to the desired function. Formulas are provided for each access level. After you enter the formula, some of the functions require you to press the return key to start implementing the function. Most functions will require that you enter additional data to implement the function, such as a device address or desired alarm threshold. 2-5.4.1 ISOLATE MENU FUNCTION

2-5.1

Menu Structure

The PEGAsys menu structure consists of a main menu, and multiple sub-level menus. The sub-level menus may also contain multiple sub-level menus. The main menu displays after you enter a valid password. You can also access the Top Level menu from any sub-level menu at almost anytime by pressing the backspace key located on the keypad. NOTE: The top level menu may not be available by using the backspace key while certain types of programming are being performed. It is possible to access a previous higher level menu from a lower level menu by pressing the backspace key. The choices of available sub menus after a valid password has been entered, correspond to the security level password that has been entered. The main menu for the 1st level, 2nd level, and Manufacturer security level is:

The isolate menu function (Table 2-2) permits the operator to isolate field devices and output modules. Isolating any device immediately places the system in a trouble condition, and initiates an audible trouble alarm and a printout with the time, date, and device isolated. The feature is typically used to temporarily isolate auxiliary devices during a system test. 2-5.4.2 LIST MENU FUNCTION

The list menu function (Table 2-3) permits the operator to list various system parameters. All lists are real time actual system conditions which are displayed and printed with the time and date. 2-5.4.3 SET MENU FUNCTION

1:ISOLATE 3:SET

2:LIST 4:TEST

The set menu function permits the operator to program various system parameters within the system. A few examples are shown in Table 2-4. 2-5.4.4 TEST MENU FUNCTION

Any one of the basic functions listed in a main menu can be selected by pressing the numeric key of the systems keypad which corresponds to the desired function. (Example: To select the LIST function from the main menu, press the 2 key on the system keypad.) You also select lower level functions from sublevel menus using the numeric keys.

2-5.2

Accessing the System Menus

Perform the steps in Paragraph 2-3.3.


August 1999 2-4

The test menu function, shown in Table 2-5, allows the operator to test individual or a group of field devices. On command, a detector or contact input device can be tested, and results will be printed and displayed at the Central Control Panel. The Test procedure in the device is activated by imposing a signal within the device that will cause an alarm output. The Control Panel verifies that an alarm output is generated and reports Test Result OK for each device.
76-100016-001

Intelligent Suppression Control/Fire Alarm System b.

PEGAsys
The 80-character display will cycle between all currently active alarms. Example:

2-6

MODES OF OPERATION

The PEGAsys system has four modes of operation. Each mode has different indications and action required. The following Paragraphs describe each mode, indications and action if required.

2-6.1

Normal Standby Mode

This is the typical mode of the system. In this mode, no alarm, trouble, or supervisory conditions exist in the system. The system display will show the time, day of the week, and date. For example:

SYSTEM STATUS NORMAL 11:06 AM_05-04-90 40_CHARACTER_CUSTOM_MESSAGE


The system provides an option which allows the System Status Normal message to be replaced with a display of battery charging voltage and current for the system standby batteries. For example: NOTE: If the alarm is a zone alarm, the Device Address 1000 - 8000 will be displayed depending on which RX/TX module detects the zone alarm. b. The outputs which have been previously programmed for activation upon alarm by the specific devices will be turned on. (Example: Signal audible signaling devices, control relays for HVAC shutdown or elevator recall.)

PS01_26.0 V_0.10_A_ _ _ _ _11:06 AM_05-04-90 40_CHARACTER_CUSTOM_MESSAGE


The green AC POWER LED will be illuminated to indicate that the systems main power source is normal. NOTE: In the Normal Standby Operation state, it is possible for the 80-character display to show data other than the time, day of date. This occurs when the system menus are being accessed either locally or remotely through one of its serial ports. This condition will be indicated by the menu selections being displayed on the display panel being illuminated. In the Normal Standby Mode, no indicating LEDs will be illuminated other than the AC POWER.

2-6.2.2 ALARM MODE USER ACTION The following steps should be performed when the system is set into alarm. a. Press the display panels ACKLDGE pushbutton to acknowledge the displayed alarm condition. The 80-character display will continue to cycle between any remaining alarms which have not been acknowledged. The ACKNOWLEDGE switch must be operated once for each alarm received at the panel. Once all current alarms have been acknowledged, the alarm indicating circuits (audible devices) can be silenced by operating the SILENCE switch. After all of the current alarms have been acknowledged, verify that the display reads: XXX ALARMS REMAIN. The XXX representing the total of all active alarms. All active alarms can be viewed on the display by pressing the scroll pushbutton.

b.

2-6.2

Active Alarm Mode

The system enters an alarm mode if a device (or devices) has detected an alarm condition, such as smoke / heat above the alarm threshold level. There are two types of alarms which can occur: Device Alarm An alarm in which a device has communicated the alarm status properly to the Central Control Panel, by providing the alarmed device address for indication to the operator. Zone Alarm An alarm condition detected by one or several devices, but which cannot be reported by a specific device due to a malfunction in communications between the system and the alarmed device(s). This is a redundant feature to increase system reliability and is called Failsoft Mode. NOTE: A device can signal a zone alarm to the system during some communication failures. 2-6.2.1 ALARM MODE INDICATIONS The following indicates the system is in its alarm mode of operation. a. The red ALARM LED will be illuminated and there will be a continuous audible signal by the system buzzer at the panel.
2-5

c.

NOTE: The first 64 alarms will only be displayed. Subsequent alarms over the initial 64 will not be displayed, even when any or all of the first 64 alarms clear. However, all alarms regardless of total will be processed in the EOC. For a complete list of active alarms access the event buffer menu using the CCM keypad. d. Any subsequent alarms will cause the alarm audible circuits to resound. Each additional alarm must be acknowledged before the alarm indicating circuits can be silenced. When a device goes out of alarm, the display will indicate the device address and an alarm off (AOF) message (nonlatching mode). Example:

e.

1080 AOF_ _ _ _PHOTOELECTRIC DETECTOR 40_CHARACTER_LOCATION_MESSAGE


NOTE: If the alarm is a zone alarm, the address 1000-8000 will be displayed, indicating that active device(s) in failsoft mode in the zone have gone out of alarm. f. Each device which goes out of alarm must be acknowledged with the ACKLDGE pushbutton (non-latching).

76-100016-001

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

Please Enter Password

1:ISOLATE

2:LIST

3:SET

4:TEST

1:LoopDevices

1:IsolatedDevices/Outputs

1:Time - Date

1:Lamp Test

2:SignalOutputs

2:EventBuffer

2:PrinterControl

2:Loop Device(Alarm Test)

3:RelayOutputs

3:Detector Level

3:Battery Test

4:Release Outputs

4:Active Events

5:City TieOutput

5:Programming

6:Digital I/O

6:Assignments

7:Voltages

Figure 2-2. Level One Menu Structure


August 1999 2-6 76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

Please Enter Password

1:ISOLATE

2:LIST

3:SET

4:TEST

1:Loop Devices

1:Isolated Devices/Outputs

1:Time - Date

1:Lamp Test

2:Signal Outputs

2:EventBuffer

2:Printer

2:Loop Device(Alarm Test)

3:Relay Outputs

3:DetectorLevel

3:Devices

3:Battery Test

4:Release Outputs

4:Active Events

4:Programming

4:WalkTest

5:CityTieOutput

5:Programming

5:Unused

5:Alarm Simulation Test

6:Digital I/O 6:GlobalI/O

6:Assignments

7:Global 6:GlobalI/O

7:Voltages

Figure 2-3. Level Two Menu Structure


76-100016-001 2-7 August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System Table 2-2. Isolate Menu Function
Function Isolate Loop Device Isolate I/O Module Signal Output Description Isolate/De-isolate an RCU by address Isolate/De-isolate a signal module output circuit by address Formula 1-1 1-2-1 1-2-2 1-2-3 1-3-1 1-3-2 1-4-1 1-4-2 1-5 1-6 1-7-1 1-7-2 Access Level 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 2/M 2/M

Isolate I/O Module Release Signal Output Isolate/De-isolate a release module signal output by address. Isolate CCM Signal Output Isolate I/O Module Relay Output Isolate CCM Relay Output Isolate I/O Module Release Output Isolate CCM Agent Release Output Isolate City Tie Output Isolate Digital Input/Output Global Isolate Inputs Global Isolate Outputs Isolate/De-isolate A CCM signal output Isolate/De-isolate a I/O module relay output by address Isolate/De-isolate CCM relay output Isolate/De-isolate an agent release output by output address Isolate/De-isolate an agent release output by CCM output address Isolate/De-isolate city tie module by output address Isolate/De-isolate digital input/output by I/O address Isolate/De-isolate all system input loop devices; I/O modules Isolate/De-isolate all system output I/O modules

NOTE:

1 = LEVEL ONE, 2 = LEVEL TWO, M = MANUFACTURER LEVEL Table 2-3. List Menu Function
Function Description List all Loop Devices which are isolated List all I/O modules which are isolated List all CCM outputs which are isolated Lists all recorded event history entries from buffer Lists a user selectable range of event history entries by date Displays a selected detectors real time smoke / heat level Lists all system detectors pre-alarm and alarm setpoints and present level. List all active system alarm(s). List all active system supervisory conditions. List all active system trouble conditions List EOC program lines List RTC program lines List all loop devices registered into the system List all I/O modules registered into the system Lists PC line voltage levels at each specified loop device Lists specified loop device 9 volt power supply level Formula 2-1-1-1 2-1-2-1 2-1-2-2 2-2-1 2-2-2 2-3-1 2-3-2 2-4-1 2-4-2 2-4-3 2-5-1 2-5-2 2-6-1 2-6-2 2-7-1 2-7-2 Access Level 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M

List Isolated Loop Devices List Isolated I/O Modules List Isolated CCM outputs List Event History Buffer(All Events) List Event History Buffer(Range of Events) List a Single Detector List Detector Level List Active Alarm(s) List Active Supervisory Conditions List Active Trouble Condition List EOC Program List RTC Program List Loop Device Addresses List I/O Module Addresses List PC Line Voltage Levels List Loop Device 9VDC power supply level

NOTE:

1 = LEVEL ONE, 2 = LEVEL TWO, M = MANUFACTURER LEVEL

August 1999

2-8

76-100016-001

Intelligent Suppression Control/Fire Alarm System Table 2-4. Set Menu Function

PEGAsys

Function Set System Time Set System Date Set Display of Battery(V+I) Set Internal Printer Disable Internal Printer Set External Printer Disable External Printer Set Device Address Set Ionization Detector Sensitivity Set Photoelectric Detector Sensitivity Set Thermal Detector Sensitivity Register Devices De-Register Devices Blink Control Set Day/Night Mode Set Day / Night Periods Activate Day Mode Set 1st level Password Set 2nd level Password Enable RTC Program Disable RTC Program Set AutoLearn Mode Set Alarm Verification Set PAS Function Clear Event Log Global Acknowledge Enable Global Acknowledge Disable
NOTES:

Description Allows user to set system time Allows user to set system date Allow user to set display of battery charging voltage and current. Enable port for internal printer connection Disable port for internal printer connection Enable port for external printer connection Disable port for external printer connection Allows user to change device address. Allows user to adjust Ionization detector Prealarm and alarm settings Allows user to adjust Photoelectric detector Prealarm and alarm settings Allows user to adjust Thermal detector Prealarm and alarm settings Allows user to register loop devices into system configuration Allows user to de-register loop devices from system configurations. Allows user to disable detector LED blinking Allows user to enable detector for day function. Allows user to set Day / Night periods Allows user to activate Day mode Allows user to set 1st level password Allows user to set 2nd level password. Allows user to enable RTC program line to function Allows user to disable RTC program line from functioning. Allows user to activate the AutoLearn Function Allows user to set the alarm verification function and time period for individual detectors or range of detectors. Allows user to set the positive alarm sequence for devices Allows user to clear event history buffer entries Enables the Global Acknowledge Feature Disnables the Global Acknowledge Feature

Formula 3-1-1 3-1-2 3-1-3 3-2-1-1 3-2-1-2 3-2-2-1 3-2-2-2 3-3-1 3-3-2-1 3-3-2-2 3-3-2-3 3-3-3 3-3-4 3-3-5 3-4-1-1 3-4-1-2 3-4-1-3 3-4-2-1 3-4-2-2 3-4-3-1 3-4-3-2 3-4-4 3-4-5 3-4-6 3-4-7 3-8-1 3-8-2

Access Level 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 1/2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M 2/M

1. For installation in the state of California, Alarm Verification Time must not exceed 30 seconds. 2. 1 = LEVEL ONE, 2 = LEVEL TWO, M = MANUFACTURER LEVEL

76-100016-001

2-9

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System Table 2-5. Test Menu Functions

Function Lamp Test Loop Device Test Battery Test Enable Walk Test Disable Walk Test Alarm Simulation Test
NOTE:

Description Enable user to test system LEDs functionality Allows user to activate an electronic test of a detector or group of detectors Allows user to activate a battery test to verify battery capacity Allows user to specify a range of devices to Walk Test Allows user to disable walk test mode Allows installer to verify programmed relation ship of inputs to outputs by activating inputs and verifying outputs are active.

Formula 4-1 4-2-1 4-3 4-4-1 4-4-2 4-5

Access L evel 1/2/M 1/2/M 1/2/M 2/M

2/M

1. WARNING: The Alarm Simulation Test must be used with care. When activated the Alarm Simulation Test (AST) processes pre-programmed outputs which are related to the activated (simulated) input device. Before using AST ensure that any associated outputs are disconnected or isolated to prevent unexpected outputs (releases, signals or shutdowns). 2. 1 = LEVEL ONE, 2 = LEVEL TWO, M = MANUFACTURER LEVEL

For latching mode: To return the system to normal, press the RESET button once. If powering 4-wire detector from the PEGAsys, the reset button will need to be pushed once to reset the detector and once to reset the panel to a normal condition. g. In a non-latching operation once all alarms have cleared, the display will read: NO ACTIVE ALARM REMAINS. At this time, the system may be reset by operating the RESET pushbutton. When the system is properly reset, the display will show the System Status Normal message, time, day and date. The preceding will happen if no active troubles or supervisories are present, in which case the Active Troubles or Active Supervisories message will be displayed.

h.

2-6.3.2 SUPERVISORY TROUBLE MODE USER ACTION The following steps should be performed when the system is set into supervisory trouble mode of operation: a. To silence the supervisory trouble audible signal, all current supervisories must be acknowledged by pressing the ACKLDGE push button. This will silence the system buzzer. When all supervisory trouble conditions have been acknowledged, the 80 character display will read: XXX ACTIVE SUPERVISORY TROUBLES REMAIN. XXX representing the total number of active supervisory troubles. All current trouble conditions can be viewed on the display by pressing the scroll push button. As each supervisory trouble condition is cleared, the display will read one less active trouble until all supervisories are clear. When all active supervisory troubles have been cleared, the SUPERVISORY and TROUBLE LEDs will be extinguished and the 80 character display will show the Standby Message. (For example: "System Status Normal") The system has the option to acknowledge both supervisory and common troubles on a global basis. The panel by default will require that each trouble be acknowledged individually. However, if the installer wishes to enable this function it can be done by accessing the "set" menu option using the CCM keypad. Refer to Table 2-4 for more information on stepping through the menus to enable and disable
76-100016-001

2-6.3

Active Supervisory Trouble Mode

The system enters supervisory trouble mode when it detects an abnormal condition on the system that has been defined to be a much higher priority than a common trouble. This type of trouble is usually assigned by the installer/designer to monitor critical parts of the system. 2-6.3.1 SUPERVISORY TROUBLE MODE INDICATION The following indicates the system is in the supervisory trouble mode of operation. a. The yellow SUPERVISORY and TROUBLE LEDs will be flashing at a 1 second rate and there will be a pulsing buzzer at the CCM. This audible is distinctively different than an alarm signal pattern at the CCM. The 80 character display will cycle between all currently active supervisory troubles. Example:

b.

c.

b.

NOTE:

August 1999

2-10

Intelligent Suppression Control/Fire Alarm System the Global Acknowledge function. With global acknowledge a total of 30 troubles can be acknowledged at one time. c.

PEGAsys
As each trouble condition is cleared, the display will read one less active trouble until all troubles are cleared. When all active troubles have been cleared, the TROUBLE LED will be extinguished and the 80-character display will show the standby message (For example: "System Status Normal").

2-6.4

Active Trouble Mode

The system enters trouble mode when it detects an abnormal condition which may prevent proper operation or display a prealarm condition. (Example: loss of communications with a smoke detector.) Refer to Appendix G for a complete list of trouble conditions. 2-6.4.1 TROUBLE MODE INDICATIONS The following indicates the system is in its trouble mode of operation. a. The yellow TROUBLE LED will be flashing at a 1 second rate and there will be a pulsing panel buzzer at the CCP. This audible signal is distinctively different than the alarm audible signal. The 80 character display will cycle between all currently active troubles and prealarms. Example:

NOTE: The system has the option to acknowledge both supervisory and common troubles on a global basis. The panel by default will require that each trouble be acknowledged individually. However, if the installer wishes to enable this function it can be done by accessing the "set" menu option using the CCM keypad. Refer to Table 2-4 for more information on stepping through the menus to enable and disable the Global Acknowledge function. With global acknowledge a total of 30 troubles can be acknowledged at one time.

2-7

PRINTING OPERATION

b.

In addition to the LCD display, the PEGAsys system information can be viewed using the Printer port of the CCM. For detailed information pertaining to connecting a RS-232 peripheral device, see the Chapter 7, Paragraph 7-18. When the printer port is enabled and a serial printer is attached the system will print out all status change information and any system information lists that the user would request from the system using the integral keypad. Serial-type annunciator devices may be connected to the printer port to provide graphical LED annunciator type indications to building occupants. Contact Kidde application engineering for compatible annunciator vendors.

2-6.4.2 TROUBLE MODE USER ACTION The following steps should be performed when the system is set into the trouble mode of operation: a. To silence the trouble audible signal, all current trouble conditions must be acknowledged by pressing the ACKLDGE pushbutton. This will silence the system buzzer. When all trouble conditions have been acknowledged, the 80-character display will read: XXX ACTIVE TROUBLES REMAIN. XXX representing the total number of active troubles. All current trouble conditions can be viewed on the display by pressing the scroll pushbutton.

2-8

SYSTEM PROGRAMMING

b.

The PEGAsys fire alarm system incorporates two unique programming languages that are easy to understand and use. These two versatile programming languages, Event Output Control (EOC) and Real Time Control (RTC), can accommodate most any fire alarm control logic application. Programming the system is accomplished by a personal computer via a system interface cable. The two programs are constructed by the system Engineer/Installer using the PEGAsys Configuration Software (PCS) program which is Windows based. The PCS program allows the user to configure, verify, upload, download, edit, retrieve, store and print the entire system configuration program. Refer to the PCS users guide (P/N 76-014) for further details.

NOTE: The first 300 troubles (supervisory or common) on a Single-Loop will be displayed only. Subsequent troubles or supervisories will not be displayed even if any or all 300 troubles clear. However, all of the active troubles or supervisories will be processed and entered into the event buffer. For a complete listing of all troubles and supervisories over the initial 300, access the event buffer using the event buffer using the CCM keypad. For the Multi-Loop the first 2100 troubles or supervisories will be displayed. Subsequent troubles or supervisories over the first 2100 will not be displayed even if any or all 2100 troubles or supervisories clear. However, all troubles or supervisories regardless of the total will be processed and entered into the event buffer. For a complete listing of all active troubles and supervisories, access the event buffer through the CCM keypad.
2-11

2-8.1

EOC Programming

The Event Output Control (EOC) program logically combines the systems input devices with the system's output devices. The program consists of sequentially numbered lines of equations containing input addresses, output addresses and logic operators. When an input becomes true (Active), the system processes the EOC program and activates any associated outputs as programmed.

76-100016-001

August 1999

PEGAsys
EXAMPLE: The simplest event output control (EOC) equation would be: Input = Output A basic equation with one or more inputs would be : Input Operator Input = Output The system normally processes the EOC from left to right. However, in equations with parenthesis the contents of the parenthesis are executed first. Refer to the PCS users guide (76-014) for further details. 2-8.1.1 LISTING EOC PROGRAMMING c.

Intelligent Suppression Control/Fire Alarm System Each line number of the RTC Program is automatically enabled when entered into the system. Once a line number in the RTC Program has been disabled using the procedure below, the line will be ignored by the RTC Program until enabled. To enable a line number which has been previously disabled follow the below procedure selecting "ENABLE" in step b. a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

PLEASE ENTER PASSWORD


b. (2) Type in the Level 1 or Level 2 password. Select the set RTC program by typing the function formula, 3-43. Verify the display reads:

The system's Event Output Control (EOC) program can be listed out using either the owner's or installer's menu functions. To list the systems EOC programming: a. Access PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

1:ENABLE 2:DISABLE
Select the desired choice and press return. Verify the display reads:

RTC LINE NUMBER _ _ _


d. e. Type the three digit line number and press the return key. You may continue with another RTC line or press backspace key to cancel this function.

PLEASE ENTER PASSWORD


(2) Type in the Level 1 or Level 2 password. (3) Press the return () key. Verify that the display reads:

1:ISOLATE 3:SET
b.

2:LIST 4:TEST

2-8.3

Types of Inputs and Outputs

Select the list EOC program by typing the function formula, 2-51.

The PEGAsys has various input and output devices/modules which are discussed in the following paragraphs: 2-8.3.1 SYSTEM INPUTS

The system will then list all lines of the Event Output Control programming on the LCD and any attached printer.

2-8.2

RTC Programming

The RTC program language permits outputs to be controlled by the systems real time clock. Outputs may be programmed to occur on an hour, day, week and month time control basis. Alarm and Prealarm threshold levels of all or individual detectors can be increased or decreased in sensitivity (within UL limits) under RTC control. The RTC programming also provides the ability to control RCU relays, I/O module Relays and smoke detector pre alarm and alarm set points. The program consists of sequentially numbered lines each containing control object, control content, time, date and day of week. For further details refer to the PCS users guide. 2-8.2.1 LISTING RTC PROGRAMMING

Devices which are classified as system inputs are smoke detectors, heat detectors, and addressable contact monitors (alarm, trouble, abort, waterflow, manual alarm, manual release, supervisory, and normal). Refer to the PCS users (76-014) guide for further details. 2-8.3.2 REMOTE CONTROL UNIT (RCU)

The RCU input and output devices, which are connected to the RX/ TX loop(s), are specified in EOC programming by the devices four digit address. 2-8.3.3 RX/TX LOOPS

The RTC program can be listed out using either the owners or installers menu functions. To list the RTC programming: a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

The system specifies the RX/TX loop controller using its loop number followed by three zeros (1000 for RX/TX 1) in single loop systems and (1000 - 8000) in multi-loop systems. The specifier (1000 -8000) will appear in cases when trouble conditions are present on a particular RX/TX loop controller (i.e., a PC Line Short on RX/TX 1 would be displayed as "RX/TX PC Line Short Loop 1"). RX/TX loop (zone) alarms occur if a loop device alarm initiates under one of the following conditions: Failed communications between the CCM and RX/TX module (Trouble Condition) Failed RX/TX processor. (Trouble Condition) Failed input circuit of RCU device.

PLEASE ENTER PASSWORD


(2) Type in the Level 1 or Level 2 password. (3) Press the return () key. Verify that the display reads:

1:ISOLATE 3:SET
b.

2:LIST 4:TEST

Select the list RTC program by typing the function formula, 2-52.

An alarmed input device on the RX/TX (in FailSoft mode) can only activate EOC programming if the RX/TX zone is used as a programmed input (ZA1=1000, ZA2=2000, ZA8 = 8000, etc.). 2-8.3.4 SYSTEM OUTPUTS

The system will then list all lines of the Real Time Control programming on the LCD and any attached printer. 2-8.2.2 ENABLE/DISABLE RTC PROGRAM LINE NUMBERS
2-12

Devices which are classified as system outputs are CCM - signals and relays (programmable / non programmable); I/O modules - signal outputs, relay outputs, agent release outputs, release
76-100016-001

August 1999

Intelligent Suppression Control/Fire Alarm System signal outputs, city tie outputs and digital I/O module outputs; Loop devices - addressable relay output module. 2-8.3.5 SYSTEM I/O MODULES The Input/Output modules which the systems support are Signal Outputs, Relay Outputs, Agent Release (agent & signal) outputs and the City Tie output.

PEGAsys
there were eight in the system, and the same holds true for the remaining modules with the only exception being the City Tie module there can only be one of these modules in a system at any time.

2-8.5

Registering I/O Module Assignments

2-8.4

Addressing I/O Modules

The I/O modules include: Signal Audible, Relay Output, Agent Release Output, City Tie output and the power supply module. I/O modules refer to any I/O module which installs into the optional I/O mother board with exception of the power supply module(s). The I/O modules communicate with the CCM over the I/O bus. Each module has inputs or outputs which can be individually addressed. The I/O address consists of two alphabetic and two numeric characters which define the module type, address and I/O circuit number. The I/O module address scheme is shown below.

I/O modules are registered into the system configuration through the use of the PCS program. The installer would configure all modules in the PCS program file and then upload this file to the system which would then internally verify the existence of the specified modules. For further details on I/O module registration refer to the PCS users guide. Added RX/TX Modules in the multi-loop systems are automatically registered by the CCM upon system power-up. 2-8.5.1 LISTING I/O MODULE ASSIGNMENT All I/O modules which are programmed into the system configuration may be listed out with the use of either the owners or installers menu functions. a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

SG 1 : 3

I/O Circuit Number (1-4), See note 1. Module Address (1-8), See note 2. Module Type, See note 3.

PLEASE ENTER PASSWORD


(2) Type in the Level 1 or Level 2 password. (3) Press the return () key. Verify that the display reads:

1:ISOLATE 3:SET
b.

2:LIST 4:TEST

NOTES:

SG - Signal / Audible Output RY - Relay Output CT - City Tie Output AR - Agent Release Output RS - Release Signal Output PS - Power Supply Monitor Module

Select the list I/O address assignments by typing the function formula, 2-6-2.

The system will then list all of the registered I/O module addresses on the LCD and any attached printer.

2-8.6

Addressing RCUs

1. The I/O modules vary in amount of inputs and outputs. Refer to section one component description for thorough descriptions of options. 2. The PEGAsys system can support a total of 16 I/O modules for single loop and 23 I/O modules for multi-loop, 8 maximum of any one type. 3. Power supply monitors only need an address, they have no need for an output number. The I/O module address is set using the three dip switches contained on each PCB assembly, each module uses different numbered switches for module address assignment. The address is set during the installation procedure by placing the switches into the correct position. Refer to the appropriate figure in Appendix I for the particular module you are working with and the addressing matrix. For a functional description of each module, refer to Chapter 3. The switches would be set for each type of module in order. For example signal modules would be addressed 1 -8 if there were eight in the system, relay modules would be addressed 1 - 8 if

RCUs refer to all devices which connect and operate from the RX/TX PC (power/communications) Line. These devices include SmartOne smoke detectors, SmartOne heat detectors, addressable contact input monitors, and addressable output contact modules. Each device has a three digit numeric address. This address is stored in the non-volatile EEPROM memory of the device. The system address is defined by the CCM by these three digits and a fourth digit representing the RX/TX channel number. There are three ways to address the RCU (Loop) devices. The RCUs can be addressed using the Hand Held Programmer (P/N 74-200013-001). This optional unit provides a convenient means of addressing RCUs without using the CCM. The user may address the devices individually on the system by performing the procedure listed below.

To address RCUs using the SET RCU Address menu function each unaddressed RCUs must be connected to the RX/TX PC line one at a time. Perform the following steps for each RCU: a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

PLEASE ENTER PASSWORD


(2) Type in the Level 2 password. (3) Press the return () key. Verify that the display reads:
2-13 August 1999

76-100016-001

PEGAsys
1:ISOLATE 3:SET
b.

Intelligent Suppression Control/Fire Alarm System

2:LIST 4:TEST

Select the set RCU address function by typing the function formula, 3-3-1. Verify that the display reads:

PRESENT LOOP DEVICE ADDRESS _ _ _ _


NOTE: All new addressable devices have an address of zero (000). c. Enter the present RCU address and press return pushbutton. The system will display the following:

tion would be to attach all pre addressed loop devices to the PC line of the RX/TX module. Power up the system (if it is not already running). As the loop devices power up they will begin to communicate with the RX/TX module. The CCM will recognize the loop devices as not being not registered and raise a trouble for each not registered (TBL NR) device attached. When the register RCU function is enabled the CCM will prompt the user to enter a range of loop device addresses to register as valid system devices. At the conclusion of the register function the CCM will display the total amount of devices registered. The AutoLearn function works much the same as the registration function, where it will automatically enter the devices which it can identify on the PC line of the RX/TX as not being registered into system configuration memory. During both the Autolearn and RCU Registration procedures the CCM will automatically register the loop devices into memory and also set each device to default settings (Sensitivity levels and Input reporting) for the particular device. The CCM will also set the default operation of the CCM outputs (MP01, MP02, MP03 and MP04). Any system alarm received after this time will cause all the CCM outputs (MP01 - MP04) to activate. Optionally, if the I/O motherboard and I/O modules have been installed, the PCS program will need to be used to configure the system for use with the I/O modules. Procedures for registering I/ O modules are provided in the PCS Users Guide (See Addressing I/O Modules). 2-8.7.1 DETECTOR REGISTRATION SmartOne smoke and heat detectors would be registered on to the system in the same fashion as the RCUs explained in the previous section. The only other information which requires selecting is detection devices application, the alarm and pre-alarm, levels and latching or non-latching. There are three specific applications for smoke detector use: Open Area, Open Area (High Air Flow) and Duct. The smoke and heat detectors pre-alarm and alarm set points are adjusted only when necessary if the user desires the set points to be different from the default values for each detector type. The detectors will use the default values unless otherwise programmed. To adjust the set points for the detectors, refer to Chapter 5 Setting and Adjusting Smoke and Heat Detector Sensitivities. The 40 character owner location message cannot be entered using the system keypad. The owners location message can only be entered by use of the PCS program and uploaded into system memory. 2-8.7.2 ADDRESSABLE CONTACT MONITOR REGISTRATION The addressable contact monitor are registered on to the system in the same fashion as the RCUs explained in the previous section. The system will by default, set the response of the device activation to alarm. During system configuration using the PCS program the following choices are allowed - Alarm, Trouble, Abort, Supervisory, Manual Alarm, Manual Release, WaterFlow or Normal. The following table describes the allowable selections for the input RCU and their EOC relationships. Contact monitor RCUs are also registered into the system by using the PCS program. The installer would specify each Contact Monitor RCU to be connected to the system and then upload the system configuration file to the system and then the system would supervise each device specified. Refer to the PCS users guide
2-14 76-100016-001

TARGET LOOP DEVICE ADDRESS _ _ _ _


d. Enter the desired address for the RCU / Detector, press return. The system will now change the RCU address if different than previously noted.

The 40 character owner location message cannot be entered using the system keypad. The owners location message can only be entered by use of the PCS program and uploaded into system memory.

2-8.7

Registering RCUs

Registration is where the device address is joined with the device information in the system's memory. Device information is comprised of; Device type, Device Messages and Device settings. There are four ways to register the RCU (Loop) devices on to the system. The user may register the devices individually on the system Register all pre-addressed RCUs at once using RCU (Loop Devices) registration function Register all pre-addressed RCUs using the Autolearn function, which sets all devices at default values and any system alarm input activates all system outputs. If pre-addressed devices are used, multiple devices can be attached and registered to the system all at one time using either the Autolearn or RCU Registration function. RCUs can also be registered into the system by using the PCS program. The installer would specify each RCU to be connected to the system and then upload the system configuration file to the system and then the system would supervise each device specified. Refer to the PCS users guide for further details on RCU registration.

1004

001-255 = Device Address (registered) 000 = Device Address (un addressed/ un registered) RXTX Loop Number 1 for single Loop Systems, 1-8 for Multi-Loop Systems

Example: RCU 1032 represents device 32 on RX/TX loop 1. Connecting an unregistered RCU address (address 000) to the RX/TX will result in a not registered trouble (TBL NR) indicating that the control panel has communicated with the device and identified the device as being unregistered. Procedures for registering RCU devices using the register RCU func-

August 1999

Intelligent Suppression Control/Fire Alarm System for further details on RCU registration. 1: Alarm Active input initiates an alarm at the central control panel and is latched in the EOC until the system is reset after alarm has cleared. 2: Trouble Active input initiates a trouble at the central control panel, but does not latch EOC programming and will self restore upon deactivation. 3: Abort Active input initiates an abort condition at the central control panel. This will delay agent release if countdown has begun. It does not latch EOC program and will self restore upon deactivation. There are 4 styles of abort available for the device. 4: Waterflow Active input initiates a waterflow alarm condition at the central control panel and is latched in EOC program until reset. Signal outputs will be inhibited from being silenced. 5: Manual Alarm Active input initiates a manual alarm condition at the central control panel, latches in EOC program until reset. 6: Manual Release Active input initiates a manual release condition at the central control panel, causes instant release of programmed output, latches in EOC program until reset 7: Normal Active input initiates a momentary display but does not latch in EOC program, self restores. 8: Supervisory Active input initiates a supervisory trouble at the central control panel, but does not latch the EOC, and will self-restore upon deactivation. The 40 character owner location message cannot be entered using the system keypad. The owners location message can only be entered by use of the PCS program and uploaded into system memory. 2-8.7.3 REMOTE RELAY REGISTRATION The addressable contact output device is registered in the same fashion as the previous RCU's. Contact Output RCUs can also be registered into the system by using the PCS program. The installer would specify each Contact Output RCU to be connected to the system and then upload the system configuration file to the system and then the system would supervise each device specified. Refer to the PCS users guide (76-014) for further details on RCU registration. The 40-character owner location message cannot be entered using the system keypad. The owners location message can only be entered by use of the PCS program and uploaded into system memory. 2-8.7.4 LISTING ALL REGISTERED RCUs All RCUs registered on the system can be listed using either the owners or installers menu function. To list all registered RCUs
76-100016-001 2-15

PEGAsys
a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

PLEASE ENTER PASSWORD


(2) Type in the Level 1 or Level 2 password. (3) Press the return () key. Verify that the display reads:

1:ISOLATE 3:SET
b.

