PIPE SIZE AS SHOWN ON PLAN

FINISHED FLOOR

CONC. FLOOR BEDDING

STRUCTURAL SLAB

COATED CAST IRON CLEANOUT FERRULE SPIGOT CONNECTION SERIATED CUT-OFF SECTION

NO HUB CONNECTION

SELF DRILLING ANCHOR SLUG

VERTICAL OFFSET PIPE CLAMP

TWO HALF CLAMPS AND TWO BOLTS WITH NUTS FOR RISER CLAMP

PIPE RISERS

SOLID SCORIATED SECURED ROUND COVER

COATED CAST IRON FERRULE AND ADJUSTABLE FLOOR CLEANOUT ,NO-HUB CONN. WITH INTERNAL BRONZE COUNTERSUNK PLUG

FINISHED FLOOR

CONC. FLOOR BEDDING

STRUCTURAL SLAB

NO HUB CONNECTION

PIPE SIZE AS SHOWN ON PLAN

WASTE PIPE FROM WASH BASIN , SHOWER OR KITCHEN SINK SQUARE / ROUND STRAINER WITH SOLID HINGED COVER COATED CAST IRON COMBINED FLOOR DRAIN & INTEGRAL TRAP SEAL WITH 2" NO-HUB AUXILLIARY INLET, INTERNAL PLASTIC CLEANOUT AND 3" / 4" SIDE OUTLET NO-HUB CONN. NO-HUB CONNECTION CONCRETE FLOOR BEDDING TOP OF SLAB FLOOR FINISH

STRUCTURAL FLOOR SLAB

SOIL PIPE B/G SIZE AS SHOWN ON PLAN

WASTE PIPE FROM WASH BASIN , SHOWER OR KITCHEN SINK SQUARE / ROUND STRAINER WITH SOLID HINGED COVER COATED CAST IRON COMBINED FLOOR DRAIN & INTEGRAL TRAP SEAL WITH 2" NO-HUB AUXILLIARY INLET, INTERNAL PLASTIC CLEANOUT AND 3" / 4" SIDE OUTLET NO-HUB CONN. NO-HUB CONNECTION CONCRETE FLOOR BEDDING TOP OF SLAB FLOOR FINISH

STRUCTURAL FLOOR SLAB

WASTE PIPE B/G SIZE AS SHOWN ON PLAN

FUNNEL SQUARE / ROUND STRAINER COATED CAST IRON TWO PIECE BODY WITH DOUBLE DRAINAGE FLANGE , WEEP HOLES, BOTTOM OUTLET INSIDE CAULK CONNECTION FINISHED FLOOR CONC. FLOOR BEDDING WATER PROOFING MEMBRANE STRUCTURAL SLAB

PIPE SIZE AS SHOWN ON PLAN WASTE PIPE AT H/L

NO HUB CONNECTION

HEAVY DUTY SURFACE BOX AND FRAME CLEAR OPENING 22.5x22.5cm SUPERSEAL RECESSED CLEAN OUT PLUG AND SPIGOT CONN. FINISHED FLOOR LEVEL.

PIPE SIZE AS SHOWN ON PLAN

SEE PLAN

SELF DRILLING ANCHOR SLUG.

BOTTOM SIDE OF STRUCTURAL SLAB. ROUND STEEL ROD SIZE AS REQUIRED.

CLEVIS HANGER

SELF DRILLING ANCHOR SLUGS. BOTTOM SIDE OF STRUCTURAL SLAB. SITE FABRICATED FRAMING. ANCHOR CHAIR. U. BOLT AND HEX NUTS

FINISHED FLOOR LEVEL CONC. SLAB

VARIABLE

REINFORCED STEEL WATER PROOFING MEMBRANE

20cm.

STEEL ROD Y10 FOR 75 AND BELOW, Y16 FOR PIPES ABOVE 75 EVERY 150cm

PIPE 20cm. 20cm. 20cm.

600 (Min.)

