You are on page 1of 43

North American

Power Fuses
The most popular North American
power fuses to meet the most
popular protection priorities.
Class RK5 / Tri-onic

TR & TRS
DC-rated / Tri-onic

TRS-RDC
Class J / Amp-trap

HSJ
Class J / Amp-trap

A4J
Class L / Amp-trap

A4BY
Class L / Amp-trap

A4BT
Class T / Amp-trap

A3T & A6T


Class RK1 /
Amp-trap

A2K & A6K


Class RK1/Amp-trap

HSRK
Class G / Amp-trap

AG
Class CC / Amp-trap

ATMR
Class K-5 / OT, OTN &
OTS One-time
Class H / RF/RFS &
RL/RLS Renewable
Your problem: Today, you need a time-delay power fuse that
can handle normal surges. Tomorrow, its a power fuse with a
high interrupting rating and the added security of rejection dimen-
sions. The day after that, one of those economical one-time power
fuses will do the trick. But where can you turn for all three?
Our solution: Ferraz Shawmuts comprehensive power fuse
offering covers a complete range of applications and a complete
range of circuit-protection needs. Whether its the characteristics
of our Tri-onic

time-delay fuses. The high current-limiting capacity


of our original Amp-trap

power fuses. The cost-efficient protec-


tion of our One-Time fuses. Or some other application-specific
power fuse solution.
Want more information fast? For more technical or application-
specific information, please call our Power Fuse experts, at
978-462-6662; 416-252-9371 in Canada; or visit our website
at us.ferrazshawmut.com.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 2
Time Delay/Class RK5
TR
aC: 1/10 to 600A
250VAC, 200kA I.R.
DC: 1/10 to 2 8/10A
& 35 to 400A, 250VDC,
20kA I.R.; 3 to 30A &
450 to 600A, 160VDC,
20kA I.R.
TRs
aC: 1/10 to 600A
600VAC, 200kA I.R.
DC: 1/10 to 12A,
600VDC, 20kA I.R.;
15 to 60A, 300VDC,
20kA I.R. 70 to 600A,
600VDC, 100kA I.R.

TRi-ONiC
TR & TRs
Ratings
Features/Benefits
solid state smartspot indicator
Time delay for motor start-ups and transformer inrush
currents without nuisance opening
Current limiting for low peak let-thru current
Rejection-style design prevents replacement errors
(when used with recommended fuse blocks)
easy-to-read label for quick recognition
and replacement
metal-embossed date and catalog number for
traceability and lasting identification
Fiberglass body provides dimensional stability in
harsh industrial settings
High-grade silica filler ensures fast arc quenching and
high current limitation

THe iNDusTRys mOsT pOpulaR Fuse FOR


mOTOR CiRCuiT pROTeCTiON.
Tri-onic

SmartSpot

fuses now provide a visual


open fuse indicator. With advanced material technol-
ogy added to the existing product the TR and TRS
current limiting time delay fuses are engineered for
overcurrent protection of motors and transformers,
service entrance equipment, feeder and branch
circuits. Tri-onic proven time delay characteristic
safely handles harmless starting currents and inrush
currents associated with todays motors and
transformers.
UL Listed to Standard
248-12 File E2137
CSA Certified to
Standard C22.2
No. 248.12
DC Listed to UL
Standard 248 TRS only

approvals
appliCaTiONs:
Motor Circuits
Mains
Feeders
Branch Circuits
Transformers
Service Entrance
Equipment
General-purpose
Protection

HiGHliGHTs:
Time Delay
Current Limiting
AC & DC Rated

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 3
TR & TRs
TRi-ONiC

AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber


Rating 250V 600V Rating 250V 600V Rating 250V 600V
1/10 TR1/10R TRS1/10R 3-1/2 TR3-1/2R TRS3-1/2R 50 TR50R TRS50R
15/100 TR15/100R TRS15/100R 4 TR4R TRS4R 60 TR60R TRS60R
2/10 TR2/10R TRS2/10R 4-1/2 TR4-1/2R TRS4-1/2R 70 TR70R TRS70R
3/10 TR3/10R TRS3/10R 5 TR5R TRS5R 75 TR75R TRS75R
4/10 TR4/10R TRS4/10R 5-6/10 TR5-6/10R TRS5-6/10R 80 TR80R TRS80R
1/2 TR1/2R TRS1/2R 6 TR6R TRS6R 90 TR90R TRS90R
6/10 TR6/10R TRS6/10R 6-1/4 TR6-1/4R TRS6-1/4R 100 TR100R TRS100R
8/10 TR8/10R TRS8/10R 7 TR7R TRS7R 110 TR110R TRS110R
1 TR1R TRS1R 8 TR8R TRS8R 125 TR125R TRS125R
1-1/8 TR1-1/8R TRS1-1/8R 9 TR9R TRS9R 150 TR150R TRS150R
1-1/4 TR1-1/4R TRS1-1/4R 10 TR10R TRS10R 175 TR175R TRS175R
1-4/10 TR1-4/10R TRS1-4/10R 12 TR12R TRS12R 200 TR200R TRS200R
1-6/10 TR1-6/10R TRS1-6/10R 15 TR15R TRS15R 225 TR225R TRS225R
1-8/10 TR1-8/10R TRS1-8/10R 17-1/2 TR17-1/2R TRS17-1/2R 250 TR250R TRS250R
2 TR2R TRS2R 20 TR20R TRS20R 300 TR300R TRS300R
2-1/4 TR2-1/4R TRS2-1/4R 25 TR25R TRS25R 350 TR350R TRS350R
2-1/2 TR2-1/2R TRS2-1/2R 30 TR30R TRS30R 400 TR400R TRS400R
2-8/10 TR2-8/10R TRS2-8/10R 35 TR35R TRS35R 450 TR450R TRS450R
3 TR3R TRS3R 40 TR40R TRS40R 500 TR500R TRS500R
3-2/10 TR3-2/10R TRS3-2/10R 45 TR45R TRS45R 600 TR600R TRS600R
StandardFuseAmpereRatings,CatalogNumbers
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
250V-TRFUSES
0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-TRSFUSES
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
Fuse CatalogNumber
Ampere250V600V
Rating 1Pole 3pole 1pole 3pole
0-30 20306R 20308R 60306R 60308R
31-60 20606R 20608R 60606R 60608R
61-100 21036R 21038R 61036R 61038R
101-200 22001R 22003R 62001R 62003R
201-400 24001R 24003R 64001R 64003R
401-600 2631R 2633R 6631R 6633R
RecommendedFuseBlocksWith
BoxConnectorsForTri-onic

ClassRK5Fuses
0-60A
61-600A
Note: Indicator not available (1/10 - 7) amps.
Time Delay/Class RK5 Fuses
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 4
TimeinSeconds
C
u
r
r
e
n
t

i
n

A
m
p
e
r
e
s
Time Delay/Class RK5 Fuses
TRi-ONiC

TR1/10 TO 12
m
e
l
t
i
n
g

T
i
m
e


C
u
r
r
e
n
t

D
a
t
a
,

2
5
0
V

F
u
s
e
s
TimeinSeconds
C
u
r
r
e
n
t

i
n

A
m
p
e
r
e
s
TR15 TO 600
m
e
l
t
i
n
g

T
i
m
e


C
u
r
r
e
n
t

D
a
t
a
,

2
5
0
V

F
u
s
e
s
TR & TRs
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 5
Time Delay/Class RK5 Fuses
TimeinSeconds
C
u
r
r
e
n
t

i
n

A
m
p
e
r
e
s
TRi-ONiC

TRs1/10 TO 12
m
e
l
t
i
n
g

T
i
m
e


C
u
r
r
e
n
t

D
a
t
a
.

