Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

IV.1 I 1 135

TRANSINT HOUSE BUILDING INTERNAL ELECTRIFICATION Primary Light points Supply and Wiring for Primary Light point with FRLS 1.5sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, FRLS stranded copper conductor cable conforming to IS:694 (with latest amendments) in 20 mm dia 2mm thick electrical grade,PVC conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of 1No 6Amp Modular(plate) control switch fixed in a suitable size metal sheet flush boxes suitable for modular switches and covered with modular switch plates and all necessary components, and earthing with 1.5Sq.mm PVC insulated copper wire run continuously inside the conduit including supply of all fixing materials, accessories and interconnections complete as required.

PT

Notes: 1. Rates for all the point wiring items are inclusive of necessary circuit mains with 3Runs of 2.5sqmm FRLS PVC insulated Copper conductor wires from the distribution board to the first switch board and also sub circuits from one switch board to the subsequent switch boards in the same circuit. 2. The secondary point in case of point wiring shall include necessary wiring looped from the primary light point as indicated in the electrical layout drawings. 3. Rates for the power point wiring items are inclusive of necessary power circuit from the DB to the power socket. 4. All 16A power Switch Sockets shall be with Built in LED indication Secondary Point Supply and wiring generally same as item 1 above but without control switch. Ceiling Fan Point Supply and Wiring for ceiling fan point with FRLS 1.5sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable conforming to IS:694 (with latest amendments) in 20 mm dia,2mm thick electrical grade,PVC conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of 1No 5Amp modular (plate) control switch & 100W step type electronic regulator fixed in suitable size metal sheet Box suitable for modular switches and regulator and covered with modular switch plates and earthing with 1.5Sq.mm PVC insulated copper wire run continuously along the conduit including supply of all fixing materials, accessories like fan hook box, termial box , interconnections complete as required.

71

PT

43

PT

Page 1 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

25

Exhaust Fan Point Supply and wiring generally same as item 1 above but for exhaust fan with 6 Amp modular SPMCB for control. Two way point Supply and wiring generally same as item 1 above, but for Twoway light point with 2nos 2 way, 6 Amps. Modular switches.(for Staircase-4 & For Rooms-16) 5 Amp 3 Pin Socket outlet poin Supply and wiring generally similar to item 1 above but for modular 5A, 3pin combined switch socket outlet point including supply and fixing of 5A 3 pin combined switch socket outlet in a suitable size metal sheet Box and covered with modular plate complete as required. 5A 3pin socket outlet in lighting switch boar Supply and fixing of modular 5A 3pin combined switch socket outlet in the metal sheet Box of lighting control switch board including interconnections complete as required. 16A Combined Switch socket outlet Supply and Wiring with FRLS 2runsX 2.5sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable conforming to IS:694 (with latest amendments) in 20 mm dia, 2mm thick electrical grade,PVC conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of modular 16Amp/5Amp modular universal switch socket outlet with LED indication fixed in a suitable size metal sheet box suitable for switches and sockets and covered with modular switch plate and earthing with 2.5SQmm insulated copper wire run continuously along the conduit including supply of fixing materials, interconnections complete as required.

PT

20

PT

10

PT

38

PT

38

PT

16

AC OUTLET Supply and Wiring with FRLS 2runsX 4sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable confirming to IS:694 (with latest amendments) in 20 mm dia, 2mm thick electrical grade,PVC conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of modular 32Amp 2ploe ELMCB 100mA Sensitivity in metal sheet box suitable for ELMCB,size and covered with modular switch plate and earthing with 2.5sqmm insulated copper wire run inside the conduit power supply shall be trapped from DB,and 20mm dia 2mm thick electrical grade PVC pipe shall be laied in wall with fish wire from ELCB board (which is fixed at 1.2m from FFL) to the height of indoor AC unit and teriminate ina suitable MS box concealed in wall including cover for interconnecting to AC unit complete as required.