2:LIST 4:TEST

Select the List RCU address function by typing the function formula, 2-6-1. Verify that the display and any attached printers list all registered RCU addresses.

2-8.7.5 UN-REGISTERING RCUs The system provides the capability to remove a single device or group of devices from the system configuration. This function removes the device address from the system memory but leaves the address in the device intact. Performing this operation will cause the system to generate a trouble NR (Not Registered) for any devices which remain connected to the RX/TX PC line. Removal or disconnection of the device(s) from the PC line will clear the trouble condition(s) on the system. This function would be used during a system retrofit where some devices may be desired to be removed from the system temporarily during a building renovation and then reattached after renovations are complete. This feature is very efficient because the device maintains its address information which speeds device reregistering after the renovations. To perform the device un-registering operation perform the following: a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

PLEASE ENTER PASSWORD


(2) Type in the Level 1 or Level 2 password. (3) Press the return () key. Verify that the display reads:

1:ISOLATE 3:SET
b.

2:LIST 4:TEST

Select the set RCU De-Registration function by typing the function formula, 3-3-4. Verify that the display reads:

DEVICE DE-REGISTRATION DEVICE FROM_ _ _ _TO_ _ _ _


c. Enter the desired RCU address(s) and press return. The display will read the following in response to verify the device de-registration:

DEVICE DE-REGISTRATION XX DEVICES DE-REGISTERED


d. Verify that the display changes to the device menu after 5 seconds. The backspace key can be pressed to return to the main menu. To reregister RCU devices, perform the procedure which is outlined in the RCU registration paragraph in this chapter.

e.

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

2-16

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

CHAPTER 3 FUNCTIONAL DESCRIPTION


Central Control Module Display Module RX/TX Module I/O Module RCUs (Field Devices) Power Supply Module

3-1

INTRODUCTION

This chapter provides a functional description of the devices/ modules used in the PEGAsys system configuration. Each functional description covers one of the blocks shown in the overall block diagram, Figure3-1.

3-2

BLOCK DIAGRAM

The PEGAsys system is divided into seven functional blocks as follows:

As described in Paragraph 1-1.2, the system comes in two configurations the single-loop system and multi-loop system. The above devices/modules for both configurations are shown in the Overall Functional Block Diagrams, Figures 3-1 and 3-2. Each device/module is described in detail in Paragraph 3-3.

Display Module

Central Control Module


24 VDC I/O Bus

RX/TX CCM Comm

AC Line Battery Backup

Receiver/ Transmitter Module (RX/TX)

Power/Comm Line

RCU's (Field Devices)

Power Supply

24 VDC I/O Bus 24 VDC

Optional I/O Motherboard

I/O Bus 24 VDC

Optional I/O Module

Figure 3-1. Overall Block Diagram, Single-Loop System

Display Module

Central Control Module


24 VDC I/O Bus

AC Line Battery Backup

Power Supply

I/O Bus 24 VDC

RX/TX CCM Comm

RX/TX CCM Comm 24 VDC I/O Bus 24 VDC

Receiver/ Transmitter Module (RX/TX) Up to 8 RX/TX Modules Optional I/O Module

Power/Comm Line

RCU's (Field Devices)

RX/TX 24 VDC

Multi-Loop I/O Motherboard

Figure 3-2. Overall Block Diagram, Multi-Loop System


76-100016-001 3-1 August 1999

PEGAsys
3-3 FUNCTIONAL DESCRIPTIONS

Intelligent Suppression Control/Fire Alarm System Internal diagnostics enhance the troubleshooting ability of the system, examples: microprocessor failure, memory failure, RS232 port troubles, etc.. Two individually programmable signal output circuits (MP1 & MP2) provided can be used for signaling devices (horns, strobes, bells) and allow up to 2.0 amps of 24 VDC power. One of the two outputs is programmed for releasing solenoid type suppression equipment (Agent and Sprinkler type systems). Two individually programmable relay outputs (MP3 & MP4) are provided on the CCM for controlling building functions during alarm occurrences. These relay outputs are activated through the EOC programming which allows system inputs to be related to system outputs. Each of these relays have Form C style, rated at 1A, 30VDC. One non programmable trouble relay is supplied which is normally powered (24 VDC) and will transfer on any system trouble, supervisory, pre-alarm and complete power off condition. Form C contact rating 1A at 30VDC. Refer to DWG. No. 06-235443001 in Appendix I for further installation details. An event history buffer is provided on the CCM which will store 1024 entries for single-loop and 6100 entries for multi-loop of system event information and allow the operator to retrieve this information for review of system operation. The PCS program provides the ability to download, store and print all or a portions of the Event History Buffer.

The functional descriptions will describe each device or module depicted in Figures 3-1 and 3-2.

3-3.1

Central Control Module

The Central Control Module (CCM) is available in two versions, P/N 76-100008-501 for single-loop and P/N 76-100008-600 for multi-loop. Figure 3-3 contains the main central processing unit, real time clock, watch dog timer and RS-232 serial communication input/output ports. The CCM controls the operation and supervision of all the system modules and software within the PEGAsys system. It receives loop device data from the RX/TX module, processes the data based on pre-programmed instructions and transmits output commands to the output modules, field devices and display module(s). The CCM provides two RS-232C serial ports for programming and monitoring the PEGAsys system. These ports accept 6wire RJ-12 modular connectors. The PCS program would be used to interface to the system for programming purposes. A multilevel password scheme protects the system from unauthorized access. The real time clock provides the CCM with the ability to display the current time & date on the system LCD and control the system with time based programming.

See Note 1
SOUNDER 1 A B + + SOUNDER 2 A B + + VOLT FREE RELAYS 1 2 NO NC C NO NC C V/F RELAY FAULT NO NC C

TB4

TB5

TB1

TB2

TB3

Note 1: The trouble relay contacts are shown in the unpowered state. Note 2: Jumpers JP1-JP4 are used to configure MP01 to be signaling or releasing (default) outputs. Refer to Dwg. No. 06-235443-001, in Appendix I, for further details.

REP 1

REP 2

CCM Reset Button

See Note 2
JP4 JP3

JP1 SW1

JP2 JK5
I/O PORT

BT1
RX/TX PORT

To I/O Modules and Power Supplies To RX/TX Loop Controller

JK1

JK2

JK3
1

PLG2 TB6
24V 5V 0V
EARTH FLT SUPPLY FLT

JK4

DISP PORT

PRINT PORT

P.C. PORT

PLG1

DISPLAY

To External Printer
Proc. Port
PLG2 PLG6

To Remote PC For Programing

24V

0V

5V 0V

24VDC From Power Supply

Display Reset
SW1 PLG3

JK3 PLG1

PLG2

JK1

JK2

Figure 3-3. Central Control Module, Details


August 1999 3-2 76-100016-001

TB6

Display Port

24VDC From Power Supply

Intelligent Suppression Control/Fire Alarm System

PEGAsys
The RX/TX receives control requests from the CCM and establishes communications with the loop devices. The RX/TX receives status changes from the loop devices and reports these changes to the CCM. The RX/TX shown in Figure 3-4 is capable of communicating with up to 255 intelligent devices and complies with the Signaling Line Circuit (SLC) requirements of NFPA-72 Style 4, 6 & 7. Style 4 initiation circuit wiring will permit T tapping or branch circuitry. Style 7 requires the use of optional loop isolator devices.

3-3.2

Receiver/Transmitter Module (RX/TX)

The RX/TX functions as the hardware & software interface between the loop devices and the CCM. Each installed RX/TX module continually monitors all addressable devices for alarm and trouble conditions. Each device is capable of initiating and sending alarm and trouble messages to the RX/TX module to which it is connected.

STYLE 6 Signal Line Circuit, with Loop Isolator

Loop Isolator

Zone 2

Loop Isolator

Zone 1

Zone 3

See Note

Loop Isolator

Loop Isolator

CPU Reset
PC Line Normal

LOOP ISOLATOR Mounted to RX/TX 74-200012-001

CPU Reset
PC Line Reset

Loop Isolator for Style 7 (74-200012-001)

RX/TX
Note: Each zone can consist of 30 loop devices between loop isolators
STYLE 7 Signal Line Circuit

Loop Isolator
See Note

Loop Isolator

Zone 2

Note: Refer to jumper table on Dwg. 06-235371-002 in appendix I

STYLE 6 Signal Line Circuit

1 2 3 4
STYLE 4 Signal Line Circuit

Zone 1

See Note

Loop Isolator

LOOP ISOLATOR Mounted to RX/TX 74-200012-001

RX/TX
NOTE: Adjacent loop isolators must be within 20ft. Of a device with wiring in conduit to be in accordance with NFPA Style 7 requirements.

Figure 3-4. Receiver/Transmitter Module, Details


76-100016-001 3-3 August 1999

1 2 3 4

1 2 3

1 2 3 4

RX/TX 76-100005-001

24V RET 24V RET

Loop Isolator Loop Isolator

Zone 3

Loop Isolator

24V RET 24V RET

PEGAsys
3-3.3 Power Supply/Charger Assembly, Rev. A

Intelligent Suppression Control/Fire Alarm System The power supply/charger assembly is addressable and communicates with the CCM over the I/O bus. The power supply/charger assembly provides terminal connections for an auxiliary power module. This module comes with 2 different wiring harnesses, as follows: P/N 76-100009-002 is supplied with a 36" harness that is meant to connect a main power supply/charger assembly to the auxiliary power module in the main cabinet. P/N 76-100009-003 is supplied with an 8" harness to mount a main power supply/charger assembly to an auxiliary power module in a expansion enclosure.

This power supply assembly was provided with earlier systems. Information is being provided for service purposes only. The power supply/charger assembly, Figure 3-5 (P/N 76-100009001) is comprised of a printed circuit board (PCB) mounted on a AC / DC switching power module. The switching power provides 4 amps of 24 VDC power from the 120 / 240 VAC input power. The PCB assembly is a microprocessor based unit which provides the system with Battery charging (up to 33 AH) and supervision Low Voltage Battery cutoff at 19VDC AC power supervision 24 VDC supervision Battery load test 24 VDC ground fault detection (+/-) Trouble relay that transfers upon any power supply trouble or power off condition (Relay shown in the unpowered state) Auxiliary 24 VDC outputs (programmable for switched or unswitched configurations)

The auxiliary 24 VDC outputs rated at 1 Amp each and can be used to power 4 wire type detection devices such as smoke, flame and gas detectors which must be sized properly to stay within output current limits.

The addition of an auxiliary power module to the main power supply/charger assembly will provide an additional 4 amps of current and make the total available current of 8 amps for this assembly. The system can support up to 8 main power supply/ charger assemblies with the capability of adding an auxiliary power module to each one to provide a maximum available current of 64 amps. Each additional power supply/charger assembly (P/N 76-100009-001) would need to have a separate address to operate in the system. The auxiliary power module would share the same address as the main power supply/charger assembly that it is connected to. Refer to drawing number 06235443-003, in Appendix I, for further installation details.

Figure 3-5. Obsolete Power Supply/Charger Assembly (Revision A), Details


August 1999 3-4 76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
P/N 76-100009-003 is supplied with an 8" harness to mount a main power supply/charger assembly to an auxiliary power module in a expansion enclosure.

3-3.4

Power Supply/Charger Assembly, Rev. C.

Battery charging (up to 99 AH) and supervision Low Voltage Battery cutoff at 19VDC AC power supervision 24 VDC supervision Battery load test 2 auxiliary 24 VDC outputs, programmable for switched or unswitched configuration Trouble relay that transfers upon any power supply trouble or power off condition (Relay shown in the unpowered state)

The power supply/charger assembly (P/N 76-100009-010) provides terminal connections for an auxiliary power module. This module is available with two different wiring harnesses, which follow: P/N 76-100009-002 is supplied with a 36" harness that is meant to connect a main power supply/charger assembly to the auxiliary power module in the main cabinet.

The addition of an auxiliary power module to the main power supply/charger assembly will provide an additional 4 amps of current and make the total available current of 8 amps for this assembly. The system can support up to 8 main power supply/ charger assemblies with the capability of adding an auxiliary power module to each one to provide a maximum available current of 64 amps. Each additional power supply/charger assembly (P/N 76-100009-010) would need to have a separate address to operate in the system. The auxiliary power module would share the same address as the main power supply/charger assembly that it is connected to. Refer to drawing number 06235443-003, in Appendix I, for further installation details. NOTE: The Rev. C. Power Supply/Charger assembly can be distinguished from the Rev. A. version by the large heat sink on the right side of the unit.

CAUTION: THE VOLTAGE FOR THE TWO BATTERIES IN SERIES MUST BE GREATER THAN 22 VDC BEFORE CONNECTION TO THE PANEL.

TWO (2) SEALED LEAD-ACID BATTERIES

POWER LIMITED TO 1.5 A DC

POWER LIMITED TO 1.5 A DC

Figure 3-6. Power Supply/Charger Assembly (Revision C), Details


76-100016-001 3-5 August 1999

PEGAsys
3-3.5 Multi-Loop I/O Motherboard

Intelligent Suppression Control/Fire Alarm System connection located on the motherboard and the loop number and addresses assigned to the connected module. Refer to Drawing. No. 06-235443-012, in Appendix I, for installation details. Table 3-1. Multi-Loop I/O Motherboard Connectors

The multi-loop I/O motherboard assembly, P/N 76-100017-001, is an assembly which can accept any combination of 9 modules consisting of up to 8 RX/TX modules and provide connections for up to 7 I/O module circuit board assemblies. The ML motherboard is mounted to standoffs on the back of the main system enclosure. It distributes the system 24 VDC power, CCMRX/TX communications modules and I/O bus communications to the I/O modules. The I/O bus communications are provided by a RJ-12 (flat phone cable) style connection. A single RJ-12 connection connects the ML motherboard to the CCM for RX/ TX communications. The 24 VDC is provided by the system power supply via a 2 conductor wiring harness connected to a terminal block (TB9) is distributed through terminal blocks (TB1TB8) for connection on RX/TXs. The 24 VDC provided by the system power supply via 2 conductor wiring connected to terminal block TB-11 is distributed through I/O bus slots for powering I/O modules. The RX/TX module communicates to the CCM via the multiplexer located on the motherboard. The CCM identifies each of the installed RX/TX modules by the RS-232 connection on the motherboard. The table below lists each RX/TX communication

CONNECTOR JP1 JP2 JP3 JP4 JP5 JP6 JP7 JP8

LOOP 1 2 3 4 5 6 7 8

ADDRESS 1001-1255 2001-2255 3001-3255 4001-4255 5001-5255 6001-6255 7001-7255 8001-8255

Figure 3-7. Multi-Loop I/O Motherboard, Details

August 1999

3-6

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
Power for normal standby and alarm operation derives from either of two sources; 1) primary supply up to its capacity, or 2) auxiliary power supply input. Provision for hardwire input of auxiliary power has been made through the use of hardwire connections between the auxiliary power supply and terminals 1 & 2 of the terminal block of the signal module. Output circuits are listed for use in power limited applications. Each circuit can be individually programmed via the PCS program for Continuous, Pulsed 60 or 120 BPM (March-Time) or Coded (Temporal Pattern) operation. Relation between each signal output and its input source shall be defined by the panel EOC logic program. In Walk Test mode the signal output circuit(s) shall sound the test signal if programmed properly. The walk test signal will be a 1.0 second pulse, then off until the next device is activated.

3-3.6

Signal Output Module

The PEGAsys panel has the capacity for a maximum of 8 Signal Output modules, shown in Figure 3-8, thus providing 32 possible signal circuits. Each Signal Output module is equipped with supervised 24 VDC outputs which can operate as Style Y or Style Z indicating circuits. The module will allow for 4 Style Y or 2 Style Z or a mix of 2 Style Y and 1 Style Z. Each circuit is supervised for open, short and ground fault. The ability to isolate individual outputs is accessed through the system operator menu options. The alarm output circuits are polarity reversing type, rated for 24 VDC signaling devices up to 2.0 Amp maximum per circuit. Careful consideration of alarm strobe in-rush currents has been made to help avoid any potential problems with the increased power requirements in support of the wide range of the ADA / UL 1971 signaling appliances in the marketplace. Refer to drawing number 06-235443-006 for installation details.

2 STYLE "Z"
5 6 7 + 8 + 9 10 11 + 12 +

CIRCUIT 1

10K EOR

Reset Switch Trouble LED


SIGNAL AUD 76-100003-001

{ {

Module Address Assignment

CIRCUIT 3

10K EOR

See Note 2 1 STYLE "Z" AND 2 STYLE "Y"


5 6 7 + 8 + 9 10 11 + 12 +

Auxiliary Power NotUsed Sounder Circuits 1-4 TB1

CIRCUIT 1

10K EOR

CIRCUIT 3 CIRCUIT 4

10K EOR

10K EOR

Note 1: Refer to DWG. No. 06-235443-006, in Appendix I, for Configuration Jumper (W1-W8). 2: Cut Jumpers W9 & W10 when Auxiliary Power Input is used to remove module from RS-485 power bus.. 3: Only 8 of this Type Module can be used on the system. Refer to Section 1-2.7, in Chapter 1, for other limitations.

4 STYLE "Y"
5 6 7 + 8 + 9 10 11 + 12 +

2 STYLE "Y" AND 1 STYLE "Z"


CIRCUIT 1 CIRCUIT 2 10K EOR 10K EOR
5 6 7 + 8 + 9 10 11 + 12 +

CIRCUIT 1 CIRCUIT 2

10K EOR

10K EOR

CIRCUIT 3 CIRCUIT 4 10K EOR

CIRCUIT 3

10K EOR

10K EOR

Figure 3-8. Signal Output Module, Details


3-7

76-100016-001

August 1999

PEGAsys
3-3.7 Relay Output Module

Intelligent Suppression Control/Fire Alarm System The auxiliary relays are rated for 2.0 Amp @ 30 VDC & 1.0 Amp @ 120 VAC. Refer to Drawing. No. 06-235371-007, in Appendix I, for further installation details. Each relay output can be individually programmed via the PCS program for operation. Relation between each relay output and its input source is defined by the panel EOC logic program. In Walk Test mode the relay output circuit(s) will not operate when the input device(s) under test are activated.

The PEGAsys panel has the capacity for a maximum of 8 Auxiliary Relay Output cards for up to 32 relays. Each Auxiliary Relay Output card (shown in Figure 3-9) is equipped with 4 Form C, dry contact relay outputs. The ability to isolate an individual relay output is accomplished through the system operator menu.

Note: A maximum of 8 Relay Output Modules can be used on the system. Refer to paragraph 1-2.7, in Chapter 1, for other limitations.

RELAY 76-100004-001

Figure 3-9. Relay Output Module, Details


August 1999 3-8 76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
Table 3-2. Approved Release Output Devices

3-3.8

Agent Release Output Module

The PEGAsys panel has the capacity for a maximum of 8 agent release output modules, which provides up to 8 possible release circuits and 24 maximum signal outputs on these modules. Each Agent Release Output card is equipped with a 24V, supervised output which is programmable for solenoid-type discharge controls. The installer must select discharge control type required during software configuration programming. The circuit shall be supervised for open or ground fault conditions. The ability for individual release output isolate is provided through the system operator menu. Each card is equipped with supervised signaling outputs for 3 Style Y 24 VDC polarity reversing type indicating circuits. Each signal circuit is supervised for open, short and ground fault conditions. The ability for individual output isolation is provided through the system operator menu. Careful consideration of alarm strobe in-rush currents has been made. The agent release output circuit is rated for 24 VDC control devices. Each release output can supervise and activate up to two (2) solenoid control heads. Table 3-2 details all devices with which the agent release module is approved for operation.

M anufacturer Kidde-Fenwal Kidde-Fenwal Kidde-Fenwal Kidde-Fenwal Kidde-Fenwal Various Manufacturers

Solenoids 486500 & 48650001 890181 897494 899175 895630 FM Groups A, B, D, E, & G Sprinkler Solenoids

Power for standby and alarm operation of release and signaling outputs shall derive from one of two sources; 1) primary supply up to its capacity, or 2) auxiliary power supply input. Input of auxiliary power is hardwired through terminals 1 & 2 on the modules terminal block. Output circuits are Listed for use in Power Limited applications. All signaling power is fully regulated.

Reset Switch Trouble LED


RELEASE 76-100001-001
1

Module Address Assignment

See Note 2

Auxiliary Power Release Circuits

TB1

Signal Circuits
12

Note 1: Only a maximum of 8 of this type module can be used on the system. Refer to paragraph 1-2.7, in Chapter 1, for other limitations. 2: W1 and W2 must be cut when the auxiliary power input is used.

Figure 3-10. Agent Release Output Module, Details


76-100016-001 3-9 August 1999

PEGAsys
3-3.9 City-Tie Module

Intelligent Suppression Control/Fire Alarm System Reverse Polarity-Type Output: Unsupervised output for trip circuit wiring only, current limited at 100 mA, 24 VDC. Reverse Polarity output circuits are listed for use in Power Limited applications. Refer to Drawing. No. 06-235443-008 for further installation details. The City Tie Module will operate during PEGAsys' FailSoft mode. Any system alarm will cause the output to transfer. In Walk Test mode the city notification outputs shall be disabled. In addition, the output has provisions for manual disable or isolate through the operator menu function. The initiation of a walk test will institute a system trouble causing the city tie output to transfer to the trouble state.

The City Notification Card (Figure 3-11) provides connection and operation for Local Energy, Shunt type Master Box and Reverse Polarity styles of output. The output type is selected by choosing which terminals terminate the field wiring. The module has an Amber LED to signify disconnect status. The ability for individual output isolate is provided through the system operator menu. Local Energy-Type Output: Monitored output for trip circuit wiring and Master Box coil status (Set/Unset), current limited at 550 mA, 24 VDC. Monitored for open, short and ground fault. Shunt-Type Output: Unsupervised contact rated at 5.0 Amp, 24 VDC resistive.

Note: Only 1 City Tie Module can be connected to the system.


Figure 3-11. City Tie Module, Details
August 1999 3-10 76-100016-001

CITY TIE 76-100002-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
SmartOne photoelectric detectors have an unobtrusive low profile look and are available using the following: Model PSD 7152 SmartOne Photoelectric Detector: P/N 71-402001-100

3-3.10 Field Devices


The SmartOne Series of Intelligent Fire Alarm devices provide the PEGAsys control system with smoke & heat detection, necessary monitoring and control functions required by todays advanced Fire Alarm systems. Each of the SmartOne devices features an intrinsic microprocessor with 4K of nonvolatile memory. Each device constantly monitors its surrounding environment and makes decisions in response to that information then reports status as required to the control panel. Each loop device communicates with the RX/TX module over the PC (power/communications) line. This Distributed Intelligence architecture allows each loop device to make decisions within the monitored area. This unique utilization of processing power makes possible a system of loop devices with greater capacity and flexibility than any typical addressable device system with centralized processing. Each SmartOne device contains a status LED which blinks in various patterns to indicate device status. The blink rates and associated status levels are as follows: Blink Rate 9 Second Rate 2 Second Rate Operation status Normal mode Alarm (activated)

Figure 3-12. Typical Detector

3-3.13 SmartOne Heat Detectors


The SmartOne heat detectors provide true distributed intelligence addressable microprocessor based heat detection to the PEGAsys system. Model THD-7252 is a analog fixed temperature thermistor type detector which does not respond to rate of rise conditions until its programmed set point is met. Unique algorithms are used to compensate for heat rise without problems associated with false alarms due to elevated rates of rise in ambient temperature. A unique sensing chamber permits 360 heat entry and response. Each detector is electronically addressable and can be fully field programmed. Calibration, device address, pre-alarm & alarm sensitivity set points and drift compensation algorithm are stored in each detector's nonvolatile memory. SmartOne Heat detectors have an unobtrusive low-profile look and are available using the following: Model THD 7252 SmartOne Heat Detector: P/N 70-404001-100

Off (not blinking) Trouble condition The following three paragraphs describe each type of available detector. A typical detector is shown in Figure 3-12.

3-3.11 SmartOne Ionization Detectors


The SmartOne Ionization smoke detectors provide true distributed intelligence addressable microprocessor based smoke detection to the PEGAsys system. Model CPD-7052 is a dual chamber analog ionization type detector which senses both visible and invisible smoke. A unique sensing chamber permits 360 smoke entry and response. Each detector is electronically addressable and can be fully field programmed. Calibration, device address, pre-alarm & alarm sensitivity set points and drift compensation algorithm are stored in each detectors non volatile memory. SmartOne Ionization detectors have an unobtrusive low profile look and are available using the following: Model CPD 7052 SmartOne Ionization Detector: P/N 70-402001-100

3-3.14 Addressable Contact Input Devices


The PEGASYS Contact Monitor (P/N 70-407008-00X) allows an installer the ability to interface typical NO/NC fire alarm devices, such as water flow and tamper switches to the PEGAsys system. The contact monitor is also used to interface to the Manual Alarm, Manual Release and Abort Stations. The addressable contact monitor device is programmable to report in the following manners: Alarm (default), Trouble, Manual Alarm, Waterflow Alarm, Manual Release, Abort, Supervisory and Normal (Silent input). Its default setting is alarm when programmed using the Autolearn function. The unit includes a connection for an optional status LED which allows the device to indicate its present operating status. In normal standby mode the LED will flash every 9 seconds, in trouble condition the LED will be extinguished, when activated the LED will flash every 2 seconds. Addressable Contact Input Device (NO): P/N 70-407008-001. Addressable Contact Input Device (NC): P/N 70-407008-002.

3-3.12 SmartOne Photoelectric Detectors


The SmartOne Photoelectric smoke detectors provide true distributed intelligence addressable microprocessor based smoke detection to the PEGAsys system. Model PSD-7152 is a analog photoelectric type detector which responds to a broad range of smoldering and flaming type fires. A unique sensing chamber permits 360 smoke entry and response. Each detector is electronically addressable and can be fully field programmed. Calibration, device address, pre-alarm & alarm sensitivity set points and drift compensation algorithm are stored in each detector's nonvolatile memory.

76-100016-001

3-11

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System The duct housing accepts either the PSD-7152 or CPD-7052 smoke detectors. A transparent Lexan cover over the detection chamber allows visual inspection of the duct detector chamber and the internal smoke detector status. Sampling of the air in the duct is accomplished through the use of sampling tubes which extend into the HVAC duct.

Model DH-2000 Air Duct Housing: P/N 70-403001-100 Model DH-2000 CPDI Air Duct Housing with Ion Det.: P/N 70-403001-052 Model DH-2000 PSDI Air Duct Housing with Photo Det.: P/N 70-403001-152

Refer to DH-2000 Installation manual 74-222 (P/N 06-235398001) for further details.

Figure 3-13. Addressable Contact Input Device

3-3.15 Addressable Relay Output Devices


The addressable relay output device (P/N 70-408004-001) provides the PEGAsys system with a Form C dry contact interface for remote control applications. The device connects directly to the RX/TX multiplex loop and contains an SPDT relay for control of auxiliary equipment. The device can be activated through the systems EOC or RTC programming and its default operation programming is done during the Autolearn function. The unit includes an intrinsic status LED which allows the device to indicate its present operating status. In normal standby mode the LED will flash every 9 seconds, in trouble condition the LED will be extinguished, in activated condition the LED will flash every 2 seconds. Addressable Relay Output Device: P/N 70-408004-001
Form-C contact rated at: 0.6 A @ 120 VAC 2.0 A @ 30 VDC (resistive) 1.0 A @ 30 VDC (inductive)
N/O COM N/C
7 6 5 Field Connections

Figure 3-15. DH-2000 Air Duct Housing

3-3.17 Loop Isolator Devices


The SmartOne series of loop devices offer optional loop isolation which protects the loop from wire-to-wire short conditions (NFPA 72 Style 7). The isolators will open the loop between two isolators in the presence of a short circuit condition, thus allowing the remainder of the loop to operate normally, however, a trouble indication for the devices effected by the isolation will be prompted on the panel. The isolators will return to normal operation when the short condition has been removed from the effected wires. The loop isolators are offered in three package styles, one stand alone style in a single gang electrical box arrangement, a second in a detector base module arrangement which allows the unit to be mounted behind a smoke detector in the 6 detector base and a third which mounts directly on the RX/TX module. The single gang mount unit includes intrinsic status LEDs which allows the device to indicate in which direction the short condition is being detected. In normal standby mode the LED will be extinguished, in activated condition the LED will be on continuously. Loop Isolator RX/TX mount: P/N 74-200012-001 Loop Isolator Stand-alone (Single Gang): P/N 74-200012-002 Loop Isolator 6 detector base mount: P/N 74-200012-004

(+) PC Line In (-)

(+) (-) PC Line Out

Figure 3-14. Addressable Relay Output Device

3-3.16 Model DH-2000 Air Duct Housing


The DH-2000 air duct housing is designed for detecting particles of combustion in air handling systems. Upon smoke detection the system can be programmed to control a variety of devices like HVAC fans and power shut down preventing unnecessary damage to the facility.

TERMINALS 1-4 ARE POWER LIMITED TERMINALS 5-7 ARE POWER LIMITED

MODEL AO CAT. NO. 70-408004-001 SEE INSTALLATION INSTRUCTIONS 06-235577-001 MAX. INSTALL. TEMP. 120F FOR SERVICE SEND TO: KIDDE-FENWAL, INC. 400 MAIN ST. ASHLAND, MA 01721 DATE OF MANUFACTURE:

SmartOne

TM

August 1999

PC PC PC PC (+) (-) (+) (-)

N/C

COM

N/O

3-12

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

Figure 3-18. Loop Isolator, 6" Detector Base Mount Figure 3-16. Loop Isolator, RX/TX Mount

Figure 3-17. Loop Isolator, Stand-Alone

76-100016-001

3-13

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

3-14

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

CHAPTER 4 MAINTENANCE PROCEDURE


is operating as intended. The test actually stimulates the detection chamber of the device and verifies the response from the device. The CCM will report a result of the test for each device tested. NOTE: This test has a pass or fail result. It will not activate alarm outputs on the system. The step-by-step procedure to perform the loop device test follows:

4-1

INTRODUCTION.

This chapter contains maintenance instructions for the PEGAsys. These procedures should be accomplished on a scheduled basis. In the event that system problems are found during the performance of a procedure, refer to Chapter 5 for corrective action.

4-2

SCHEDULED MAINTENANCE.

The scheduled maintenance of the system should be performed at an established interval. The interval that the maintenance procedures are performed should not exceed any imposed regulations (NFPA 72 or local codes).

NOTE: Addressable Contact Input Modules cannot be tested with this procedure. This is for SmartOne smoke and heat detectors only. a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

PLEASE ENTER PASSWORD 4-3 MAINTENANCE PROCEDURES.


(2) Type in the Level 1 or Level 2 password. (3) Press the return () key. Verify that the display reads:

The following paragraphs outline general scheduled maintenance procedures to be performed on an as-necessary basis.

1:ISOLATE 3:SET
b.

2:LIST 4:TEST

Press number 4 push-button, verify that the display reads:

4-3.1

Lamp Test
c.

This test allows the user to check the system display LEDs. The step-by-step procedure to perform the lamp test follows: a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

1:LAMP TEST 2:LOOP DEVICES 3:BATTERY TEST SCROLL for more


Press number 2 push-button, verify that the display reads:

START DEVICE TEST TEST DEVICES FROM _ _ _ _TO_ _ _ _


d. e. Enter the device address to be tested and then press the return push-button. Verify the display scrolls through each selected address and read as below:

PLEASE ENTER PASSWORD


(2) Type in the Level 1 or Level 2 password. (3) Press the return () key. Verify that the display reads:

1:ISOLATE 3:SET
b.

2:LIST 4:TEST
f.

Press number 4 push-button, verify that the display reads:

START DEVICE TEST TESTING (Device Address #)


When the device testing is completed the display will read:

1:LAMP TEST 2:LOOP DEVICES 3:BATTERY TEST SCROLL for more


c. Press number 1 push-button, verify that the display reads:

TEST COMPLETED (Address #) TEST (PASSED or FAILED)


g. Press the SCROLL push-button to read the status of each device tested.