6
0
0
V

F
u
s
e
s
TimeinSeconds
C
u
r
r
e
n
t

i
n

A
m
p
e
r
e
s
TRs15 TO 600
m
e
l
t
i
n
g

T
i
m
e


C
u
r
r
e
n
t

D
a
t
a

,

6
0
0
V

F
u
s
e
s
TR & TRs
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 6
Time Delay/Class RK5 Fuses
TRi-ONiC

AvailableCurrentinRMSSymmetricalAmperes
M
a
x
i
m
u
m

I
n
s
t
a
n
t
a
n
e
o
u
s

P
e
a
k

L
e
t
-
T
h
r
u

A
m
p
e
r
e
s
AvailableCurrentinRMSSymmetricalAmperes
M
a
x
i
m
u
m

I
n
s
t
a
n
t
a
n
e
o
u
s

P
e
a
k

L
e
t
-
T
h
r
u

A
m
p
e
r
e
s
peak let-Thru Current Data TR30 to 600, 250 Volts aC
peak let-Thru Current Data TRs15 to 600, 600 Volts aC
Note: See Application Information
page L9 for All Motor and
Transformer Tables.
TR & TRs
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 7
TRi-ONiC

TRs-RDC
appliCaTiONs:
Mine Circuits
Trailing Cables
Pump Motors
Rail Heaters

DC: 1 to 30A
300VDC, 20kA I.R.
(Consult Factory for
Availability)
DC: 35 to 400A
600VDC, 20kA I.R.

Ratings
Features/Benefits
DC rated for mine duty and other long time-constant
applications
Time delay for motor start-ups and high inrush loads
without nuisance opening
Rugged glass melamine body for superior
Reliability in harsh environments

DC RaTeD FOR TOuGH DC appliCaTiONs


The Tri-onic

DC fuse series is designed for DC


circuit protection in surface and underground mines.
The TRS-RDC is MSHA approved and meets the
industrys most severe third party requirements for
600VDC rated fuses.
The TRS-RDC is a time-delay fuse with essentially
the same time-current characteristic as the
standard Tri-onic

.
MSHA Approval
No. 28-26-0

approvals
HiGHliGHTs:
Time Delay
DC Rated

Time Delay/DC RaTeD


Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 8
AMPERE CATALOG
RATING NUMBER
1/10 TRS1/10RDC
15/100 TRS15/100RDC
2/10 TRS2/10RDC
3/10 TRS3/10RDC
4/10 TRS4/10RDC
1/2 TRS1/2RDC
6/10 TRS6/10RDC
8/10 TRS8/10RDC
1 TRS1RDC
1-1/8 TRS1-1/8RDC

AMPERE CATALOG
RATING NUMBER
1-1/4 TRS1-1/4RDC
1-4/10 TRS1-4/10RDC
1-6/10 TRS1-6/10RDC
1-8/10 TRS1-8/10RDC
2 TRS2RDC
2-1/4 TRS2-1/4RDC
2-1/2 TRS2-1/2RDC
2-8/10 TRS2-8/10RDC
3 TRS3RDC
3-2/10 TRS3-2/10RDC

AMPERE CATALOG
RATING NUMBER
3-1/2 TRS3-1/2RDC
4 TRS4RDC
4-1/2 TRS4-1/2RDC
5 TRS5RDC
5-6/10 TRS5-6/10RDC
6 TRS6RDC
6-1/4 TRS6-1/4RDC
8 TRS8RDC
9 TRS9RDC
10 TRS10RDC

AMPERE CATALOG
RATING NUMBER
12 TRS12RDC
15 TRS15RDC
17-1/2 TRS17-1/2RDC
20 TRS20RDC
30 TRS30RDC
35 TRS35RDC
40 TRS40RDC
45 TRS45RDC
50 TRS50RDC
60 TRS60RDC

AMPERE CATALOG
RATING NUMBER
70 TRS70RDC
80 TRS80RDC
90 TRS90RDC
100 TRS100RDC
125 TRS125RDC
150 TRS150RDC
175 TRS175RDC
200 TRS200RDC
250 TRS250RDC
300 TRS300RDC
400 TRS400RDC
Time Delay/600VDC Fuses
TRi-ONiC

StandardFuseAmpereRatings,CatalogNumbers
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
C
u
r
r
e
n
t

i
n

A
m
p
e
r
e
s
TimeinSeconds
0-60Amperes
61-400Amperes
TRs-RDC60 TO 400
m
e
l
t
i
n
g

T
i
m
e


C
u
r
r
e
n
t

D
a
t
a
,

6
0
0
V

F
u
s
e
s
TRs-RDC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 9
Features/Benefits
Optimized over-load capability for withstanding
elevated levels of current during electronic
motor controller starts
low i
2
t (low thermal energy)
excellent Cycling ability for frequent starts/stops
without nuisance opening

pROTeCT yOuR wiRiNG aND pOweR semi-


CONDuCTORs wiTH a siNGle Fuse.
The new High Speed J (HSJ) combines the low
I
2
t of a semiconductor fuse and the branch circuit
performance of a Class J UL listed fuse. This fuse
was designed for the starting characteristics of solid
state motor controllers. The HSJ can provide branch
circuit protection per NEC requirements, as well as
very low I
2
t for protection of power semiconductors
such as Diodes, SCRs, GTOs and SSRs.
appliCaTiONs:
Branch Circuits
Control Panels
Electronic Motor
Controllers
Phase Controllers
Drives
Soft-Starters
Solid State Relays

HiGHliGHTs:
Current-Limiting
AC & DC Ratings
Low l
2
t
Compact Size

amp-TRap

HsJ
aC: 1-600A 600VAC,
200kA I.R.
300kA I.R. Self Certified
DC: 15-600A 500VDC,
100kA I.R. L/R 10mS

Ratings
HsJ (15 TO 600a)
UL Listed to
Standard 248-8
File E2137
DC Listed to UL248
CSA Certified to
Standard C22.2
No. 248.8

approvals
HiGH speeD/Class J
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 10
amp-TRap

HiGH speeD/Class J HsJ


FuseCatalogNumber
Ampere600VORLESS
Rating 1Pole 3pole
0-30 US3J1I US3J3I
31-60 US6J1I US6J3I
61-100 61036J 61038J
101-200 62001J 62003J
201-400 64031J 64033J
401-600 6631J 6633J
RecommendedFuseBlocks
WithBoxConnectorsfor
Amp-trap

