Panelboards and Lighting Control

Pow-R-Command

10.6
Page 451 453 454 457 460 463 467 470 473

Pow-R-Command Family

Contents
Description Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Eaton Green Solution

10 10 10 10 10 10 10 10 10 10 10

Product Overview
Eatons Pow-R-Command family of lighting control panelboards is designed to meet the lighting control needs for buildings of all sizes and complexity. The system incorporates microprocessorbased distributed intelligence within a traditional panelboard, simplifying wiring in the field. The system can be networked over customers LAN or directly interfaced to the Internet, allowing for password protected web access. The panelboard design allows the Pow-R-Command lighting control system to meet shortcircuit ratings, as required by the National Electrical Code (NEC). The Pow-R-Command panelboard mounting, power wiring and branch wiring are the same as in traditional panelboards. Depending on the controller model, PRC controllers can be applied to distribution systems rated single-phase three-wire and three-phase four-wire 120, 120/240, 208Y/120 and 480Y/277 Vac. The PRC family consists of the PRC2000, PRC1000, PRC750, PRCEP, PRC100, PRC50 and the PRC25 for panelboard installations and the PRC4000 building control devices, which have wireless communications.

Lighting Control Overview


Traditional lighting control employs lighting contactors or relay panels to turn groups of lighting on or off. Input devices are typically time clocks, photo cells, wall switches, or, in more sophisticated applications, contact inputs from a building automation system (BAS). Pow-R-Command is a lighting control panelboard with remote controllable circuit breakers. These controllable circuit breakers perform a dual function: 1. They provide the overcurrent and overload protection for the circuit. 2. They perform the same function as relays and contactors in traditional lighting control systems, opening and closing the circuit in response to a remote signal. Design Considerations Short-Circuit Protection: In the past, contactors or relay panels were mounted close to the lighting load and shortcircuit ratings were not a major concern. Today, most of the lighting control devices are located in electrical rooms, often adjacent to the panelboards that feed them. These devices are subjected to short-circuit conditions

almost as high as those of the electrical distribution equipment. The current version of the National Electrical Code requires that these lighting control devices carry a short-circuit rating (Article 110-10). Although some traditional lighting control components are available with short-circuit ratings, these ratings are limited and may require upstream fusing. A lighting control panelboard makes meeting the requirements of NEC 110-10 as simple as specifying the short-circuit rating of the panelboard. Flexibility: Lighting control panelboards allow simple and inexpensive changes during startup. Contactor and relay panels often require rewiring to make changes in the field. Choices: Eatons lighting control panelboards offer varying levels of flexibility, from six zones per panel with the Pow-R-Command 25 up to 250 zones per panel with the Pow-R-Command 2000. Space: Lighting control panelboards eliminate contactor panels and/or relay panels, freeing up valuable wall space. Pow-R-Command panels are the same width as standard panelboards.

Retrot Applications: Retrofitting traditional lighting control methods into an existing electrical distribution system often requires extensive rewiring and unwanted downtime. In most cases, a Pow-R-Command panel interior can be installed into an existing panelboard back box, and the cables can be re-terminated on the new circuit breakers, with minimal downtime.

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

447

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
448

Panelboards and Lighting Control


Pow-R-Command

Installation Considerations Simplicity: Lighting control panelboards are as easy to install as standard panelboards. There are no additional components to install. Labor: Because contactors and relays are eliminated, the labor associated with installing them and the additional cables and conduit associated with them is eliminated. Startup: Startup for the PowR-Command panelboards is straightforward. The PRC25 requires no startup. It is prewired at the factory. The PRC100 is provided with factory startup assistance for trouble-free installation. The PRC750 is provided with an LCD display and keypad for on-site programming. The PRC1000 and PRC2000 are programmed over the network. They have an optional display available for local interface. Operational Considerations Failure Modes: If a lighting contactor or relay fails to operate due to a mechanical or control system failure, it is very difficult to control the lights manually. Often, it is necessary to hard-wire around the device on a temporary basis. With a lighting control panelboard system, the circuit breaker can be manually switched on or off as necessary until the system is back in operation. Flexibility: In many cases, the lighting control scheme may change over the life of the facility. With traditional lighting control methods, changes require major rewiring and facility downtime. Breaker control schemes can be changed within the lighting control panelboard, often with a simple modification through software.

Pow-R-Command 4000 (PRC4000)


The Power-R-Command 4000 wireless lighting control system is a robust wireless communication system that can be utilized in new and retrofit applications. The wireless system components consist of the Pow-RCommand 4000 (PRC4000) controller, the Pow-RCommand Wireless I/O Module (PRCWIOM) and the Pow-R-Command Wireless Switch (PRCWS). It has a multitude of advanced features that perform the seamless control of every zone in your entire facility, as well as complex energymanagement tasks. Basic programming of the PRC4000 is done through a standard Web page interface including the scheduling, status and override.

and provides increased flexibility in component and device selection for the control system.