***LAMP TEST*** ***VERSION 1.0***


d. Ensure the following LEDs are momentarily lit:

4-3.3

Battery Test

POWER ON TROUBLE GROUND FAULT CPU ERROR 4-3.2

ALARM SUPERVISORY PREALARM SILENCE

This test allows the user to activate a battery test to verify battery capacity. The step-by-step procedure to perform the battery test follows: a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

Loop Device Test

The PEGAsys system provides a unique detector test function which allows a user to initiate a test of a detection device through the use of the system menus and verify the detection device(s)

PLEASE ENTER PASSWORD


(2) Type in the Level 1 or Level 2 password. (3) Press the return () key. Verify that the display reads:

1:ISOLATE 3:SET
4-1

2:LIST 4:TEST
August 1999

76-100016-001

PEGAsys
b. Press number 4 push-button, verify that the display reads:

Intelligent Suppression Control/Fire Alarm System Heat Detectors: When testing SmartOne heat detectors use of a low powered heat gun is acceptable. Heat the detector for a minimum of ten seconds. When a sufficient amount of heat has been detected by the detector, the control panel will respond with an alarm indication. The status LED of the detector will flash at a 2 second rate during the alarm period. Take care during the heating of the detector to avoid over heating the plastic housing. Maintain a minimum of 1 foot between the detector and the heat gun nozzle. Use of open flame devices are not recommended as discoloration of the plastic housing is likely and this is a potentially hazardous practice. 4-3.4.2 WALK TEST PROCEDURE The step-by-step procedure to perform the walk test follows: a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

1:LAMP TEST 2:LOOP DEVICES 3:BATTERY TEST SCROLL for more


c. Press number 3 push-button, verify that the display reads:

BATTERY TEST BATTERY TEST ON PS*_ _


d. Enter the power supply address which the batteries are connected to. Verify the display reads:

BATTERY TEST TEST ACTIVATED ON PS(_ _)


e. Upon the completion of the test the display will read:

TEST ON PS(_ _) COMPLETED >_>_ _._V


f. Verify that the voltage is within allowable tolerances.

4-3.4

Walk Test

PLEASE ENTER PASSWORD


(2) Type in the Level-2 password. (3) Press the return () key. Verify that the display reads:

The PEGAsys system provides a one person walk test function. This allows the service person to enable a group of devices for walk test, then proceed through the installation activating the specified devices. The system will respond to each activation with a short burst of the programmed signal circuit. The related signal circuit will only be pulsed if it has been configured for the Walk Test feature when defining it in the PCS software. During the system installation/configuration operation the installer would need to enable each signal circuit installed in the system for Walk Test, if desired. The systems signal outputs default to walk test disabled. When walk test is activated and carried out the system enters each activation with a time and date stamp. The operator can then print out all walk test results for review. The walk test feature can be deactivated two ways, the service person can deactivate it through the user menus or the walk test function will time out after 10 minutes of non activation ensuring system response if the service person is called away for an extended period of time. NOTE: When the walk test is active the panel will annunciate a trouble condition. 4-3.4.1 WALK TESTING DETECTORS Place the system in walk test as described in Paragraph 4-3.4.2. To place a detector into alarm perform the applicable procedure below: Smoke Detectors: When testing SmartOne smoke detectors use a "punk-stick" or "cotton wick" to generate smoke. Apply smoke to the detector for a minimum of 10 seconds. When a sufficient amount of smoke has entered the device, the control panel will respond with an alarm indication. The status LED of the detector will flash at a 2 second rate during the alarm period. Use of aerosol smoke simulation product may be used if acceptable to the Authority having Jurisdiction and if the product is used as directed in the instructions.

1:ISOLATE 3:SET
b.

2:LIST 4:TEST

Press number 4 push-button, verify that the display reads:

1:LAMP TEST 2:LOOP DEVICES 3:BATTERY TEST SCROLL for more


c. Press the SCROLL push-button, verify that the display reads:

4:WALK TEST
d. e.

5:ALARM SIM TEST 5:STOP WALK TEST

Press number 4 push-button, verify that the display reads:

1:START WALK TEST

Press number 1 push-button, verify that the display reads:

START DEVICE WALK TEST WALK TEST STARTED ON LOOP( _ _)


f. After completion of the walk test, press number 2 pushbutton to disable the walk test mode.

4-3.5

Alarm Simulation Test (AST)

The PEGAsys system provides a feature which allows the system installer/inspector to verify the actual output operation in relation to the input(s) which are programmed to activate the output of interest. The service person would enable the AST function for a particular input and the system would operate the output(s) as it is programmed in the Event Output Control program. The system will respond with an alarm condition when the AST feature is enabled. The user would have to disable the AST when output operation has been verified. WARNING Any outputs which are controlling critical processes or agent releasing should be physically disconnected from the process or agent container to avoid unwanted shutdowns and/or agent releases. When the AST function is enabled the pre- programmed outputs for the activated input(s) will activate.

August 1999

4-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System 4-3.5.1 AST PROCEDURE The step-by-step procedure to perform the AST follows: a. b. Be sure to observe the above warning. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads: 5. 4.

PEGAsys
"Testing shall include verification that the releasing circuits and components energized or actuated by the fire alarm system are electrically supervised and operate as intended on alarm." "Suppression systems and releasing components shall be returned to their normal condition upon completion of system testing."

PLEASE ENTER PASSWORD


(2) Type in the Level-2 password. (3) Press the return () key. Verify that the display reads:

4-4.1

Disarming Release Circuits

1:ISOLATE 3:SET
c.

2:LIST 4:TEST

Perform the following step-by-step procedure prior to system testing. a. Isolate all agent release circuits using the system menu (Refer to Paragraph 2-5.4.1). WARNING Use safety precautions when removing solenoids and connections from initiators (i.e. use the shorting cap when the initiators are disconnected) to prevent unwanted discharge or activation. b. Physically remove the solenoids at the storage containers. WARNING The suppression system is now fully disarmed from all automatic activation and, in some cases, all manual activation. c. The system can now be tested without the risk of an inadvertent release of agent.

Press number 4 push-button, verify that the display reads:

1:LAMP TEST 2:LOOP DEVICES 3:BATTERY TEST SCROLL for more


d. Press the SCROLL push-button, verify that the display reads:

4:WALK TEST
e.

5:ALARM SIM TEST

Press number 5 push-button, verify that the display reads:

ALARM SIMULATION TEST DETECTOR ADDRESS _ _ _ _


f. Type in the selected device address and then press the return push-button. Verify that the display reads:

ALARM SIMULATION TEST 1:ACTIVATE 2:DE-ACTIVATE


g. h. i. Press number 1 push-button and then the return push-button. Verify that the system responds as programed. Press the ACKLDGE push-button to acknowledge the alarm. De-activate the AST programming by: (1) Repeat steps b. through f. (2) Press number 2 push-button and then return ().

4-4.2

Arming Release Circuits

Perform the following step-by-step procedure upon completion of system testing. a. b. c. Verify that all solenoids are disconnected from storage containers. Isolate all agent release circuits using the system menu (Refer to Paragraph 2-5.4.1). Reconnect the solenoids at the storage containers. Ensure the system is free of any alarms to prevent unwanted discharge or activation. De-isolate agent release circuit(s). The system is now in full operation in accordance with system programming.

4-4

DISARMING AND REARMING RELEASE CIRCUITS

d. e. f.

The disarming and rearming procedures which follow must be performed when testing the PEGAsys system. Prior to preceding ensure the notes below from NFPA 72 Chapter 7 are understood. IMPORTANT NOTES 1. "Testing personnel shall be familiar with the specific arrangement and operation of the suppression system(s) and releasing function(s) and cognizant of the hazards associated with inadvertent system discharge." "Occupant notification shall be required whenever a fire alarm system configured for releasing service is being serviced or tested." "Discharge testing of suppression systems shall not be required by this code. Suppression systems shall be secured from inadvertent actuation, including disconnection of releasing solenoids/electric actuators, closing of valves, other actions, or combinations thereof, as appropriate for the specific system, for the duration of the fire system testing."

4-5 4-5.1
a.

POWERING DOWN THE SYSTEM Power-Down Procedure

The step-by-step procedure to power-down the system follows: Ensure that the panel does not have any active alarms to prevent unwanted discharge or activation. CAUTION If alarms do exist during power-down, power-up of the panel will cause a reactivation of the alarm sequence and possible activation of the suppression system. b. Disarm release circuits as per Paragraph 4-4.1.

2.

3.

76-100016-001

4-3

August 1999

PEGAsys
c. d. Remove DC power by disconnecting batteries first. Remove AC power by shutting off the circuit breaker to the panel, second. c.

Intelligent Suppression Control/Fire Alarm System

SYSTEM TIME (AM/PM) 1:AM 2:PM


(d) Type in appropriate selection (1 for AM or 2 for PM). Rearm release circuit per Paragraph 4-4.2.

4-6 4-6.1
a.

POWERING UP THE SYSTEM Power-Up Procedure

Ensure that all solenoids are disconnected from the storage containers to prevent unwanted discharge or activation. If the system has been powered down energize the system by performing the following steps: (1) Set the circuit breaker for the CCP power to ON. Verify that the display reads "Main Processor Power On" and that the CPU ERROR indicator is lit. Ensure that the audible device is buzzing continuously. (2) Press the display module reset switch. Verify that the CPU ERROR indicator is extinguished and the audible device is silenced. (3) Verify that the display reads as follows:

b.

MAIN PROCESSOR POWER ON


(4) After ten seconds, verify that the display reads as follows:

RXTX NON-MONITORING TROUBLE ON RXTX1


NOTE: The RX/TX message will repeat itself for each RX/TX module in the system while the system initializes itself. This initialization can take up to 90 seconds. (5) Verify that the POWER ON and TROUBLE indicators are lit. (6) Connect the backup batteries to the CCP in accordance to the procedure in Chapter 7. (7) Press the ACKLDGE push-button. After approximately one minute the display will momentarily read:

RXTX NON-MONITORING TROUBLE OFF


(8) Verify the display reads the correct time and date. If the incorrect time is displayed perform step a.9. (9) Set time and date as follows: (a) Press 0 (zero) key. Verify that the display reads:

PLEASE ENTER PASSWORD


(b) Type in the default 1st level password (987). (c) Press the return () key. Verify that the display reads:

1:ISOLATE 3:SET

2:LIST 4:TEST

(d) Type in 3111 on the keypad. Verify that the display reads:

SYSTEM TIME (AM/PM) ENTER THE TIME _ _ : _ _ (HH:MM)


(e) Type in the time (HH=hours 0-12 and then MM=minutes 0-59). Press the return key. Verify that the display reads:

August 1999

4-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

CHAPTER 5 TROUBLESHOOTING AND CORRECTIVE MAINTENANCE

5-1

INTRODUCTION

5-3

TROUBLESHOOTING

The effectiveness of this chapter is greatly increased by first reading the entire manual. The service technician must have a sure understanding of the purpose and correct function of the module/device before attempting corrective maintenance. This chapter contains instructions to aid a technician in locating faulty modules/devices. This chapter also provides instructions for the removal and replacement of the replaceable modules/devices of the PEGAsys system. WARNING All service to panel must be done with panel powered down to prevent damage to panel components, personnel injury, or both

The PEGAsys system utilizes internal programming for continuous system testing. Most system faults can be isolated through the operation of the front panel. Users/technicians can initiate various testing via the use of the system menu (See Paragraph 2-5) after entering a valid password. Table 5-1. Troubleshooting Index

Module/Device

Detailed Illustration

Functional Description Paragraph 3-3.1

Replacement Procedure

Central Control Module Receiver/Transmitter Module RXTX

3-3

5-4.2

3-4

3-3.2

5-4.3 7-7.6, 7-7.7 & 7-7.8

5-2

STANDARD FAULT-ISOLATION TECHNIQUES

Failure of the PEGAsys system to function properly will usually be caused by one or more of the following faults: a. b. c. e. Failure of the Power Supply Burned Out Indicator Damaged Wiring or Corrosion Component Failure

Power Supply Module Multi-Loop Motherboard Basic I/O Motherboard Signal Output Module Relay Output Module Agent Release Module City Tie Module Field Device Addressable Contact Input Device Addessable Relay Output Device Air Duct Housing Loop Isolators

3-5 & 3-6

3-3.3 & 3-3.4

3-7

3-3.5

1-6

1-2.5

7-5

When a failure occurs and the cause is not known, check as many of these items as is practical before starting a detailed check. If possible, obtain information about any changes taking place that may affect the system.

3-8

3-3.6

7-7.1

3-9

3-3.7

7-7.2

5-2.1

Visual Inspection

3-10 3-11 --

3-3.8 3-3.9 3-3.8

7-7.3 7-7.4 5-4.4

When troubleshooting, the fault may often be discovered through visual inspection alone. Some faults, such as burned out indicators, shorted transformers, or wiring, can be located by sight or smell. Check for smoke or the odor of burned or overheated parts. Look for loose connections. Visual inspection is also useful in avoiding damage to the system which could occur through improper servicing methods. Refer to Table 5-1, Troubleshooting Index, and the paragraphs of this chapter for troubleshooting beyond visual inspection.

3-11

3-3.12

5-4.4

5-2.2

Power Checks

3-12 3-13 3-14 thru 316

3-3.13 3-3.14 3-3.15

5-5.4 See Manual

Many faults on the system can be caused by problems with power. Ensure battery and line voltages are checked prior to troubleshooting the system.

76-100016-001

5-1

August 1999

PEGAsys
5-4 REMOVAL AND REPLACEMENT a. b. c. d. e. f. g. The following paragraphs provide required tools and step-by-step replacement procedures for the PEGAsys. The procedures should also be used to assist module and device installation. CAUTION Some components are subject to damage from electrostatic discharge (ESD). These components are not to be removed from their protective wrappings until they are to be installed in their respective equipment locations, and then only by personnel connected to earth ground.

Intelligent Suppression Control/Fire Alarm System Disconnect plug from terminal T1. Remove the two mounting screws from the module and move module to gain access to connected wiring. Remove the plug from the RS-232 port. Remove power plug from connector jack J1. Remove new RX/TX module from packing and inspect for physical damage. Ensure jumper configuration is set. Install new RX/TX in the reverse order of removal.

5-4.1

Required Tools

The following tools will be required to perform the removal and replacement procedures. a. b. c. d. e. f. Small Flat-Blade Screwdriver 6" Flat-Blade Screwdriver No. 2 Philips Screwdriver Wire Striper Small Needle Nose Pliers Ground strap

5-4.2

Central Control Module

The following paragraph provides the step-by-step procedure for replacing the CCM. a. b. c. d. e. f. g. Ensure all programming is saved using PCS software. Disconnect plugs from the I/O Port and RX/TX port, and PC port (if connected to IIM) Remove the wiring from TB6. Remove the six mounting screws while holding the CCM in place. Remove CCM from cabinet. Remove new CCM from packing and inspect for physical damage. Install new CCM in the reverse order of removal. Figure 5-1. Installation for Single Loop

5-4.3

RX/TX Module

The following paragraph provides the step-by-step procedure for replacing the RX/TX module. Depending on the system configuration refer to the appropriate Figure, 5-1 or 5-2. Ensure that the RX/TX jumpers are set properly during the procedure. Verify that the settings of the jumpers on the RX/TX Module conform to the wiring style of the system being installed. The RX/TX is shipped from the factory programmed for Style 6 wiring style. Refer to drawing 06-235443-002, in Appendix I, the installation drawing which shows the jumper locations on the RX/TX module. The settings are used to set the wiring style ( 4, 6 or 7), with 7 being used with loop isolators. Jumpers on the RX/TX Module are noted by JP x and Wx (x = a single digit) call-outs on the module board. Table 5-2 lists the types of allowable configurations you can select along with their respective jumpers.

Figure 5-2. Installation for Multi-Loop

August 1999

5-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System Table 5-2. RX/TX Configuration Selection
Style 6 W/Loop Isolator Shorted Open Open

PEGAsys

Jumper

Style 4

Style 6

Style 7

W1 & W2 JP 2 JP 3

Open Shorted Shorted

Shorted Shorted Shorted

Shorted Open Open

NOTE: Style-7 requires the use of loop isolators, the RX/TX module requires the use of one (1) P/N 74-200012001 isolator module to operate in the Style-7 configuration.

5-4.4

Field Devices

The following paragraph provides the step-by-step procedure to replace field devices into the PEGAsys system. NOTE: Smoke and heat detectors can be replaced without powering down the system. If adding new loop devices to the system, then the panel will need to be powered down. NOTE: If device is in alarm, the alarm must be cleared prior to removal from the system. If the alarm cannot be cleared, remove the device from the system and push the hard reset on the CCM motherboard and RX/TX. Once the system is on-line insert the replacement device onto the loop. a. b. c. d. e. f. Identify the defective device to be replaced. Remove the defective device from the PC Line. Record the Model Number and Device Type. Ensure the new device is an exact replacement. Verify that the Model Number is the same as the defective device. Set the address of the new device to the same as the defective device using the procedure in Paragraph 2-8.6. Connect the new device to the PC Line where the defective device was removed, if not accomplished in the previous step. Use the same detector base or electrical box of the defective device. Perform the appropriate test listed below: Loop Device Test (Paragraph 4-3.2) for Detection Devices. Walk Test (Paragraph 4-3.4.2) for AI or AO.

g.

76-100016-001

5-3

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

5-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

CHAPTER 6 PARTS LIST

6-1

INTRODUCTION

The PEGAsys system parts list, Table 6-1 provides a list of all repair parts. Table 6-1. PEGAsys System Parts List

NOMENCLATURE SYSTEMS PEGAsys Control Unit (includes CCM with One RX/TX Module, One Power Supply/ Charger Assembly and Enclosure) PEGAsys Multi-Loop Control Unit (includes CCM with One Multi-Loop Motherboard One RX/TX Module, One P.S./Charger Assembly and Enclosure) MAIN SYSTEM COMPONENTS Central Control Module (CCM), Single-loop Central Control Module (CCM), Multi-loop Power Supply/Charger Assembly, includes 4 Amp. P.S., Rev. C. RX/TX Module for Single Loop System RX/TX Module for Multi-Loop System Main Enclosure INPUT/OUTPUT MODULES Agent Release Module Signal Output Module Relay Output Module City Tie Module I/O Motherboard for 8 Option Modules I/O Multi-Loop Motherboard for up to 8 RX/TX or 7 I/O modules POWER SUPPLIES Power Supply Module, 4 Amp., including 36" Wiring Harness (for main cabinet) Power Supply Module, 4 Amp., including 8" Wiring Harness (for expansion cabinet) ADDITIONAL COMPONENTS PEGAsys Expansion Enclosure (order backplane separately) Expansion Backplane, for Mounting Motherboard and 4 Power Supplies Expansion Backplane, for Mounting 8 Power Supplies Expansion Backplane, for Mounting two I/O Motherboards Battery Enclosure for Additional Batteries Battery 12V, 17AH Battery 12V, 33AH

PART NUMBER

76-100000-501 76-100000-600

76-100008-501 76-100008-600 76-100009-010 76-100005-001 76-100005-002 76-100000-502 76-100001-001 76-100003-001 76-100004-001 76-100002-001 76-100007-001 76-100017-001 76-100009-002 76-100009-003 76-100000-505 76-100000-006 76-100000-007 76-100000-008 76-100010-001 06-115915-046 89-100052-001

76-100016-001

6-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System Table 6-1. PEGAsys System Parts List (Continued)

NOMENCLATURE SMARTONE FIELD DEVICES Intelligent Photoelectric Detector, Model PSD-7152 Intelligent Ionization Detector, Model CPD-7052 Intelligent Thermal Detector, Model THD-7252 6' Universal Detector Base, Model 6SB 4' Universal Detector Base, Model 4SB Addressable Contact Input Device (N.O.) Addressable Contact Input Device (N.C.) Addressable Relay Output Device Loop Isolator - 1 Gang Box Mounted Loop Isolator - Detector Base Mounted Loop Isolator - RXTX Mounted DUCT HOUSING AND COMPONENTS DH-2000 Duct Housing without Detector Installed DH-2000 PSDI - Duct Housing with Photoelectric Detector Installed DH-2000 CPDI - Duct Housing with Ionization Detector Installed Sampling Tube - 12", The number of sampling holes vary with tube length. Order sampling tubes that approximate duct width. Sampling Tube - 24" Sampling Tube - 48" Sampling Tube - 72" Sampling Tube - 96" Sampling Tube - 120" Exhaust Tube Kit MISCELLANEOUS Handheld Device Programmer 6-Conductor Telephone Cable with DB25 Adapter (DTE) for Computers and Terminals 6-Conductor Telephone Cable with DB25 Adapter (DCE) for Modems 6-Conductor Telephone Cable with DB9 Adapter (DTE) for Laptop Computers DB25 Adapter (DTE) for Computers and Terminals (use with 6-Conductor Telephone Cable) DB25 Adapter (DCE) for Modems (use with 6-Conductor Telephone Cable) DB9 Adapter (DTE) for Laptop Computer

PART NUMBER

71-402001-100 70-402001-100 70-404001-100 70-400001-100 70-400001-101 70-407008-001 70-407008-002 70-408004-001 74-200012-002 74-200012-004 74-200012-001 70-403001-100 70-403001-152 70-403001-052 06-129500-001 06-129500-002 06-129500-003 06-129500-004 06-129500-005 06-129500-006 06-129554-001 74-200013-001 74-100016-001 74-100016-002 74-100016-003 06-129341-001 06-129317-003 06-129373-001

August 1999

6-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

CHAPTER 7 INSTALLATION

7-1

INTRODUCTION

This chapter provides information necessary to install the PEGAsys system. Installation consists of installing a complete system. The procedures in this chapter should be accomplished by technicians familiar with fire alarm system installation and the requirements of relevant NFPA regulations.

7-2

MATERIALS REQUIRED FOR INSTALLATION

The materials listed below are not supplied with the system, but are required for installation. No. 10 or 1/4 inch Mounting Hardware Electrical Conduit for AC Input Power 4-inch Electrical Junction Boxes (as required) Wire-Nuts and Crimp-On Terminals (as required) Ground Strap (for use when handling printed circuit boards

7-3

INSTALLATION PROCEDURE FOR CENTRAL CONTROL PANEL

Figure 7-1. CCP Installation Drawing With the enclosure held by the top two screws place the bottom two mounting screws in place. Tighten the screws. Reinstall the enclosure door at this time. Care must be taken when installing the door to ensure that the hinge pins are lined up correctly.

The PEGAsys Central Control Panel enclosure is 28 inches high x 18 inches wide x 5 inches deep. It is designed to be surface or semi-flush mounted using No. 10 or inch hardware. The type of hardware to be used is at the discretion of the installer but must be in accordance with good electrical and safety practices. Figure 7-1 shows the enclosures mounting hole layout. The lower set of mounting holes should typically be 44 inches from the floor in order that the display panel is at a convenient viewing height. To facilitate mounting the enclosure to its wall position, remove the enclosures front door. Be sure to disconnect the ground wire before removing the door. To remove the front door, open the door approximately 90 from its closed position and lift it up enough to allow the doors hinge pins to clear their mating hinge sockets located on the left side of the Central Control Panel. Place the mounting screws in to the top two holes in the wall. Leave approximately 1/4 of both screws exposed. Carefully place the two key holes over the screws in the wall. Ensure the enclosure has its door hinge sockets located to the left as you face the enclosure. Allow the enclosure to gently come to rest on the screws. Tighten the screws.

7-4

INSTALLATION PROCEDURE FOR EXPANSION ENCLOSURES

The expansion enclosure (P/N 76-100000-505) uses a back plate installed in the enclosure to meet various system component requirements. The expansion enclosure maintains the same outside dimensions as the main system enclosure. There are three versions of the backplate: An I/O module cardcage with mounting provisions for up to 4 power supplies Mounting provisions for up to eight power supplies Two motherboard cardcages for mounting up to 16 I/O modules in the expansion enclosure.

The optional I/O motherboard and I/O modules must be installed prior to the system being powered up. The I/O bus (communications) and 24 VDC power are attached to connectors located on the I/O Motherboard. NOTE: The I/O Bus (RS-485) wiring must be enclosed in raceway from the main enclosure for a maximum run of 20 feet, with expansion enclosures located in the same room as the main enclosure. Figure 7-2, shows the expansion backplate which provides mounting for 4 power supplies and one I/O motherboard. Fig-

76-100016-001

7-1

August 1999

PEGAsys
ure 7-3 shows the expansion backplate which provides mounting for up to 8 auxiliary power supplies. Figure 7-4, shows the expansion backplate which provides mounting for two I/O motherboards. To install, position the back plate in the enclosure and fasten it to the seven studs located in the enclosure using the nuts supplied with the enclosure.

Intelligent Suppression Control/Fire Alarm System

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.

ASHLAND, MA 01721

W2 W3

TBL RELAY

= Back Plate Mounting Studs (7 Locations)

Figure 7-2. Back Plate, I/O Motherboard & 4 P.S.

= Back Plate Mounting Studs (7 Locations)

Figure 7-3. Back Plate, 8 P.S.

06-129562-001
RET 24V RET

NO

NC

A W4 W4 S2 2 1 S1 2 1 S3 S3

DS1

24V

RET

SHR

AC OUT 1 2 AC IN DC IN 1

L N L G N L

AUX 1 AUX 2 AUX 1 AUX 2

24V

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V

SHR

+ -

MOTHER BD CCM

RET

SYSTEM POWER

24V

RET

24V

RET

24V

BAT

DC IN 2

RS485 KIDDE-FENWAL, INC.

ASHLAND, MA 01721

W2 W3

TBL RELAY

06-129562-001
RET 24V RET 24V

NO

NC

A W4 W4 S2 2 1 S1 2 1 S3 S3

DS1

24V

RET

SHR

AC OUT 1 2 AC IN DC IN 1

L N L G N L

R
W1 TB8 TB9 TP3 TP4 F1
RET RET 24V SHR

R
RET 24V RET 24V

+ -

SYSTEM POWER

MOTHER BD CCM

RET

24V

BAT

DC IN 2

= Back Plate Mounting Studs (7 Locations)

Figure 7-4. Back Plate, 2 I/O Motherboard

7-5

INSTALLATION PROCEDURE FOR I/O MOTHERBOARD

RS485 KIDDE-FENWAL, INC.

ASHLAND, MA 01721

W2 W3

TBL RELAY

The following paragraph provides the step-by-step procedure to install a I/O motherboard into a single loop configured system. a. b. c. d. Place motherboard on standoffs in the back of the enclosure. Insert and tighten the 12 mounting screws provided with the motherboard. Connect the 24VDC wiring from the power supply to terminal TB1. Connect the RJ-12 phone style wire from the MOTHER BD connector (on the power supply) to J9 on the motherboard.

06-129562-001
RET 24V RET

NO

NC

A W4 S1 2 1 S3 S2 S2 2 1

DS1

24V

RET

SHR

AC OUT 1 2 AC IN DC IN 1

L N L G N L

AUX 1 AUX 2 AUX 1 AUX 2 AUX 1 AUX 2 AUX 1 AUX 2 AUX 1 AUX 2 AUX 1 AUX 2

24V

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V 24V

SHR

+ -

MOTHER BD CCM

RET

SYSTEM POWER

24V

RET

24V

RET

24V

BAT

DC IN 2

RS485 KIDDE-FENWAL, INC.

ASHLAND, MA 01721

W2 W3

TBL RELAY

06-129562-001
RET 24V RET 24V

NO

NC

A W4 S1 2 1 S3 S2 S2 2 1

DS1

24V

RET

SHR

AC OUT 1 2 AC IN DC IN 1

L N L G N L

R
W1 TB8 TB9 TP3 TP4 F1
RET RET 24V 24V SHR

R
MOTHER BD CCM
RET 24V RET 24V

+ -

SYSTEM POWER

RET

24V

BAT

DC IN 2

RS485 KIDDE-FENWAL, INC.

ASHLAND, MA 01721

W2 W3

TBL RELAY

06-129562-001
RET 24V RET 24V

NO

NC

A W4 S1 2 1 S3 S2 S2 2 1

DS1

24V

RET

SHR

AC OUT 1 2 AC IN DC IN 1

L N L G N L

R
W1 TB8 TB9 TP3 TP4 F1
RET RET 24V 24V SHR

R
MOTHER BD CCM
RET 24V RET 24V

+ -

SYSTEM POWER

RET

24V

BAT

DC IN 2

RS485 KIDDE-FENWAL, INC.

ASHLAND, MA 01721

W2 W3

TBL RELAY

06-129562-001
RET 24V RET 24V

NO

NC

A W4 S1 2 1 S3 S2 S2 2 1

DS1

24V

RET

SHR

AC OUT 1 2 AC IN DC IN 1

L N L G N L

W1

TB8

TB9

7-6

TP3

TP4 F1

SYSTEM POWER

BAT

DC IN 2

INSTALLATION PROCEDURE FOR RX/TX MODULE (MULTI-LOOP ONLY)

R
RET RET 24V 24V SHR

R
RET 24V RET 24V

+ -

RET

24V

The following paragraph provides the step-by-step procedure for replacing the RX/TX module. Refer to Figure 7-5. Ensure the RX/TX jumpers are set properly during the procedure. Verify that the settings of the jumpers on the RX/TX Module conform to the wiring style of the system being installed. The RX/TX is shipped from the factory programmed for Style 6 wiring style. Refer to Drawing No. 06-235443-002, in Appendix I, which is the installation drawing which shows the jumper locations on the RX/TX module. The settings are used to set the wiring style ( 4, 6 or 7), 7 being used with loop isolators. Jumpers on the RX/TX Module are noted by JP x and Wx (x = a single digit) call-outs on the module board. Table 7-1 lists the types of allowable configurations you can select along with their respective jumpers.

August 1999

7-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
NOTE: Since the RX/TX's are not addressed by switches the slot that they are installed in will become there address. Example: A RX/TX installed in JP1 on the multi-loop motherboard will become RX/TX 1, Loop 1. If the same RX/TX was changed into JP4, the address would become RX/TX 4, Loop 4.

7-7

INSTALLATION OF I/O MODULES

The I/O modules can be inserted into the motherboard in any order. The CCM automatically reads the I/O modules type and address upon registration. However, it is recommended that you insert modules performing like functions adjacent to each other to facilitate identification and field wiring runs. After powering up the system, you can request a list of I/O Module assignments from the system menu to verify their registration and accuracy of module address(s). CAUTION All personnel installing or servicing PEGAsys equipment must wear a grounding strap when working in the Central Control panel to avoid generating static electricity which can destroy integrated circuits. Input / Output Module printed circuit boards are shipped in anti-static plastic bags and should be kept in these bags until you are ready to install them. When you remove these circuit boards from the Motherboard, they should be replaced in to the appropriate bags. NEVER PACK THESE BOARDS IN STYROFOAM OR PLASTIC PELLETS. WARNING Input/Output Modules should never be installed in a powered-up system. Always disconnect both AC and battery power before installing or removing I/O Modules. To remove a I/O module from the system; secure power, remove terminal block from module, remove the two mounting screws and pull out the module. The following paragraphs describe the installation procedure for each available I/O module type.

Figure 7-5. Installation for Multi-Loop Table 7-1 RX/TX Configuration Selection

Jumper

Style 4

Style 6

Style 6 W/Loop Isolator Shorted Open Open

Style 7

W1 & W2 JP 2 JP 3

Open Shorted Shorted

Shorted Shorted Shorted

Shorted Open Open

NOTE: Style seven (7) requires the use of loop isolators, the RX/TX module requires the use of one (1) P/N 74200012-001 isolator module to operate in the Style 7 configuration. a. b. c. d. Remove RX/TX module from packing and inspect for physical damage. Ensure jumper configuration is set. Refer to Table 7-1 setting per wiring style used. Install loop isolator, P/N 74-200012-001, if used. Connect 24VDC wiring from terminal block (TB1-TB8) to 24VDC input plug J1. The terminal block which will be used to power the RX/TX will be dependant upon which slot the RX/TX will be installed into. Install the short 6 conductor cable from the RS-232 port on the RX/TX to either RJ12 sockets JP1-JP8. The socket selected is dependant upon which slot the RX/TX will be installed into. Place the RX/TX against the mounting bracket, in the PEGAsys, over the desired slot to be placed in. Install the two mounting screws and tighten until snug. Removal of the RX/TX would be in the reverse order.

7-7.1

Signal Audible Output Module

The following paragraph provides the step-by-step procedure to install a signal audible output module into the PEGAsys system. a. b. c. Remove the signal audible output module from packing and inspect for physical damage. Set address switches. Refer to drawing 06-235371-006 in Appendix I for address switch settings. Set jumpers W1-W3 for appropriate Y/Z wiring styles (refer to Drawing No. 06-235443-006 in the back of the manual for jumper settings). Cut jumper between W9 & W10 if using an auxiliary 24VDC power input. Install module onto the motherboard. Ensure the connector mates properly. Insert and tighten mounting screws. Refer to appropriate Figure 5-1 or 5-2.

e.

f.

d. e. f.

g.

76-100016-001

7-3

August 1999

PEGAsys
7-7.2 Relay Output Module
e. f. g.

Intelligent Suppression Control/Fire Alarm System Set jumpers in accordance with Drawing No. 06-235443003 (located in the back of this manual). Install module in the desired position on the back plate of the main or extension enclosure. Insert and tighten the four mounting screws/nuts into the four corners of the mounting plate.

The following paragraph provides the step-by-step procedure to install a relay output module into the PEGAsys system. a. b. c. d. Remove the relay output module from packing and inspect for physical damage. Set address switches. Refer to Drawing No. 06-235443007 in Appendix I for address switch settings. Install module onto the motherboard. Ensure the connector mates properly. Insert and tighten mounting screws. Refer to appropriate Figure 5-1 or 5-2.