ClassJFuses
A variety of pole configurations and
termination provisions is available.
StandardFuseAmpereRatings,CatalogNumbers
15-30 2-1/4 57 13/16 21 - - - - - - - - - - - -
31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -
61-100 4-4/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7
101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7
201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10
401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
AMPERE
RATING
A B C D E F G H
In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm
Dimensions
Fig1
AMPERE
RATING
CATALOG
NUMBER
OUTLINE
FIGURE
AMPERE
RATING
CATALOG
NUMBER
OUTLINE
FIGURE
1 HSJ1 1 90 HSJ90 2
3 HSJ3 1 100 HSJ100 2
6 HSJ6 1 110 HSJ110 2
10 HSJ10 1 125 HSJ125 2
15 HSJ15 1 150 HSJ150 2
17-1/2 HSJ17-1/2 1 175 HSJ175 2
20 HSJ20 1 200 HSJ200 2
25 HSJ25 1 225 HSJ225 2
30 HSJ30 1 250 HSJ250 2
35 HSJ35 1 300 HSJ300 2
40 HSJ40 1 350 HSJ350 2
45 HSJ45 1 400 HSJ400 2
50 HSJ50 1 450 HSJ450 2
60 HSJ60 1 500 HSJ500 2
70 HSJ70 2 600 HSJ600 2
80 HSJ80 2
Fig2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 11
amp-TRap

HiGH speeD/Class J
1.0
.8
.6
.4
.2
0
0 100 200 300 400 500 600
110-600 AMP
15-100 AMP
Clearing i
2
t vs Operating Voltage
1.0
.8
.6
.4
.2
50 60 70 80 90 100
watts loss vs. % Rated Current
C
o
r
r
e
c
t
i
o
n

F
a
c
t
o
r

f
o
r

I
2
t

OperatingVoltage(ACRMSVolts) PercentRatedCurrent
I
2
tData-600VoltsAC,100kA
C
o
r
r
e
c
t
i
o
n

F
a
c
t
o
r

f
o
r

W
a
t
t
s

L
o
s
s
Max Clearing I
2
t @ Max Clearing I
2
t @ Watts
Ampere 600V AC 100kA 480V AC 100kA Loss at
Rating Pre-Arc 1 Fuse 2 in Series 1 Fuse 2 in Series Rated
(A) (A
2
s x 10
3
) (A
2
s x 10
3
) (A
2
s x 10
3
) (A
2
s x 10
3
) (A
2
s x 10
3
) Current
15 0.02 0.36 0.15 0.23 0.12 2.6
17.5 0.03 0.45 0.19 0.29 0.15 3.5
20 0.04 0.58 0.24 0.37 0.19 3.7
25 0.08 1.2 0.50 0.77 0.40 4
30 0.16 2 0.84 1.3 0.66 4.1
35 0.16 1.5 0.63 0.96 0.50 5.3
40 0.27 2.3 1.0 1.5 0.76 5.5
45 0.32 3.3 1.4 2.1 1.1 6
50 0.44 5.5 2.3 3.5 1.8 6.8
60 0.72 8.0 3.4 5.1 2.6 8.4
70 1.2 12 5.0 7.7 4.0 10
80 1.6 15 6.3 9.6 5.0 11
90 2.3 21 8.8 13 6.9 13
100 2.7 23 9.7 15 7.6 14
110 2.3 21 10 13.9 8 18
125 3.4 29 14 19 11 19
150 5.1 41 20 27 16 22
175 8.0 60 29 40 23 24
200 14 92 44 61 35 26
225 14 110 53 73 42 30
250 16 130 62 86 49 36
300 26 200 96 132 76 38
350 37 290 139 191 110 40
400 63 450 216 297 171 42
450 67 500 240 330 190 58
500 98 600 288 396 228 59
600 141 900 432 594 342 68
HsJ
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 12
peak let-Thru Data - HsJ15 to 600, 600Volts aC
Clearing i
2
t at 500 VDC 100ka, l/R = 10ms
DC Voltage vs. Time Constant
D
C

V
o
l
t
a
g
e

C
a
p
a
b
i
l
i
t
y
L/RTimeConstant(mS)
amp-TRap

HiGH speeD/Class J
AMPERE
RATING
CLEARING I
2
t @ 500 VDC
L/R = 10 ms (A
2
s X 10
3
)
15 0.12
17.5 0.18
20 0.24
25 0.46
30 0.91
35 0.60
40 0.92
45 1.3
50 2.2
60 3.2
70 4.8
80 6.2
90 8.9
100 10
110 8.8
125 13
150 19
175 28
200 46
225 52
250 59
300 96
350 136
400 230
450 270
500 390
600 560
M
a
x
i
m
u
m

I
n
s
t
a
n
t
a
n
e
o
u
s

P
e
a
k

L
e
t
-
T
h
r
u

A
m
p
e
r
e
s
AvailableCurrentinRMSSymmetricalAmperes
HsJ
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 13
melting Time - Current Data, HsJ15 to 600, 600Volts aC
AvailableCurrentinRMSSymmetricalAmperes
T
i
m
e

i
n

S
e
c
o
n
d
s
T
i
m
e

i
n

S
e
c
o
n
d
s
amp-TRap

HiGH speeD/Class J
AvailableCurrentinRMSSymmetricalAmperes
HsJ
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 14
appliCaTiONs:
Capacitors
Loadcenters
Panelboards
Switchboards
Bus Duct
Feeder Circuits
Circuit Breakers
Lighting, Heating, and
General Loads

amp-TRap

a4J
aC: 1 to 600A
600VAC, 200kA I.R.
DC: 1 to 600A
300VDC, 100kA I.R.

Ratings
Features/Benefits
High current limitation for low peak let-thru current
unique dimensions prevent replacement by other fuse
classes
Fiberglass body provides dimensional stability in
harsh industrial environments
easy-to-read imprint label for quick recognition
and replacement

FOR excellent CuRReNT limiTiNG


pROTeCTiON
A4J Class J fuses deliver excellent current-limiting
protection to a wide variety of applications. Their
unique dimensions prevent the substitution of other
fuses with lower voltage ratings, interrupting ratings,
or current-limiting capability.
UL Listed to
Standard 248-8
File E2137
CSA Certified to
Standard C22.2
No. 248.8
DC Listed to UL 248
IEC 269-2-1

approvals
HiGHliGHTs:
Fast Acting
Very Current-Limiting
DC Ratings

FasT aCTiNG/Class J
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 15

ampeRe CaTalOG ampeRe CaTalOG ampeRe CaTalOG


RaTiNG NumBeR RaTiNG NumBeR RaTiNG NumBeR
1 A4J1 50 A4J50 200 A4J200
3 A4J3 60 A4J60 225 A4J225
6 A4J6 70 A4J70 250 A4J250
10 A4J10 75 A4J75 300 A4J300
15 A4J15 80 A4J80 350 A4J350
20 A4J20 90 A4J90 400 A4J400
25 A4J25 100 A4J100 450 A4J450
30 A4J30 110 A4J110 500 A4J500
35 A4J35 125 A4J125 600 A4J600
40 A4J40 150 A4J150
45 A4J45 175 A4J175
StandardFuseAmpereRatings,CatalogNumbers
FasT aCTiNG/Class J Fuses
Fuse Catalog Number
ampere 600V OR less
Rating 1 pole 3 pole
0-30 US3J1I US3J3I
31-60 US6J1I US6J3I
61-100 61036J 61038J
101-200 62001J 62003J
201-400 64031J 64033J
401-600 6631J 6633J
RecommendedFuseBlocks
WithBoxConnectorsfor
Amp-trapClassJFuses
A variety of pole configurations and termina-
tion provisions are available. Refer to the
fuse block section of this catalog for details.
Dimensions
amp-TRap

a4J
ampeRe a B C D e F G H
RaTiNG in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
1-30 2-1/4 57 13/16 21 - - - - - - - - - - - -
31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -
61-100 4-5/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7
101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7
201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10
401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
1-60A
61-600A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 16
FasT aCTiNG/Class J Fuses
amp-TRap