200

250

250
600

100

300

100

600

RAIN WATER PIPE

CAST BRONZE NOZZLE LOOSE WALL FLANGE AND INLET THREADED CONNECTION 150MM ABOVE FFL

FLOOR FINISH

FLOOR TOPPING

STRUCTURAL FLOOR SLAB

DOME STRAINER CAST IRON BODY

ROOF FINISHING AS PER ARCH. DETAILS

WATERPROOFING MEMBRANE

STRUCTURAL SLAB

RAIN WATER PIPE SIZE AS SHOWN ON PLAN

WATERPROOFING MEMBRANE WATERPROOFING MEMBRANE

SIDE OUTLET ROOF DRAIN PIPE WITH EXTTENSION PIECE & ELBOW

ROOF FINISHING AS PER ARCH. DETAILS

LIGHTWEIGHT CONCRETE LAID TO SLOPE

STRUCTURAL CONCRETE SLAB

PUDDLE FLANGE ON PIPE SLEEVE.

STRUCTURAL RETAINING WALL.

EXTERNAL SIDE OF WALL. WATER PROOFING MEMBRANE

PIPE AS PER SPECIFICATION AND SIZE AS SHOWN ON DRG.

CAULKED LEAD JOINT. FIBERGLASS FILLER.

MASTIC SEALANT.

ESCUTCHEON PLATE

INTERNAL WALL PARTITION STEEL JACKET OR COLLAR CONTAINING SECTIONS OF INTUMESCENT MATERIAL MASTIC SEALANT

PIPE AS PER SPECIFICATION AND SIZE AS SHOWN ON DRG.

FIRE SEAL MATERIAL (FIRE RATING 1hr./2hr./4hr. AS PER ARCHITECTURAL SPECIFICATIONS) PIPE SLEEVE

CAPACITY ................................................ SLUDGE TRAP CAPACITY IN LITER .. SLUDGE DISPOSAL VOLUME IN LITER ................................................................ D min.......................................................... D max......................................................... h2 (Inlet bottom in mm).............................. h1 (Outlet bottom in mm)........................... Oil storage capacity in liter......................... Weight in kg .............................................. Article # Cover Class B/D .........................

3 l/s 800 liter 400 liter 110 545 995 1105 1055 200 175 99703.04B

STACK

TO BE LAGGED WITH SOUND INSULATION AS SPECIFIED.

1500

FIRE RETARDANT FOAM FILL

PIPE TO BE CASTED IN LIGHT WEIGHT CONCRETE, AFTER INSTALLATION AND TESTING EXACT STRUCTURAL DETAILS TO BE AGREED WITH STRUCTURE ENGINEER. 1500 500 300

TO BE LAGGED WITH SOUND INSULATION AS SPECIFIED.

150

NON-SLIP S./STEEL GRATING 300 NON-SLIP FLOOR TILES 20 260 20 300

ST.STEEL DRAINAGE CHANNEL

255

50

200

50

REMOVABLE STAINLESS STEEL PERFORATED TRAY

300

STAINLESS STEEL GRATING (NON SLIP TYPE) OPTIONAL SIDE INLETS TO SUIT 50, 75 OR 100 MM PIPE WORK UP TO 3 AT 90 RODDING ACCESS PLUG 300

210

150

60

INTEGRAL TRAP

60 93 OUTLET TO SUIT 100MM BS416 STAINLESS STEEL SEDIMENT BUCKET

300

VARIES

VENT PIPE

PUMPED DISCHARGE PIPE

INSPECTION OPENING AND COVER

VENT PIPE DISCHARGE HEADER SLUICE VALVE SELF CLOSING CHECK VALVE SLEEVE INSPECTION OPENING AND COVER CONDUIT TO CONTROL PANEL

CHAIN

PIT DEPTH SEE STRUCTURAL DRGS

DRAINAGE MAIN INLET FROM DRAINAGE NET WORK GUIDE TUBE DISCHARGE PIPE FLOATS SUMP PUMP

PIT OPENING SEE STRUCTURAL DRGS

DUCTILE IRON/STAINLESS STEEL DRAWING CHANNEL DUCTILE IRON GRATING VARIES

300

NON-SLIP FLOOR TILES NON-SLIP DUCTILE IRON GRATING 360 30 300 30 30 X 30MM. `L' D.I 30MM. D.I ALL AROUND

ST.STEEL DRAINAGE CHANNEL

200

50

200

50

REMOVABLE STAINLESS STEEL PERFORATED TRAY

NON SLIP FLOOR TILES NON SLIP DUCTILE IRON GRATING 30 X 30MM. `L' D.I

VARIES

ST.STEEL DRAINAGE CHANNEL -200 50 200 50

-150

REMOVABLE STAINLESS STEEL PERFORATED TRAY

50

200

50

TYPICAL SECTION FOR FUTURE BACKDROP CONNECTION 600 (CLEAR OPENING) MANHOLE COVER AND FRAME WITH GRP SEALING PLATE ( ORIENTATION SHOULD BE ACCORDING TO TOP PLAN DETAIL)