7-7.7

Power Supply/Charger Assembly, Expansion Enclosure

The following paragraph provides the step-by-step procedure to install a power supply/charger assembly into the expansion enclosure. a. b. c. d. Remove the power supply/charger assembly from packing and inspect for physical damage. Set address switches. Refer to Drawing No. 06-235443003 in Appendix I for address switch settings. Identify module revision by referring to Figures 3-5 and 36. Ensure the wiring connections between the switching power supply (Aux. Power Supply) and monitor module (Main Power Supply) are accomplished in accordance with the appropriate Figure, Figure 7-8 or 7-9.
WHT BLK/WHT

7-7.3

Agent Release Module

The following paragraph provides the step-by-step procedure to install a agent release module into the PEGAsys system. a. b. c. Remove the agent release module from packing and inspect for physical damage. Set address switches. Refer to drawing 06-235443005 in Appendix I for address switch settings. Set switches S3 & S4 for solenoid or initiator activation (refer to drawing 06-235443-005 in the back of the manual for switch settings). Cut jumper between W1 & W2 if using an auxiliary 24VDC power input. Install module onto the motherboard. Ensure the connector mates properly. Insert and tighten mounting screws. Refer to appropriate Figure 5-1 or 5-2.

d. e. f.

L
attribute ?

N
attribute ?

attribute ?

7-7.4

City-Tie Output Module

The following paragraph provides the step-by-step procedure to install a city tie output module into the PEGAsys system. a. b. c. d. Remove the agent release module from packing and inspect for physical damage. Set module configuration. Refer to drawing 06-235443-008 in Appendix I. Install module on the motherboard. Ensure the connector mates properly. Insert and tighten mounting screws. Refer to appropriate Figure 5-1 or 5-2.

MAIN POWER SUPPLY (76-100009-001)

AUXILIARY POWER SUPPLY (76-100009-002)

attribute ?

7-7.6

Power Supply/Charger Assembly

The following paragraph provides the step-by-step procedure to install a power supply/charger assembly into the PEGAsys system. a. b. c. d. Remove the power supply/charger assembly from packing and inspect for physical damage. Set address switches. Refer to drawing 06-235443-003 in Appendix I for address switch settings. Identify module revision by referring to Figures 3-5 and 36. Ensure the wiring connections between the switching power supply (Aux. Power Supply) and monitor module (Main Power Supply) are accomplished in accordance with the appropriate Figure, Figure 7-6 or 7-7.
7-4

Figure 7-6. Power Supply/Charger (Rev A), Wiring Diagram

August 1999

attribute ?

SPV

attribute ?

24V

RET

AC OUT 2 1
attribute ?

AC IN

DC IN 1

SHARE 24V

RET RET

ORN RED RED BLK BLK

DC IN 2

WHT BLK/WHT

BLK BLK RED RED ORN

76-100016-001

Intelligent Suppression Control/Fire Alarm System


WHT BLK/WHT ORN RED RED BLK BLK VIO
SHARE SPV
N L N L
attribute ?

PEGAsys
g. Insert and tighten the four mounting screws into the four corners of the mounting plate.

Table 7-2. Aux. Power Supply Module Connections to Rev A, Main Power Supply/Charger Assembly
Aux. Power Su p p l y White Function AC input (Neutral) AC Input (Hot) DC Output (Pos.) DC Output (Neg.) Share M ain Supply TB13 (N) TB13 (L) TB9 (24VDC) TB8 (Ret) TB9 (SHR)

N
attribute ?

MAIN POWER SUPPLY (76-100009-010)

AUXILIARY POWER SUPPLY (76-100009-002)

Figure 7-7. Power Supply/Charger (Rev C), Wiring Diagram e. f. Set jumpers in accordance with drawing 06-235443-003 (located in the back of this manual). Install module in the desired position on the back plate of the expansion enclosure.

attribute ?

attribute ?

attribute ?

attribute ?

attribute ?

attribute ?

ORN RED RED BLK BLK

Figure 7-8. Power Supply/Charger (Rev A), Wiring Diagram for Expansion Enclosure

attribute ?

attribute ? attribute ?

attribute ? attribute ?

MAIN POWER SUPPLY (76-100009-010)

attribute ? attribute ?

attribute ? attribute ?

attribute ? attribute ?

attribute ? attribute ?

Figure 7-9. Power Supply/Charger (Rev C), Wiring Diagram for Expansion Enclosure
76-100016-001 7-5 August 1999

attribute ? attribute ?

DC IN 2

attribute ?

SPV

RET

24V

attribute ?

24V

RET

AC OUT 2 1
attribute ?

AC IN

DC IN 1
attribute ?

DC IN 2

attribute ?

Black / White Red Black Orange

Table 7-3. Aux. Power Supply Module Connections to Rev C, Main Power Supply/Charger Assembly
WHT BLK/WHT BLK BLK VIO RED RED ORN

Aux. Power Supply White Black / White Red Black Violet Orange

Function AC input (Neutral) AC Input (Hot) DC Output (Pos.) DC Output (Neg.) Supervision Share

M ain Supply TB13 (N) TB13 (L) TB9 (24VDC) TB8 (Ret) TB8 (SPV) TB9 (SHR)

AC OUT 1 2

L N L G

WHT BLK/WHT

MAIN POWER SUPPLY (76-100009-001)

24V

RET

AUXILIARY POWER SUPPLY (76-100009-003)

AC IN DC IN 1

SPV

N L

RET

RET

24V

SHARE

24V

RET

SPV

SHARE 24V

RET

SPV

AC OUT 1 2 AC IN DC IN 1 DC IN 2

L N L N G

WHT BLK/WHT

ORN RED RED BLK BLK VIO

AUXILIARY POWER SUPPLY (76-100009-003)

PEGAsys
7-7.8. Power Supply Communication Connections 7-9

Intelligent Suppression Control/Fire Alarm System

Both Rev. A & C communicate with the CCM over the I/O bus of the PEGAsys system. To that end, there are different ways of connecting these components. The power supply unit in the main enclosure of the PEGAsys system communicates with the CCM over a short phone style cable. The I/O bus extends out of the power supply when needed, i.e., a motherboard installed or other power supplies installed in expansion enclosure without a motherboard. These two examples are accomplished as follows: 1. Power supply in main enclosure to motherboard in main enclosure; A flat six conductor phone type cable is attached to CON 2 of power supply and then inserted into the RJ12 jack on the motherboard labeled I/O buss. Remove jumper W4 to enable the terminating resistor on the motherboard, the terminating resistor is used to balance the RS485 communications. Power supplies installed in expansion enclosure without a motherboard can use the RS-485 terminal block (TB1). This connection allows the installer to connect a twisted pair AWG-18 cable to terminals A & B of TB1 on the power supply in the main enclosure and connect to the same terminals on the power supply in the expansion enclosure, as shown in the following diagram. This connection must be daisy chained to other power supplies in the expansion enclosure, if installed. Jumper W4 must be removed from all power supplies in line except the last power supply unit in the expansion enclosure. This will maintain the terminating resistor at the end of the RS-485 circuit, which is required to ensure proper operation of the RS-485 communications.

INSTALL AND CONNECT DC POWER

Space is provided within the Central Control Panel for two 12V 33AH sealed lead acid batteries used for 24 hour standby operation.

7-9.1

Battery Enclosure

A separate UL Listed battery enclosure, shown in Figure 7-10, (P/N 76-100010-001) is used to house up to two 12V, 40AH, sealed lead-acid batteries. The enclosure is designed to be surface mounted using only hardware similar to that used on the CCP (See Paragraph 7-3) and must be mounted within 100 feet of the panel. NOTE: Wiring for the batteries to the power supply must be sized accordingly to prevent unacceptable voltage drops.

2.

7-9.2

Batteries

Refer to Appendix A for required system power calculations. Refer to Appendix E for FM Pre-Action/Deluge sprinkler requirements for 90-hour standby periods. Recommended battery manufacturers and models are: Standby Time 24 Hours 60 Hours 90 Hours Battery Panasonic LCR 12V 17AP,17 AH (P/N 06-115915-046) Power Sonic 12330, 33 AH (2 sets) (P/N 89-100052-001) Power Sonic 12330, 33 AH (3 sets) (P/N 89-100052-001)

7-8

CONNECTING AC POWER

AC power must be provided to the Central Control Panels internal power supply using three conductors. The AC power cable is to be run through a conduit from a dedicated, 15 amp circuit breaker. The conduit must be attached to the right side of the Central Control Panel enclosure through one of the knockouts near the upper right corner of the enclosure. See Appendix A for AC branch circuit requirements details. WARNING High voltages may be present when connecting AC power to the Central Control Panel. Suitable precautions must be taken to avoid injury. NOTE: All Non-Power-Limited wiring must be routed away from Power Limited wiring by a minimum of 1/4", per NFPA & UL requirements. For Power Limited Circuits use Type FPL, FPLP, or FPLR cable per NEC Article 760. Insure that the circuit breaker at the dedicated AC power source is in the OFF position. Attach the three AC power conductors to TB1 on the Central Control Panels power supply PCB as shown on drawing No. 06-235443-003, in Appendix I.

The batteries should be rated for standby power use and fit within the physical dimensions of the respective enclosure. The batteries must have terminals that accept standard ring-type solderless connectors. CAUTION Do not connect the batteries to the systems power supply at this time. Connect the batteries at the end of the system's installation. Connection to the power supply must be according to drawing 06-235443-003, in Appendix I.

August 1999

7-6

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
circuits (signal & release), using unshielded cable for all circuits is only recommended when all output devices connected are Kidde products. All conduit and conductors must meet NEC, NFPA-72 and any applicable local code requirements. See Figure 7-12 for shielded cable termination. Optionally, the PC line can be installed in a separate conduit as shown previously, thus allowing the PC line to remain straight lay wire.

Figure 7-10. Battery Enclosure Figure 7-11. Conduit to CCP

7-10

FIELD DEVICE CONNECTION TO RX/TX MODULE

Field devices connect to terminal block (TB1) located on the PEGAsys Systems Receiver/Transmitter (RX/TX). The cable connecting the field devices to the RX/TX module provides power and bidirectional communications to the loop devices. One RX/ TX module can support up to 255 SmartOne addressable field devices. These 255 addresses can be any mixture of intelligent loop device inputs and outputs without restriction to amounts of either inputs or outputs. NOTE: All Non Power Limited wiring must be routed away from Power Limited wiring by a minimum of 1/4", per NFPA & UL requirements. For Power Limited Circuits use Type FPL, FPLP, or FPLR cable per NEC Article 760. Figure 7-12. Shielded Wire to CCP NOTE: All new RCUs are shipped from Kidde with their address set to 000. This address is reserved for unregistered devices and cannot be used as a registered address. You must connect unaddressed devices to the RX/TX Module one at a time in order to address them. Otherwise you may pre address devices using the hand held device programmer (P/N 74-200013-001) and connect multiple pre-addressed loop devices to the RX/ TX PC line at the same time. Table 7-1 lists the types of allowable configurations you can select along with the respective jumper settings for those configurations. As described in this chapter the PC line can be configured in Style 4, 6, or 7. Each Style is represented in Figures 7-13 through 7-16. Style 4 configurations allow T-tapping. T-tapping is only limited by sound installation techniques.

7-10.1 Wiring the RX/TX PC Line


The RX/TX PC line uses Broadcast Indexing Protocol (BIP) for communications with intelligent loop devices. The PC Line may be configured in NFPA-72, Style 4, 6, or 7. The PC Line is capable of supporting 255 intelligent loop devices on a 2-wire loop. In retrofit applications, existing wiring can be used as long as it meets NEC 760 and NFPA 72 requirements. When installing new wiring or using existing wiring it is necessary to check line resistance and capacitance. Total line resistance can not be greater than 26 Ohms, and capacitance can not exceed 1.0 microFarad. Kidde recommends that you use No. 18 AWG minimum wiring as the connection cable between the RX/TX Module and the field devices The PC line to the loop devices can be run in conduit to the Central Control Panel cabinet. The conduit, if used must be attached through any convenient Central Control Panel enclosure knockout. Route the connection cable to TB1 on the RX/ TX PCB, and insert the end of each connection cable wire into its proper TB1 slot and tighten the slot screws firmly. See Figure 7-11. In retrofit applications where the PC line of the RX/TX may be mixed in an existing conduit with appropriately loaded output
76-100016-001 7-7

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

Figure 7-13. Style 4, RX/TX PC Line Connections In the Style 6 wiring, configuration the RX/TX automatically transmits data and power bidirectionally when a break in the PC line wiring occurs. If the break is in a single conductor, all loop devices will remain fully operational. For Style 6 PC line connections, if a PC line open trouble is encountered, use the system reset switch on the display and control board, or push the bottom button on the RX/TX board, to reset the PC line to normal once the fault is corrected. Figure 7-14. Style 6, RX/TX PC Line Connections Loop Isolator devices are available to support NFPA-72 Wiring Style 7 and would be installed on the PC line of the RX/TX module. Isolator packages are available for electrical box mount (Single Gang), 6 Base mount and RX/TX mount. By "flanking" each group of loop devices with a pair of loop isolators, each zone is protected from opens and shorts. A zone is defined as a group of loop devices. In this style of installation, a short circuit between any two loop isolators will not effect any other zone. The isolators on each side of the short will open the PC line.

August 1999

7-8

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

Figure 7-16. Style 7, RX/TX PC Line Connection

7-11

OUTPUT SIGNAL CONNECTION

The PEGAsys System provides output signals to drive alarm devices and communicate with central stations and control equipment. These outputs are provided on the CCM and optional I/O modules. Figure 7-15. Style 6, RX/TX PC Line Connections with Loop Isolators Figure 7-16 and the RX/TX Module Installation Wiring Diagram (Dwg. No. 06-235443-002), located in the back of this manual, depicts a typical NFPA Style 7 installation. NOTE: The maximum number of loop devices that can be connected between loop isolators is 30. During a short circuit fault condition, the control panel will register a trouble condition for each device located between the two affected loop isolators. Each connection cable to output devices is to be run from the output device circuit to the Central Control Panel. The cable must be brought through any convenient Central Control Panel enclosure knockout. Route each connection cable to the terminal block located on the respective Output Module, insert the end of each connection cable wire into its proper terminal block slot, and tighten the slot screws firmly. Instructions for connecting output devices are provided on their respective Installation Wiring Diagrams located in the Appendix I of this manual. Refer to the respective manufacturers literature for specific installation instructions of output devices. NOTE: All Non Power Limited wiring must be routed away from Power Limited wiring by a minimum of 1/4", per NFPA & UL requirements. For Power Limited Circuits use Type FPL, FPLP, or FPLR cable per NEC Article 760.

76-100016-001

7-9

August 1999

PEGAsys
7-12 EXTERNAL POWER FAILURE INDICATOR CONNECTION

Intelligent Suppression Control/Fire Alarm System

7-14.1 Setting and Adjusting Smoke and Heat Detector Sensitivity Procedure
The step-by-step procedure to perform the setting sensitivity test follows: a. Access the PEGAsys system menus by: (1) Press 0 (zero) key. Verify that the display reads:

The PEGAsys System provides a 2 A @ 30 VDC SPDT relay on the power supply control unit that de-energizes (normally powered) in the event of a power supply monitor trouble - troubles include: AC Power Failure 24 VDC Power Supply Failure Battery Failure Ground Fault Communications Failure

PLEASE ENTER PASSWORD


(2) Type in the Level 2 password. (3) Press the return () key. Verify that the display reads:

The power supply trouble relay is normally powered so that in the event of power failure the relay will transfer to the normally closed position. The contact can be used to signal an external power supply trouble indicator. The connection cable to an external power supply trouble indicating device is to be run through a conduit from the indicating device to the Central Control Panel. The conduit must be attached to any convenient Central Control Panel enclosure knockout. Connect cable to TB1 on the Central Control Panels power supply PCB as shown in Figure 3-6.

1:ISOLATE 3:SET
b.

2:LIST 4:TEST

Select the Detector Sensitivity by typing in 3-3-2. Verify that the display reads:

1:IONIZATION 3:THERMAL
c.

2:PHOTOELECTRIC (<) to return

Select the desired detector style which is to have its sensitivity adjusted. After type selection, the system display:

SET DETECTOR SENSITIVITY DETECTORS FROM _ _ _ _ TO _ _ _ _


NOTE: The user would enter the address range of the detectors to be adjusted. The range can be from 1 to 255. The system will adjust the sensitivity of all the specified type of detectors which were previously chosen (Ion, Photo or Heat) within the range. d. Press the return pushbutton and the display will read:

7-13

DETECTOR INSTALLATION

Refer to the SmartOne Smoke and Heat Detector Installation Sheet (74-212) for installation instructions. Also, refer to Chapter 2, Paragraph 2-8.6 for setting addresses and registering RCUs.

SET DETECTOR SENSITIVITY PREALARM _._ (0.2 -3.0 / FT)


TOLERANCE RANGES Device Ionization Photoelectric Device Thermal e. Open Area 0.5 - 1.5%/FT 0.2 - 3.5 %/FT 50-FT spacing 80 - 155 F High Velocity 0.5 -1.0 %/FT 0.2 - 2.0 %/FT 70-FT Spacing 80 - 145 F

7-14

SETTING AND ADJUSTING SMOKE & HEAT DETECTOR SENSITIVITIES

Setting the sensitivity of SmartOne ionization and photoelectric smoke detectors and heat detectors is accomplished by setting the threshold alarm and pre-alarm smoke density levels. The SmartOne smoke detectors (Ionization and Photoelectric) were previously programmed for a device application during the registration process. The smoke detectors have specific sensitivities for particular applications. There are 3 applications which represent the majority of detector use: Open Area, Open Area (High AirFlow) and Duct. The sensitivity adjustment is accomplished in one of two ways: 1. Smoke & Heat Detector Configuration. During the process of configuring the system using the PCS program, the operator selects the application of the detector and adjusts the settings of the alarm and pre-alarm values within the range for the application chosen, or accept the default values for the application. 2. Level Setting Operation. This procedure is selected from the menus. This method is generally used for systems which have been installed and operational for a period of time. It should only be used if there is a need to change the sensitivity of the device.
7-10

This prompt asks the user for the Pre-alarm level for the detector(s) to be set. Key in the desired pre alarm level and press the return key. After pressing return the display will read:

SET DETECTOR SENSITIVITY ALARM _._ (0.5 -3.0 / FT)


TOLERANCE RANGE Device Ionization Photoelectric Open Area 0.5 - 1.5%/FT 0.5 - 3.5 %/FT High Velocity 0.5 -1.0 %/FT 0.5 - 2.0 %/FT

August 1999

76-100016-001

Intelligent Suppression Control/Fire Alarm System Device Thermal f. 50-FT spacing 135 - 155 F 70-FT Spacing 135 - 145 F d. This prompt asks the user for the alarm level for the detector(s) to be set. Key in the desired alarm level and press the return key. After pressing return the display will read: e. f. c.

PEGAsys
CCMs configuration jumpers configured correctly to insure proper operation of the programmable (signal / release) output (MP1). Optional Motherboard if installed, is connected to the CCM (I/O bus) and System Power Supply (24 VDC). RX/TX Module is connected to the CCM (RJ-12) and system power supply (24 VDC). Output Modules if used, are installed in the Motherboard, addressed correctly, configured for appropriate mode of operation and their external wiring is connected correctly. Perform the Power-Up procedure in Chapter 4, Paragraph 4-5. Refer to Chapter 2 for system operations and programming.

LEVELS SET ON XX DETECTORS


g. This message verifies that the desired sensitivity adjustments were done on XX amount of detectors. The sensitivity of all specified detectors (depending on which type was previously selected) will be set in the previous procedure.

g. h.

7-15

ADDRESSABLE CONTACT INPUT DEVICE INSTALLATION

7-18

CONNECTION OF PERIPHERALS

The Addressable Contact Input Devices are designed to be installed in a North American 2-1/2 in. (64 mm) deep one-gang box, or a standard 4 in. square box 1-1/2 (38 mm) deep with a one-gang blank cover. The AI terminal block will accept #14, #16, and #18 AWG wire (1.5, 1.0, and 0.75 mm2 respectively) with size #18 being a minimum requirement. Refer to the wiring the diagram in Appendix I for specific connection information. Also refer to Chapter 2, Paragraphs 2-8.6 and 2-8.7 for setting addresses and other parameters. The installation must comply with national and local electrical codes.

The following paragraphs will describe how to connect a terminal or personal computer and a printer.

7-18.1 Connecting a Terminal or Personal Computer


A UL Listed EDP terminal or computer can be connected to the systems RS-232 port. A 6-wire RJ-12 type modular phone jack (PC port), located on the CCM, provides easy connection. The terminal or computer connection cable must have a RJ-12 type modular phone plug that connects to the CCM (use P/N 74-100016-003, for a DB9 connector for laptops, or P/N 74100016-001 for a DB25 connector for personal computers). The connector at the terminal end must be of the type required by the terminal device. Route the connection cable to one of the RS-232 modular plug into the jack until it snaps into place. The terminal or computer must be located in the same room as the Central Control Panel. The parameters and connections for the RS-232 printer port are as follows: PARAMETERS 9600 Baud 8 Data Bits 1 Stop Bit No Parity NOTE: These parameters are fixed and not adjustable. PIN and FUNCTION 1 2 3 4 5 6 TX Signal Ground RTS CTS N/C RX

7-16

ADDRESSABLE RELAY OUTPUT DEVICE INSTALLATION

The Addressable Contact Output Devices are designed to be installed in a North American 2-1/2 in. (64 mm) deep one-gang box, or a standard 4 in. square box 1-1/2 (38 mm) deep with a one-gang blank cover. The AI terminal block will accept #14, #16, and #18 AWG wire (1.5, 1.0, and 0.75 mm2 respectively) with size #18 being a minimum requirement. Refer to drawing number 06-234563-001 located in Appendix I, for specific connection information on both devices. Also, refer to Chapter 2, Paragraphs 2-8.6 and 2-8.7 for setting addresses and other parameters. The installation must comply with national and local electrical codes. NOTE: All Non Power Limited wiring must be routed away from Power Limited wiring by a minimum of 1/4", per NFPA & UL requirements. For Power Limited Circuits use Type FPL, FPLP, or FPLR cable per NEC Article 760.

7-17

INSTALLATION CHECKOUT

7-18.2 Connecting a Printer


The RS-232 printer port of the CCM is a supervised connection. The installer must enable the printer port for operation. The enabling or disabling of the printer port would be done by accessing the 1st or 2nd level menu.

Before powering up the PEGAsys for the first time, ensure that the following has been completed: a. b. Central Control Module (CCM), RX/TX Module and System Power Supply are secured to the back of the enclosure. CCM is connected to the RX/TX Module, Display Assembly, System Power Supply (I/O bus and 24 VDC), and Remote RS-232 peripheral(s) if any.

76-100016-001

7-11

August 1999

PEGAsys
A simple connection cable is all that is needed to connect the serial printer to the RS-232 port of the CCM. The following diagram represents the cable. CCM TX Sig. Gnd. RTS CTS* N/C RX PIN 1. 2. 3. 4. 5. 6. PRINTER RX (receive data) Sig. Gnd. DTR*

Intelligent Suppression Control/Fire Alarm System

* +8 to +12 VDC signal needed for supervision if using a graphic annunciator.

Figure 7-17. CCM Printer Port

August 1999

7-12

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX A POWER SUPPLY REQUIREMENTS

A-1

AC BRANCH CIRCUIT

The PEGAsys fire alarm/suppression control system requires connection to a separate dedicated AC branch circuit (120 or 240 VAC), which must be labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the protected premises. No other equipment may be powered from the fire-alarm branch circuit. The branch circuit wire must run continuously, without any disconnect devices, from the power source to the fire alarm/suppression control panel. When multiple power supplies are installed in the system enclosure(s) they must all be fed from the same circuit. Over-current protection for this circuit must comply with Article 760 of the National Electric Code, NFPA-72 as well as applicable local codes. Use a minimum of # 14 AWG with 600-volt insulation for this branch circuit. Table A-1: AC Branch Circuit Requirements (120 VAC)

Device Type

Number of Devices 1 X

Current Draw (Amps) 1.9 =

Total Current per Device 1.9

Control Panel AuxiliaryPower Supply or Module

1.9 Sum column for AC Branch Current required

Amps

NOTE:

Each main power supply and power supply module added to the system would increase the AC requirement by 1.9 Amps (max.) Table A-2: AC Branch Circuit Requirements (220 VAC)

Device Type

Number of Devices 1 X

Current Draw (Amps) 0.95 =

Total Current per Device 0.95

Control Panel AuxiliaryPower supply

0.95 Sum column for AC Branch Current required

Amps

NOTE:

Each main power supply and power supply module added to the system would increase the AC requirement by 0.95 Amps (max.)

76-100016-001

A-1

August 1999

PEGAsys
A-2 SYSTEM STANDBY POWER REQUIREMENTS

Intelligent Suppression Control/Fire Alarm System

The control panel provides regulated power for operating external devices, system operation, and standby battery charging. The power for operating external devices is expandable. When using additional main power supplies in expansion cabinets, each supply must be evaluated for its loading in the same way as the primary power supply in the main cabinet. NOTE: Use Table A3 (Standby or non-alarm) to determine main system power supply and any installed auxiliary power module standby current requirements. Table A-3: Standby Power Requirements (24 VDC)

Module / Device Central Control Module RXTX module Power supply Monitor Auxiliary Output 1, Max 1.5A (See Notes 1 & 2) Auxiliary Output 2, Max 1.5A (See Notes 1 & 2) Multi-Loop Mother Board Signal Audible Output Module Relay Output Module City Tie Output Module Agent Release Output Module FIELD DEVICES Ionization Detector Photoelectric Detector Addressable Contact Input Addressable Contact Output Loop Isolators

Standby Current(Amps) 0.070 0.035 0.060 X X X X X 0.035 0.025 0.010 0.030 0.065 X X X X X X 0.000400 0.000405 0.000310 0.000330 0.001 X X X X X

Module / System 1 = = = = = = = = = = = = = = = =
Sum Column for Standby Load (Notes 2)

Maximum Standby Current (Amps) 0.070

Amps

NOTE:

1. Auxiliary Outputs and each must be considered for total standby alarm loading of the system power supply. 2. Use of auxiliary 24 VDC outputs of during standby operation must not cause the calculated standby current of the system to exceed its rated maximum as defined in the Table A-6.

August 1999

A-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

A-3
NOTE:

SYSTEM ALARM POWER REQUIREMENTS


Use Table A4 (Alarm ) to determine main system power supply and any installed auxiliary power module combination, alarm current requirements. When using additional main power supplies in expansion cabinets, each supply must be evaluated for its own loading in the same way as the primary power supply in the main cabinet. Table A-4: Alarm Power Requirements (24 VDC)

Module / Device Central Control Module CCM MP01 and MP02 Output (See Note 1) RXTX Module Power Supply Monitor Auxiliary Output 1, Max 1.5A (See Note 2) Auxiliary Output , Max 1.5A (See Note 2) Multi-Loop Mother Board Signal Audible Output Module Signal Module Outputs (See Note 3) Relay Output Module City Tie Output Module Agent Release Output Module Agent Release Module Signal Circuit (See Note 5) Agent Release Module Signal Circuits (Note 4) FIELD DEVICES Ionization Detector Photoelectric Detector Addressable Contact Input Addressable Zone Monitor Addressable Contact Output Loop Isolators (Active)

Alarm Current (Amps) 0.210 X X 0.035 0.060 X X X X .035 0.135 X X X 0.075 0.080 0.150 X X X X X X 0.000440 0.000445 0.000380 0.000400 0.000350 0.007 X X X X X X

Module / System 1 =

Maximum Alarm Current (Amps) 0.210

= = = = = = = = = = = = = = = = = = =
Sum Column for Alarm Load

Amps

NOTE:

1. Central Control Module (CCM) Alarm condition power requirements must be evaluated for loading of the signaling devices. Each signal circuit can provide up to 2 amps of 24 VDC power for signaling device use. 2. Auxiliary Outputs would have to be considered for total alarm loading of the system power supply. 3. Each Signal output modules alarm condition power requirements must be evaluated for loading of the signaling devices. Each signal circuit can provide up to 2 amps of 24 VDC power for signaling device use. There are a total of 4 signal circuits per module. 4. Each Agent Release module contains three signaling circuits which must be evaluated for loading. Each signal circuit will provide up to 2 amps of 24 VDC power for signaling device use. There are a total of 3 signal circuits per module. 5. When using constant power solenoids, the current draw of the solenoid must be added in the calculation. Momentary solenoids and initiators are negligible in there current draws and do not need to be added into the total calculation.

76-100016-001

A-3

August 1999

PEGAsys
A-4 CALCULATING BATTERY SIZE REQUIRED

Intelligent Suppression Control/Fire Alarm System

Table A-5 sums the standby and alarm loads to arrive at the battery size, in amp hours (AH), needed to support the control panel. There is a maximum battery size which the system power supply (P/N 76-100009-010) is capable of charging. Select batteries which meet or exceed the total amp hours (AH) calculated and are within the acceptable range of the system battery charger output, which is 12 to 99 AH. Using the totals from Table A-3 and Table A-4, complete Table A-5 to determine the total battery (AH) capacity necessary for the power supply. Table A-5: Total Battery Capacity Required
Total Standby Load (From table A-3) ( ) Total Alarm Load(From table A-4) ( ) Required Standby Time (4, 24, 60 or 90) hours ( ) Required Alarm Time (5 min. enter 0.084) (10 Min. enter 0.167) ( ) Total Amp Hours Required (Sum of above) (Derating Factor) X 0.1 Total AH Required (Original AH required + Derating Factor)

NOTE: 1. Main system enclosure can house up to (2) 33 AH batteries (P/N 89-100052-001). If an auxiliary power module is added to the system the batteries must be moved to a separate battery box or secondary enclosure, if used. 2. NFPA 72 - 1996 Protected Premises or Proprietary fire alarm systems require 24 hours of standby power followed by 5 minutes alarm activation. 3. NFPA 72 - 1996 Auxiliary or Remote Station require 60 hours of standby power followed by 5 minutes alarm activation. 4. NFPA 72 - 1996 allow 4 hours of standby battery capacity if there is an automatic starting engine driven generator. 5. NFPA 12, 12A, 12B require 24 hours of standby and five minutes of alarm activation. 6. Factory Mutual requires Pre-action and Deluge systems to have 90 hours of battery standby and 10 minutes of alarm activation.

August 1999

A-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

A-5

POWER SUPPLY/BATTERY CAPACITY.

The system is capable of charging batteries of various capacities up to 99 AH, refer to Table A-6 for details concerning battery capacities and charging capabilities. Table A-6. Battery Capacities
Maximum Available Standby Current Amps (For One Power Supply) 2.5 3.6 N/A 1.2 Not Allowed for 1 Power Supply 0.9 1.4 0.9 Not Allowed for 1 Power Supply 1.6 6.0 7.1 Maximum Available Standby Current Amps (For Two Power Supply)

Battery (Backup Hours) 12 Ah (4 hours) 17 Ah (4 hours) 33 Ah (4 hours) 33 Ah (24 hours) 160 Ah (24 hours) 66 Ah (24 hours) 99 Ah (60 hours) 99 Ah (60 hours) 160 Ah (90 hours)

A-6

POWER REQUIREMENT EXAMPLE


Field Devices: Ten (10), Ionization Detectors Twenty (20), Photoelectric Detectors Ten (10), Heat Detectors Six (6), Addressable Contact Input Devices Four (4), Addressable Contact Output Devices One (1), Signaling Device, connected to MP1 of the CCM

The following power calculations will be based on a the system configuration listed below: Central Control Panel (CCP) with: Central Control Module Two (2), RX/TX Modules One (1), Power Supply Module One (1), Multi-Loop Motherboard Two (2), Signal Output Modules, with signal appliances totaling .800A on each One (1), Output Relay Module One (1), Agent Release Output Module, has a momentary control head on the releasing circuit and signaling appliances totalling 0.5 A.

AC Branch Current Calculation Example: This example is based on the system specified in the previous paragraph. This system current calculation is for a 120VAC main feed. Refer to Paragraph A-1 for additional information.