C
u
r
r
e
n
t

i
n

A
m
p
e
r
e
s
AvailableCurrentinRMSSymmetricalAmperes
M
a
x
i
m
u
m

I
n
s
t
a
n
t
a
n
e
o
u
s

P
e
a
k

L
e
t
-
T
h
r
u

A
m
p
e
r
e
s
TimeinSeconds
a4J30 TO 600
m
e
l
t
i
n
g

T
i
m
e


C
u
r
r
e
n
t

D
a
t
a
,

6
0
0
V

F
u
s
e
s
peak let-Thru Current Data 30 to 600, 600 Volts aC
a4J
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 17
amp-TRap

a4By Class l
appliCaTiONs:
Mains, Feeders
Circuit Breakers
Loadcenters
Panelboards
Switchboards
Metering Centers

aC: 200 to 6,000A


600VAC,200kA I.R.
DC: 200 to 2500A
300VDC, 100kA I.R.


Ratings

Features/ Benefits
unique dimensions prevent replacement by other
fuse classes
Blade stamped catalog numbers for permanent
identification
Glass melamine body and plated terminals
provide superior reliability in harsh environments

COuNT ON THe HiGH iNTeRRupTiNG RaTiNG


OF OuR most widely-used Class l Fuse
When it comes to protecting service entrance
equipment, feeder circuits, and circuit breakers,
A4BY fuses have been the industrys favorite. The
A4BY is a 100% rated device and may be applied
at continuous currents up to its ampere rating.
A 4-second minimum time delay at 500% rating
allows the A4BY to pass normal current surges
and to coordinate with ground fault relays.
UL Listed to Standard
248-10 (601-6000A)
File E2137
CSA Certified to
Standard C22.2
No. 248.10 (601-6000A)
Ferraz Shawmut Certified
for DC per UL248
(601-6000A)


approvals
HiGHliGHTs:
Current-Limiting
4-Second Time Delay
DC Ratings
Uniform Characteristics
in all Ampere Ratings

Indicators
Optional built-in fuse indicators (-TI) are available. Consult factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 18
Class l Fuses a4By
amp-TRap

AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG


RATING NUMBER RATING NUMBER RATING NUMBER
200 A4BY200 801 A4BY801 2000 A4BY2000
250 A4BY250 900 A4BY900 2001 A4BY2001
300 A4BY300 1000 A4BY1000 2200 A4BY2200
350 A4BY350 1100 A4BY1100 2500 A4BY2500
400 A4BY400 1200 A4BY1200 3000 A4BY3000
450 A4BY450 1201 A4BY1201 3001 A4BY3001
500 A4BY500 1350 A4BY1350 3500 A4BY3500
600 A4BY600 1400 A4BY1400 4000 A4BY4000
601 A4BY601 1500 A4BY1500 4001 A4BY4001
650 A4BY650 1600 A4BY1600 4500 A4BY4500
700 A4BY700 1601 A4BY1601 5000 A4BY5000
750 A4BY750 1800 A4BY1800 6000 A4BY6000
800 A4BY800
StandardFuseAmpereRatings,CatalogNumbers
200-800A
801-2000A
3001-4000A
2001-3000A
4001-6000A

AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
200-600 8-5/8 219 2 51 5/16 8 1-5/8 41 2-13/32 61
601-800 8-5/8 219 2-1/2 63 3/8 9 2 51 2-13/32 61
801-1200 10-3/4 273 2-1/2 63 3/8 9 2 51 3-15/32 88
1201-1600 10-3/4 273 3 76 7/16 11 2-3/8 60 3-15/32 88
1601-2000 10-3/4 273 3-1/2 89 1/2 13 2-3/4 70 3-15/32 88
2001-2500 10-3/4 273 4-1/2 114 3/4 19 3-1/2 89 3-15/32 88
2501-3000 10-3/4 273 5 127 3/4 19 4 102 3-15/32 88
3001-4000 10-3/4 273 5-3/4 146 3/4 19 4-3/4 121 3-15/32 88
4001-5000 10-3/4 273 6-1/4 159 1 25 5-1/4 133 3-15/32 88
5001-6000 10-3/4 273 7-1/8 181 1 25 5-3/4 146 3-15/32 88
Dimensions
safety Note: Class L fuses are dimensioned for one-way interchangeability.
A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 19
Class l Fuses a4By
amp-TRap

Time in seconds
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
A4BY200to6000
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

6
0
0
V

F
u
s
e
s
PeakLet-ThruCurrentDataA4BY300to6000,600VoltsAC
available Current in Rms symmetrical amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 20
appliCaTiONs:
Motors
Motor Controllers
Transformers
Mains
Feeders

amp-TRap

a4BT Time Delay/Class l


aC: 200 to 2,000A
600VAC, 200kA I.R.
DC: 200 to 2,000A
500VDC, 100kA I.R.


Ratings

Features/ Benefits
unique dimensions prevent replacement by other fuse
classes.
Blade-stamped catalog numbers for permanent
identification
Glass melamine body and plated terminals
provide superior reliability in harsh environments

wHeN yOuR heavier loads NeeD


pROTeCTiON a4BT Fuses wONT leT yOu
DOwN
The high interrupting rating of A4BT current
limiting fuses is ideally suited for protecting
mains, feeders, and general circuits. The 10-sec-
ond time delay at 500% of fuse rating is ideal for
large motors and other loads with a high inrush.
A4BT fuses are suitable for DC applications up to
500VDC. An A4BT fuse can be applied to normal
loads up to its full ampere rating to allow 100%
rating of equipment.
UL Listed to Standard
248-10 (601-2000A)
File E2137
CSA Certified to
Standard C22.2
No. 248.10
(601-2000A)
Ferraz Shawmut Certified
for DC per UL248
(601-2000A)


approvals
HiGHliGHTs:
Current-Limiting
Full 10-Second Delay
DC Ratings
Uniform
Characteristics
in all Ampere Ratings

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 21
Time Delay/Class l Fuses a4BT
amp-TRap

AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG


RATING NUMBER RATING NUMBER RATING NUMBER
200 A4BT200 601 A4BT601 1100 A4BT1100
250 A4BT250 650 A4BT650 1200 A4BT1200
300 A4BT300 700 A4BT700 1400 A4BT1400
350 A4BT350 750 A4BT750 1500 A4BT1500
400 A4BT400 800 A4BT800 1600 A4BT1600
450 A4BT450 900 A4BT900 1800 A4BT1800
500 A4BT500 1000 A4BT1000 2000 A4BT2000
600 A4BT600
StandardFuseAmpereRatings,CatalogNumbers
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm

