You are on page 1of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No

QTY IV.3

DESCRIPTION OF ITEM

UNIT

I 1

30

INTERNAL ELECTRIFICATION FOR SECUIRTY BLOCK INTERNAL ELECTRIFICATION Primary Light points Supply and Wiring for Primary Light point with FRLS 1.5sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable conforming to IS:694 (with latest amendments) in 20 mm dia, 16SWG MS conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of 1No 5Amp Modular(plate) control switch fixed in a suitable size metal sheet flush boxes suitable for modular switch plates and all necessary components, and earthing with 14SWG bare copper wire run continuously along the conduit including supply of all fixing materials, accessories and interconnections complete as required. (wiring shall be from control switch to Sensor and to light point ) (NORMAL POINTS-18& EMERGENCY POINTS12)

RATE (in Figures& Words)

AMOUNT

PT

Notes: 1. Rates for all the point wiring items are inclusive of necessary circuit mains with 3Runs of 2.5sqmm FRLS Copper conductor wires from the distribution board to the first switch board and also sub circuits from one switch board to the subsequent switch boards in the same circuit. 2. The secondary point in case of point wiring shall include necessary wiring looped from the primary light point as indicated in the electrical layout drawings. 3. Rates for the power point wiring items are inclusive of necessary power circuit from the DB to the power socke 4. All 16A power Switch Sockets shall be with Built in LED indication Secondary Point Supply and wiring generally same as item 1 above but without control switch. (NORMAL POINTS-127& EMERGENCY POINTS-6)

22

PT

Page 1 of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No 3

QTY 11
Ceiling Fan Point

DESCRIPTION OF ITEM

UNIT PT

RATE (in Figures& Words)

AMOUNT

Supply and Wiring for ceiling fan point with FRLS 1.5sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable conforming to IS:694 (with latest amendments) in 16SWG MS conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of 1No 5Amp modular (plate) control switch & 100W step type electronic regulator fixed in suitable size metal sheet Box suitable for modular switches and regulator and covered with modular switch plates and earthing with 14SWG bare copper wire run continuously along the conduit including supply of all fixing materials, accessories like fan hook box, terminal box , interconnections complete as required.

Exhaust Fan Point Supply and wiring generally same as item 1 above but for exhaust fan with 6 Amp modular SPMCB for control.

PT

5 Amp 3 Pin Socket outlet poin Supply and wiring generally similar to item 1 above but for modular 5A, 3pin combined switch socket outlet point including supply and fixing of 5A 3 pin combined switch socket outlet in a suitable size metal sheet Box and covered with modular plate complete as required. Buzzer point

PT

PT

Supply and wiring for Electrical call bell point with FRLS 1.5Sq.mm 1.1KV grade ISI mark PVC insulated single core strandard copper conductor cable conforming the IS 694 in 20mm dia 16SWG MS conduit concealed in ceiling including supply fixing of 5A modular plate bell push for control in independent metal sheet box suitabel size with 14SWG bare copper

5A 3pin socket outlet in lighting switch board

PT

Supply and fixing of modular 5A 3pin combined switch socket outlet in the metal sheet Box of lighting control switch board including interconnections complete as required.

16A Combined Switch socket outlet

PT

Page 2 of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No

QTY

DESCRIPTION OF ITEM

UNIT

Supply and Wiring with FRLS 2runsX 2.5sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable conforming to IS:694 (with latest amendments) in 16SWG MS conduit conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of modular 16Amp/5Amp modular universal switch socket outlet and LED indication fixed in a suitable size metal sheet box suitable for switches and sockets and covered with modular switch plate and earthing with 16SWG bare copper wire run continuously along the conduit including supply of fixing materials, interconnections complete as required.