PT

Page 2 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

10

16

16A socket outlet for Geze Supply and Wiring with FRLS 2runsX4 sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable conforming to IS:694 (with latest amendments) in 20 mm dia, 2mm thick electrical grade,PVC conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of modular 16Amp modular socket outlet fixed in a suitable size metal sheet box suitable for sockets and covered with modular switch plate and earthing with 4SQmm PVC insulated copper wire run continuously along the conduit including supply of fixing materials,the power supply shall be tapped from exsisting 32A ELMCB fixed at the door including interconnections complete as required.

PT

11 16

Control switch for Geyser Supply and Wiring with FRLS 2runsX 4 sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable conforming to IS:694 (with latest amendments) in 20 mm dia, 2mm thick electrical grade,PVC conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of modular 32Amp 2pole ELMCB in metal sheet box sutable for modular ELMCB of suitable size and covered with modular switch plate and earthing with 4SQmm PVC insulated copper wire run continuously along the conduit including supply of fixing materials,thepower supply is tapped from DB, & switch board shall be fixed at out side of the door including interconnections complete as required.

PT

12 12.1

Run of mains

500 Supply and wiring with 4runs of 6sq.mm, 1.1 KV grade FRLS
pvc insulated, single core stranded copper conductor cable confirming to IS:694 (with latest amendments) in 3 2mm dia 2mm thick electrical grade PVC pipe insulated concealed in wall/ceiling, or floor and earthing with 2 run of 4sq.mm copper wire run continuously along the conduit including supply of all fixing materials and accessories, interconnections complete as required. (from Vertical Dbs to room wise Dbs )

Mtr

12.2

100 Supply and wiring with 4runs of 10sq.mm, 1.1 KV grade FRLS
pvc insulated, single core stranded copper conductor cable confirming to IS:694 (with latest amendments) in 40mm dia 2mm thick PVC electrical grade concealed in wall/ceiling, or floor and earthing with 2 run of 6sq.mm copper wire run continuously along the conduit including supply of all fixing materials and accessories, interconnections complete as required (from panel to Vertical Dbs )

Mtr

Page 3 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

12.3

50

13

Supply and wiring with 2runs of 4sq.mm, 1.1 KV grade FRLS pvc insulated, single core stranded copper conductor cable confirming to IS:694 (with latest amendments) in 25mm dia 2mm thick PVC electrical grade concealed in wall/ceiling, or floor and earthing with 2 run of 2.5sq.mm copper wire run continuously along the conduit including supply of all fixing materials and accessories, interconnections complete as Distribution Boards Supply installation Testing and commissioning of TPN MCB Double Door Distribution boards dust and vermin protected and rated for 440V Three phase 50hz AC supply operation, including of bus bar suitable capacity, neutral link with required outgoings, din bar, fully factory fabricated with powder coated incoming ELMCB as per specifications and required capacity and Earth terminal complete as required and installed in flush with wall including all fixing materials required. (All MCB's in UDBs shall be of 'D' Curve & other MCB's shall be 'C' Curve.

Mtr

13.1

6way VTPNMCCB DB with 100ATPN MCCB 35KA incomer-1 and 32A TPMCBs as outgoings 6nos.

as

sets

13.2

4way VTPNMCCB DB with 63ATPN MCCB 35KA as incomer 1 and 32A TPMCBs as outgoings 4nos. 6way TPNMCBDB with 63A,100mA leakage current sensitivity FP ELMCB as incomer and 18nos 6A SPMCBs as outgoings.(LDBs) Customized DB TPNMCBDB with 32A FP ELMCB with,100mA leakage current sensitivity as incomer-1and 32A TP contactor with 230V coil one number and 6A ,16A &20A SPMCBs 6 nos as outgoings. 8way SPNMCB DB with 32A MCB as incomer-1 and 6A SPMCBs as outgoings 8nos. BUZZER POINT Supply and Wiring for buzzel/call bell point with 1.5 sq.mm 1.1kV grade, ISI marked, PVC insulated ,FRLS single core , stranded copper conductor cable conforming to IS:694 ( with latest amendments) in 20mm. Dia 2mm thick ele.grade PVC conduit concealed in ceiling or buzzer/call bell fixed in suitable size independent metal sheet boxes covered with modular switch plates sheet, and earthing with 1.5sq.mm insulated copper wire run inside the conduit including supply of fixing materials and interconnections complete as required.