200-600* 8-5/8 219 2 51 5/16 8 1-5/8 41 2-13/32 61
601-800 8-5/8 219 2-1/2 63 3/8 9 2 51 2-13/32 61
801-1200 10-3/4 273 2-1/2 63 3/8 9 2 51 3-15/32 88
1201-1600 10-3/4 273 3 76 7/16 11 2-3/8 60 3-15/32 88
1601-2000 10-3/4 273 3-1/2 89 1/2 13 2-3/4 70 3-15/32 88
safety Note: Class L fuses are dimensioned for one-way interchangeability.
A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
801-2000A
200-800A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 22
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
Time Delay/Class l Fuses a4BT
amp-TRap

Time in seconds
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
available Current in Rms symmetrical amperes
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

6
0
0
V

A
C
/
5
0
0
V

D
C

F
u
s
e
s
A4BT200to2000
PeakLet-ThruCurrentDataA4BT300to2000,600VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 23
appliCaTiONs:
Loadcenters
Panelboards
Switchboards
Circuit Breakers
Metering Centers

amp-TRap

a3T & a6T FasT aCTiNG/Class T


a3T
aC:1 to 1200A
300VAC, 200kA I.R.
DC: 1 to 1200A
160VDC, 50kA I.R.
a6T
aC: 1 to 800A
600VAC, 200kA I.R.
DC: 1 to 800A
300VDC, 100kA I.R.


Ratings

Features/ Benefits
extremely current limiting for low peak let-thru
current
unique dimensions prevent replacement by other fuse
classes
Blade-stamped catalog numbers for permanent
identification
small physical size for greater design flexibility

THese small DimeNsiON Fuses aRe THe


RiGHT FiT... FOR a TiGHT FiT
Fast acting A3T and A6T Class T fuses combine
two highly desirable features -- high current
limitation and a small physical size. Their unique
dimensions prevent the substitution of other fuses
with lower voltage ratings or current limiting
capability. These fuses have glass melamine
bodies for superior dimensional stability and
catalog numbers stamped into the blades for
permanent identification.
UL Listed to
Standard 248-15
File E2137
CSA Certified to
Standard C22.2
No. 248.15
DC Listed to UL
Standard 248


approvals
HiGHliGHTs:
Fast Acting
Extremely Current
Limiting
Small Physical Size
DC Ratings

RecommendedFuseBlocksWithBoxConnectorsfor
Amp-trapClassTFuses
A variety of pole configurations and termination provisions are available.
Refer to the fuse block section of this catalog for details.
Ampere
Rating
30
60
100
200
400
600
1-pole
30306T
30606T
31031T
32031T
34031T
36031T
3-pole
30308T
30608T
31033T
32033T
34033T

1-pole
60306T
60606T
61031T
62031T
64031T
66031T
3-pole
60308T
60608T
61033T
62033T

CatalogNumber
300V 600V
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 24
FasT aCTiNG/Class T Fuses
amp-TRap

StandardFuseAmpereRatings,CatalogNumbers

AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber


Rating 300V 600V Rating 300V 600V Rating 300V 600V

1 A3T1 A6T1 60 A3T60 A6T60 300 A3T300 A6T300


3 A3T3 A6T3 70 A3T70 A6T70 350 A3T350 A6T350
6 A3T6 A6T6 80 A3T80 A6T80 400 A3T400 A6T400
10 A3T10 A6T10 90 A3T90 A6T90 450 A3T450 A6T450

15 A3T15 A6T15 100 A3T100 A6T100 500 A3T500 A6T500
20 A3T20 A6T20 110 A3T110 A6T110 600 A3T600 A6T600
25 A3T25 A6T25 125 A3T125 A6T125 700 A3T700 A6T700
30 A3T30 A6T30 150 A3T150 A6T150 800 A3T800 A6T800

35 A3T35 A6T35 175 A3T175 A6T175 1000 A3T1000
40 A3T40 A6T40 200 A3T200 A6T200 1200 A3T1200
45 A3T45 A6T45 225 A3T225 A6T225
50 A3T50 A6T50 250 A3T250 A6T250

AMPERE A B C D F G J
RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm
A3T
1-30 .88 22.4 .41 10.3 - - - - - - - - - -
31-60 .88 22.4 .56 14.1 - - - - - - - - - -
61-100 2.16 54.9 .81 20.6 .12 3.2 .75 19.0 1.56 39.6 .28 7.1 .82 20.8
101-200 2.44 62.0 1.06 26.9 .19 4.8 .88 22.4 1.70 43.2 .34 8.6 .83 21.1
201-400 2.75 69.8 1.33 33.8 .25 6.4 1.00 25.4 1.84 46.7 .41 10.4 .84 21.3
401-600 3.06 77.7 1.62 41.1 .31 7.8 1.25 31.8 2.03 51.6 .48 12.2 .84 21.3
601-800 3.38 85.8 2.08 52.8 .38 9.7 1.75 44.4 2.22 56.4 .55 14.0 .88 22.4
801-1200 4.00 102 2.52 64.0 .44 11.2 2.00 50.8 2.53 64.3 .61 15.5 1.03 26.2

A6T
1-30 1.50 38.1 .57 14.5 - - - - - - - - - -
31-60 1.57 39.9 .81 20.6 1.51 38.4 1.00 25.4 - - - - - -
61-100 2.95 75.0 .82 20.8 .12 3.2 .75 19.0 2.35 59.7 .28 7.1 1.58 40.1
101-200 3.26 82.8 1.07 27.2 .19 4.8 .88 22.4 2.51 63.7 .34 8.6 1.61 41.0
201-400 3.62 92.1 1.62 41.3 .25 6.4 1.00 25.4 2.72 69.1 .41 10.4 1.70 43.2
401-600 3.98 101.2 2.06 52.4 .31 7.9 1.25 31.8 2.95 75.0 .48 12.2 1.70 43.2
601-800 4.33 110.0 2.50 63.5 .37 9.5 1.75 44.4 3.17 80.5 .56 14.1 1.70 43.2
Dimensions
A3T1-60
A3T61-1200
A3T
A6T31-60
A6T61-800
A6T
A6T1-30
a3T & a6T
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 25
FasT aCTiNG/Class T Fuses a3T & a6T
amp-TRap

C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
Time in seconds
A3T30to1200
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

3
0
0
V

F
u
s
e
s
PeakLet-ThruCurrentDataA3T30to1200,300VoltsAC
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 26
Time in seconds
FasT aCTiNG/Class T Fuses a3T & a6T
amp-TRap

C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
available Current in Rms symmetrical amperes
A6T1to800
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

6
0
0
V

F
u
s
e
s
PeakLet-ThruCurrentDataA6T30to800,600VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 27
appliCaTiONs:
Loadcenters
Panelboards
Switchboards
Bus Duct
Feeder Circuits
Non-inductive Loads
Lighting Circuits

amp-TRap

a2K & a6K Class RK1


a2K
aC: 1 to 600A
250VAC, 200kAI.R.
DC: 1 to 600A 250VDC,
200kA I.R.
a6K
aC: 1 to 600A
600VAC, 200kA I.R.
DC: 1 to 600A 300VDC,
20kA I.R.