76-100016-001

A-5

August 1999

PEGAsys
Device Type Control Panel Auxiliary Power Supply Number of Devices 1 (0) X X Current Draw (Amps) 1.9 1.9

Intelligent Suppression Control/Fire Alarm System

Total Current per Device = = 1.9 0

Sum column for AC Branch Current required

1.9 Amps

Main Power Supply Loading Examples: This example is based on the same system as above. Refer to Paragraph A-2 for additional information. Standby or Non-Alarm Power Requirement Calculation

Module / Device Central Control Module RXTX module Power supply Monitor Auxiliary Output 1, Max 1.5A Auxiliary Output 2, Max 1.5A Multi-Loop Mother Board Signal Audible Output Module Relay Output Module City Tie Output Module Agent Release Output Module FIELD DEVICES Ionization Detector Photoelectric Detector Heat Detector Addressable Contact Input Addressable Contact Output Loop Isolators

Standby Current(Amps) 0.070 0.035 0.060 X X X X X 0.035 0.025 0.010 0.030 0.065 X X X X X

Module / System 1 2 1 = = = = = 1 2 1 = = = = 1 =

Maximum Standby Current (Amps) 0.070 0.070 0.060

0.035 0.050 0.010

0.065

0.000400 0.000400 0.000400 0.000310 0.000330 0.001

X X

10 20 10

= =

0.004 0.008 0.004

X X X

6 4

= = =

0.0024 0.0016

Sum Column for Standby Load

0.380 Amps

Alarm Power Requirement Calculation

August 1999

A-6

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
Alarm Current(Amps) 0.210 0.100 0.035 0.060 0 0 0.035 0.135 0.800 0.075 0.080 0.150 0 Using momentary device .500 X X X X X X X X X X X X X X X 0.000440 0.000445 0.000440 0.000380 0.000400 0.007 X X X X X X
Sum Column for Alarm Load

Module / Device Central Control Module CCM MP01 and MP02 Output RXTX Module Power Supply Monitor Auxiliary Output 1, Max 1.5A Auxiliary Output 2, Max 1.5A Multi-Loop Mother Board Signal Audible Output Module Signal Module Outputs Relay Output Module City Tie Output Module Agent Release Module Agent Release Output Circuits Agent Release Module Signal Circuit FIELD DEVICES Ionization Detector Photoelectric Detector Heat Detector Addressable Contact Input Addressable Contact Output Loop Isolators (Active)

Module / System 1 1 2 1 = = = = = = 1 2 total 1 = = = = = 1 1 1 = = = = 10 20 10 6 4 = = = = = = =

Maximum Alarm Current (Amps) 0.210 0.100 0.070 0.060

0.035 0.270 0.800 0.075

0.150 0 0.500

0.0044 0.0088 0.0044 0.0026 0.0018

2.292 Amps

Battery Size Requirement Calculation Example: This example is based on the same system as above. Refer to Paragraph A-4 for additional information.

76-100016-001

A-7

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System Battery Size Requirement Calculation


Total from Standby Power Requirement X Calculation (0.380) Total from Alarm Power Requirement X Calculation (2.292) Required Standby Time (4, 24, 60 or 90) hours (24) Required Alarm Time (5 min. enter 0.084) (10 Min. enter 0.167) (0.084) Total of both sums equals Amp Hours Required (Sum of Above) (Derating factor) X 0.1 Total AH Required (Original total AH required + Derating Factor)

9.12

0.1925

9.312

0.9312

10.24

Example Results: The results of the prior calculations are as follows: a. b. c. d. Current requirement of the 120VAC Main Feed is 1.9 Amps. System Power Requirement when in Standby is 0.380 Amps. System Power Requirements when in Alarm is 2.292 Amps. Battery Size Requirement is 10.241 Amp-Hours. Select 12 AH batteries.

August 1999

A-8

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX B SYSTEM EXPANSION


The PEGAsys system is capable of substantial expansion in the number of RX/TX loops, I/O modules and system output power. The system will support up to 16 I/O modules for single loop and 23 I/O modules for multi-loop - a maximum of 8 of any one type of module. The system power supply monitor module can supervise two power supply units (4 amps each for a total of 8 amps per module) which allows for up to 64 amps of 24 VDC power. The following diagrams will demonstrate the available ways of expanding the system. Figure B-1 shows the single loop PEGAsys system (P/N 76100000-501). This includes the Central Control Module (CCM), Receiver/Transmitter (RX/TX) module, Power Supply/Charger assembly and the system enclosure. The basic system can be expanded as shown in the following sections

SHR

RET

24V

AC OUT 1 2

AC IN

DC IN 1

TB9

24V RET RET

TBL RELAY

C NC

W1

TB8

NO

ASHLAND, MA 01721

KIDDE

PEGAsys

W2 W3

TP4
S1 W4 A B S2 2 1 2 1
24V

RS485 KIDDE-FENWAL, INC.

TP3

S3

+ -

R
MOTHER BD CCM

RET 24V

RET 24V RET

RET

RET

06-129562-001

AUX 1 AUX 2

SHR

RET

24V

AC OUT 1 2

AC IN

DC IN 1

TB9

24V RET RET

TBL RELAY

C NC

W1

TB8

NO

ASHLAND, MA 01721

KIDDE

PEGAsys

W2 W3

TP4

RS485 KIDDE-FENWAL, INC.

S1 W4 A B S2

2 1 2 1

TP3

S3

+ -

R
MOTHER BD CCM

RET 24V

RET 24V RET

RET

RET

06-129562-001

AUX 1 AUX 2

24V

24V

SYSTEM POWER

24V

BAT

F1

DC IN 2

DS1

SHR

Figure B-2. Single Loop with Motherboard Figure B-3 shows the PEGAsys system with an auxiliary power module (P/N 76-100009-002) installed. The auxiliary power supply module provides an additional 4 amps of 24 VDC power for a total of 8 amps for system use. The unit would be installed if the system required more than the base system's 4 amps of 24 VDC power. When the auxiliary module is installed the system batteries are moved to a battery cabinet. P/N 76-100010-001 is an UL listed battery enclosure for use with the PEGAsys. This figure could also be a multi-loop system with the inclusion of the multi-loop motherboard and additional RX/TX loop controllers. Figure B-1. Single Loop Figure B-2 shows the single-loop PEGAsys system with the optional I/O motherboard (P/N 76-100007-001) installed. The I/ O motherboard provides the system with mechanical and electrical interfaces for up to eight I/O modules of any style. The I/O modules are installed by inserting them into the desired motherboard slot and fastening with the two screws provided. The PEGAsys ML (Multi-loop) system (P/N 76-100000-600) looks much the same as the system in Figure B-2 with the exception of the multi-loop motherboard (P/N 76-100017-001) in the place of the basic motherboard (P/N 76-100007-001). The Multi-loop motherboard has the ability to connect up to 8 RX/TX loop controllers, for a maximum of 2040 Intelligent addressable points per system.

76-100016-001

B-1

24V

24V

SYSTEM POWER

BAT

F1

DC IN 2

DS1

SHR

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

SHR

RET

24V

AC OUT 1 2

AC IN

DC IN 1

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

W2 W3

TBL RELAY
NO NC C

06-129562-001

SHR

RET

24V

24V RET RET

DC IN 2

TBL RELAY

TB8

AC OUT 1 2
L N

TB9

AC IN
L G N L

DC IN 1

DS1 NO C NC

SHR

W4 DS1 S2 2 1 S1 2 1

AC OUT 1 2 AC IN

L N N L

L G

TB9

DC IN 2

DS1

W1

F1

SHR
ASHLAND, MA 01721

24V

S3

W2 W3

24V RET RET

RET

TBL RELAY

TB8

NO C NC

SHR RET 24V RET

DC IN 1

AUX 1 AUX 2

KIDDE

PEGAsys

TP4

24V

RS485 KIDDE-FENWAL, INC.

TP3

S3 S1 W4 A B S2 2 1 2 1

+ -

BAT

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V 24V

SHR

RET

SYSTEM POWER

24V

RET

24V

RET

24V

+ BAT

DC IN 2

W1

ASHLAND, MA 01721

W2 W3

F1

R
MOTHER BD CCM

SYSTEM POWER

24V RET 24V

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

KIDDE

PEGAsys

W2 W3

TBL RELAY
NO NC C

06-129562-001

RET 24V RET

TP4

W4 DS1 S2 S1

AC OUT 1 2

RS485 KIDDE-FENWAL, INC.

RET

RET

TP3

24V

24V

S3 S1 W4 A B S2 2 1 2 1

+ -

BAT

2 1

2 1

AC IN

N L

06-129562-001

AUX 1 AUX 2
S3

24V

RET

SHR RET 24V RET

DC IN 1

AUX 1 AUX 2

24V

R
MOTHER BD CCM

RET 24V

SYSTEM POWER

24V

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V 24V

SHR

+ -

RET

SYSTEM POWER

24V

RET

24V

RET

24V

BAT

DC IN 2

RET 24V RET

RET

RET

06-129562-001

AUX 1 AUX 2

24V

24V

Figure B-4. Expanded Single Loop System Figure B-5 shows an expanded PEGAsys system which is capable of having 8 I/O modules of various types and a maximum 24VDC power at 40 amps. This DC power would be hardwired into signal and release modules whose loading would otherwise cause more than 8 amps of 24 VDC current to be drawn from the motherboard during activation. The hardwire option allows the system installer to provide individual modules with their own power source. Refer to the particular modules installation diagram in Chapter 7 and Appendix A for power-supply expansion guidelines.

Figure B-3. System with Auxiliary Power Supply Module Figure B-4 shows an expanded single-loop PEGAsys system which contains two motherboard assemblies, three complete power supply assemblies (24 Amps of 24 VDC power), and up to 16 total possible I/O modules. The I/O bus interconnections between the two motherboards are done using 6 conductors from the I/O bus terminal block on the motherboard in the main enclosure to connect to the same terminal block on the motherboard in the expansion enclosure. This connection allows complete supervision of all I/O modules installed on the second motherboard by the CCM in the main enclosure. 24 VDC power for the motherboard in the expansion enclosure would derive from one of the power supply assemblies installed in that enclosure. A simple two-wire connection is all that would be required. The power supplies need to be tied to the I/O bus for communications purposes. To accomplish this in the above example, the installer would use a two conductor cable to connect the RX/TX of the I/O bus from the motherboard assembly to the power supply. The second power supply could then be daisy chained to the first to complete the communications connections. Auxiliary power supplies in the expansion enclosure can share a set of batteries or could support their own set of batteries separately.

August 1999

B-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
NOTE: One main power supply/charger assembly can be used to charge a common set of batteries. All other power supply/charger assemblies could be connected to the common set of batteries in parallel for backup DC power only. You will also need to disable the charging circuit on the additional power supply/charger assemblies by cutting jumper W1. Be careful not to exceed the maximum charging capacity of the main power supply.

SHR

RET

24V

AC OUT 1 2

AC IN

DC IN 1

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

W2 W3

TBL RELAY
NO NC NC C

06-129562-001

TB9

24V RET RET

TBL RELAY

TB8

NO C NC

DC IN 2

DS1

SHR

W4 DS1 S2 2 1 S1 2 1

AC OUT 1 2 AC IN

L N L G N

W1

F1

24V

S3

DC IN 1

ASHLAND, MA 01721

W2 W3

RET

SHR RET 24V RET

AUX 1 AUX 2

KIDDE

PEGAsys

TP4

RS485 KIDDE-FENWAL, INC.

TP3

S3 S1 W4 A B S2 2 1 2 1

+ -

24V

BAT

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V

SHR

RET

SYSTEM POWER

24V

RET

24V

RET

24V

+ BAT

DC IN 2

R
MOTHER BD CCM

RET 24V

SYSTEM POWER

24V

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

RET 24V RET

W2 W3

TBL RELAY
NO NC NC C

06-129562-001

W4 DS1 S2 2 1 S1 2 1

AC OUT 1 2

L N L

RET

RET

24V

24V

AC IN

06-129562-001

AUX 1 AUX 2
S3

24V

RET

SHR RET 24V RET

DC IN 1

Figure B-5. Expanded Sys. with I/O Modules & P.S.

SHR

RET

24V

TB9

24V RET RET

DC IN 2

AUX 1 AUX 2 06-129562-001 AUX 1 AUX 2 AUX 1 AUX 2 AUX 1 AUX 2 AUX 1 AUX 2 06-129562-001

24V

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V

SHR

+ -

MOTHER BD CCM

RET

SYSTEM POWER

24V

RET

24V

RET

RS485 KIDDE-FENWAL, INC.


A W4 S2 2 1 S1 2 1 S3 B

24V

BAT

DC IN 2

ASHLAND, MA 01721

W2 W3

TBL RELAY
NO
N

NC

DS1

24V

RET

SHR RET 24V RET

AC OUT 1 2 AC IN DC IN 1

L N L G N L

24V

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V

SHR

MOTHER BD CCM

RET

SYSTEM POWER

24V

RET

24V

RET

24V

RS485 KIDDE-FENWAL, INC.


A W4 S2 2 1 S1 2 1 S3 B

+ BAT

DC IN 2

ASHLAND, MA 01721

W2 W3

TBL RELAY
NO
N

NC

DS1

24V

RET

SHR RET 24V RET

AC OUT 1 2 AC IN DC IN 1

L N L G N L

24V

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V

SHR

+ -

RET

SYSTEM POWER

24V

RET

24V

RET

24V

BAT

DC IN 2

Figure B-6 shows a expanded PEGAsys system which could have 16 I/O modules and 56 amps of 24 VDC power. The figure also displays the flexibility to bring all four power supply assemblies in the second expansion enclosure to one set of batteries. In this arrangement one of the four power supplies charges the batteries, and all four receive standby power from the batteries. Each power supply must have its own two conductors connected directly to the battery set to meet code requirements. The three non-charging power supplies must have Jumper W1 cut to disable their charging circuits. Refer to Chapter 7 and Appendix A for more details on power expansion. Figure B-7 shows an expanded PEGAsys ML system which could have up to 8 RX/TX loop controllers and 9 I/O modules installed in the two motherboards. The system also has a maximum 24 VDC power of 24 amps as shown in the diagram. Refer to Chapter 7 and Appendix A for power supply expansion guidelines.

AC OUT 1 2

AC IN

DC IN 1

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

W2 W3

TBL RELAY
NO NC C

06-129562-001

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

W2 W3

TBL RELAY
NO NC C

06-129562-001

DS1
TBL RELAY

SHR

W4

TB8

NO C NC

W4

DS1

AC OUT 1 2

S1 2 1

S2 2 1

DS1

L N N L

AC OUT 1 2

S1

S2

L N

L G

AC IN

2 1

2 1

AC IN

W1

F1

24V

S3

ASHLAND, MA 01721

RET

DC IN 1

24V

S3

W2 W3

SHR RET 24V RET

RET

SHR RET 24V RET

DC IN 1

AUX 1 AUX 2

AUX 1 AUX 2

KIDDE

PEGAsys

TP4

24V

RS485 KIDDE-FENWAL, INC.

TP3

S3 S1 W4 A B S2 2 1 2 1

+ -

BAT

W1

TB8

TB9

24V

W1
TP3 TP4 F1
RET RET 24V SHR RET 24V RET 24V RET 24V

TB8

TB9

+ BAT

SYSTEM POWER

DC IN 2

TP3

TP4 F1

RET

RET

24V

SHR

+ -

RET

SYSTEM POWER

24V

RET

24V

RET

24V

BAT

DC IN 2

R
MOTHER BD CCM

SYSTEM POWER

24V RET 24V

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

W2 W3

TBL RELAY

06-129562-001

MOTHER BD CCM

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

RET 24V RET

W2 W3

TBL RELAY
NO NC C

NO

NC

06-129562-001

W4 DS1 S1 2 1 S2 2 1

AC OUT 1 2 AC IN

W4

L N N

DS1

AC OUT 1 2

S1

S2

L G

2 1

2 1

RET

RET

24V

24V

AC IN

06-129562-001

AUX 1 AUX 2
S3

24V

RET

SHR RET 24V RET

DC IN 1

24V

S3

RET

DC IN 1

Figure B-6. Expanded Sys. with I/O Modules & P.S.

AUX 1 AUX 2

SHR RET 24V RET

AUX 1 AUX 2

24V

W1

TB8

TB9

24V

W1
TP3 TP4 F1
RET RET 24V SHR RET 24V RET 24V RET 24V

TB8

TB9

+ BAT

SYSTEM POWER

DC IN 2

TP3

TP4 F1

RET

RET

24V

SHR

+ -

MOTHER BD CCM

RET

SYSTEM POWER

24V

RET

24V

RET

RS485 KIDDE-FENWAL, INC.


A B

24V

BAT

DC IN 2

ASHLAND, MA 01721

W2 W3

TBL RELAY
NO NC C

06-129562-001
RET 24V RET

W4 DS1 S1 2 1 S3 S2 2 1

24V

RET

SHR

AC OUT 1 2 AC IN DC IN 1

L N N L L

AUX 1 AUX 2 AUX 1 AUX 2

24V

W1

TB8

TB9

TP3

TP4 F1

RET

RET

24V

SHR

+ -

MOTHER BD CCM

RET

SYSTEM POWER

24V

RET

24V

RET

24V

BAT

DC IN 2

RS485 KIDDE-FENWAL, INC.


A B

ASHLAND, MA 01721

W2 W3

TBL RELAY
NO NC C

06-129562-001
RET 24V RET 24V

W4 DS1 S1 2 1 S3 S2 2 1

24V

RET

SHR

AC OUT 1 2 AC IN DC IN 1

L N N L

L G

R
RET 24V RET 24V

SYSTEM POWER

R
W1 TB8 TB9 TP3 TP4 F1
RET RET 24V SHR

+ -

RET

24V

BAT

DC IN 2

76-100016-001

B-3

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

Figure B-7. Expanded ML Sys. with 8 RX/TX & 9 I/O Modules

August 1999

B-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX C RELEASING APPLICATIONS


The PEGAsys system can be used for agent release, pre-action, sprinkler and deluge sprinkler control applications. When used with UL listed, compatible actuating and initiating devices, the PEGAsys system meets the requirements of the following standards: NFPA 12 NFPA 12A NFPA 13 NFPA 15 NFPA 16 NFPA 17 NFPA 17A NFPA 2001 CO2 Extinguishing Systems (High Pressure) HALON 1301 Extinguishing Systems Sprinkler Systems Water Spray Systems Foam-Water Deluge and Foam-Water Spray Systems Dry-Chemical Extinguishing Systems Wet-Chemical Extinguishing Systems Clean-Agent Fire Extinguishing Systems leasing. For complete details refer to the PCS users guide. The following features are supported for releasing functions, with which the system will be compatible.

C-2

ABORT

The abort function is a feature which manually stops a discharge time delay. The PEGAsys supports four styles of aborts, as listed in Table C-1.

C-3

DELAY

The time delay period is an installer programmable value which begins to count down after alarm activation of an initiating device(s) which is protecting the protected area and mapped to the agent-release output. The time delay can be programmed for activation after one or two alarm occurrences.

C-1

PROGRAMMING C-4 SOAK

The PEGAsys system can support up to nine independently controlled releasing outputs (AR1 - AR8 and MP1), which are used to control releasing functions. AR1 - AR8 are the agent release I/O modules, which are inserted into the I/O motherboard and MP1 is the CCM releasing output, which is optionally programmable to be a signal release output. The PCS program is used to program the system for all functions including the re-

The soak function is used to automatically shut off the releasing solenoid at a predetermined time after the mapped inputs activate them. It may be programmed as a 10 minute or 15 minute soak period. This soak function is for use in NFPA 16 applications only.

Table C-1. Abort Styles

Abort Type

Description

Underwriter Laboratories Delay timer continues to count down upon abort activation, and stops at 10 (UL)(Complies with UL second mark until release of abort switch. Upon release of abort switch, 864) timer resumes the countdown starting at 10 seconds. Industrial Risk Insurers (IRI)(Complies with UL 864) Functions in similar manner to the UL-type abort, with the only exception that the abort will only function if held prior to the receipt of the second alarm. Operation of the abort switch, once an alarm exists, changes the delay timer to the selected delay plus an additional 90 seconds. The timer will not start as long as the abort switch is held. Release of the abort switch continues the countdown from the initial value plus the 90 seconds additional delay. Once the delay timer has started, operation of the abort switch restores the timer to its original value. The delay timer will not start as long as the abort switch is held. Release of the abort switch continues the countdown.

New York City

Local Jurisdiction

NOTE: The abort function will not work if a time delay value is not entered in the EOC programming for the hazard. Maximum allowable delay is 60 seconds as allowed by UL864. The abort input is not intended to be used for a service disconnect.
76-100016-001 C-1 August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(+) PC Line In (-)

(+) (-) PC Line Out

PUSH / HOLD

10K ohms P/N 06-129025-003


ALL TERMINALS ARE POWER LIMITED

MODEL AI, N/O CAT. NO. 70-407008-001 SEE INSTALLATION INSTRUCTIONS 06-235578-001 MAX. INSTALL. TEMP. 120F FOR SERVICE SEND TO: KIDDE-FENWAL, INC. 400 MAIN ST. ASHLAND, MA 01721 DATE OF MANUFACTURE:

SmartOne TM

.
SUPPRESSION SYSTEM ABORT

Remote LED (Optional)

Addressable Contact Monitor P/N 70-407008-001

NOTE:

The 10-K ohm resistor must be connected across the abort station Failure to install this resistor will result in a "Trouble Open" message for that monitor.

C-5

SPECIAL MODULE TYPES

The PEGAsys provides specific styles of devices which have special releasing functions, these devices are:

C-5.1

Abort Switch

The abort switch is connected to an addressable contact monitor (P/N 70-407008-001) which is programmed as an abort input, with a selected abort style as explained in Table C-1. The addressable contact monitor would be connected to a listed abort station, such as the Kidde Suppression System Abort switch

(+) PC Line In (-)

10K ohms P/N 06-129025-003


ALL TERMINALS ARE POWER LIMITED

MODEL AI, N/O CAT. NO. 70-407008-001 SEE INSTALLATION INSTRUCTIONS 06-235578-001 MAX. INSTALL. TEMP. 120F FOR SERVICE SEND TO: KIDDE-FENWAL, INC. 400 MAIN ST. ASHLAND, MA 01721 DATE OF MANUFACTURE:

SmartOne TM

Remote LED (Optional)

Addressable Contact Monitor P/N 70-407008-001


Figure C-2. Manual Release Switch NOTE:

The 10-K ohm resistor must be connected across the manual poll station contacts for supervision. Failure to install this resistor will result in a "Trouble Open" message for that contact monitor.
C-2 76-100016-001

August 1999

PC PC PC PC SW SW LED LED (+) (-) (+) (-) A B (+) (-)

PC PC PC PC SW SW LED LED (+) (-) (+) (-) A B (+) (-)

Figure C-1. Addressable Contact Monitor Interconnection contacts for supervision.

P/N 87875201

(P/N 87875201). Figure C-1 shows the interconnection of the addressable contact monitor and the abort station switch.

C-5.2

Manual Release Switch

The manual release switch is an addressable contact monitor (P/N 70-407008-001) which is programmed as an manual release input. The addressable contact monitor would be connected to a listed manual release station such as the Kidde Suppression Agent Release switch (P/N 84-100007-00X). Figure C-2 shows the interconnection of the addressable contact monitor and the manual release switch.

(+) (-) PC Line Out

FIRE ALARM

FIRE ALARM

PUSH PULL

P/N 84-100007-00X

Intelligent Suppression Control/Fire Alarm System

PEGAsys
C-7 PRE-ACTION SPRINKLER APPLICATIONS

C-6 C-6.1

AGENT RELEASE APPLICATIONS CCM Release Output Wiring

The PEGAsys system provides one output on the CCM (MP01, Terminal TB4(A)), is fully supervised and can is defaulted as a release output. Refer to Appendix I, Drawing No. 06-235443001, and to the PCS program users guide for details on the configuration of this output. An example of the CCM releasing circuit wiring is shown in Figure C-3. For wiring details refer to the CCM wiring diagram, Drawing No. 06-235443-001 (Appendix I).

The PEGAsys system can be used to activate and supervise preaction sprinkler and deluge sprinkler systems for protection of facilities. The CCM output (MP1) and agent release output modules (AR1 - AR8) can be programmed for use with most popular sprinkler solenoids. For sprinkler applications the addressable input module P/N 70407008-00x can be used to monitor and supervise any of the following sprinkler type inputs as required for each particular application. Inputs could be air pressure, waterflow, water level (tank), pump running, etc. Refer to Chapter 2 for details on programming the addressable input device for various reporting styles.

Figure C-3. CCM Release Output, Wiring Basics

C-6.2

Release Module Output Wiring

The agent release modules which the PEGAsys system uses to provide the release function offer one release output capable of powering two solenoids simultaneously. Refer to Appendix I, Drawing No. 06-235443-005, and to the PCS program users guide for details on configuration of the release outputs along with all other system parameters. All wiring from the agent release module to the release device is fully supervised, including the actual device in the circuit. Examples of the releasing circuit wiring is provided in figure C-4. For all wiring detail refer to the Release Module wiring diagram, drawing number 06-235443-005 (in Appendix I) for specific wiring details. For a list of approved devices, refer to Table 3-2 in this manual.

Figure C-4. Release Module, Wiring Basics

76-100016-001

C-3

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

C-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX D

Space Reserved for Future Use.

76-100016-001

D-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

D-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX E FACTORY MUTUAL SPRINKLER REQUIREMENTS FOR PRE-ACTION AND DELUGE TYPE SPRINKLER SYSTEMS
Initiating Circuits (RX/TX - PC line) must be configured for Style 6 wiring. Refer to Drawing No. 06-235443-002 for complete RX/TX PC line wiring instructions. Provide 90 hours of standby battery and 10 minutes of alarm operation. Refer to Appendix A. Agent release output can be CCM output MP1 or I/O module agent release module AR1 - AR8. Each output would be required to be configured for solenoid activation. The solenoid output-on time period would need to be set to either 90 seconds or on until reset using the PCS program.

E-1

GENERAL INFORMATION

PEGAsys system installation applications which require Factory Mutual (FM) approval of pre-action and deluge sprinkler systems must conform to the following guidelines. SmartOne Thermal Detectors, Model THD-7252, when used must be installed at 20 Ft. spacings. The pre-alarm and alarm setpoint ranges are as follows: Pre-alarm Alarm 80 to 155 deg F 135 to 155 deg F

76-100016-001

E-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

E-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX F GLOSSARY

Address Addressable Device Addressable Contact Device (ACID) AdministrativeTask AlarmVerification

A fou r d ig it cod e in d icatin g th e ad d ress of a smart or ad d ressab l e d evice. 1st d ig it is th e RX/TX l oop n u mb er an d th e remain in g th ree d ig its are th e d evice n u mb er. A d evice with th e cap ab il ity to au tomatical l y commu n icate its ad d ress an d state via a mu l tip l ex tru n k to a Cen tral Con trol Pan el . An ad d ressab l e d evice wh ich mon itors a stan d ard fire al arm d evice. Two d evice typ es are avail ab l e: Normal l y Op en & Normal l y Cl osed . Rep orts, l ists, statu s, an d oth er h ou sekeep in g fu n ction s of th e Cen tral Con trol Pan el . A p re p rog rammed time d el ay wh ich cau ses th e system to wait for th e verification time d el ay p eriod to el ap se b efore activatin g th e p re p rog rammed al arm ou tp u ts. Meets th e NFPA 72 - 1993 d efin ition . Pertain in g to rep resen tation b y mean s of a con tin u ou s variab l e an d p h ysical q u an tity. For examp l e, to d escrib e a p h ysical q u an tity su ch as vol tag e, %/ft, etc. See Smart Device. An en cl osu re th at h ou ses Cen tral Con trol Mod u l e(CCM), Receiver/Tran smitter Mod u l e (RX/TX), Power Su p p l y, an d op tion al I/O Moth erb oard , Ou tp u t Mod u l es. Th is mod u l e is th e h eart of th e system. It con tain s th e main Cen tral Processin g Un it, Disp l ay Assemb l y, Prog rammab l e Memory, Real Time Cl ock, Watch Dog Timer, two RS-232-C serial p orts, two p rog rammab l e sig n al ou tp u ts an d two Form "C" rel ays. A d evice with two d iscrete states, su ch as a Con tact In p u t or Rel ay Ou tp u t RCUs. Comp u tin g p ower is d istrib u ted to th e actu al real worl d d evice. Th is red u ces th e commu n ication b u rd en on th e l oop , th u s p rovid in g g reater immu n ity to EMI an d RFI. Al l Al arm & Preal arm d ecision s are mad e at th e d evice l evel . Th e CPU in p h otoel ectric or ion ization d etectors measu res an d stores its d etection smoke ch amb er val u e 256 times p er d ay. Th e CPU averag es each d ays val u es an d stores th e d ail y averag e for 30 d ays. Th e d ail y averag e is stored in a scrol l in g fash ion ad d in g th e fin al d ays averag e an d d rop p in g th e averag e th at is 30 d ays ol d . Th e val u es th at are stored refl ect th e u n iq u e en viron men tal con d ition th at th e d etector exp erien ces in d ail y op eration . Th e su m of th e scrol l in g 30 d ays is u sed to estab l ish a referen ce p oin t for smoke d etection u n d er th e u n iq u e en viron men tal con d ition s th at th e d etector exp erien ces. Th is featu re red u ces fal se al arms from en viron men tal in fl u en ces with ou t red u cin g sen sitivity. Th e d isp l ay assemb l y in cl u d es: an in d icatin g 80 ch aracter al p h an u meric d isp l ay, p u sh b u tton switch es to con trol th e system, an d in d icatin g LEDs to d isp l ay system statu s. Th e PEGAsys d isp l ay assemb l y is mou n ted on th e CCM an d it commu n icates with th e Cen tral Con trol Mod u l e. Th e EOC p rog rammin g al l ows comb in in g of in p u ts to ob tain th e d esired ou tp u ts. Th e EOC l an g u ag e is fl exib l e to su it most an y fire al arm / su p p ression ap p l ication .

Analog Analog Input Device Central Control Panel Central Control M odule (CCM ) Digital Device Distributed Intelligence

Drift Compensation

Display Assembly

Event Output Control (EOC)

76-100016-001

F-1

August 1999

PEGAsys
Internal Identifier (I001 - I255)

Intelligent Suppression Control/Fire Alarm System

Symb ol s th at are u sed to n ame or id en tify a comb in ation of in p u ts.(For examp l e 1001 + 1004= I001). An op tion al assemb l y, l ocated in th e Cen tral Con trol Pan el , th at h as th e cap acity for eig h t Ou tp u t Mod u l es. Typ ical Ou tp u t Mod u l es are Rel ay, Sig n al Au d ib l e, Ag en t Rel ease, Dig ital In p u t or Ou tp u t an d In tel l ig en t In terface Mod u l e. A set of b ran ch es formin g a cl osed cu rren t p ath p rovid ed th at th e omission of an y b ran ch el imin ates th e cl osed p ath . A d evice wh ich p rovid es p rotection ag ain st wire to wire sh ort con d ition s on th e RX/TX PC l in e. Con forms to (NFPA Styl e 7.0) Lin e or circu it in tercon n ectin g several d evices from a cen tral p oin t. Th e u se of on e tru n k or p air of wires to commu n icate with on e or more d evices. Th e PEGAsys al l ows 255 d evices to commu n icate on on e tru n k. Smart d evices or smoke d etectors may b e ord ered with an op tion al rel ay th at can con trol extern al d evices su ch as el evators an d n on -emerg en cy p rocess con trol . Ou tp u t Mod u l es, l ocated in th e Cen tral Con trol Pan el en cl osu re, p rovid e real worl d ou tp u t cap ab il ity from th e Cen tral Con trol Mod u l e. Typ ical mod u l es are: Rel ay an d Sig n al Au d ib l e. Memory l ocation s th at are p rog rammab l e b y th e own er to store a 40 ch aracter al p h an u meric d escrip tion of th e l ocation of th e fire d etection d evice. Power an d commu n ication wires orig in atin g from th e RX/TX Mod u l e. Al so cal l ed Sig n al Lin e Circu it (SLC). An Ou tp u t Mod u l e l ocated in th e Cen tral Con trol Pan el en cl osu re th at in terfaces with au xil iary eq u ip men t. Each mod u l e con tain s fou r in d ivid u al p rog rammab l e SPDT 2 Amp 24 VDC rel ays. A total of eig h t Rel ay Ou tp u t Mod u l es may b e u sed in th e system for a total of 32 circu its. An ad d ressab l e or smart fiel d d evice th at p rovid es a rel ay con tact to con trol a d evice su ch as a fan . Typ ical l y mou n ts in a 4 in ch sq u are el ectrical b ox. An ad d ressab l e or smart fiel d d evice. Th e Receiver / Tran smitter mod u l e is l ocated in th e Cen tral Con trol Pan el en cl osu re an d fu n ction s as a d ata tran smission in terface b etween th e Cen tral Con trol Mod u l e an d remote con trol u n its - (RCUs). An ou tp u t mod u l e, l ocated in th e Cen tral Con trol Pan el en cl osu re, th at p rovid es fou r Styl e Z or Styl e Y, 24 V, 2 Amp p ol arized sig n al circu its. Al l circu its are su p ervised for an op en or sh ort con d ition . A maximu m of eig h t mod u l es with 32 circu its may b e in stal l ed in th e PEGAsys system. Smart smoke d etectors (ion ization or p h otoel ectric) measu re smoke l evel every 9 secon d s with in th eir smoke sen sin g ch amb er. After in itail l y d etectin g smoke th e d etector en ters an al ert state wh ere it measu res smoke con cen tration every 2 secon d s. If th e d etector d etects smoke th ree ou t of fou r samp l es, it sen d s a p re-al arm or al arm statu s to th e Cen tral Con trol Pan el . A d evice with th e featu res of an ad d ressab l e d evice b u t ad d ition al l y h as th e comp u tin g p ower to make al arm d ecision s b ased on stored cal ib ration an d en viron men tal d ata, an d con d ition of th e d etector. Al so th e d evice tran smits an d receives an al og val u es. Examp l es wou l d b e p h otoel ectric or ion ization d etectors. A d evice with ou t th e el ectron ics n ecessary to tie d irectl y to th e mu l tip l ex tru n k. It req u ires an ad d ressab l e in p u t or ad d ressab l e ou tp u t d evice to in terface with th e PEGAsys system. (ie..con ven tion al smoke an d h eat d etectors)
F-2 76-100016-001

I/O M otherboard

Loop Loop Isolators M ulti drop Line M ultiplex (Per NFPA-72) Optional Relay

Output M odule

Owner Locations PC Line

Relay Output M odule

Relay Output RCU Remote Control Unit (RCU) RX/TX M odule

Signal Audible Output M odule

Smart SmokeDetector

Smart Device

Standard Fire Alarm Device


August 1999

Intelligent Suppression Control/Fire Alarm System

PEGAsys

State

A code on the display that identifies an RCUs status. There are eight field programmable states a RCU may be programmed to: Alarm, Trouble, Abort, Manual Alarm, Manual Release, WaterFlow, Supervisory and Normal. Provides primary and secondary system power. Stand-by batteries, provide DC voltage to the Power Supply in the event of an AC power failure. The stand-by batteries are located in the Central Control Panel enclosure. See Multi drop Line. Only allowable in Style 4 configuration. A non programmable relay which operates during any system trouble condition. A message on LCD display that identifies the type of device reporting. The message identifies Smoke & Heat detectors and Input and Output RCU devices. See Internal Identifier (I001-I255). This timer senses abnormality in the Central Control Modules CPU. If the CPU is operating normally, it periodically resets the timer. If the timer is not reset, it times out and indicates a CPU error. Percent of smoke obscuration per foot of light.