set

13.3

sets

14

16

sets

15 16

sets

16

PT

Page 4 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

II 1

Supply & Installation of Light Fixtures & Fans Supply &Installation of Light Fixtures Supply, installation, testing & commissioning of the following light fittings with electronic ballast and all other accessories including supply of lamps. Installation of light fittings complete with supply of all materials like balancing socket, conduit pipe, nipples, check nuts, bolts, nuts, metallic flexible hose, suspension rod/ Chain, clamps etc., required for such installtion as per specifications for the following fittings including painting with aproved synthetic paint, necessary interconnections in an approved manner. 1X28W TL5 light fixture (CAT NO:-TCH 207 1X TLF 28HF similar to PHILIPS)

a) 15 15 b) 52 52 c) 16 16 d 16 16 e 10 10 f 33 33

Supply Installation 1X14W wall bracket light fixture (In bed rooms) (CAT NO:TCH 207/1XTL5-14W similar to PHILIPS) Supply Installation 1X9W wall bracket light fixture (for dressing table) (CAT NO:FMC 21/109 similar to PHILIPS) Supply Installation 1X9W wall bracket light fixture (for mirror light) (CAT NO:-FMS 200/111 similar to PHILIPS) Supply Installation 2X18W Surface mounting light fixture (CAT NO:-FCS 518/218 similar to PHILIPS) Supply Installation 4X14W T5 recess mounted light fixture (CAT NO:-TBS 869/414 D8 HF similar to PHILIPS) Supply Installation

Each Each

Each Each

Each Each

Each Each

Each Each

Each Each

Page 5 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

2X28W T5 mirror optic type fixture (surface mounted) (CAT NO:-TCS 398/2 X28 MDGN HF similar to PHILIPS)

28 28 h 12 12 i 20 20 j 16 16 2

Supply Installation 2X28W FTL (T5)-WEF 83228 SGW AEROS-DP Indirect Direct pendent mounted luminary with lamp(WIPRO Make) Double height area Supply

Each Each

Each Each

Installation with using of a set of 2.Quick install suspension system for areos-DP suitable for RCC Ceiling(WVX 821) 4W WALL MOUNTED LED LIGHT FIXTURE (bed side) (CAT NO:-BBG 410 K2-10/CW PSU 220-240V similar to PHILIPS) Supply Installation 1X5W CFL-DF foot luminary with lamp (Similar to Compton grieves CHL 218 LSB) Supply Installation Supply, installation, testing and commissioning of light duty, totally enclosed motor type exhaust fans suitable for operation on 230Volts, 50Hz single phase AC supply complete with 3core flexible copper conductor cable, gravity louvers shutters rigid frame with rubber mountings and of flooring sizes confirming to IS-2312 (with latest amendments) 225mm sweep 1400RPM with double Ball Bearing (in rooms)

Each Each

Each Each

2.1 20 20

Supply Installation of exhaust fan with gravity louvers on wall including grouting of bolts for installation supply of material as Dwg. CED/24/S/17 300 mm sweep 900RPM with double Ball Bearing Supply Installation of exhaust fan with gravity louvers on wall including grouting of bolts for installation supply of material as Dwg. CED/24/S/17

Each Each

a b

5 5

Each Each

Page 6 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

4 43 43

Supply of 1200mm sweep ceiling fan capacitor type complete with 300mm down road suitable of 230V AC supply Supply Installation of ceiling fans of having standard down rod with all materials required for installation complete with necessary interconnections as per Dwg. CED/24/S/19 Extra down rod with 20mm dia class C GI pipe including supply of GI pipe,cutting threading and providing interconnection pipe etc Geyser Supply & Installation of the following non -pressure type gezers with all required material, geysers conforming to IS 2082 (with latest amendments) and suitable for 230V 50HZ single phase AC supply complete with inlet and outlet manifolds and saftey devices like thermostat cutout with reset,LED indication lamp,3C flexible copper cable and plug top