Ratings

Features/ Benefits
THese Fast-actinG Fuses DeliVeR a
HiGH DeGRee OF CuRReNT limiTaTiON
wHeRe yOu NeeD iT mOsT
Current-limiting A2K and A6K fuses provide
excellent protection where high available short
circuit currents exist. These fast-acting fuses are
particularly good for branch/feeder circuits and
back-up protection.
UL Listed to Standard
248-12 File E2137
CSA Certified to
Standard C22.2
No. 248.12
Ferraz Shawmut Certified
for DC per UL248


approvals
HiGHliGHTs:
Highly Current-Limiting
Fast Acting
Rejection Style

Rejection style design prevents replacement by other


fuse classes
Fiberglass body provides dimensional stability in harsh
industrial environments
easy-to-read imprint label for quick recognition and
replacement
High degree of current limitation for low peak
let-thru current

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 28
FasT aCTiNG/Class RK1 Fuses a2K & a6K
amp-TRap


AMPERECATALOGNUMBER AMPERECATALOGNUMBER AMPERECATALOGNUMBER
RATING 250V 600V RATING 250V 600V RATING 250V 600V


1 A2K1R A6K1R 35 A2K35R A6K35R 175 A2K175R A6K175R
3 A2K3R A6K3R 40 A2K40R A6K40R 200 A2K200R A6K200R
4 - A6K4R 45 A2K45R A6K45R 225 A2K225R A6K225R
5 A2K5R A6K5R 50 A2K50R A6K50R 250 A2K250R A6K250R

6 A2K6R A6K6R 60 A2K60R A6K60R 300 A2K300R A6K300R
8 - A6K8R 70 A2K70R A6K70R 350 A2K350R A6K350R
10 A2K10R A6K10R 80 A2K80R A6K80R 400 A2K400R A6K400R
12 A2K12R - 90 A2K90R A6K90R 450 A2K450R A6K450R

15 A2K15R A6K15R 100 A2K100R A6K100R 500 A2K500R A6K500R
20 A2K20R A6K20R 110 A2K110R A6K110R 600 A2K600R A6K600R
25 A2K25R A6K25R 125 A2K125R A6K125R
30 A2K30R A6K30R 150 A2K150R A6K150R
StandardFuseAmpereRatings,CatalogNumbers

AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
250V-A2KFUSES
0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-A6KFUSES
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
Fuse CatalogNumber
Ampere250V600V
Rating 1Pole 3pole 1pole 3pole
0-30 20306R 20308R 60306R 60308R
31-60 20606R 20608R 60606R 60608R
61-100 21036R 21038R 61036R 61038R
101-200 22001R 22003R 62001R 62003R
201-400 24001R 24003R 64001R 64003R
401-600 2631R 2633R 6631R 6633R
RecommendedFuseBlocksWithBox
ConnectorsForAmp-trapClassRK1Fuses
A variety of pole configurations and termination provisions
are available. Refer to the fuse block section of this catalog
for details.
0-60A
61-600A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 29
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
FasT aCTiNG/Class RK1 Fuses a2K & a6K
amp-TRap

Time in seconds
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
available Current in Rms symmetrical amperes
A2K30to600
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

2
5
0
V

F
u
s
e
s
PeakLet-ThruCurrentDataA2K30to600,250VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 30
FasT aCTiNG/Class RK1 Fuses a2K & a6K
amp-TRap

Time in seconds
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
available Current in Rms symmetrical amperes
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
A6K30to600
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

6
0
0
V

F
u
s
e
s
PeakLet-ThruCurrentDataA6K30to600,600VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AC: (70 to 600A)
600VAC, 200KA I.R.
300KA I.R. Self certified


Ratings
HiGH speeD RK1 (HsRK)
Protect your electrical power wiring and power semi-
conductors with a single fuse.
The new HIGH SPEED RK1 (HSRK) combines semi-
conductor fuse performance with NEC branch circuit
compliance. The fuse was designed with two specifc
applications in mind:
1. To provide semiconductor fuse performance
to solid state drive applications but in the
larger RK body sizes that have been typically
installed in older systems.
2. To provide industrial power applications with
the most current limiting fuse available,
which in turn provides the best arc fash
mitigation available to power systems using
the larger RK size fuses.
HsRK (70 TO 600a)
UL listed to 248-12
File E2137
CSA certified to
C22.2 - No. 248.12


approvals
amp-TRap

HsRK
Current Limiting
Low I
2
t
Drive protection in
larger RK body sizes
for older installations
Fast acting

HiGHliGHTs:
Branch circuits
AC drives
Solid state controllers
Feeder circuits
Arc flash mitigation

appliCaTiONs:
Most current limiting RK1 available
Provides the best Arc flash mitigation for feeder and
branch circuits (non motor load circuits)
Excellent cycling ability for frequent drive starts and
stops without nuisance opening
Extremely Low I
2
t


Features/Benefits
HiGH speeD/Class RK1
B
B 31
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 32
Ampere Catalog# Ampere Catalog#
Rating 600V Rating 600V
70 HSRK70R 200 HSRK200R
80 HSRK80R 225 HSRK225R
90 HSRK90R 250 HSRK250R
100 HSRK100R 300 HSRK300R
110 HSRK110R 350 HSRK350R
125 HSRK125R 400 HSRK400R
150 HSRK150R 450 HSRK450R
175 HSRK175R 500 HSRK500R
600 HSRK600R
StandardFuseAmpereRatings,CatalogNumbers
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
600V-HSRKFUSES
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
FuseCatalogNumber
Ampere600V
Rating 1pole 3pole
61-100 61036R 61038R
101-200 62001R 62003R
201-400 64001R 64003R
401-600 6631R 6633R
RecommendedFuseBlocksWithBox
ConnectorsForAmp-trap

ClassRK1Fuses
A variety of pole configurations and ter-
mination provisions are available. Refer
to the fuse block section of this catalog
for details.
70-600A
amp-TRap

HiGH speeD/Class RK1 HsRK


Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 33
amp-TRap

HiGH speeD/Class RK1 HsRK


% Rated Current working Voltage (aC Rms Volts)
C
o
r
r
e
c
t
i
o
n

F
a
c
t
o
r

f
o
r

l
2
t
C
o
r
r
e
c
t
i
o
n

F
a
c
t
o
r

f
o
r

w
a
t
t
s

l
o
s
s
Ampere
Rating(A)
Pre-arc(A
2
s
X10
3
)
MaxClearing
I
2
t@600VAC
(A
2
sX10
3
)
70 1.2 14
80 1.6 17
90 2.3 24
100 2.7 26
110 2.3 23
125 3.4 32
150 5.1 45
175 8.0 65
200 14 100
225 14 110
250 16 130
300 26 200
350 37 290
400 63 450
450 67 500
500 98 600
600 141 900
i
2
t vs working Voltage watts loss vs % Rated Current
i
2
t Data HsRK (amp Rating)R
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 34
p
r
e
a
r
c
i
n
g