System Power Supply T-TAP Trouble Relay Type Variable Identifier M odule Watch Dog Timer %/FT

76-100016-001

F-3

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

F-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX G DISPLAY ABBREVIATIONS


Abbreviation 232 A.V. ACK ADDR. ALM AOF BAT. C.L. CD CT DISCON DISP DR EW EX INP IT I/O L9 LEV. LV NA NG NR O.L. Meaning RS-232-C Alarm Verification Acknowledge Address Alarm Alarm Off Battery Combinational Logic Contact Detector Error City Tie Disconnect Panel Display Drift Error EEPROM Write Error External Trouble Input Illegal RCU Type Input / Output Module Line + 9V Trouble Level Line Voltage Trouble NOV RAM Access Error No good Not Registered Owner Location Abbreviation OF OK OP OR OUT P.C. P.S. P.W. POF PRE PRNT PROG R.P. RTC RY SG SH SPV TBL TE TOF TST UK VOLT. ZA Meaning Off All Right Open Optional Relay Output Power Communications Line Power Supply Password Pre-alarm Off Pre-alarm Printer Program Remote Panel Real Time Control I/O Relay Output Module I/O Signal Output Module Short Supervisory Trouble RCU Test No Good Trouble Off RCU Test Unknown Device Connected Voltage Zone Alarm

76-100016-001

G-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

G-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX H INDEX
Subject Page Paragraph
A Accessing the System Menus .......................................................................... 2-4 ................................................... 2-5.2 Active Alarm Mode ............................................................................................ 2-5 ................................................... 2-6.2 Active Supervisory Trouble Mode ..................................................................... 2-10 ................................................. 2-6.3 Active Trouble Mode ......................................................................................... 2-11 ................................................. 2-6.4 Addressable Contact Input Device Installation .................................................. 7-11 ................................................. 7-15 Addressable Contact Input Devices ................................................................. 1-5, 3-11 .......................................... 1-2.11,3-3.14 Addressable Contact Monitor Registration ....................................................... 2-14 ................................................. 2-8.7.2 Addressable Relay Output Device Installation .................................................. 7-11 ................................................. 7-16 Addressable Relay Output Devices .................................................................. 1-5, 3-12 .......................................... 1-2.12, 3-3.15 Addressing I/O Modules ................................................................................... 2-13 ................................................. 2-8.4 Addressing RCUs ............................................................................................. 2-13 ................................................. 2-8.6 Agent Release Module ...................................................................................... 3-9, 7-4 ........................................... 3-3.8, 7-7.3 Agent Release Output Module .......................................................................... 1-4 ................................................... 1-2.7.3 Alarm Mode Indications .................................................................................... 2-5 ................................................... 2-6.2.1 Alarm Mode User Action ................................................................................... 2-5 ................................................... 2-6.2.2 Alarm Simulation Test (AST) ............................................................................ 4-2 ................................................... 4-3.5 Arming Release Circuits .................................................................................. 4-3 ................................................... 4-4.2 AST Procedure ................................................................................................. 4-3 ................................................... 4-3.5.1 Audible Device .................................................................................................. 2-2 ................................................... 2-2.2 B Basic Motherboard ........................................................................................... 1-2 ................................................... 1-2.5 Batteries ........................................................................................................... 7-6 ................................................... 7-9.2 Battery Enclosure ............................................................................................. 7-6 ................................................... 7-9.1 Battery Test ...................................................................................................... 4-1 ................................................... 4-3.3 C Central Control Module (CCM) .......................................................................... 1-1, 3-2, 5-2 .................................... 1-2.1, 3-3.1, 5-4.2 City Tie Module ................................................................................................. 1-4, 3-10 .......................................... 1-2.7.4, 3-3.9 City Tie Output Module ..................................................................................... 7-4 ................................................... 7-7.4 Component Description .................................................................................... 1-1 ................................................... 1-2 Connecting a Printer ......................................................................................... 7-11 ................................................. 7-18.2 Connecting a Terminal or Personal Computer .................................................. 7-11 ................................................. 7-18.1 Connecting AC Power ...................................................................................... 7-6 ................................................... 7-8 Connection of Peripherals ................................................................................ 7-11 ................................................. 7-18 Control and Indicator Description ..................................................................... 2-2 ................................................... 2-2.3 Control and Indicators ...................................................................................... 2-1 ................................................... 2-2 D Default Passwords ........................................................................................... 2-2 ................................................... 2-3.2 Detector Installation .......................................................................................... 7-10 ................................................. 7-13 Detector Registration ....................................................................................... 2-14 ................................................. 2-8.7.1 Disarming and Rearming Release Circuits ...................................................... 4-3 ................................................... 4-4 Disarming Release Circuits ............................................................................. 4-3 ................................................... 4-4.1 Display Control Card (DCC) .............................................................................2-12 ................................................. 2-8.3.3 Display Module ................................................................................................. 1-1 ................................................... 1-2.2

76-100016-001

H-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

INDEX (Cont.)
Subject Page Paragraph

E Enable/Disable RTC Program Line Numbers ................................................... 2-12 ................................................. 2-8.2.2 Entering Passwords ......................................................................................... 2-2 ................................................... 2-3.3 EOC Programming .......................................................................................... 2-11 ................................................. 2-8.1 Exiting the System Menus ................................................................................ 2-4 ................................................... 2-5.3 External Power Failure Indicator Connection .................................................... 7-10 ................................................. 7-12 F Field Device Connection to RX/TX Module ....................................................... 7-7 ................................................... 7-10 Field Devices .................................................................................................... 3-11, 5-3 .......................................... 3-3.10, 5-4.4 Functional Descriptions .................................................................................... 3-2 ................................................... 3-3 I Input/Output Modules ........................................................................................ 1-3 ................................................... 1-2.7 Install and Connect DC Power ......................................................................... 7-6 ................................................... 7-9 Installation Checkout ........................................................................................ 7-11 ................................................. 7-17 Installation Procedure for Central Control Panel ............................................... 7-1 ................................................... 7-3 Installation Procedure for Expansion Enclosures ............................................. 7-1 ................................................... 7-4 Installation Procedure for I/O Motherboard ....................................................... 7-2 ................................................... 7-5 Installation Procedure for RX/TX Module .......................................................... 7-2 ................................................... 7-6 Installation Procedure for I/O Module ................................................................ 7-3 ................................................... 7-7 Intelligent Loop Devices .................................................................................... 1-4 ................................................... 1-2.9 Isolate Menu Function ....................................................................................... 2-4 ................................................... 2-5.4.1 L Lamp Test ......................................................................................................... 4-1 ................................................... 4-3.1 LCD Display ..................................................................................................... 2-1 ................................................... 2-2.1 Levels of Security ............................................................................................. 2-2 ................................................... 2-3.1 List Menu Function ........................................................................................... 2-4 ................................................... 2-5.4.2 Listing all Registered RCUs .............................................................................2-15 ................................................. 2-8.7.4 Listing EOC Programming ...............................................................................2-12 ................................................. 2-8.1.1 Listing I/O Module Assignment ......................................................................... 2-13 ................................................. 2-8.5.1 Listing RTC Programming ................................................................................2-12 ................................................. 2-8.2.1 Loop Device Test .............................................................................................. 4-1 ................................................... 4-3.2 Loop Isolator Devices ....................................................................................... 1-6 ................................................... 1-2.14 Loop Isolator Devices ....................................................................................... 3-12 ................................................. 3-3.17 M Maintenance Procedures ................................................................................. 4-1 ................................................... 4-3 Materials Required for Installation ..................................................................... 7-1 ................................................... 7-2 Menu Functions ................................................................................................ 2-4 ................................................... 2-5.4 Menu Structure ................................................................................................. 2-4 ................................................... 2-5.1 Mode of Operation ............................................................................................ 2-1 ................................................... 2-1.1 Model DH-2000 Air Duct Housing ..................................................................... 1-5, 3-12 .......................................... 1-2.13, 3-3.16 Modes of Operation .......................................................................................... 2-5 ................................................... 2-6 Multi-Loop Motherboard .................................................................................... 1-3, 3-6 ........................................... 1-2.6, 3-3.5

August 1999

H-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

INDEX (Cont.)
Subject Page Paragraph

N Normal Standby Mode ...................................................................................... 2-5 ................................................... 2-6.1 O Output Signal Connection ................................................................................. 7-9 ................................................... 7-11 Overall Block Diagram Description .................................................................. 3-1 ................................................... 3-2 P Parts List .......................................................................................................... 6-1 ................................................... 6 Power-Down Procedure ................................................................................... 4-3 ................................................... 4-5.1 Power-Down System ....................................................................................... 4-3 ................................................... 4-5 Power-Up Procedure ........................................................................................ 4-4 ................................................... 4-6.1 Power-Up System ............................................................................................ 4-4 ................................................... 4-6 Power Checks .................................................................................................. 5-1 ................................................... 5-2.2 Power Supply Communication Connections .................................................... 7-6 ................................................... 7-7.7 Power Supply/Charger Assembly ..................................................................... 1-2, 7-4 ........................................... 1-2.4, 7-7.5 Power Supply/Charger Assembly, Expansion Enclosure ................................. 7-4 ................................................... 7-7.6 Power Supply/Charger Assembly, Revision A .................................................. 3-4 ................................................... 3-3.3 Power Supply/Charger Assembly, Revision C .................................................. 3-5 ................................................... 3-3.4 Printing Operation ............................................................................................. 2-11 ................................................. 2-7 R Receiver/Transmitter (RX/TX) Module .............................................................. 1-2, 3-3 ........................................... 1-2.3, 3-3.2 Registering I/O Module Assignments ............................................................... 2-13 ................................................. 2-8.5 Registering RCUs ............................................................................................2-14 ................................................. 2-8.7 Relay Output Module ........................................................................................ 1-3, 3-8, 7-4 .................................... 1-2.7.2, 3-3.7, .................................................................................................................................................................................. 7-7.2 Remote Control Unit (RCU) ............................................................................. 2-12 ................................................ 2-8.3.2 Remote Relay Registration .............................................................................. 2-15 ................................................ 2-8.7.3 Removal and Replacement ............................................................................. 5-2 .................................................. 5-4 Required Tools ................................................................................................ 5-2 .................................................. 5-4.1 RTC Programming ........................................................................................... 2-12 ................................................ 2-8.2 RX/TX Loops .................................................................................................... 2-13 ................................................ 2-8.3.4 RX/TX Module ................................................................................................. 5-2 .................................................. 5-4.3 S Scheduled Maintenance .................................................................................. 4-1 .................................................. 4-2 Set Menu Function .......................................................................................... 2-4 .................................................. 2-5.4.3 Setting and Adjusting Smoke & Heat Detector Sensitivities ........................... 7-10 ................................................ 7-14 Setting and Adjusting Smoke & Heat Detector Sensitivity Procedure ............ 7-10 ................................................ 7-14.1 Signal Audible Output Module ......................................................................... 7-3 .................................................. 7-7.1 Signal Output Module ...................................................................................... 1-3, 3-7 ........................................... 1-2.7.1, 3-3.6 SmartOne Detector Bases ............................................................................... 1-5 .................................................. 1-2.10 SmartOne Heat Detectors ............................................................................... 1-5, 3-11 ......................................... 1-2.9.3, 3-3.13 SmartOne Ionization Detectors ........................................................................ 1-4, 3-11 ......................................... 1-2.9.1, 3-3.11 SmartOne Photoelectric Detectors .................................................................. 1-5, 3-11 ......................................... 1-2.9.2, 3-3.12 Standard Fault Isolation Techniques ............................................................... 5-1 .................................................. 5-2 Standby Batteries ............................................................................................ 1-4 .................................................. 1-2.8 Supervisory Trouble Mode Indication .............................................................. 2-10 ................................................ 2-6.3.1
76-100016-001 H-3 August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

INDEX (Cont.)
Subject Page Paragraph

Supervisory Trouble Mode User Action .............................................................2-10 ................................................. 2-6.3.2 System Components ....................................................................................... 1-1 ................................................... 1-1.2 System Description .......................................................................................... 1-1 ................................................... 1-1.1 System I/O Modules .........................................................................................2-13 ................................................. 2-8.3.5 System Inputs ...................................................................................................2-12 ................................................. 2-8.3.1 System Menus .................................................................................................. 2-4 ................................................... 2-5 System Outputs ...............................................................................................2-13 ................................................. 2-8.3.4 System Power-Up ............................................................................................ 2-2 ................................................... 2-4 System Programming ...................................................................................... 2-11 ................................................. 2-8 System Security ............................................................................................... 2-2 ................................................... 2-3 System Specification ........................................................................................ 1-6 ................................................... 1-3 T Test Menu Function .......................................................................................... 2-4 ................................................... 2-5.4.4 Trouble Mode Indications .................................................................................. 2-11 ................................................. 2-6.4.1 Trouble Mode User Action ................................................................................. 2-11 ................................................. 2-6.4.2 Troubleshooting ................................................................................................ 5-1 ................................................... 5-3 Troubleshooting and Corrective Maintenance ................................................... 5-1 ................................................... 5 Types of Inputs and Outputs .............................................................................2-12 ................................................. 2-8.3 U Un-registering RCUs ........................................................................................ 2-15 ................................................. 2-8.7.5 V Visual Inspection .............................................................................................. 5-1 ................................................... 5-2.1 W Walk Test .......................................................................................................... 4-2 ................................................... 4-3.4 Walk Test Procedure ........................................................................................ 4-2 ................................................... 4-3.4.2 Walk Testing Detectors .................................................................................... 4-2 ................................................... 4-3.4.1 Wiring the RX/TX PC Line ................................................................................ 7-7 ................................................... 7-10.1

August 1999

H-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX I SYSTEM DRAWINGS


This appendix provides installation diagrams and instructions for various PEGAsys system modules.

COMPONENT Central Control Module Receiver/Transmitter Module Power Supply Module (Revision XC) Power Supply Module (Revision AC) Agent Release Module Signal Audible Module Relay Output Module City Tie Module Basic I/O Motherboard Multi-Loop Motherboard Addressable Input Device Addressable Output Device Addressable Input Device Addressable Output Device

DRAWING No. 06-235443-001 06-235443-002 06-235443-003 06-235443-003 06-235443-005 06-235443-006 06-235443-007 06-235443-008 06-235443-011 06-235443-012 06-234563-001 06-234563-001 New Design New Design

PAGE No. I-2 I-6 I-8 I-9 I-11 I-14 I-17 I-18 I-20 I-22 I-24 I-25 I-26 I-27

76-100016-001

I-1

August 1999

PEGAsys

JK5

I/O PORT

JK1

JK2

JK3
1

PLG2 TB6
24V 5V 0V
EARTH FLT SUPPLY FLT

JK4

RX/TX PORT

DISPLAY

TO REMOTE PC FOR PROGRAMMING TO EXTERNAL PRINTER OR INTELLIGENT GRAPHIC ANNUNCIATOR 24VDC FROM POWER SUPPLY

24V

0V

PLG2

PLG6

SW1

JK3 PLG1

PLG2

PLG3

DISPLAY PORT

TB6

JK1

JK2

August 1999
CCM RESET BUTTOM
JP4

SOUNDER 1 A B + + -

SOUNDER 2 A B + + -

VOLT FREE RELAYS 1 2 NO NC C NO NC

V/F RELAY FAULT NO NC C

REP 1

REP 2

TB4

TB5

TB1

TB2

TB3

DISPLAY ASSEMBLY

SEE NOTE 1 JP3 SEE NOTE 1 JP1 SW1 SEE NOTE 1 IC1 JP2

BT1

TO I/O MODULES AN POWER SUPPLIES

I-2

DISP PORT

PRINT PORT

P.C. PORT

PLG1

5V 0V

TO RX/TX LOOP CONTROLLER

Intelligent Suppression Control/Fire Alarm System

PROCESSOR PORT

SHEET 1 of 4
76-100016-001

REVISION AD

DRAWING No. 06-235443-001

TITLE Installation Wiring Diagram CCM/ Display & Control Assembly (PEGAsys)

DISPLAY RESET

24VDC FROM POWER SUPPLY

NOTES: 1. JUMPER ARRANGEMENTS FOR SOUNDER 1 SIGNAL SOUNDER JP1 JP2 JP3 JP4 ON OFF ON OFF AGENT RELEASE OFF ON OFF ON 8. RELEASING OUTPUT DEVICES SOLENOIDS 890181 899175 895630 897494 486500 486500-01 FM GROUPS SPRINKLER SOLENOIDS A,B,D,E,G 9. FOR SPECIFIC SIGNAL DEVICE INFORMATION REFER TO FENWAL DATA SHEETS 75.XXX

76-100016-001 I-3

Intelligent Suppression Control/Fire Alarm System

2. SOUNDER/RELEASE CIRCUITS ARE RATED AT 24VDC, 2A POWER LIMITED. SUPERVISORY CURRENT - 2.4mA/CIRCUIT 3. ALL RELAY OUTPUTS (VOLT/FREE RELAYS AND V/F RELAY) ARE RATED AT 30VDC, 1A. 4. SIGNAL OUTPUT REQUIRE THE USE OF END OF LINE RESISTOR (EOR) 10K, 0.5W; NOT SUPPLIED WITH PANEL. AVAILABLE AS PART NO. 06-129520-001 (KIT OF 50). 5. IF MP01 IS CONFIGURED AS A RELEASING OUTPUT, A 220 OHM (5W MIN.) RESISTOR COULD BE USED TO SIMULATE THE CIRCUIT IF NO SOLENOID IS CONNECTED. CAUTION: DO NOT USE RESISTOR IF SOLENOID IS CONNECTED. 6. TO GUARANTEE THE REQUIRED VOLTAGE AT THE RELEASING DEVICE, THE FOLLOWING TABLE SHALL BE USED. EX: TO DETERMINE THE TOTAL LOOP LENGTH, MEASURE THE DISTANCE BETWEEN THE CONTROL HEAD AND THE CONTROL PANEL TERMINAL BLOCK, THEN MULTIPLY BY TWO. DEVICE PART NO. 890181 899175 895630 897494 486500 486500-01 FM SOLENOID GROUP A B,D E,G 12 AWG 300 300 300 380 3000 3000 1440 940 1570 WIRE LENGTH (FT.) 14 AWG 16 AWG 200 120 200 120 200 120 240 150 2000 1200 2000 1200 760 480 500 300 760 525 18 AWG

S L

- FOR SUPERVISED CIRCUITS. - FOR POWER LIMITED CIRCUITS.

RELEASING

800 800 340 220 370

POSITION OF RELAY OUTPUTS DURING NORMAL STANDBY MODE. VOLT FREE RELAYS (PROGRAMMABLE) FAULT RELAY V / F RELAY FAULT NO NC C TB1, TB2 NO NC C TB3

MAXIMUM OF ONE #12 AWG WIRE PER TERMINAL. 7. RELEASING OUTPUT DEVICES SPECIFICATION DEVICE 890181 899175 895630 897494 486500 486500-01 FM SOLENOID GROUP I max. 2.4 A 2.4 A 2.0 A 1.5 A 240 mA 240 mA 458 mA 700 mA 420 mA RESISTANCE (min.) 10 OHM 10.8 OHM 12 OHM 15.9 OHM 103 OHM 103 OHM 52 OHM 34 OHM 57 OHM "ON" TIME MOMENTARY MOMENTARY MOMENTARY CONTINUOUS CONTINUOUS CONTINUOUS CONTINUOUS CONTINUOUS CONTINUOUS

SHEET 2 of 4
August 1999

REVISION AD

DRAWING No. 06-235443-001

TITLE Installation Wiring Diagram CCM/ Display & Control Assembly (PEGAsys)

NOTE: THE TROUBLE RELAY CONTACTS ARE SHOWN IN THE UNPOWERED STATE.

A B,D E,G

PEGAsys

PEGAsys

Intelligent Suppression Control/Fire Alarm System

TITLE Installation Wiring Diagram CCM/ Display & Control Assembly (PEGAsys) DRAWING No. 06-235443-001 REVISION AD SHEET 3 of 4
August 1999 I-4 76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

TITLE Installation Wiring Diagram CCM/ Display & Control Assembly (PEGAsys) DRAWING No. 06-235443-001 REVISION AD SHEET 4 of 4
76-100016-001 I-5 August 1999

PEGAsys

KIDDE-FENWAL, INC. ASHLAND, MA 01721

J3

August 1999
24 VDC (RED) 24 VDC FROM POWER SUPPLY NOTES: 1. SMART DEVICES MAY UTILIZE T-TAP WIRING METHOD IN STYLE 4 CONFIGURATION ONLY. 2. MAXIMUM OF 255 LOOP DEVICES PER RX/TX LOOP. ANY COMBINATION OF DEVICE TYPE IS ACCEPTABLE. 3. MAXIMUM 20 LOOP ISOLATORS EXCLUDING ONE ON RX/TX CAN BE INSTALLED ON PC LINE. NO MORE THAN 30 LOOP DEVICES BETWEEN TWO ADJACENT LOOP ISOLATORS. STYLE 6 (4-WIRE) PC LINE CONFIGURATION IS RECOMMENDED TO FULLY UTILIZE LOOP ISOLATION FUNCTION. 4. ARRANGEMENTS FOR PC LINE WIRING CONTACT INPUT DEVICES: PRODUCT NO'S. 70-407002-00X 70-407003-001 70-407004-001 70-407008-001 70-407008-002 JUMPER STYLE 6 STYLE 6 w/LOOP ISO. SHORTED OPEN OPEN OUT OUT SHORTED SHORTED IN IN SEE NOTE 4 JP2 JP3 IN IN W1 & W2 OPEN STYLE 4 STYLE 7 SMART DETECTORS USED: PRODUCT NO'S. 70-401001-000 70-401004-000 71-401001-000 71-401004-000 RS232 PORT FOR COMMUNICATION WITH CCM.

MODULE

RET (BLK)

70-402001-100 71-402001-100 70-404001-100 70-403001-XXX

J1 J2

W1

W2

RELAY OUTPUT DEVICES: PRODUCT NO.'S 70-408002-000 70-408003-000 70-408004-001 LOOP ISOLATORS: PRODUCT NO.'S RXTX 74-200012-001 ELECT. BOX 74-200012-002 BASE MOUNT 74-200012-004 ANALASER INTERFACE MODULE PRODUCT NO. 89-100081-001

RX/TX 76-100005-001
RX/TX 4.1- STYLE SEVEN (7) REQUIRES THE USE OF LOOP ISOLATORS, THE RXTX MODULE REQUIRES THE USE OF ONE (1) P/N 74-200012-001 ISOLATOR MODULE TO OPERATE IN THE STYLE 7 CONFIGURATION. CPU RESET
LED1 LED2
LOOP ISOLATOR RX/TX

PC LINE NORMAL CPU RESET SW1


SHORT-1

4.2- WHEN LOOP ISOLATOR USED: PLUG IN THE LOOP ISOLATOR (RXTX) 74-200012-001 AND INTERCONNECT IT USING FLEX CABLES TO J3 ON RXTX. MAKE SURE THAT UNEVEN PINS ARE INTERCONNECTED. 5. MAXIMUM OF ONE #12 AWG WIRE PER TERMINAL. (OPTIONAL) LOOP ISOLATOR 74-200012-001 SIGNALING LINE CIRCUIT CHARACTERISTICS

PC LINE RESET SW2


1
SHORT-2

I-6
T1 J3 JP3 JP2
12

1 2 3 4

T1

MAX VOLTAGE: MIN. VOLTAGE: MAX. LINE CAPACITANCE: MAX. LINE RESISTANCE: MAX. NUMBER OF RCU'S: MAX. RIPPLE VOLTAGE:

26.4 VDC 19.0 VDC 1.0 uF 26.0 OHMS 255 100 mV RMS

SEE NOTE 4

LED 1 - RED LED INDICATES RXTX RESET WHEN ON. LED 2 - GREEN LED INDICATES NORMAL OPERATION OF RXTX PC LINE TRANSMITTER WHEN BLINKING. SW 1 - CPU RESET. SW 2 - PC LINE REST / DISCONNECT 24V FROM TERM. 2 & 3.

RX/TX ASSEMBLY 74-200005-001

SHEET 1 of 2

REVISION AC

DRAWING No. 06-235443-002

TITLE Installation Wiring Diagram Receiver/Transmitter Module (PEGAsys)

Intelligent Suppression Control/Fire Alarm System

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

TITLE Installation Wiring Diagram Receiver/Transmitter Module (PEGAsys) DRAWING No. 06-235443-002 REVISION AC SHEET 2 of 2
76-100016-001 I-7 August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

TITLE Installation Wiring Diagram Power Supply (PEGAsys) DRAWING No. 06-235443-003 REVISION XC SHEET 1 of 1
August 1999 I-8 76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

TITLE Installation Wiring Diagram Power Supply (PEGAsys) DRAWING No. 06-235443-003 REVISION AC SHEET 1 of 2
76-100016-001 I-9 August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

WHT BLK/WHT

BLK

VIO

MAIN POWER SUPPLY

RED

BLK

TITLE Installation Wiring Diagram Power Supply (PEGAsys) DRAWING No. 06-235443-003 REVISION AC SHEET 2 of 2
August 1999 I-10 76-100016-001

AUXILIARY POWER SUPPLY

RED

ORN

BLK/WHT

AC IN

WHT

AC OUT 2 1

RET

DC IN 1

RET

DC IN 2

VIO RED RED ORN

BLK BLK

24V

SPV

24V

SHARE

SPV

Intelligent Suppression Control/Fire Alarm System

PEGAsys

TITLE Installation Wiring Diagram Release Module (PEGAsys) DRAWING No. 06-235443-005 REVISION AD SHEET 1 of 3
76-100016-001 I-11 August 1999

SOLENOID PART NO. 890181 AND 895630


(U.L. LISTED) (U.L. LISTED)

August 1999
SOLENOID PART NO. 897494
SINGLE CONTROL HEAD 2
3 S 2

PEGAsys

TB1 1 CONTROL HEAD 2 2 + 3 CKT #1 +24V 4 5 CKT #2 6 RET. S L

DAUL 1 1
L S

TB1 1 2 + 3 4 5 6 + CKT #1
L

SINGLE SOLENOID TB1

TWO SOLENOIDS TB1

+ 3 CKT #1 4
S 3 2 S 1 L

+ 3 4 5 CKT #2 6 NOTES: 1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ". 2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.7 OHMS. + + -

AUXILARY POWER CONNECTION


TB1 1 2

2 3

+ 5
L

CKT #2
1

NOTE: JUMPERS W1 & W2 TO BE REMOVED WHEN AUXILARY POWER USED.

NOTES: 1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ". 2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS.

SOLENOID PART NO. 899175


(U.L. LISTED) SINGLE SOLENOID TB1 1
L S L

SOLENOID PART NO. 486500, 486500-01


TWO SOLENOIDS TB1 1 2
S

SIGNAL CIRCUITS

TWO SOLENOIDS TB1 1 2 BLK 3


L RED

SINGLE SOLENOID TB1 1 2 + 3 CKT #1 4 5 CKT #2 6


S

TB1 7 8 + CKT #1

MICROSWITCH 2
S L

10K EOR +
S L

I-12
BLU WHT 4 4
S

BLK 3 BLU WHT BLU WHT 6


S L

+ YEL BLK 5
BLK

+ + + -

RED BLK

3 +
RED BLK L

9 4 5 6 10 11 12

+ +

YEL + SOLENOID 6 YEL 5

CKT #2
S

10K EOR
L

SAFETY FUSE

CKT #2

10K EOR

NOTES: 1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ". 2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS.

NOTES: 1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ". 2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 6.0 OHMS.

SHEET 2 of 3

REVISION AD

DRAWING No. 06-235443-005

TITLE Installation Wiring Diagram Release Module (PEGAsys)

Intelligent Suppression Control/Fire Alarm System

76-100016-001

76-100016-001
FM GROUP SPRINKLER SOLENOIDS GROUP A
(U.L. LISTED) SINGLE SOLENOID TB1 1
L

GROUP B,D
(U.L. LISTED) TWO SOLENOIDS TB1 1 2 2 + 3 4
S L S L

SINGLE SOLENOID TB1 1 2 + + 3 CKT #1 4 5 CKT #2 6 1

TWO SOLENOIDS TB1

2 + 3 CKT #1 4 4
S S L S

+ 3 CKT #1
L

+ 5 CKT #2 6 6 6 CKT #2 + 5 5 + -

Intelligent Suppression Control/Fire Alarm System

NOTES:

1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ".

NOTES: 1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ". 2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 1.5 OHMS.

I-13
+
L

2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 2.3 OHMS.

GROUP E,G
(U.L. LISTED) SINGLE SOLENOID TB1 1
L

TWO SOLENOIDS TB1 1 2


S

2 3 S

+ CKT #1 4 + 5 CKT #2 6
S L

3 + 4 5 6 NOTES: 1. SWITCH S1 AT "SOL" POSITION. SWITCH S3,1 TO "OFF ". 2. MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 2.5 OHMS.

SHEET 3 of 3

REVISION AD

DRAWING No. 06-235371-005

TITLE Installation Wiring Diagram Release Module (PEGAsys)

PEGAsys

August 1999

TROUBLE LED

1 2 1 2 1 2

NOT USED

12

August 1999
NOTES: 1. MAXIMUM OUTPUT CURRENTS: SIGNAL CIRCUIT - 2.0 A SUPERVISORY CURRENT - 2.4 mA/CIRCUIT 2. NOMINAL VOLTAGE 24.0 VDC 3. SIGNAL OUTPUT REQUIRE THE USE OF END OF LINE RESISTOR (EOR) - 10K, 0.5W; NOT SUPPLIED WITH PANEL. AVAILABLE AS PART NO. 06-129520-001 (KIT OF 50). 4. MODULE ADDRESS ASSIGNMENT MODULE ADDRESS 1 2 3 4 5 6 7 8 SWITCH POSITION SW2,2 SW1,1 ON ON ON ON ON OFF ON OFF OFF OFF OFF OFF ON ON OFF OFF SW1,2 ON OFF ON OFF ON OFF ON OFF
06-129569-001 SIGNAL AUDIBLE MODULE

PEGAsys

ON

RESET SWITCH

SEE NOTE 4 MODULE ADDRESS ASSIGNMENT SEE NOTE 5

SIG. AUD. 76-100003-001

I-14

AUXILIARY POWER

1 2 3 4 5 6 7 8 9 10 11 12

SOUNDER CIRCUITS 1-4

TB1 SEE NOTE 8

5. EITHER SOUNDER OUTPUT (2) MAY BE CONFIGURED FOR EITHER 2 STYLE "Y" OR 1 STYLE "Z", USING JUMPER AND DIP SWITCH SETTINGS SHOWN ON SHEETS 2 & 3. 6. FOR SPECIFIC SIGNAL DEVICE INFORMATION REFER TO FENWAL DATA SHEETS 75.XXX ONLY POLARIZED SIGNALLING DEVICES TO BE USED. 7. S - FOR SUPERVISED CIRCUITS L - FOR POWER LIMITED CIRCUITS 8. JUMPERS W9 & W10 MUST BE CUT OUT WHEN AUXILIARY POWER INPUT IS USED. 9. MAXIMUM OF 8 MODULES PER SYSTEM. 10. MAXIMUM OF ONE #12 AWG WIRE PER TERMINAL.

Intelligent Suppression Control/Fire Alarm System

12

KIDDE-FENWAL, INC.