RATE (in Figures& Words)

AMOUNT

9 2

16A 3pin combined switch socket outlet point (UPS) Supply and fixing of 1no 16A 3 pin modular socket outlet with switches & sockets and LED indication fixed in the same modular type metal sheet boxes of suitable size with front plates complete as required AC OUTLET

PT

10

PT

Supply and Wiring with FRLS 2runsX 4sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable confirming to IS:694 (with latest amendments)in 20mm dia 12SWG MS conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of modular 32Amp 2pole ELMCB in metal sheet box suitable for ELMCB,size and covered with modular switch plate and earthing with 12SWG copper wire run inside the conduit power supply shall be trapped from DB,and 20mm dia 16SWG HGMS conduit shall be laied in wall with fish wire from ELCB board (which is fixed at 1.2m from FFL) to the height of indoor AC unit and teriminate ina suitable MS box concealed in wall including cover for interconnecting to AC unit complete as required.

11 11.1

50

Run of mains Supply and wiring with 4runs of 6sq.mm, 1.1 KV grade FRLS pvc insulated, single core stranded copper conductor cable confirming to IS:694 (with latest amendments) in 32mm dia MS conduit on wall/ceiling,or floor and earthing with 2 run of 10SWG bare copper wire run continuously along the conduit including supply of all fixing materials and accessories, interconnections

Mtr

Page 3 of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No 11.2

QTY 50

DESCRIPTION OF ITEM

UNIT Mtr

Supply and wiring with 4runs of 10sq.mm, 1.1 KV grade FRLS pvc insulated, single core stranded copper conductor cable confirming to IS:694 (with latest amendments)in 40mm dia 2mm thick electrical grade concealed in wall/ceiling, or floor and earthing with 2runs of 8SWG copper wire run continuously along the conduit including supply of all fixing materials and accessories, interconnections complete as reuired. (from panel to Pdb )

RATE (in Figures& Words)

AMOUNT

11.3

50

Supply and wiring with 5runs of 6sq.mm, 1.1 KV grade FRLS pvc insulated, single core stranded copper conductor cable confirming to IS:694 (with latest amendments) in 32MM MS 16SWGconduit concealed in wall/ceiling, or floor and earthing with 2runs 4sq.mm insulated CU conductor run continuously along the conduit including supply of all fixing materials and accessories, interconnections complete as required (from UPS DP switch to UPS DB )

Mtr

11.4

20

Supply and wiring 2runs of 1.5sq.mm cable PVC insulated FRLS copper conductor cable in 20mm dia MS conduit concealed and one run of 14SWG bare copper as wire along conduit etc. complete as required.(From DB to flame proof switch board at Ammunition room) Distribution Boards Supply installation Testing and commissioning of TPN MCB Double Door Distribution boards dust and vermin protected and rated for 440V Three phase 50hz AC supply operation, including of bus bar suitable capacity, neutral link with required outgoings, din bar, fully factory fabricated with powder coated incoming ELMCB as per specifications and required capacity and Earth terminal complete as required and installed in flush with wall including all fixing materials required. (All MCB's in UDBs shall be of 'D' Curve & other MCB's shall be 'C' Curve.

Mtr

12

12.1 12.2

1 1

4way TPNMCBDB with 40A,100mA leakage current sensitivity FP ELMCB as incomer and 12nos 6A SPMCBs as outgoings (LDBs) 4way TPNMCBDB with 63A,100mA FP ELMCB as incomer and 12nos 16A/20A SPMCBs as outgoings.(PDBs) 4way TPNMCBDB with 40A, TPMCB as incomer and 12nos 6A/10A/16A SPMCBs as outgoings.(UDBs) Supply and laying of 3CX2.5Sq.mm Pvc armored copper conductor cable on the surface on wall/ ceiling with all fixing materials complete as required

sets sets

12.3 12.4

sets

20

Supply

Mtr

Page 4 of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No

QTY 20
Laying

DESCRIPTION OF ITEM

UNIT Mtr

RATE (in Figures& Words)

AMOUNT

12.5 12.6 12.7

1 1 1

Providing FLP Double compression Gland for above FLP Fitting Each 3CX2.5Sq.mm Providing cable end termination for 3CX2.5Sq.mm