T
i
m
e
(
s
)
AmpereRating
(A)
WattsLossat
RatedCurrent
70 10
80 11
90 13
100 14
110 18
125 19
150 25
175 26
200 27
225 35
250 43
300 45
350 47
400 53
450 62
500 63
600 83
amp-TRap

HiGH speeD/Class RK1 HsRK


melting Time Current Data HsRK70 600R, 600V aC
prearc Current (a Rms)8% prearc Current (a Rms)8%
p
r
e
a
r
c
i
n
g

T
i
m
e
(
s
)
m
a
x
i
m
u
m

p
e
a
k

l
e
t
-
T
h
r
u

C
u
r
r
e
n
t

(
a
)
60Hz Rms symmetrcal prosective Current (a)
peak let-Thru Data HsRK70 600R, 600V aC watts loss Data HsRK70 600R, 600V aC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 35
amp-TRap

aG Class G
amp-TRap aG Fuses FiT RiGHT iN TO a wide
variety OF iNDusTRial appliCaTiONs
The Ferraz Shawmut Amp-trap AG fuse series is
a complete line of Class G fuses. AG fuses safely
fit a wide variety of applications. Class G fuses
are made in four physical sizes and provide good
branch-circuit protection for lighting,
heating, and appliance circuits.

AMPERE CATALOG AMPERE CATALOG

RATING NUMBER RATING NUMBER

1/2 AG1/2 15 AG15


1 AG1 20 AG20
1-1/2 AG1-1/2 25 AG25
2 AG2 30 AG30
3 AG3 35 AG35

4 AG4 40 AG40
5 AG5 45 AG45
6 AG6 50 AG50
8 AG8 60 AG60
10 AG10
StandardFuseAmpereRatings,
CatalogNumbers
Dimensions
AMPERE A B C
RATING
In. mm In. mm In. mm

1/2-15A 1.31 33.3 .406 10.3 .28 7.1


20A 1.41 35.8 .406 10.3 .28 7.1
25,30A 1.62 41.2 .406 10.3 .28 7.1
35-60A 2.25 57.2 .406 10.3 .50 12.7
Cross Reference:
AG will replace the following fuses: Bussmann SC, Littelfuse SLC

Features/ Benefits
Four unique sizes from -60 amperes do not allow
inter-changeability with other fuse classes
Fiberglass bodies provide dimensional stability in
harsh industrial settings

appliCaTiONs:
Lighting
Heating*
Appliances
Branch Circuits
* Except in Canada, where fuses must
be P or D type.

UL Listed to
Standard 248-5
File E2137
CSA Certified to
Standard C22.2
No. 248.5


approvals
HiGHliGHTs:
Current-Limiting
Time Delay (above 5A)


Ratings
aC: 1/2 to 20A
600VAC, 100K A I.R.
25 to 60A, 480VAC,
100k A I.R.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 36
Time Delay/Class G Fuses aG
amp-TRap

Time in seconds
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
Time in seconds
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

4
8
0
V

F
u
s
e
s
AG1to10
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

4
8
0
V

F
u
s
e
s
AG15to60
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
PeakLet-ThruCurrentDataAG1to60,480VoltsAC
available Current in Rms
symmetrical amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 37
appliCaTiONs:
Control Circuits
Lighting
General Loads
Branch Circuit
Protection

amp-TRap

aTmR Class CC
aC: 1/10 to 30A
600VAC, 200kA I.R.
DC: 1/10 to 30A
600VDC, 100kA I.R.


Ratings

Features/ Benefits
Rejection style design prevents replacement errors
when used with recommended fuse blocks
Versatile design for individual component and
branch circuit protection

small Fuse - BiG pROTeCTiON


FOR GeNeRal CiRCuiTs
Amp-trap

ATMR fuses, in the Class CC family,


are the smallest dimension 600VAC/DC fuses suitable
for branch circuit protection. The ATMR is a popular
choice for economical protection of control circuits and
control circuit transformers where available short cir-
cuit currents exceed 10,000 amperes. ATMRs rejec-
tion dimensions prevent substitution by lesser rated
fuses. These fast acting fuses give current limiting
protection to general circuits.
UL Listed to
Standard 248-4
File E2137
CSA Certified to
Standard C22.2 No.
248.4
DC Listed to
ULStandard 248


approvals
HiGHliGHTs:
Fast Acting
Very Current-Limiting

StandardFuseAmpereRatings,
CatalogNumbers
AMPERE CATALOG AMPERE CATALOG
RATING NUMBER RATING NUMBER

1/10 ATMR1/10 3-1/2 ATMR3-1/2


1/8 ATMR1/8 4 ATMR4
2/10 ATMR2/10 5 ATMR5
1/4 ATMR1/4 6 ATMR6
3/10 ATMR3/10 7 ATMR7
1/2 ATMR1/2 8 ATMR8
3/4 ATMR3/4 9 ATMR9
1 ATMR1 10 ATMR10
1-1/4 ATMR1-1/4 12 ATMR12
1-1/2 ATMR-1-1/2 15 ATMR15
2 ATMR2 20 ATMR20
2-1/2 ATMR2-1/2 25 ATMR25
3 ATMR3 30 ATMR30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 38

CATALOGNUMBER

ULTRASAFE ScrewConnector PressurePlate
Numberof Indicating withDouble Connector CopperBox
Poles FuseHolders QuickConnects withDouble Connector
QuickConnects

ADDER 30310R 30320R 30350R


1 USCC1I 30311R 30321R 30351R
2 USCC2I 30312R 30322R 30352R
3 USCC3I 30313R 30323R 30353R
3 USFMCCI
RecommendedFuseBlocksForAmp-Trap

ClassCCFuses
Refer to the Class CC Fuse Block section of this catalog for other details.
Dimensions
FasT aCTiNG/Class CC Fuses aTmR
amp-TRap

Time in seconds
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

6
0
0
V

F
u
s
e
s
ATMR1/10to30
Current in amperes
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
PeakLet-ThruCurrentDataATMR3/4to30,600VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 39
appliCaTiONs:
Feeders
Branch Circuits
Resistive Heating
Residential and Small
Commercial
Installations

ONe-Time
OT/OTN/OTs Class K-5
OT
aC: 1 to 600A
250VAC, 50kA I.R.
DC: 1 to 600A
250VDC, 20kA I.R.
OTN (Canada)
aC: 15 to 60A
250VAC, 50kA I.R.

OTs
aC: 1 to 600A
600VAC, 50kA I.R.
DC: 1 to 600A
300VDC, 20kA I.R.