ASHLAND, MA 01721

SHEET 1 of 3
76-100016-001

REVISION AC

DRAWING No. 06-235443-006

TITLE Installation Wiring Diagram Signal Audible Module (PEGAsys)

4 STYLE "Y" TB1


-

2 STYLE "Y" AND 1 STYLE "Z" TB1 5


CIRCUIT 1 CIRCUIT 2

76-100016-001
10K EOR 10K EOR W1 ON

Intelligent Suppression Control/Fire Alarm System

5
CIRCUIT 1 CIRCUIT 2 10K EOR L S 10K EOR L S

S 10K EOR

6 7 8

6 7 8 9
CIRCUIT 3

S 10K EOR

9
CIRCUIT 3 CIRCUIT 4 L S 10K EOR

10
-

10
-

11
+

11
+

12
+

12
+

JUMPERS W2 ON W3 ON W4 OFF W5 ON W6 ON W7 ON W8 OFF ON

SWITCHES SW2,1 SW3,2 ON W1 ON W2 ON W3 ON

JUMPERS W4 OFF W5 OFF W6 OFF W7 OFF W8 ON ON

SWITCHES SW2,1 SW3,2 OFF

I-15

AUXILIARY POWER CONNECTION TB1 +24VDC AUXILIARY POWER 1 2

SHEET 2 of 3
August 1999

REVISION AC

DRAWING No. 06-235443-006

TITLE Installation Wiring Diagram Signal Audible Module (PEGAsys)

RET

PEGAsys

2 STYLE "Z" TB1


L
-

1 STYLE "Z" AND 2 STYLE "Y" TB1


S
-

August 1999
L L

PEGAsys

5
CIRCUIT 1 10K EOR

5
CIRCUIT 1

10K EOR

6 7 8 9
CIRCUIT 3 CIRCUIT 4

7 8 9
CIRCUIT 3 10K EOR L S 10K EOR L S

10K EOR

10
-

10
-

11
+

11
+

12
+

12
+

I-16

JUMPERS W1 OFF W2 OFF W3 OFF W4 ON W5 OFF W6 OFF W7 OFF W8 ON

SWITCHES SW2,1 OFF SW3,2 OFF W1 OFF W2 OFF W3 OFF

JUMPERS W4 ON W5 ON W6 ON W7 ON W8 OFF

SWITCHES SW2,1 OFF SW3,2 ON

Intelligent Suppression Control/Fire Alarm System

SHEET 3 of 3
76-100016-001

REVISION AC

DRAWING No. 06-235443-006

TITLE Installation Wiring Diagram Signal Audible Module (PEGAsys)

Intelligent Suppression Control/Fire Alarm System

PEGAsys

RELAY 76-10004-001

TITLE Installation Wiring Diagram Relay Output Module (PEGAsys) DRAWING No. 06-235443-007 REVISION AB SHEET 1 of 1
76-100016-001 I-17 August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

CITY TIE 76-100002-001

TITLE Installation Wiring Diagram City Tie Module (PEGAsys) DRAWING No. 06-235443-008 REVISION AB SHEET 1 of 2
August 1999 I-18 76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

TITLE Installation Wiring Diagram City Tie Module (PEGAsys) DRAWING No. 06-235443-008 REVISION AB SHEET 2 of 2
76-100016-001 I-19 August 1999

August 1999
C 1. POWER CONNECTIONS:1. 2. COMMUNICATIONS:

PEGAsys

I/O MOTHER BOARD


J1 R1 JP1 J2 J3 J4 J5 J6 J7 J8

J9 RS-485

Rv2 Rv1

COM. TBL. COM. ALM. SIG. GND 485A 485B RET

Tb1

KIDDE-FENWAL, INC. ASHLAND, MA 01721

Tb2

+24V

NOTE:

1. USE RED WIRES FOR +24VDC AND BLACK FOR RET. 2. JUMPER JP1 SHOULD BE IN. MAKE SURE THAT JUMPER W4 ON POWER SUPPLY CONTROL BOARD IS OUT.

1). TB1 BRINGS 24VDC POWER FROM POWER SUPPLY TB5 OR TB6 TERMINAL BLOCKS. 2). 24VDC POWER TO RX/TX MODULES (J1) FROM TB5 OR TB6 ON POWER SUPPLY. 3). TERMINAL TB1 CAN BE USED TO BRING POWER TO I/O MODULES IN THE AUXILIARY BOX.

I-20 76-100016-001

1). J9 CONNECTS TO CCM PORT AND PROVIDES I/O MODULES WITH RS485 COMMUNICATIONS. 2). J1 THROUGH J8 TO BE USED TO PLUG IN I/O MODULES AND SUPPLY THEM WITH +24VDC POWER AND RS485 COMMUNICATIONS. 3). RS232 COMMUNICATIONS FOR RX/TX MODULE TO BE PROVIDED THROUGH PHONE CABLE PLUGGED INTO "RX/TX" PORT ON CCM.

Intelligent Suppression Control/Fire Alarm System

4). TB2 TO BE USED TO INTERCONNECT TO AUXILIARY PANELS' MOTHER BOARD AND POWER SUPPLIES TO PROVIDE RS485 COMMUNICATIONS.

SHEET 1 of 2

REVISION AB

DRAWING No. 06-235443-011

TITLE Installation Wiring Diagram Basic I/0 Motherboard (PEGAsys)

Intelligent Suppression Control/Fire Alarm System


TO POWER SUPPLY

PEGAsys

TO CCM I/O PORT TO CCM RX/TX PORT

E I/OUL OD M

TITLE Installation Wiring Diagram Basic I/0 Motherboard (PEGAsys) DRAWING No. 06-235443-011 REVISION AB SHEET 2 of 2
76-100016-001 I-21 August 1999

/TX E RXDUL O M

MULTILOOP CONTROLLER/MOTHERBOARD

+24V

+24V

+24V

+24V

+24V

+24V

RET

RET

+24V

RET

RET

RET

RET

RET

RET

+24V

KIDDE-FENWAL, INC. ASHLAND, MA 01721

+24V

NOTE: 2. INSTALL THE W1 JUMPER IF THE MOTHERBOARD IS HOOKED AS THE LAST DEVICE ON THE RS-485 I/O BUS, REMOVE THE JUMPER OTHERWISE. 3. THE FIRST RX/TX MODULE (LOOP #1) SHOULD BE ALWAYS ON THE FAR RIGHT AND INTERCONNECTED TO JP1 AND TB1. ALL CONSECUTIVE RX/TX MODULES SHOULD BE PLUGGED FROM RIGHT TO LEFT STARTING FROM THE FIRST RX/TX. (CONNECTOR NUMBER IS ASSOCIATED WITH LOOP NUMBER). 1. POWER CONNECTIONS:1. 1). TB9 AND TB11 BRING 24VDC POWER FROM POWER SUPPLY TB5 AND TB6. 2). TB1 THROUGH TB8 TO BE USED TO CONNECT 24VDC POWER TO RX/TX MODULES (J1). 3). TERMINAL TB9 CAN BE USED TO BRING POWER TO I/O MODULES IN THE AUXILIARY BOX. 2. COMMUNICATIONS: 1). JP0 CONNECTS TO CCM MODULE AND SUPPLIES RS232 COMMUNICATION FOR RX/TX MODULES. 2). JP1 THROUGH JP8 TO BE CONNECTED TO RX/TX MODULES' J2 CONNECTORS TO PROVIDE RS232 COMMUNICATIONS. 3). JP9 CONNECTS TO CCM PORT AND PROVIDES I/O MODULES WITH RS485 COMMUNICATIONS. 4). J1 THROUGH J7 TO BE USED TO PLUG IN I/O MODULES AND SUPPLY THEM WITH +24VDC POWER AND RS485 COMMUNICATIONS. 5). TB10 TO BE USED TO INTERCONNECT TO AUXILIARY PANELS' MOTHER BOARD AND POWER SUPPLIES TO PROVIDE RS485 COMMUNICATIONS.

1. USE RED WIRES FOR +24VDC AND BLACK FOR RET.

I/O MODULES

August 1999
RS232

PEGAsys
RET +24V
RS485 COM. TBL. COM. ALM. SIG. GND 485A 485B

RET

I-22

SHEET 1 of 2

REVISION AB

DRAWING No. 06-235443-012

TITLE Installation Wiring Diagram Multi-Loop I/0 Motherboard (PEGAsys)

Intelligent Suppression Control/Fire Alarm System

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

I/OUL D MO

TITLE Installation Wiring Diagram Multi-Loop I/0 Motherboard (PEGAsys) DRAWING No. 06-235443-012 REVISION AB SHEET 2 of 2
76-100016-001 I-23 August 1999

/TX E RXDUL O M

GRAY ORANGE BROWN WHITE BN TO REMOVE CONTACT DEVICE EOL TO CATHODE TO ANODE 1. RED AND BLACK WIIRES ARE NON-POLERIZED POWER INPUTS. REFER TO RX/TX (CAT. NO. 30-402001-000) WIRING DIAGRAM FOR CONNECTION TO SMART DETECTOR MULTIPLEX TRUNK CIRCUIT AND CIRCUIT CHARACTERISTICS.

August 1999
TO REMOTE LED NOTES

PEGAsys

N/O
WH EOL SEE NOTE 3

2. SUPERVISED LINE FOR REMOTE CONTACT DEVICE CONNECTION. CAUTION: CONTACT DEVICE MUST BE IN THE SAME ROOM AS ADDRESSABLE CONTACT INPUT DEVICE, WITH ALL WIRING ENCLOSED IN CONDUIT, AND A MAXIMUM LENGTH OF 150 FT. 3. EOL RESISTOR: 820 OHM .5 WATT (FENWAL PART NO. 06-129025-001)

PROTECTIVE COVERING UL LABEL

4. TO REMOTE LED (FENWAL PART NO. 70-410001-000) OBSERVE POLARITY: ORANGE (ANODE), GRAY (CATHODE) CAUTION: LED MUST BE IN THE SAME ROOM AS ADDRESSABLE CONTACT INPUT DEVICE, WITH ALL WIRING ENCLOSED IN CONDUIT AND A MAXIMUM LENGTH 50FT.. LED CIRCUIT IS NOT SUPERVISED. 5. MAXIMUM CURRENT REQUIREMENTS STANDBYALARM 380uA 310uA

TYPICAL CONFIGURATIONS N.O. CONTACT DEVICES MANUAL PULL STATION BK SEE NOTE 1 EOL RD

6. SMART DETECTOR PRODUCT NO.S 70-40XXXX-XXX AND 71-40XXXX-XXX MAY BE MIXED ON THE SAME MULTIPLEX TRUNK CIRCUIT, BUT SHALL NOT EXCEED 255 TOTAL DEVICES PER CIRCUIT, 2040 PER SYSTEM. 7. TYPICAL PULES RATE: NORMAL: ALARM: TROUBLE: 9 SECONDS 2 SECONDS NO LED PULSING 8. REFER TO SYSTEM OPERATION MANUAL FOR APPLICATION OF ADDRESSABLE CONTACT INPUT DEVICE. 9. WIRING INFORMATION SHOWN FOR 70-407002-00X THRU 70-407004-00X.

I-24
WATERFLOW EOL SEE NOTE 3

CAT. NO. -000 -001

DESCRIPTION NORMALLY OPEN NORMALLY CLOSED FOR SUPERVISORY USE ONLY

SHEET 1 of 1

REVISION BB

DRAWING No. 06-234563-003

TITLE Installation Wiring Diagram Addressable Contact Input Device NO/NC (Obsolete)

Intelligent Suppression Control/Fire Alarm System

76-100016-001

BROWN ( N/C ) ORANGE ( COM ) N.C. COM. N.O. NOTES 1. RED AND BLACK WIIRES ARE NON-POLERIZED POWER INPUTS. REFER TO RX/TX (CAT. Number 30-402001-000 & 74-200005-001) WIRING DIAGRAM FOR CONNECTION TO SMART DETECTOR MULTIPLEX TRUNK CIRCUIT AND CIRCUIT CHARACTERISTICS. CAUTION: 2. RELAY OUTPUTS ARE NOT SUPERVISED. RATING: 2A, 30 VDC (RESISTIVE) .6A, 120 VAC (RESISTIVE) 3. MAXIMUM CURRENT REQUIREMENTS: STANDBY: 325uA FIELD CONNECTION WHITE ( N/O ) SEE NOTE 2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PROTECTIVE COVERING

UL LABEL

4. SMART DETECTOR PRODUCT NO.S 70-40XXXX-XXX AND 71-40XXXX-XXX MAY BE MIXED ON THE SAME MULTIPLEX TRUNK CIRCUIT, BUT SHALL NOT EXCEED 255 TOTAL DEVICES PER CIRCUIT, 2040 PER SYSTEM. 5. TYPICAL PULSE RATE: RELAY RESET (STANDBY): RELAY SET: TROUBLE STATE: 9 SECONDS 2 SECONDS NO LED PULSING 6. REFER TO SYSTEM OPERATION MANUAL FOR APPLICATION OF ADDRESSABLE RELAY OUTPUT 7. MOUNTS IN 4 SQUARE ELECTRICAL BOX.

I-25
LED (SEE NOTE 5)

8. MUST BE INSTALLED IN A U.L. LISTED GANG BOX.. 9. WIRING INFORMATION SHOWN FOR 70-408002-000 THRU 70-408003-000.

RD

BK

SEE NOTES 1 & 9

SHEET 1 of 1

REVISION BA

DRAWING No. 06-234563-001

TITLE Installation Wiring Diagram Addressable Relay Output Device (Obsolete)

PEGAsys

August 1999

ALL TERMINALS ARE POWER LIMITED

MODEL AI, N/O CAT. NO. 70-407008-001 SEE INSTALLATION INSTRUCTIONS 06-235578-001 MAX. INSTALL. TEMP. 120F FOR SERVICE SEND TO: KIDDE-FENWAL, INC. 400 MAIN ST. ASHLAND, MA 01721 DATE OF MANUFACTURE:

SmartOne TM

AI, N/O

PC PC PC PC SW SW LED LED (+) (-) (+) (-) A B (+) (-)

AI, N/C

PC PC PC PC SW SW LED LED (+) (-) (+) (-) A B (+) (-)

August 1999

PEGAsys

Typical N.O. Initiating Devices

NOTES 1.
See Notes: 1, 2, and 4

Maximum 25 resistance per wire for initiating circuit. For a total circuit wiring resistance of 50 max. Terminal connection supports wiring from #18 AWG (0.75 mm2) to #14 AWG (1.5 mm2) Refer to Control Panel Manual for addressable loop wiring specification. Maximum 10 VDC @ 1 mA. This module will not support 2-wire smoke detectors. N/O initiating device circuit is NFPA Class B/Style B. Rating on LED circuit: 26 VDC Max. 7 mA Max. If not used leave terminals open circuit. All wiring is power limited and supervised. The AI, N/C Device is intended for use within the control equipment providing the normally closed contact. The initiating device and remote LED annunciator (if used) must be located in the same room as the AI. Use Listed 10K Ohm end-of-line resistor, P/N 06-129025-003.

2.
See Note 3 (+) PC Line In (-) See Note 3 Remote LED (Optional) See Note 7 (+) (-) PC Line Out EOL (Listed 10K Resistor)

3. 4. 5. 6. 7.

Typical N.C. Supervisory Devices

I-26

8. 9.

Intelligent Suppression Control/Fire Alarm System

EOL (Listed 10K Resistor)

10.

SHEET 1 of 1
76-100016-001

REVISION -

DRAWING No. New Design

TITLE Installation Wiring Diagram Addressable Contact Input Device NO/NC

11.

TERMINALS 1-4 ARE POWER LIMITED TERMINALS 5-7 ARE POWER LIMITED

MODEL AO CAT. NO. 70-408004-001 SEE INSTALLATION INSTRUCTIONS 06-235577-001 MAX. INSTALL. TEMP. 120F FOR SERVICE SEND TO: KIDDE-FENWAL, INC. 400 MAIN ST. ASHLAND, MA 01721 DATE OF MANUFACTURE:

SmartOne

TM

PC PC PC PC (+) (-) (+) (-)

N/C

COM

N/O

76-100016-001

Intelligent Suppression Control/Fire Alarm System

N/O COM N/C

7 6 5 Field Connections
NOTES

1.

AO must be installed in the same room as the device it is controlling . Terminal connection supports wiring from #18 AWG (0.75 mm2) to #14 AWG (1.5 mm2) Refer to Control Panel Manual for addressable loop wiring specification. PC Line wiring is power limited and supervised.

See Note 3 (+) PC Line In (-)

See Note 3 (+) (-) PC Line Out

2.

3.

4.

I-27

SHEET 1 of 1
August 1999

REVISION -

DRAWING No. New Design

TITLE Installation Wiring Diagram Addressable Relay Output Device

PEGAsys

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

I-28

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX J PEGAsys NETWORK INTERFACE CARD


Note that it is not possible to download configuration information to all the NICs on a network simultaneously. Each NIC (node) must be configured independently. The operator can set network configuration options on the PEGAsys(s) in three ways: Via the keypad on the Central Control Module. Via PCS. Via a dumb terminal.

J-1

INTRODUCTION

The PEGAsys Network Interface Card (NIC) provides the capability for peer-to-peer communication between PEGAsys fire/ suppression control panels (nodes). The NIC mounts as a daughter card on the PEGAsys Central Control Module (CCM). Up to 32 nodes may be networked to form groups. Groups are numbered logical groupings that delineate the extended coverage area and simplify programming.
NETWORK INTERFACE CARD CAT. NO. 74-200036-001
J1 DS4 DS2 DS3 DS1

Below are the network options which can be configured for each node and which are stored in that panel's memory. Paragraphs detailing each option follow.
U11

B2NA2 B1NA1 B2IA2

B1IA1

N2 C26

N1

I2

I1

1 CR2 K2 CR1 K3 K1 C27 U13 R46 R45 RV6 RV4 RV5 RV8 RV9 RV7 RV2 RV3 C20 RV1 1

Network Style: None, Single-Channel (Style 4), or Redundant Channel (Style 7). Node number: 0 to 32 Network group number: 0 to 32 Processing of network RESET messages: Enabled/Disabled Processing of network SILENCE messages: Enabled/Disabled Logging all events: Enabled/Disabled. Time resynchronization (resynch) period Central Station

RV12

RV11

R23

K4

CR3
C12 U2 1 R10 C4 C13 Y1

TB4

TB2

TB3

TB1

U12

GND +5 TP1 TP2 I1 TP3 TP4 TP5 1 U3 C14 U4 TP6 N1 N2 I2

RV10

R24

E8

E1

R25

R6

R5

R4

R3

E7

E3

E6

E5

E4

E2

+
C5

R20 R41 R40 U20 1 U19

R2

U18

C18

R21

R13

R36

C2

R22 1 1 1 U21 R44 U14 C9 Q4 Q3 1 C8 R7 R17 R1 U15 1 U17 U16 C22 R32 U10 C16 1

U5

C11

R14

U7

C23

+
C3

J-2.1.1 NETWORK STYLE Both of the two independent data channels can be enabled (Style 7), or either one of the channels can be disabled (Style 4). These data channels transmit network information from one node to the next, or bi-directionally if nodes are connected on either side of the transmitting node. In Style-7 configuration, data transfer is redundant so that if there is a failure on one channel, or its cable, the other channel will maintain communication. J-2.1.2 NODE NUMBER ASSIGNMENT Nodes may be assigned a number from 0 to 32. Number 0 (the default) means that the node does not participate in any network activity. Any assignment from 1 to 32 means that the node actively participates in all pre-configured network activity. J-2.1.3 NETWORK GROUP NUMBER ASSIGNMENT
R33 R15

1 C25

C1

R12

R19 R29 R34

R43

C10

U9

U8 1 R26 R28 R27 C17 1 1 R31 C15 R38 C24

R42

Q1 1 1 C7 U6 R18

Q2

KIDDE-FENWAL, INC.

ASHLAND, MA 01721

Figure J-1. Network Interface Card (NIC) Each PEGAsys control panel which is a network node (i.e., equipped with a NIC) may be assigned to a designated network group (numbered 1 through 32) or to network group 0. When an event occurs at a node, notification of the particular alarm, trouble, abort, etc., will be delivered to each of the other nodes on the network in the form of a message.

J-2 J-2.1

CONFIGURATION/ADDRESSING Overview

Each node can be configured independently using any of the three methods described in the following paragraphs. The configuration process is dealt with in more detail in the PEGAsys Configuration Software (PCS) Program User's Guide (76-014), which should be referred to.

Nodes may be assigned to groups 0 through 32. A node assigned to network group 0 receives and processes messages received from all nodes only if configured to Log All Events. A node assigned to groups 1 through 32 will process only those messages from nodes in the same network group unless configured to Log All (Network) groups . J-2.1.4 RESET ENABLE/DISABLE Enabling RESET on a node means that it can be reset from any other node in its group. If it is assigned to network group 0, it can be reset from any node on the network.

76-100016-001

J-1

August 1999

PEGAsys
J-2.1.5 SILENCE ENABLE/DISABLE Enabling SILENCE on a node means that it can be silenced from any other node in its group. If it is assigned to network group 0, it can be silenced from any node on the network. J-2.1.6 EVENT LOGGING ENABLE/DISABLE Enabling Log All Events causes all network events to be logged at this node. This includes the receipt of an ACKNOWLEDGE from a button on a remote node. Disabling will result in logging events only in its own (non-zero) group. J-2.1.7 TIME RESYNCHRONIZATION PERIOD (SET IN MINUTES) A time-resynchronization message is broadcast on the network at intervals determined by the resynch period. If a node does not receive a resynchronization message during this interval, it uses its network connection to ask for the time, or uses its own locally stored time if its query does not result in a resynch message.

Intelligent Suppression Control/Fire Alarm System J-2.1.8 CENTRAL STATION OPERATION A node can be configured as a central station if that node is properly connected to a Silent Knight DACT, Model 5104. Central Station configuration automatically forces that node to Log All Events and also MP04, a volt-free relay on the CCM, is configured to activate on any alarm on any node in the network.

J-2.2

Configuring Networking Options via the Display/Keypad

Configuration can be performed through the system menus, accessible using a panels built-in membrane keypad and LCD display panel. The software will initially use default values, with networking style set to None until changed by an operator.

J-2.2

PEGAsys Panel Network Menus

The menu structure of the PEGAsys has been upgraded to accommodate network configuration. All of the network options listed in Paragraph J-2.1 are configurable via the front panel

3. SET

1. TIME:DATE

2. PRINTER

3. DEVICES

4. PROGRAMMING

5. DCC's 7. CLEAR EVENTS

7. NETWORK 9.CLR RMT EVENTS

REMOVE QUEUED EVENTS RECIEVED FROM NODE #___

1. STYLE

CH1: ENABLE/DISABLE

CH2: ENABLE/DISABLE 0: STAND ALONE 0: NOT GROUPD

2. NODE NUMBER

NODE NUMBER ( 1 TO 64) GROUP NUMBER ( 1 TO 64)

3. GROUP

4. ADD/RMV NODES

ADD OR REMOVE NODE#__ TO NODE# __ ENABLE/DISABLE NETWORK RESET ENABLE/DISABLE NETWORK SILENCE LOG ALL GROUP OR ONLY NETWORK EVENTS SET RESYNC: 0(off) OR 1-60000 MIN 1:ISOLATE NODE 2:DE-ISOLATE NODE

5. RESET EVENT

6. SILENCE EVENTS
7. LOG EVENTS

8. RESYNC PERIOD

9. ISOLATE

Figure J-2. Network Menu


August 1999 J-2 76-100016-001

Intelligent Suppression Control/Fire Alarm System Table J-1. Network Configuration Table

PEGAsys

Remote Node Location

ACK

SILENCE

RESET

LOG EVENT S/EOC/RT S

If a node is in a non-zero group, it will accept button pushes and events from remote nodes if configured as shown below:

All nodes in group 0 All nodes in same group All nodes in different groups

L Yes L

SE, L SE SE, L

RE, L RE RE, L

L Yes L

If a node is in group 0, it will accept button pushes and events from remote nodes if configured as shown below:

All nodes in all groups

SE, L

RE, L

L: If node is configured to "Log All Groups." SE: If node is configured for remote SILENCE Enable. RE: If node is configured for remote RESET Enable membrane keypad. In addition, the menu provides the ability to add or remove individual or groups of nodes to/from the network. The additions to the PEGAsys menu structure are diagramed in Figure J-2. gram. The ACKNOWLEDGE function will be automatic, the SILENCE and RESET functions must be enabled in PEGAsys Configuration Software (PCS), or by using the panels membrane keypad and LCD display panel. A node in a different non-zero network group configured to log all groups will process network message(s) from any node in the entire network, depending on its own installed program. ACKNOWLEDGE is automatic, however SILENCE and RESET functions must be enabled in PEGAsys Configuration Software (PCS), or by using the panels membrane keypad and LCD display panel. A node in network group zero, the default group, will not be recognized by any other nodes in network group zero for functions other than receiving messages unless it is configured to log all groups in PEGAsys Configuration Software (PCS). Nodes can be added or deleted from network only via Network Menu.

J-2.3

Configuring Networking Options via PCS

Configuration of all CCM parameters, including network parameters, can be accomplished using PCS. The software will initially use default values, with networking Style set to None until changed by an operator. See the PEGAsys Configuration Software (PCS) Program User's Guide (76-014) for details.

J-2.4

Configuring Networking Options via a Dumb Terminal

Control panel configuration can be performed through use of the system menus using a dumb terminal attached to the serial PC Port. The software will initially use default values, with networking style set to None until changed by an operator. NOTE: Menus cannot be accessed with an alarm condition in effect.

Refer to Table J-1 for a summary of these relationships.

J-4

FUNCTIONAL DESCRIPTION

J-3

OPERATION

This section describes the hardware used to implement the PEGAsys Network: Central Control Module (CCM) CPU Board Network Interface Card (NIC) Network Wiring

Networked PEGAsys panels may be configured to communicate differently depending on Whether they are assigned to network group 0 or to groups 1 through 32, Whether they are communicating panels in their local group, Or with panels in a remote group. with other

J-4.1

Central Control Module CPU Board

Table J-1 sets forth these relationships. In more detail, however: A node which receives the network message from another node in the same non-zero group, will process the network message appropriately, depending on its own installed pro-

The CCM board is a slightly modified version of the original CPU board designed so that the NIC will plug in as a daughter board. This modification has no effect on normal operation of the PEGAsys panel or system.

J-4.2

Network Interface Card (NIC)

The NIC contains the hardware necessary for data-communication between network nodes. The channel is an EIA-485 bus

76-100016-001

J-3

August 1999

PEGAsys
line. Each node uses one (1) NIC. The NIC performs the following functions: Dual Channel Support Messaging Repeater Fail Safe Isolation

Intelligent Suppression Control/Fire Alarm System without power will not participate in networking, this pass-through function allows all other network nodes to function normally while providing the proper trouble indications. J-4.2.5 ISOLATION One half of each channel is an isolated, floating RS-485 transceiver and the other half is a non-isolated, grounded RS-485 transceiver. This assures that the chassis of any two nodes are physically disconnected, eliminating the possibility of groundloop current, while retaining the ability to detect ground faults.

J-4.3
ISOLATED NETWORK MEDIUM

Network Wiring

TA1 TB1 Rx out Tx in Driver Enable

Hardware Repeater Logic Rx/Tx Selection Logic

TA2 TB2 Rx out Tx in Driver Enable

NON-ISOLATED NETWORK MEDIUM

The panels are networked by attaching two twisted, shieldedpair cables between the appropriate NICs. The node-to-node wire must not exceed a length of 4000 ft. and must be AWG 18 or heavier gauge. Under adverse conditions (for example, high electrical noise) shielded twisted pairs may be required. Connect panels together as shown in Figure J-4.
Channel 2 Note B

Channel 1

RTS Rx

Tx

Note A

1/2

NETWORK INTERFACE CARD (NIC)

B2NA2 B1NA1 B2IA2

B1IA1

B2NA2 B1NA1 B2IA2 B1IA1

To CCM CPU

Figure J-3. NIC Block Diagram (Shown With Power To NIC Lost) J-4.2.1 DUAL CHANNEL SUPPORT The NIC optionally supports operation of Style-4 or Style-7 channels. Under normal operation with Style 7, network communication is divided between the two channels. In case of a short circuit or a break in any of the connecting wires, either channel by itself can execute all network communications, although somewhat more slowly than if both channels are in operation. J-4.2.2 MESSAGING When a node wishes to transmit over a network channel, the data is written to the NIC which sends the signals out to the bus for receipt by remote NICs. While a node is not transmitting data, the NIC reads the bus data traffic, and converts it to a form readable by the nodes software. Data communication will be configured on the NICs UART as 8 bits, no parity, 1 stop bit (8-N-1), and 9600 baud. The NIC will either transmit locally produced data or receive and retransmit bus activity as a repeater. J-4.2.3 REPEATER (TRANSCEIVER) The NIC acts as a repeater, regenerating bus information as it moves through the NIC. Its bidirectional repeater function is implemented completely in hardware; no software is needed to control this process. The transceivers transmit and receive switching (in half-duplex mode) is also performed automatically by hardware. J-4.2.4 FAIL SAFE If a power failure occurs in a node, the NIC includes a normally closed (NC) relay which maintains the communications integrity of the network. When the NIC loses power, the relay passes the network signals directly through the board. While the node
August 1999 J-4

NETWORK INTERFACE CARD

NETWORK INTERFACE CARD

CCM CPU BOARD PEGAsys PANEL

CCM CPU BOARD PEGAsys PANEL

Note A: Attach the shields on the 'N' side of the network line to the grounding screw on the CCM. Note B: The shields on the 'I' side of the network line are to be cut short and left floating. Note C: All circuits are supervised and power limited.

Figure J-4. Network Wiring

J-5

MAINTENANCE AND/OR REPLACEMENT

No maintenance is required. In the event of failure, the module should be returned to the factory for repair or replacement.

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
NOTE: For proper network configuration it is necessary to use version 7.X of PCS, PEGAsys Configuration Software. For complete information on this aspect of installation see the PEGAsys Configuration Software (PCS) Program Users Guide (P/N 06-235766-001). As of this date, version 7.X of PCS is required for proper configuration.

J-6

PARTS LIST

The NIC Installation Kit (P/N 76-100036-500) consists of the following:

Description Network Interface Card (NIC) Snap-in Nylon Standoff, 3/4-in. 8-32 Theadless Brass Standoff, Nickel plated 8-32 x 1-1/4-in. Screw with Washer Installation Sheet

Part Number 74-200036-500 06-118142-001 06-118143-001 06-250116-030 06-235848-001

J-7.2

Required Tools

Some or all of the following tools will be required to perform removal and installation. 1. 2. 3. 4. 5. 6. 7. Small flat-blade screwdriver. 6" flat-blade screwdriver. No. 2 Philips screwdriver. Wire striper. Small needle nose pliers. Ground strap (wrist strap) for ESD protection. IC chip extraction tool.

J-7

INSTALLATION

J-7.3

Central Control Module.

The NIC is installed as a daughter board to the CCM board. After this is accomplished, the panels are wired together using twisted, shielded-pair cable, AWG-18 or heavier. Shielded twisted pair is recommended to reduce interference caused by electrical noise in the vicinity of the wires. For full Style-7 operation, two twisted pair cables must connect each pair of panels, as shown in Figure J-4. Single-channel operation (using only one twisted pair cable between NICs) is possible and provides Style-4 operation. With single-channel operation, an open circuit on any network wire will effectively break the network into two separate peer-to-peer networks, both functional and both reporting troubles.

The PEGAsys panel will be delivered with a separate network interface card; some existing panels can also can be retrofitted with a network interface card. Following are instructions both for replacement of complete CCM modules, and for installing a NIC in an existing CCM module. The CCM module consists of both the CPU panel and its attached LCD display and keypad assembly.

J-7.4

Removing And Replacing A Complete CCM Module

The old CCM module can removed as a whole and replaced with a new module. The following provides the procedure for removing the and replacing a complete CCM module 1. Ensure that all programming is saved using PEGAsys Configuration Software (PCS). For the proper procedure, see the PEGAsys Configuration Software (PCS) Program Users Guide (P/N 06-235766-001). Ensure that the power supply EPROM is of a version compatible with PEGAsys networking. See Note above. Put on a properly grounded ESD-protective wrist strap. Disconnect plugs from the I/O Port and Rx/Tx port, and P.C. port. Make note of each wire and cable connection for use during reassembly Remove the remaining wiring from CCM panel. Remove the six mounting screws while holding the CCM assembly in place. Remove CCM assembly from cabinet. Remove new CCM assembly from packing and inspect for physical damage. If undamaged... Install new CCM in the reverse order of removal making sure that each wire and cable is properly reconnected.

J-7.1

NIC Installation
CAUTION

PEGAsys system installation applications require that when a NIC is installed, pre-discharge and release-state activation, as well as abort-state activation are limited to the originating fire-alarm control panel. NOTE: Determine whether you have a newer or older CCM; a new CCM can be recognized by a single-line 20 pin header on the top edge on right side of board. If the networking upgrade is for an older system, the new CCM and Network Interface Card (NIC) will be separate. First replace the old CCM with the new CCM and then install the NIC. See following instructions for NIC installation. CAUTION Many electronic components are subject to damage from electrostatic discharge (ESD). These components are not to be removed from their protective wrappings until they are to be installed in their respective equipment locations, and then only by personnel connected to earth ground.

2. 3. 4.

5. 6. 7. 8. 9.

10. Reinstall programming and configure the network using PCS. See J-2.

76-100016-001

J-5

August 1999

PEGAsys
J-7.5
1. 2. 3. 4.