Each Each

5 6

15

Mtr

6.1

16

Storage type vertical fixing 15ltrs capacit Supply

Each

16

Installation on wall/coloumnwith necessary base plate brackets made out of MS angle iron/flat of suitable size including cutting,welding,groutingand supply of all Installation materials fixing of inlet/outlet water pipes interconnection complete as required. Supply and fixing of 10A Fab switch with Fab key and engraving the room number 230V 50HZ

Each

7 16 8 9 1

Supply & Installation (To control DB cont actor) Supply & fixing of 32 DP MCB in a sheet steel en closer suitable for wall concealed for outgoing of UPS OLYMPIA light poles with 4X18W CFL lamps, 3.6mts height including fixing of junction box 16Aconnector and MCB

Each Each

Page 7 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

Supply and erection of 3.6Mts height garden light pole fabricated out of 60mm dia MS Pipe OYMPIA LIGHT POLE with 4 arms core aluminum bracket with end portion suitable for 4 numbers 18W CFL integral Post top lanthern type Decorative light fitting, built in stainless steel control box etc. the pole shall be finished neatly with one coat of primer and two coats of enamel paint of approved color. The scope of work includes necessary earth work upto a depth of 600mm with 300X300X600mm 1:2:4 concrete pedastal, necessary concrete coping 300X300X375mm, providing suitable ms junction box with fuse units, connectors suitable hole for termination of 2.5Sq.mm cable with 25mm Pvc pipe and outgoing including interconnections with 1.5Sq.mm single core copper conductor cable and earthing with 1.5Sq.mm copper conductor complete as required. (OLYMPIA COLUMN 522 of Metal Coats)

Each

Supply, fixing and testing of Pre-wired decorative 1X18W CFL integral Post top lanthern of size 240mmX360mm with louvers clear glass complete with all accessories such as holder, lamps etc suitable for mounting on 60mm dia GI/ MS Pole complete with interconnections as specified and directed by the EIC.

Each

Supply and fixing of one way Metal enclosure for SPMCB independent mounting suitable for terminations cable gland on MS conduit with 6A SPMCB concealed in wall interconnection earthing complete as required (For FL tube light) (similar Legrand no 60788) MV CABLES Supply of 1.1KV grade XLPE insulated, and overall sheathed, stranded aluminum/ Copper conductor, flat steel strip/wire armored / unarmored cables confirming to IS:7098/Part I (with latest amendments)and of following sizes. The cable shall bear ISI certification mark. Note: The Actual Lengths of cables shall be verified at site before procurements

Each

*** 10

10.1 a

2Core 2.5sq.mm Un- Armoured Flexible Cu. Cable (for Land scape lighting) 30 Supply Laying of above cables in 25mm 2mm thick PVC pipe includin supply of PVC pipe and partly laying in wall/ Concealed and in ground including excavation refilling and providing baked bricks on top and side in depth 750mm below ground level complete including interconnections etc as required.

Mtr

b c

20 Laying in Ground. 10 Laying in wall (Concealed in wall)

Mtr Mtr

Page 8 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

11

2 Providing Spiral coil earthing with 8SWG GI wire including


spreading of salt and charcoal as per IS 3043/87 with latest amendments.

Nos

III 1 500

INTERNAL COMMUNICATION Internal Telephone/TV wiring & Networking Facility. Supply and embedmentof 20mm dia 2mm thick electrical grade PVC conduit concealed in wall floor/ ceiling including supply and drawing of 12SWG wire as fish wire including supply of all fixing materials as required and as directed by EIC. (250Mtr for Telephone & 250Mtrs for Lan, ) PVC conduit concealed in wall floor/ ceiling including supply and drawing of 12SWG wire as fish wire including supply of all fixing materials as required and as directed by EIC. (200Mtr for Telephone & 100Mtrs for Lan,)

Mtr

100 Supply and embedmentof 25mm dia 2mm thick electrical grade

Mtr

300 Supply and laying of PVC insulated copper conductor 0.5mm


dia 2 pair Telephone wire in already embedded conduits including interconnections complete as required.