Ratings

Features/ Benefits
easy to read imprint label for quick recognition and
replacement
low cost for high protection value

FOR versatility and economy, THese


GeNeRal puRpOse Fuses aRe HaRD TO
BeaT
OT, OTN and OTS general purpose fuses provide
low cost protection for feeder and branch circuits
serving lighting, heating, and other non-motor
loads. OT, OTN and OTS fuses will safely interrupt
available short circuit currents up to 50,000
amperes in all ratings.
OT, OTN and OTS fuses are not rejection fuses
care should be taken to ensure that replacement
fuses do not have lower interrupting ratings than
original fuses.
OTN 15 through 60 satisfy the Canadian electrical
code requirement for Type P, low melting-point,
non-time delay fuses.
UL Listed to Standard
248-9 File E2137
CSA Certified to
Standard C22.2
No. 248.9*
Ferraz Shawmut Certified
for DC per UL248

*The Canadian Electrical
Code requires these fuses in
ratings 15 through 60A to be of
the low melting point design use
OTN 15-60.


approvals
HiGHliGHTs:
Versatile
Lowest cost protection
for circuits serving
non-inductive loads

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 40
GeNeRal puRpOse/Class K-5 Fuses OT/OTN/OTs
ONe-Time

AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber
Rating 250V 600V Rating 250V 600V Rating 250V 600V

1 OT1 OTS1 30 OT30, OTN30* OTS30 125 OT125 OTS125


2 OT2 OTS2 35 OT35, OTN35* OTS35 150 OT150 OTS150
3 OT3 OTS3 40 OT40, OTN40* OTS40 175 OT175 OTS175
4 OT4 OTS4 45 OT45, OTN45* OTS45 200 OT200 OTS200

5 OT5 OTS5 50 OT50, OTN 50* OTS50 225 OT225 OTS225
6 OT6 OTS6 60 OT60, OTN60* OTS60 250 OT250 OTS250
7 OT7 65 OT65 300 OT300 OTS300
8 OT8 OTS8 70 OT70 OTS70 350 OT350 OTS350

10 OT10 OTS10 75 OT75 OTS75 400 OT400 OTS400
12 OT12 OTS12 80 OT80 OTS80 450 OT450 OTS450
15 OT15, OTN15* OTS15 90 OT90 OTS90 500 OT500 OTS500
20 OT20, OTN20* OTS20 100 OT100 OTS100 600 OT600 0TS600
25 OT25, OTN 25* OTS25 110 OT110 OTS110
StandardFuseAmpereRatings,CatalogNumbers

AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
250V-OT,OTNFUSES
0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-OTSFUSES
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
Fuse CatalogNumber
Ampere250V600V
Rating 1Pole 3pole 1pole 3pole
0-30 20306 20308 60306 60308
31-60 20606 20608 60606 60608
61-100 21036 21038 61036 61038
101-200 22001 22003 62001 62003
201-400 24001 24003 64001 64003
401-600 2631 2633 6631 6633
RecommendedFuseBlocksWithBox
ConnectorsForOne-TimeClassK-5Fuses
A variety of pole configurations and termination provi-
sions are available. Refer to the fuse block section of this
catalog for details.
61-600A
0-60A
* In Canada
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 41
m
a
x
i
m
u
m

i
n
s
t
a
n
t
a
n
e
o
u
s

p
e
a
k

l
e
t
-
T
h
r
u

a
m
p
e
r
e
s
available Current in Rms symmetrical amperes
PeakLet-ThruCurrentDataOT,OTN&OTS30to600,250and600VoltsAC
GeNeRal puRpOse/Class K-5 Fuses OT/OTN/OTs
ONe-Time
Time in seconds
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

2
5
0
V

F
u
s
e
s
OT30to600;OTN30,60
C
u
r
r
e
n
t

i
n

a
m
p
e
r
e
s
Time in seconds
OTS30to600
M
e
l
t
i
n
g

T
i
m
e

C
u
r
r
e
n
t

D
a
t
a
,

6
0
0
V

F
u
s
e
s
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 42
appliCaTiONs:
General purpose loads
where short circuits
are 10,000 amperes
or less

ReNewaBle
RF/RFs & Rl/Rls Class H
RF
aC: 1 to 600A
250VAC, 10kA I.R.
RFs
aC: 1 to 600A
600VAC, 10kA I.R.


Ratings

Features/ Benefits
Knurledbushings for ease of disassembly
Ruggedconstruction for maximum service life
Precisiondie-cutrenewallinks renew quickly and
give repeatable performance

TRaDiTiONal pROTeCTiON FOR CiRCuiTs


wiTH less THaN 10,000a sHORT CiRCuiT
CuRReNT
RF and RFS general purpose fuses are suitable
for application where available short circuit cur-
rents do not exceed 10,000 amperes. RF and RFS
renewable fuses use matched RL and RLS die-cut
zinc links from 1 to 600 amperes in 32 ratings.
UL Listed to Standard
248-7 File E2137
CSA Certified to
Standard C22.2
No. 248.7


approvals
HiGHliGHTs:
Renewable
32 Renewal Link
Ratings

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 43 B 43
61-600A
0-60A
ReNewaBle Class H Fuses/liNKs RF/RFs & Rl/Rls

AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber


Rating 250V 600V Rating 250V 600V Rating 250V 600V

1 RF1/RL1 RFS1/RLS1 45 RF45/RL45 RFS45/RLS45 225 RF225/RL225 RFS225/RLS225


2 RF2/RL2 RFS2/RLS2 50 RF50/RL50 RFS50/RLS50 250 RF250/RL250 RFS250/RLS250
3 RF3/RL3 RFS3/RLS3 60 RF60/RL60 RFS60/RLS60 300 RF300/RL300 RFS300/RLS300
5 RF5/RL5 RFS5/RLS5 70 RF70/RL70 RFS70/RLS70 350 RF350/RL350 RFS350/RLS350
6 RF6/RL6 RFS6/RLS6 80 RF80/RL80 RFS80/RLS80 400 RF400/RL400 RFS400/RLS400
10 RF10/RL10 RFS10/RLS10 90 RF90/RL90 RFS90/RLS90 450 RF450/RL450 RFS450/RLS450

15 RF15/RL15 RFS15RLS15 100 RF100/RL100 RFS100/RLS100 500 RF500/RL500 RFS500/RLS500
20 RF20/RL20 RFS20/RLS20 110 RF110/RL110 RFS110/RLS110 600 RF600/RL600 RFS600/RLS600
25 RF25/RL25 RFS25/RLS25 125 RF125/RL125 RFS125/RLS125
30 RF30/RL30 RFS30/RLS30 150 RF150/RL150 RFS150/RLS150
35 RF35/RL35 RFS35/RLS35 175 RF175/RL175 RFS175/RLS175
40 RF40/RL40 RFS40/RLS40 200 RF200/RL200 RFS200/RLS200
StandardFuseAmpereRatings,CatalogNumbers
Fuse CatalogNumber
Ampere250V600V
Rating 1Pole 3pole 1pole 3pole
0-30 20306 20308 60306 60308
31-60 20606 20608 60606 60608
61-100 21036 21038 61036 61038
101-200 22001 22003 62001 62003
201-400 24001 24003 64001 64003
401-600 2631 2633 6631 6633
RecommendedFuseBlocksWithBox
ConnectorsForRenewableClassHFuses
A variety of pole configurations and termination provisions is avail-
able. Refer to the fuseholder section of this catalog for details.

AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
250V-RFFUSES
0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 18 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 54 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-RFSFUSES
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 18 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 67 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

You might also like