Each

Supply and fixing with MS Box and including of 5A switch Each suitable for controlling FLP fitting suitable to mount on surface\concealed out side the wall of ammunition block Supply & Installation of Light Fixtures & Fans Supply &Installation of Light Fixtures Supply, installation, testing & commissioning of the following light fittings with electronic ballast and all other accessories including supply of lamps. Installation of light fittings complete with supply of all materials like balancing socket, conduit pipe, nipples, check nuts, bolts, nuts, metallic flexible hose, suspension rod/ Chain, clamps etc., required for such installation as per specifications for the following fittings including painting with approved synthetic paint, necessary interconnections in an approved manner. (CFL fixtures with low loss copper ballast)

II 1

a) 2

1X28W TL5 light fixture (CAT No:-TCH 207 1X TLF 28HF similar to PHILIPS) Supply

Each

Installation

Each

b) 6

2X11W wall bracket light fixture (CAT No:-TCS 518/211similar to PHILIPS) Supply Each

6 c) 4

Installation

Each

1X9W wall bracket light fixture (CAT No:-FMC 21/109 similar to PHILIPS) Supply Each

Installation

Each

Page 5 of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No d

QTY

DESCRIPTION OF ITEM

UNIT

20

2X18W Surface mounting light fixture (CAT NO:-FCS 518/218 similar to PHILIPS) Supply

RATE (in Figures& Words)

AMOUNT

Each

20 e 25

Installation

Each

2X28W T5 mirror optic type fixture (surface mounted) (CAT NO:TCS 398/2 X28 MDGN HF similar to PHILIPS) Supply Each

25

Installation

Each

FLP Florescent light fitting Supply & installation of Flame proof fluorescent light fitting complete with copper ballast PF improvement,lampholder & with lamp the lamp fitting with cast iron LM6 alloy enc loser,flame proof clear glass tubing surtified by IS 2148 & IS 2206 single 4feet 36W (IIa/IIb) 1NO

Supply

Each

Installation of light fitting with supply of all materials like balancing Each socket,conduit pipe nipple check nuts,bolts,nuts,metallic flexible hose necessary interconnection dia in an approved manner mounting on ceiling complete as required.

Supply and fixing of one way Metal enclosure for SPMCB Each independent mounting suitable for terminations cable gland on MS conduit with 6A SPMCB concealed in wall interconnection earthing complete as required (For FL tube light) (similar Legrand no 60788) Supply, installation, testing and commissioning of light duty, totally enclosed motor type exhaust fans suitable for operation on 230Volts, 50Hz single phase AC supply complete with 3core flexible copper conductor cable, gravity ouvres shutters rigid frame with rubber mountings and of following sizes confirming to IS-2312 (with latest amendments)

2.1 4 4

225mm sweep 1400RPM with double Ball Bearin Supply

Each

Installation of exhaust fan with gravity louvers on wall including Each grouting of bolts for installation supply of material as Dwg. CED/ELE/S/17

Page 6 of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No 2.2

QTY

DESCRIPTION OF ITEM

UNIT

10

Supply of 1200mm sweep ceiling fan capacitor type complete with 300mm down road suitable of 230V AC supply Supply Each

RATE (in Figures& Words)

AMOUNT

10

Installation of ceiling fans of having standard down rod with all Each materials required for installation complete with necessary interconnections as per Dwg.CED/ELE/S/19 INTERNAL COMMUNICATION Internal Telephone/TV wiring & Networking Facility. Supply and embedment of 20mm dia HGMS conduit concealed in wall floor/ ceiling including supply and drawing of 12SWG wire as fish wire including supply of all fixing materialsas required and as directed by EIC. (200Mtr for Telephone & 100Mtrs for Lan, )

III 1 400

Mtr

400

Supply and embedment of 25mm dia HGMS conduit concealed in wall floor/ ceiling including supply and drawing of 12SWG wire as fish wire including supply of all fixing materialsas required and as directed by EIC. (200Mtr for Telephone & 100Mtrs for Lan,)

Mtr

300

Supply and laying of PVC insulated copper conductor 0.5mm dia 2 pair Telephone wire in already embedded conduits including interconnections complete as required. Supply and laying of PVC insulated copper conductor 0.5mm dia 5 pair Telephone unarmored cable in already embeddedconduits including interconnections complete as required.