TYPICAL SECTION FOR BACKDROP TO BE CONSTRUCTED

CLASS B SCREED CONCRETE TO BE FLUSH WITH MANHOLE COVER AND PAVEMENT LEVEL MANHOLE COVER & FRAME PER SPEC. EPOXY COATING MINIMUM THICKNESS 0.75mm TO INTERNAL FACES OF BLOCKWORK PAVING MIN. 100 THICK ONE COURSE OF CONCRETE BLOCK WORK OR PRECAST CONCRETE RING CLASS A PRECAST REINFORCED CONC. RING JOINT SEALANT
250

300mm THICK PRECAST REINFORCED CONCRETE CLASS A TOP SLAB

7mm GRP LINER TYPICAL ALL INTERIOR SURFACES

CLASS A PRECAST REINFORCED CONCRETE WALL 90 TEE 13mm THICK X 150mm WIDE BAND OF RUBBER WRAPPED AROUND PIPE

PRECAST COVER SLAB

(DIA) ALL INTERFACE CONCRETE TO BE THOROUGHLY SCABBLED

600 LONG PIPE INLET PLUGGED, OR HOUSE CONNECTION LATERAL OR MAIN SEWER LINE CONNECTED AS DIRECTED BY THE ENGINEER PIPE TO BE FITTED WITH REMOVABLE STOPPER SECURELY RETAINED ON INTERNAL WALL BY APPROVED METHOD 4mm. WATER PROOFING MEMBRANE AND 4mm. PROTECTION BOARD. BACKDROP CLASS C CONCRETE SURROUND TO BACKDROP PIPE WORK 90 BEND SAND/CEMENT SCREED CLASS C BLINDING CONCRETE UNDISTURBED SOIL

250

ANCHOR BOLT

DOWEL BARS TO BE INSERTED AT THE INTERFACE AS INSTRUCTED BY THE ENGINEER JOINT BETWEEN GRP LINER AND PIPE TO BE LAMINATED AS SPECIFIED CLASS B BENCHING 1:6 SLOPE MAIN SEWER (INVERT GIVEN ON PROFILE SHEETS)

PRECAST CONC. RING WITH GRP LINER

DETAIL AT PAVED LOCATIONS


MANHOLE/COLLECTION CHAMBER/ INSPECTION CHAMBER COVER SLAB

300

300

REBATE FOR MH COVER FRAME INSTALLATION 300X300 HEAVY DUTY FRAME & COVER 600 CLEAR OPENING

SECTION BACKDROP MANHOLE TOP PLAN


BACKDROP MANHOLE SCALE 1:25

NOTE :

COVER SLAB SHOWN HERE IS FOR NON PAVED AREA,

MAIN SEWER LINE

LEGEND:
MANHOLE FOOTING 4mm. WATER PROOFING MEMBRANE

PRECAST REINFORCED CONCRETE IN SITU REINFORCED CONCRETE PLAIN CONCRETE SAND/CEMENT SCREED

BACKDROP INLET

7mm GRP LINER

MANHOLE DEPTH (DEPTH) 1510 TO 2000 SECTIONAL PLAN


BACKDROP MANHOLE

SIZE (DIA) 1200 1300

SEWER

2010 TO 4000

FLEXIBLE CONNECTIONS WALL PROTECTION SLEEVE WITH RUBBER SLEEVE.

MANHOLE DEPTH (DEPTH (H)) mm UPTO 900 910 TO 1200 1210 TO 1500

SIZE (L x W) mm 600 x 600 800 x 800 1000 x 1000

PLAN

SECTION C - C

VANDAL-PROOF COATED CAST IRON HOODED VENT CAP

60cm

FLASHING SLEEVE

WATERPROOFING MEMBRANE

ROOF FINISHING AS PER ARCH. DETAILS

STRUCTURAL SLAB

VENT THRU ROOF SIZE AS SHOWN ON PLAN