Mtr

100 Supply and laying of PVC insulated copper conductor 0.5mm


dia 5 pair Telephone unarmoured cable in already embedded conduits including interconnections complete as required.

Mtr

100 Supply and laying of PVC insulated copper conductor 0.5mm


dia 10 pair Telephone unarmoured cable in already embedded conduits including interconnections complete as required.

Mtr

Supply and installation of the following Telephone krone in 2mm thick CRCA sheet steel enclosure flush mounting type with a removable hinged top cover and duly painted, including providing of mounting bracket for Krone type connector and inter connections as required

a) b) c) 7

1 2 1

10 Pair 20 Pair 50 Pair Supply and laying the following 0.5mm dia copper conductor armoured telephone cables on existing cable trays/trench including all fixing accessories & connections and complete as required.

each each each

a) b) c)

100 10 Pair 122 20 Pair 100 50 Pair

Mtr Mtr Mtr

Page 9 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

( Cable shall be laid in ground wherever required including excavation & back filling with sand & brick protection )

Supply and fixing of 6 way TV Tap off in 2mm thick MS box covered with 3mm thick hylam sheet, including supply of all fixing materials as required Supply and laying of RG6 copper conductor Co -axial joint less TV antenna cable in existing conduit including supply of all fixing materials as required Supply and fixing of Telephone jack with RJ11 modular type jack including supply and fixing of anodised GI box and its front plate including interconnections as required. Supply and fixing of LAN jack with RJ45 modular type jack including supply and fixing of anodised GI box and its front plate including interconnections as required. Supply and fixing of following TV Sockets outlets ( Modular typ ) in anodized box concealed in wall. Including front plate & other accessories Earthing & Lightning Protection Providing standard pipe earth to earth stations with 2.5m long, 38mm dia GI pipe earth stations confirming to IS : 3043 with latest amendments and as per standard dwg., and including supply of all materials and providing chamber complete as per standard drawing as required. (2Nos for panel,4Nos for LP,1no for UPS body) Providing standard 2.5m depth with copper plate earth for earth station with 600x600x3.15mm electrolytic copper plate, confirming to IS:3043 with latest amendments and as per standard dwg., including supply of all materials and providing chamber complete as required. ( for UPS-1no ) Note: 1) Copper plate shall be tinned 2) Rate of earth station includes the cost of suitable medium class GI pipe for watering

Each

400

Mtr

10

30

each

11

24

each

12

25

each

IV 1

each

each

Supply and laying of electrolytic copper/GI strip of following sizes including supply and fixing using MS/Aluminium spacers, saddles welding with all fixing materials required and when laid inside the building and inclusive of excavation & refilling of earth when laid outside the building and tinning of all the joints & terminations interconnections interconnections with earth pit and equipment, terminations/ interconnections in an approved manner as per IS 3043 (with latest amendments) inclusive of supply of all hardwares complete as required.

Note: Strips when laid on roof for lightning protection shall be as per standard dwg

Page 10 of 11

Package-II Part-IV Electrical Works- Transit House Building

Sl.No QTY

DESCRIPTION OF ITEM

UNIT

RATE (in Figures& Words)

AMOUNT

3.1

500 25 x 3mm GI strip with flat GI on surface of building at every


1Mtr spacing (for Lightning Protection as roof conductor)

Mtr

3.2 3.3

200 32 x 6mm GI strip burried in ground (For Lightning Protection


as ground conductor)

Mtr Mtr Rs

75

25 x 6mm GI strip ( For Panel, UPS- Body& Cable tray) TOTAL

Page 11 of 11