Mtr

140

Mtr

100

Supply and laying of PVC insulated copper conductor 0.5mm dia 10 pair Telephone unarmored cable in already embedded conduits including interconnections complete as required.

Mtr

Supply and installation of the following Telephone krone in 2mm thick CRCA sheet steel enclosure flush mounting type with a removable hinged top cover and duly painted, including providing of mounting bracket for Krone type connector and inter connections as required

a) b) 7

1 1

10 Pair 20 Pair Supply and laying the following 0.5mm dia copper conductor armoured telephone cables on existing cable trays/trench including all fixing accessories & connections and complete as required.

each each

Page 7 of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No a) b) c)

QTY 100 200 200


10 Pair 20 Pair 50 Pair

DESCRIPTION OF ITEM

UNIT Mtr Mtr Mtr

RATE (in Figures& Words)

AMOUNT

( Cable shall be laid in ground wherever required including excavation & back filling with sand & brick protection )

8 9 10

1 50 2

Supply and fixing of 8 way TV Tap off in 2mm thick MS box Each covered with 3mm thick hymnal sheet, including supply of all fixing materials as required Supply and laying of RG6 copper conductor Co -axial joint less Mtr TV antenna cable in existing conduit including supply of all fixing materials as required Supply and fixing of Telephone jack with RJ11 modular type jack each including supply and fixing of anodized GI box and its front plate including interconnections as required. Supply and fixing of LAN jack with RJ45 modular type jack each including supply and fixing of anodized GI box and its front plate including interconnections as required. Supply and fixing of following TV Sockets outlets ( Modular type ) each in anodized box concealed in wall.Including front plate & other accessories Earthing & Lightning Protection Providing standard pipe earth to earth stations with 2.5m long, each 38mm dia GI pipe earth stations confirming to IS : 3043 with latest amendments and as per standard dwg., and including supply of all materials and providing chamber complete as per standard drawing as required. (2Nos for panel,4Nos for LP,2for UPS body earth) Providing standard 2.5m depth with copper plate earth for earth each station with 600x600x3.15mm electrolytic copper plate, confirming to IS:3043 with latest amendments and as per standard dwg., including supply of all materials and providing chamber complete as required. ( for UPS-4nos ) Note: 1) Copper plate shall be tinned 2) Rate of earth station includes the cost of suitable medium class GI pipe for watering

11

12 IV 1

Page 8 of 9

Package-II Part-IV Electical Works Security Office Building

Sl.No 3

QTY

DESCRIPTION OF ITEM

UNIT

Supply and laying of electrolytic copper/GI strip of following sizes including supply and fixing using MS/Aluminum spacers, saddles welding with all fixing materials required and when laid inside the building and inclusive of excavation & refilling of earth when laid outside the building and tinning of all the joints & terminations interconnections interconnections with earth pit and equipment, terminations/ interconnections in an approved manner as per IS 3043 (with latest amendments) inclusive of supply of all hard wares complete as required.

RATE (in Figures& Words)

AMOUNT

250

Note: Strips when laid on roof for lightning protection shall be as per standard dwg 25 x 3mm GI strip with flat GI on surface of building at evry 1Mtr spacing (for Lightning Protection as roof conductor) 32 x 6mm GI strip buried in ground (For Lightning Protection as ground conductor) 2Core 10Sq.mm Pvc insulated copper conductor cable for Neutral Earthing of UPS using lugs for termination etc. 25 x 6mm GI strip ( For Panel, UPS- Body& Cable tray)

Mtr

100

Mtr

6 7

50 50

Mtr Mtr

TOTAL

Rs

Page 9 of 9