Intelligent Suppression Control/Fire Alarm System

Installing a NIC in an existing CCM Module

Ensure that all programming is saved using PCS software. Put on a properly grounded ESD-protective wrist strap. Remove power from panel but be sure the chassis remains grounded. Remove 4 nylon screws holding membrane keypad and remove membrane by pulling it straight out of its connector. Remove the 6 threaded spacers that secure the display electronics board and lift board out. Do not disconnect board - let it hang down. Data and power lines will remain connected. Insert the three plastic standoffs that were included with the NIC into the holes shown in Fig J-5. Carefully plug the NIC into the 20-pin receptacle and onto the plastic standoffs. Secure upper right corner of NIC with long screw and spacer. Spacer will separate NIC and the CCM board and screw will go through to the panel. Replace the display electronics board and reattach the 6 threaded spacers.

J-8

POWER SUPPLY REQUIREMENTS

The NIC is powered by the panel to which it is attached via the CCM board. No other power connections are required.

J-9

TESTING

5.

Testing is a function of the PEGAsys system in which the NIC is installed. No local test functions exist. For more information on testing the NIC and the network, see the PEGAsys Configuration Software (PCS) Program User's Guide.

6. 7. 8.

J-10

SPECIFICATIONS
Input Voltage Supervisory Current Alarm Current 24 VDC 50 mA max. 50 mA max.

9.

10. Carefully plug in the membrane keypad and attach the 4 screws. Make sure pins and receptacle are properly aligned. 11. Attach network wiring as previously described. 12. Reinstall programming and configure the network using PCS. See J-2.
20-PIN RECEPTACLE FOR NIC

LONG SCREW AND SPACER THROUGH HERE INSERT PLASTIC STANDOFFS HERE

DISPLAY PORT PRINT PORT P.C. PORT

I/O PORT Rx/Tx PORT


I/O PORT RX/TX PORT

DISP PORT

PRINT PORT

P.C. PORT

Figure J-5. CCM Board Showing NIC Attachment Points

J-7.6

Replacing Firmware Chips

For complete instructions, see PEGAsys Firmware Upgrade datasheet (P/N 06-235763-001). This document covers the CCM EPROM. Be sure to follow ESD prevention procedures.

August 1999

J-6

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX K ADDRESSABLE SIGNAL/SOUNDER MODULE

K-1

INTRODUCTION

K-3

OPERATION

The SmartOne Addressable Signal/Sounder Module (ASM) is an intelligent field device that contains its own microprocessor, 4K of memory, and all necessary electronics to provide standard notification or audio output. Connection is via the SmartOneTM compatible control panels power/communication line. This component is a UL Listed field device. The ASM can be individually field programmed via hardware to support notification appliances and NFPA Style Y (Class B) or Style Z (Class A) operation. See Figure K-2 for audio/auxiliary notification appliance switch and jumper selections, and NFPA operation Style Y/Z terminal selections. NOTE: The ASM is not intended to be used as a releasing device and is not compatible with solenoids or squibs. For installation details and complete electrical and mechanical specifications, see the ASM Installation Data Sheet (P/N 06235717-001).
AUXILIARY MODE P1=2&3 S1=1&2 ON KIDDE-FENWAL, INC. ASHLAND, MA 01721 U.S.A. CAT. NO. 70-200200-001 INSTRUCTIONS P/N 06-235717-001 PC LINE TERMINALS - POWER LIMITED ALL OTHERS - POWER LIMITED DEVICE ADDRESS # _ _ _ _

Once installed and configured, the ASM requires little or no maintenance. The module's 24 VDC or 25/70 VAC modes can be changed from the factory defaults using switch S1 and jumper P1 (See Figure K-1).

K-4

FUNCTIONAL DESCRIPTION

The SmartOne Addressable Signal/Sounder Module (ASM) provides a fully supervised remote-output circuit for connection to either 24 VDC audible/visual notification signaling devices or 25/ 70.7 V RMS speakers. The module provides continuous internal supervision of: Alarm contact position Connections to loop voltage and communications Internal power supply Auxiliary power supply connections and status Memory status

PC LINE

TM
AUX./AUDIO MODE SETTINGS
AUX. IN TROUBLE CKT.

The output circuit is monitored by reverse polarity and will not actuate into a short. If the circuit has a ground fault, open, short or a relay contact failure, the device will transmit a specific trouble status. A status LED is mounted on the unit and indicates the output circuit status by a 2 second (active) or 9 second (normal) flash interval. A trouble condition inhibits the status LED completely.

ADDRESSABLE SIGNAL/SOUNDER MODULE (ASM)


AUDIO MODE P1=1&2 S1=3 ON

+ -

+ -

+ -

OUTPUT CKT.

UL
R

FM
APPROVED

K-5

MAINTENANCE OR REPLACEMENT

Figure K-1. ASM Front Panel

The ASM is shipped from the factory as an assembled component and is not field serviceable. Little or no maintenance is required. Testing is accomplished through the testing capabilities of the PEGAsys panel. See Chapter 5, Troubleshooting and Corrective Maintenance, for particulars. In the event of a failure, the module should be replaced. For replacement, follow the instructions in the ASM Installation Data Sheet.

K-2

ADDRESSING AND REGISTRATION

As with any SmartOne loop device, addressing is through the Kidde hand-held programmer (P/N 74-200013-001) or the PEGAsys control panel menu/keypad as described in Chapter 2 of this manual. Module-programmable parameters include owners-location message, non-silenceable (waterflow), walk test, drill mode and silence. The programming process is described in PEGAsys Configuration Software (PCS) Program Users Guide, 76-014, (P/ N 06-235766-001). Addressing and programming the module's registration into the PEGAsys system is described in Paragraph 2-8 (and sub-paragraphs) of this manual. Registration of the module at the PEGAsys panel is mandatory to ensure proper operation.

76-100016-001

K-1

August 1999

PEGAsys
K-6 PARTS LIST K-7.2

Intelligent Suppression Control/Fire Alarm System

Output Circuit Characteristics


2.0 A max. @ 30.0 VDC 20.0 W @ 70.7 V RMS 20.0 W @ 25.0 V RMS

Output Circuit Rating

The following parts are required for installation and operation. All are supplied with the ASM. Addressable Signal/Sounder Module P/N 70-200200-001 Front Cover Plate P/N 06235714-001 End-of-Line (EOL) Resistor, 4.7 K Ohms, 1/2 W P/N 06-250166-452 End-of-Line (EOL) Resistor, 47 K Ohms, 1/2 W P/N 06-250166-596 Installation Data Sheet, P/N 06-235717-001

Maximum Line Resistances (with 12 AWG wire)

Load (amps) 0.22 0.55

Resistance (ohms) 20.0 8.0 4.0 2.7 2.0

Length (feet)* 12.0k 5.0k 2.5k 0.6k 1.2k

K-7

INSTALLATION

1.00 1.50 2.00

Refer to Figure K-2 and to the ASM Installation Instruction Data Sheet.

K-7.1

Installation Notes

Consider total line lengths from module to field and return.

The ASM single printed circuit board is intended for indoor use and can be mounted in a North American 4-11/16" electrical box, or 4" square 2-1/8" deep box. The module terminal block will accept #12, #14, #16 and #18 AWG wire (4.0 mm2, 2.5 mm2, 1.5 mm2 & 1.0 mm2 respectively). Size #18 AWG being a minimum requirement. The use of solid wire and an extension ring is recommended. Strip 1/4" from the ends of all wires that connect to the terminal block of the module.
1/4 (6.4mm) NTS

CAUTION Exposing more than 1/4 of wire may cause a ground fault. Exposing less than 1/4 of wire may result in a faulty connection. Refer to the National Electrical Code for proper box specifications. ASM volume is 8.94 cubic-inches. Refer to the RX/TX specifications in the chapters on Operation, and Functional Description for addressable-loop wiring specifications. Power/Communication (PC) line wiring is power limited and supervised. For power-limited circuits, use Type FPL, FPLR, or FPLP cable per Article 760 of the National Electrical Code (NEC). The note located on the module's product label (ALL OTHERSPOWER LIMITED) must be removed if the module is connected to a non-power limited supply source. If the auxiliary notification appliance power source is not power limited, the output circuit, auxiliary input circuit, and the trouble circuit are non-power limited. Otherwise, all three circuits are power limited. Supervision of audio to ASM must be provided by the audio equipment. Power limited or non-power limited amplifier outputs are available.

August 1999

K-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX L REMOTE DISPLAY CONTROL MODULE AND REMOTE DISPLAY MODULE


L-1 INTRODUCTION
This manual contains the information necessary to support the PEGAsys Remote Display Control Module (RDCM)(Figure L-1), P/N 76-300000-502, and Remote Display Module (RDM)(Figure L-2), P/N 76-300000-501. Both modules function as remote addressable adjuncts to the PEGAsys and mimic the main control panels LCD and LED front displays. Additionally, the RDCM contains system control switches and a tactile response numeric keypad. These controls match the PEGAsys layout. The RDM does not permit operation of the control features (operation is read only). The RDCM is key and password secured with the password needed being the one used on the associated PEGAsys panel. as the maximum quantity for each module is not exceeded. The RDCM, in addition to emulation of the PEGAsys LEDs and LCD displays, provides remote access to the system and, if programmed, the PEGAsys network panel(s) and menu options via this emulation of the PEGAsys front panel function and numeric keys. Remote power is required and can be provided by the control panel PSU or a separate supply UL listed for fire alarm application. In each instance, remote power is supervised by the RDCM and RDM with failure displayed locally and at the control panel. The units also contain a buzzer with sequencing that follows the buzzer contained in the control panel. Either the PEGAsys control panel or one RDCM can be programmed as the master unit to control the system under alarm or fault conditions. Operation of an alternate (non-master) unit will grant that module exclusive control over the system for 30 seconds. Under these conditions, attempts to input from another module will prompt a lockout display message on the module attempting the interrupt. This acts to prevent conflicting inputs. Under all circumstances, the master will be granted immediate system control.

System Status Display

AC POWER ALARM PRE-ALARM

SYSTEM TROUBLE SUPERVISORY SILENCE 1

SYSTEM ACKNOWLEDGE SYSTEM RESET 2 3 4

SILENCE

SCROLL

L-2.1

Operator Interface

Figure L-1. RDCM Front Panel

All operator interfaces are contained in the front panel assembly. Operator inputs are passed to the PEGAsys for processing. The RDCM operator-interface function keys are: Acknowledge: Acknowledge alarms/troubles and silence all local buzzers. Silence: Silence signal/audibles after Acknowledge. Reset: Reset latched alarm conditions. Scroll: Review active alarms/troubles.

System Status Display


SCROLL

AC POWER ALARM PRE-ALARM

SYSTEM TROUBLE SUPERVISORY SILENCE

NOTE: Drill operation is available through the PEGAsys menu. The RDCM operator interface needed to enter the password and access the PEGAsys menu is provided via the alphanumeric keypad: 0 - 9: Used to enter digits to access PEGAsys menus. Delete: Used to exit menu and correct entries. Enter: Used when selecting from PEGAsys menus.

Figure L-2. RDM Front Panel Module installers must be fully factory trained in all aspects of the PEGAsys system. Additional supporting documentation is also contained in this manual and in the PEGAsys Configuration Software (PCS) Program, Users Guide 76-014, P/N 06235766-001.

NOTE: Operation of above keys will be hereinafter described. The RDCM and RDM operator interface status LEDs for monitoring the PEGAsys and remote modules are: Alarm: Indicates an alarm condition. Trouble: Indicates a trouble condition. Silence: Indicates PEGAsys signal/audibles have been silenced after Acknowledge. Supervisory: Indicates a supervisory condition. Power-on: Indicates the system is receiving AC power. Pre-alarm: Indicates a smoke or thermal detector is in preAugust 1999

L-2

GENERAL DESCRIPTION


L-1

The RDCM and RDM communicate with the PEGAsys via an RS-485 interface (one pair #18 AWG, twisted/shielded wire) in a multi-drop configuration capable of supporting up to 15 RDCM display/control and 16 RDM display only modules. The installation can be in any combination of RDCM/RDM modules so long
76-100016-001

PEGAsys
alarm condition. CPU fail: Mounted on main PCB and available to the installer only. Indicates RDCM/RDM processor has failed to initialize. Red: Alarm. Green: Power-on. Yellow: CPU failure, trouble, silence, supervisory and prealarm.

Intelligent Suppression Control/Fire Alarm System

L-3

OPERATION

LED colors used to represent indications are:

Before proceeding with operations, please become totally familiar with PEGAsys Fire Alarm/Suppression Control System manual, especially the sections on Active Alarm Mode, Active Supervisory Trouble Mode, and Active Trouble Mode. Please note differences between latching and non-latching Active Alarm Modes. For RX/TX loop input devices. To set either latching or nonlatching, please refer to the PEGAsys Configuration Software (PCS) manual, PCS Operations chapter. The following example is for latching alarm mode (for these examples, assume the device to be manual release, address 1004). In Normal Standby Mode, the display will show: SYSTEM STATUS NORMAL 10:00AM 06-08-99 PEGASYS In practice, the actual local time and date will be presented. When a RX/TX loop device goes into active alarm, the display will show: 1004 ALARM ON - MANUAL RELEASE Default or user text

The RDM functions as read only. Therefore, it has a scroll key, but does not provide the other function keys nor an operable keypad.

L-2.2

Interconnection

The RDCM and RDM operate on a shared RS-485 bus which supports wire runs of up to 4000 ft. from the PEGAsys control panel. The primary RS-485 bus from the PEGAsys will support up to 15 RDCMs and 16 RDMs in any combination not exceeding maximum of each module.

L-2.3

Addressing

Address selection is via setting of the 16-way, 4-bit hexadecimal coded rotary switch, SW1, mounted on the printed circuit board. See Figure L-4. Table L-1. Address Switch Settings

L-3.1

Switch Functions

The switch functions are listed in sequence of use:

Switch Setting 1 2 3 4 5 6 7 8

RDM/RDCM Address RDM or RDCM 01 RDM or RDCM 02 RDM or RDCM 03 RDM or RDCM 04 RDM or RDCM 05 RDM or RDCM 06 RDM or RDCM 07 RDM or RDCM 08

Switch Setting 9 A B C D E F 0

RDM/RDCM Address RDM or RDCM 09 RDM or RDCM 10 RDM or RDCM 11 RDM or RDCM 12 RDM or RDCM 13 RDM or RDCM 14 RDM or RDCM 15 RDM 16

L-3.1.1 ACKNOWLEDGE All ALARM ON, ALARM OFF, TROUBLE ON/OFF, or SUPERVISORY ON/OFF messages must be acknowledged by operation of this switch. Multiple alarms must be individually acknowledged, all other multiple inputs will default to individual acknowledge, but may be programmed to global acknowledge by accessing the SET" menu from the PEGAsys or any RDCM. The RDCM will pass the acknowledge input to the PEGAsys causing its LED to go from a pulsing to a steady mode, and the buzzer to silence. The PEGAsys sends a global command to silence all remote RDCM/RDM buzzers. The PEGAsys sends out a global lockout command to all other RDCMs. This gives the calling device exclusive control over the system for 30 seconds. Under these conditions, attempts to input from another module will prompt a lockout display message (See Paragraph L-3.1.2 for example) on the module attempting the interrupt to prevent conflicting inputs. Under all circum-

PEGAsys
POWER SUPPLY DCM ASSEMBLY
AUX. 24V TB1 PINS + 5 6 TB1 PINS

TWISTED SHIELDED CABLE TO CHASSIS/EARTH GROUND. 1 2 7 8


IN PINS 3 & 4 ARE TIED TOGETHER WHEN USING THE PANELS POWER SUPPLY

RDCM/RDM ASSEMBLY 6 5
OUT

3 4 TB1 PINS

7 8

RDCM/RDM ASSEMBLY
IN

5 6 1 2

UP TO 31 REMOTE DEVICES

AUX. SUPPLY + - 24V


(IF REQ'D.)

3 4

TB1 PINS

TO TROUBLE CONTACTS CLOSED = NORMAL OPERATION

76-100016-001

PIN 1 OF TB1 IS AT TOP OF CONNECTOR NOTE: ALL CIRCUITS ARE SUPERVISED AND POWER LIMITED

Figure L-3. Interconnection of PEGAsys panel, RDM, RDCM(s)


August 1999 L-2 76-100016-001

Intelligent Suppression Control/Fire Alarm System stances, the module (or control panel) programmed as the system master will be granted immediate system control. The display at the calling device will then show: 1004 ALARM ON ACK - MANUAL RELEASE Default or user text (The default or user text is that entered at the associated PEGAsys panel. This message cannot be changed from the RDCM.) Then the display will show how many active alarms are still present in the system (if any), and subsequently display how many active trouble conditions are still present in the system (if any). For example: 001 ACTIVE ALARMS REMAINING Again in the case of multiple alarms (either On or Off), each event must be acknowledged separately. In the case of multiple troubles, actuation of the acknowledge input may be separate or programmed to global acknowledge. A maximum of 32 trouble message can be displayed/scrolled at any one time. For non-latching sequence, each ALARM OFF will display and must be acknowledged. 1004 ALARM OFF - MANUAL RELEASE Default or user text In the event of loss of communications between the RDCM and the PEGAsys on the RS-485 bus, the local buzzer will sound and the trouble LED will light. L-3.1.2 SILENCE When all alarm and trouble conditions have been acknowledged, operation of the silence switch will have the following results: The RDCM will pass the silence input to the PEGAsys causing all outputs programmed for silence to de-energize. The PEGAsys sends out a global lockout command to all other RDCM(s). This gives the calling device exclusive control over the system for 30 seconds. For these examples, assume RDCM address 02. If another (non-master) module attempts an interrupt, the following lockout message will display for 5 seconds: RDCM 02 IN CONTROL NOTE: RDCM 02 is the default. This message can be customized in PCS. Please refer to the PEGAsys Configuration Software (PCS) Program Manual After the 30 second control period, any other module can provide system inputs (unless a module programmed as system master assumes control). L-3.1.3 RESET After all active alarms and troubles have been cleared, input devices programmed to the latching sequence will show: XXX ALARMS ACTIVE Input devices programmed to the non-latching sequence will show: NO ACTIVE ALARM REMAINS

PEGAsys
Now, operation of the reset switch will have the following results: The RDCM will pass the reset input to the PEGAsys causing all conditions programmed to cancel on reset to de-energize. The PEGAsys sends out a global lockout command to all other RDCMs. This gives the calling device exclusive control over the system for 30 seconds and displays the following message: SYSTEM RESET If there are no further key entries at the calling device (address 02), and no further system events are detected, all modules and the PEGAsys will display the system default message: SYSTEM STATUS NORMAL 10:00AM 03-08-99 PEGASYS In practice, the actual local time and date will be presented. In the event of an RDCM's microprocessor going into fault condition, actuation of hardware switch S3 located behind the display membrane will cause a hardware reset of the microprocessor. L-3.1.4 SCROLL When the Scroll key is pressed during any active system event, the following will result: The PEGAsys sends out a global lockout command to all other RDCM(s). This gives the calling device (address 02) exclusive control over the system as described in reset above. NOTE: The RDM scroll key does not provide the global lockout command. The PEGAsys, RDCMs and RDMs will then be updated by the next event in the buffer. When a Scroll key is actuated at any RDCM, RDM or the PEGAsys, the resulting scroll display is sent globally to the system. LED Test Feature: With no active inputs, press and hold the scroll key for 2 seconds. All LEDs will light for 5 seconds. System Information Entry Keys: To enter passwords and gain access the PEGAsys menu functions, the relevant keys are: Numeric 0-9: Enters password and system function information. Enter: Enter information into the system menu. Delete: Exit system menu and correct wrong entries.

To enter the password, press the 0 key. The RDCM opens the password entry menu and displays: PLEASE ENTER PASSWORD Each key entry will then display the # character: PLEASE ENTER PASSWORD #### If the password entry is incorrect, the display will become: PASSWORD ENTRY FAILED The RDCM will request another password entry request, and, if correct, the PEGAsys will send the 30 second global lockout
L-3 August 1999

76-100016-001

PEGAsys
command to all other RDCMs. The calling device (address 02) will then have access to the PEGAsys menu. Please refer to this manual for menu operating instructions. If during the password entry sequence any key other than the numeric key (except Delete) is pressed before the Enter key, the PEGAsys will update the RDCM with the default display.

Intelligent Suppression Control/Fire Alarm System

L-4

SPECIFICATIONS

ELECT RICAL Input voltage Supervisory current Alarm current RS-485 network 24 VDC nominal 64 mA nominal 85 mA nominal Up to 4000 ft from FenwalNET control panel using #18 AWG twisted/shelded wire 15 RDCMs/16 RDMs in any combination, not exceeding maximum for each module NFPA Style 4, Class "B"

L-3.2

LED Status Display

The front panel display LEDs will operate in three modes: Off: No system activity. On Continuously: Acknowledge alarm or trouble. Pulsing: 1 second on, 1 second off; active alarm or trouble.

L-3.3

LCD Display

Maximum RDCM/RDMs

With no active events in the system, all RDCM/RDMs will display the default message: SYSTEM STATUS NORMAL 10:00am 03-08-99 PEGASYS PEGASYS is the default message. This can be customized by PCS. Please refer to the PEGAsys Configuration Software (PCS) Program manual.

Wiring style

MECHANICAL Dimensions Weight 12.05" W X 7.156" H 4 lbs, 13 oz

L-3.4

Password Data Structure

Two system levels are available from the RDCM. These are: Level 1, User Level and Level 2, Installer Level. Please refer to the Menu Function and Menu Structure sections of the PEGAsys Fire Alarm/Suppression Control System manual for descriptions of the capabilities available through these levels. Each PEGAsys is shipped from the factory with default passwords for Level 1 of 987 and Level 2 of 1865. Default passwords can be customized in the level 2 Set Menu Function. Changing passwords for the system can be accomplished from any RDCM or directly from the PEGAsys.

ENVIRONMENTAL Operating temperature Operating humidity


L-5 INSTALLATION

32oF (0oC) - 120oF (49oC) 85% non-condensing

See Figure L-4.

L-3.5

RDCM/RDM Local Trouble Conditions

The RDCM/RDM is supervised for failure of the power supply and failure to communicate with the PEGAsys during the polling routine. The power failure display is: REMOTE PSU FAULT ON RDCM XX If no communication is detected with the PEGAsys during the polling routine and the PSU is active, a local trouble message will be displayed on the RDCM/RDM. NO COMMUNICATION WITH MAIN PANEL

August 1999

L-4

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys
.409

MOUNTING FOR #10 (.190 DIA.) SCREWS

12.000 5.875 9.500

SW1 ADDRESS 1 TO 16 (F) W1 LED BACKLIGHT ENABLE VR1 LED BACKLIGHT ADJUST 1/2" & 3/4" COMBINATION KNOCKOUTS (2) LOCATED ON TOP SURFACE (1) LOCATED ON EACH SIDE. VR2 LCD CONTRAST ADJUST

1.250

DS1
. ND OU GR

SW3 HARDWARE FOR GND. CONNECTION CONNECTOR

ED IELD D SH ISTE TW

LE CAB

TO

RTH EA SIS/ AS CH

R WE PO

LY PP SU
FM
VED RO APP

UL
R

INSTRUCTION LABEL
. NO R. SE

Figure L-4. Installation of RDM or RDCM

76-100016-001

L-5

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

L-6

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX M ADDRESSABLE ALARMLINE MODULE

M-1

INTRODUCTION

M-3

OPERATION

The Addressable AlarmLineTM Module (AAM) permits an AlarmLine sensor cable to be directly interfaced to the PEGAsys control panel. This interface will allow for pre-alarm, alarm, and trouble conditions to be transmitted to the control panel via the RX/TX (Receive/Transmit) loop. The AAM monitors the resistance of the sensor cable and generates a pre-alarm (if enabled), alarm, or overheat output (if enabled) when the resistance drops below the programmed threshold. The module also supervises the AlarmLine cable for opens and shorts, which will generate a fault condition. All of the pre-alarm, alarm, overheat, and trouble conditions will be displayed on the Central Control Module (CCM) of the PEGAsys panel. Up to 255 AAM modules can be connected to a single RX/TX module. Use of multiple AAMs allows flexibility in zoning larger installations for location of alarm and zone output control; the control panel acts as a central display and control interface. For complete information, please refer to the AlarmLine Addressable Linear Heat Detector Installation, Operation and Maintenance Manual (73.04).

A change in temperature produces a change in resistance between the loops within the sensor cable (as the temperature increases, resistance decreases exponentially). This change is continuously monitored by the AAM, which generates an alarm or pre-alarm signal at a predetermined level corresponding to the temperature set point. The temperature at which the system will alarm is determined by selecting one of 16 configuration settings using the control panels configuration software or CCM menu options. The appropriate configuration setting for a given set point is established by the use of a nomogram incorporating two know factors: Maximum ambient temperature of the alarm zone Length of the sensor cable

The integrating (averaging) effect of the sensor cable allows it to detect localized hot spot or a low level temperature increase over the entire length. For more detailed information, please refer to the AlarmLine Addressable Linear Heat Detector Installation, Operation and Maintenance Manual.

TM

M-4

MAINTENANCE OR REPLACEMENT

The AAM is shipped from the factory as an assembled component and is not field serviceable. Little or no maintenance is required. Refer to Chapters 4 and 5 of this manual and to the AlarmLine Addressable Linear Heat Detector Installation, Operation and Maintenance Manual for further information on maintenance and testing of field devices connected to the FN-2000 panel's RX/TX loop. Figure M-1. Addressable AlarmLine Module Front Panel

M-5

PARTS LIST

Refer to Section 9 of the AlarmLine Addressable Linear Heat Detector Installation, Operation and Maintenance Manual.

M-2

ADDRESSING AND REGISTERING M-6 INSTALLATION

Each AAM is shipped from the factory with the default address of 000. This permits connection to the Power Communication (PC) line without interfering with devices already on the loop. Only one device with this default address should be connected to the PC line at a time. Alternately, the AAM address can be preset with a hand-held programmer (P/N 74-200013-001) after which the module can be connected to the PC line. If a handheld programmer is not available, the address can be changed directly at the CCM using the procedure outlined in Chapter 2 of this manual.

Refer to Paragraph 3-2 of the AlarmLine Addressable Linear Heat Detector Installation, Operation and Maintenance Manual.

M-7

TESTING

Refer to Section 7 of the AlarmLine Addressable Linear Heat Detector Installation, Operation and Maintenance Manual.

76-100016-001

M-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

M-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX N NETWORKABLE CENTRAL CONTROL MODULE (NCCM)


play the current time and date on the system LCD and provides basic information for real-time operations. Internal diagnostics enhance the troubleshooting ability of the system. Examples include: microprocessor failure, memory failure, RS-232 port troubles, etc. Network diagnostics are separately controlled and report to appropriate panels. Two individually programmable signal output circuits (MP1 & MP2) provided are used primarily for signaling devices (horns, bells, strobes) and deliver up to 2.0 amps of 24 VDC power. The MP1 output can be optionally programmed for releasing applications using solenoid-actuated suppression equipment (agent and sprinkler). Two individually programmable relay outputs (MP3 & MP4) are provided on the NCCM for controlling building functions during alarm occurrences. Relays are Form C, 1 Amp @ 30 VDC rated. All four NCCM outputs can be programmed via EOC to activate from either panel or, if provided, network inputs. One non-programmable trouble relay is supplied which is normally powered (24 VDC) and will transfer on any system (or, if provided, network) trouble, supervisory, pre-alarm and complete power-off condition. Relay is form C style, rated 1 Amp @ 30 VDC. Refer to Appendix I, page I-2, for mechanical installation details. An event history buffer is provided on the NCCM which will store 1024 entries for single-loop and 6100 entries for multi-loop system events information. Network option does not alter event limits however, network events are recorded. The system menu permits operator retrieval of recorded events. The PCS program provides the ability to download, store and print all or a portion of the event history buffer. The NCCMs common display module assembly (which is physically and electronically attached to the main processor module) provides the system with the operator interface and, if provided, network interface for control switches, system status LEDs, system trouble/alarm buzzer, an 80 character (2x40) LCD display and an integral numeric keypad. The keypad is used for entering the security password and navigating through the user menus. The system buzzer provides two distinct signaling patterns for audible warning of system alarms and troubles.

N-1

INTRODUCTION

The Networkable Central Control Module (NCCM), shown in Figure N-1, is the heart of the PEGAsys system and is composed of two printed circuit board assemblies; the display control module (DCM), and the CCM printed circuit board. The NCCM is available in two versions, P/N 76-100008-501 for single-loop systems and P/N 76-100008-600 for multi-loop systems.

System Status Display

AC POWER ALARM PRE-ALARM

SYSTEM TROUBLE SUPERVISORY SILENCE 1

SYSTEM ACKNOWLEDGE SYSTEM RESET 2 3 4

SILENCE

SCROLL

Figure N-1. Networkable Central Control Module Front Panel The NCCM is essentially identical to the CCM described earlier in this manual, and has the same capabilities. However, the CCM printed circuit board has been designed to receive the optional Network Interface Card (See the physical description and menu options in Appendix J of this manual), enabling networked operation. Additionally, the display control module adjunct to the main processor module provides connection to the Remote Display Control Module (RDCM) and Remote Display Module (RDM) described in Appendix L of this manual.

N-2

CONFIGURATION/FUNCTION

The CCM PCB controls the operation and supervision of all the system modules and software within the PEGAsys system. It receives loop device data from the RX/TX module, and system data from the optional NIC and/or RDCM. It processes the data based on pre-programmed instructions and transmits output commands to the output modules, optional NIC and/or RDCM or RDM modules, loop output devices, and the adjunct display control module. The CCM PCB contains the systems CPU, real-time clock, watchdog timer and two serial RS-232 ports: A programming input/output and a remote printer output port. These ports accept 6-wire RJ-12 modular connectors. PEGAsys Configuration Software (PCS) is used to program the system. A multilevel password scheme protects the system from unauthorized access. The real-time clock provides the NCCM with the ability to dis-

76-100016-001

N-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

N-2

76-100016-001

Intelligent Suppression Control/Fire Alarm System

PEGAsys

APPENDIX O CENTRAL STATION OPERATION

O-1

CENTRAL STATION OPERATION

For central station operation, the PEGAsys control panel must be configured for central station use through PCS menu (Network Settings). A Silent Knight DACT Model 5104 must be wired to the PEGAsys control panel as shown in Figure O-1. See Model 5104 Installation Manual for information regarding connection of the DACT to the telephone line for alarm and trouble transmission(s).

Silent Knight DACT Model 5104 PCB

NO NC C Volt Free Relay 2

NO NC C Fault Relay

PegaSYS CCM PCB

4.7k 8 9 4.7k 10 11 12 Zone 4 Trouble Zone 3 Alarm

18 17 16 15 14 13

Figure O-1. Wiring for DACT

76-100016-001

O-1

August 1999

PEGAsys

Intelligent Suppression Control/Fire Alarm System

(THIS PAGE INTENTIONALLY LEFT BLANK)

August 1999

O-2

76-100016-001

TECHNICAL MANUAL USER FEEDBACK FORM


(Use this report to indicate deficiencies, user remarks and recommendations relating to the publication. Fold on dotted line, tape and mail to KIDDE-FENWAL, Inc., 400 Main Street, Ashland, MA 01721, Attn. Documentation Manager or FAX to 508-881-8920)

DATE: 1. PART NUMBER 2. VOLUME NO. 3. TITLE (NOMENCLATURE) 5. SYSTEM/EQUIPMENT 6. PRIORITY OF COMMENT

4. CHANGE NO. OR REV. DATE 7. USER EVALUATION MANUAL IS: 8.

G EXCELLENT G QUESTION

G GOOD

G FAIR

G POOR

G COMPLETE

G INCOMPLETE

G PROBLEM

G SUGGESTION G COMMENT: (check one)

9. RECOMMENDED CHANGE TO PUBLICATION PAGE PARAGRAPH LINE FIGURE TABLE NO. NO. NO. NO. NO. RECOMMENDED CHANGES AND REASON (Use Blank Continuation Sheets as Required)

10. ORIGINATOR 12. ADDRESS

11. COMPANY NAME

13. KIDDE-FENWAL USE ONLY a. Received b. Action Necessity c. Priority d. Comments

220423

FOLD

Place Stamp Here

KIDDE-FENWAL, Inc. 400 Main Street Ashland, MA 01721 Attn. Documentation Manager

FOLD

220423

LIMITED WARRANTY STATEMENT Kidde-Fenwal, Inc. represents that this product is free from defects in material and workmanship, and will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of twelve (12) months from the date of purchase but not to exceed eighteen (18) months after shipment by the manufacturer. For a full description of KiddeFenwals LIMITED WARRANTY which, among other things, limits the duration of warranties of MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE and EXCLUDES liability for CONSEQUENTIAL DAMAGES, please read the entire LIMITED WARRANTY on the Kidde-Fenwal Quotation, Acceptance of Order, and/or Original Invoice which will become part of your sales agreement. Please contact Kidde-Fenwal directly for a return material authorization (RMA) number before returning material to the factory at Ashland, Massachusetts, shipment prepaid. Kidde-Fenwal will repair or replace and ship prepaid.

Fire Systems

Kidde-Fenwal Inc. 400 Main Street Ashland, MA 01721 (508) 881-2000 Fax: (508) 881-8920

These instructions do not purport to cover all the details or variations in the equipment described, nor do they provide for every possible contingency to be met in connection with installation, operation and maintenance. All specifications subject to change without notice. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchasers purposes, the matter should be referred to Kidde-Fenwal Inc., Ashland, MA.

76-100016-001

Rev. BB

1998 Kidde-Fenwal Inc.

Printed in USA