Pow-R-Command 1000 (PRC1000)


Eatons PRC1000 is a microprocessor-based programmable lighting control system. With ratings from 100225A, the PRC1000 can be used as a standalone panelboard or networked as a system. The panelboard utilizes both branch mounted standard breakers through 100A, and controllable thermal-magnetic breakers controlled by the Pow-R-Command 1000 System Controller. The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants, memory loss protection, hardware diagnostics and real-time clock for optimal energy management functions. The PRC1000 system contains networkable intelligence and provides automated switching of branch circuit breakers.

ballasts to achieve a fully integrated zone lighting control from one device. Each PRC controller can have up to 99 digital switches connected to its DSN using CAT6 cable. This gives distributed control throughout the entire facility at a much lower cost of installation. In addition, there is local feedback through a status LED illuminated in each button on the switch. The Pow-R-Command Low Voltage Switch (PRCLS) is a momentary dry contact switch that is used for inputs into the Pow-R-Command controllers. This simple switch does not need a power supply; it is connected directly between the digital or universal inputs and its common of the PRC controller. This provides the ability to have up to six individual switches in one standard switch location. Both the PRCDS and PRCLS are offered in three configurations, a 2-button, 4button or 6-button. In addition, each configuration is offered in three colors, Black, White or Almond.

Pow-R-Command 2000 (PRC2000)


Eatons PRC2000 is a microprocessor-based programmable lighting control system that can be used to control all of the lighting in your industrial facilities, high-rise office buildings and airports. Being on the cutting edge of technology, the Pow-RCommand 2000 is an IPbased device with an embedded Web server. Capable of being utilized in both standalone and networkable applications, the PRC2000 can incorporate both standard branch mounted breakers and controllable thermal-magnetic breakers for tailored control. The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants, memory loss protection, hardware diagnostics and real-time clock for optimal energy management functions. The PRC2000 also incorporates the ability to communicate with networked devices over the Building Automation and Control Network (BACnet) protocol. BACnet is an industry standard protocol

Advanced Control Devices


The PRC2000 and PRC1000 controller has an onboard Digital Switch Network (DSN) that provides interaction with the Pow-R-Command Digital Switches. The Pow-RCommand Digital Switch (PRCDS) is a state-of-the-art microprocessor-based low voltage device. Each PRCDS is completely customizable and can be programmed to meet the needs of the customers lighting control strategy. This programming is stored directly in the switchs integrated memory, which adds to the reliability of the digital switch network. Each switch has the ability to communicate directly to a PRC1000 or PRC2000 lighting controller through a dedicated switch network. In addition to its network communication capabilities, the PRCDS has built-in inputs and outputs that allow the connection of photo sensors, occupancy sensors and dimmable

Pow-R-Command 750 (PRC750)


Designed for standalone applications, Eatons PRC750 is a premier microprocessorbased lighting control system that can be used to control all of the lighting in your industrial facilities, high-rise office buildings and airports. A single PRC750 panelboard can be connected to a maximum of three expansion panelboards for the ability to control up to a total of 168 Smart Breakers. The PRC750 also boasts load override, holiday scheduling, memory loss protection, astronomical time clocks and scheduling, 16 switch inputs, and alarm and message log features.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10

Pow-R-Command Expansion Panelboard (PRCEP)


The PRCEP is a slave panelboard designed to work in conjunction with the PRC750, PRC1000 and PRC2000 controller. The PRCEP is configured the same as a standard panelboard, but has PRC Breaker Control Bus (BCB) units installed that communicate to the PRC controller. To aid in cost reduction in some applications, there can be controllable and standard breakers installed in the panelboard, and the panelboard can be configured with a BCB on the left, the right or on both sides of the panelboard for a more custom solution. The PRC controller has the ability to control up to eight BCBs in any of the various PRCEP configurations. The PRCEP breaker compatibility is the same as the PRC controller panelboards and the layout and sizing rules are the same as a standard 1A/2A panelboard.

remotely operated circuit breakers into 8 individual zones. Each zone is designed to be switched by a dry contact from an external time clock, switch or Interposing relay. The PRC50 programming board included with the controller allows the breakers to be grouped locally without the need of special equipment or software. The groupings can be easily changed without the need of any field rewiring. The grouping configurations are made using simple pushbutton inputs. The panelboards are available with a full line of ratings and accessories.

native JCI Metasys protocol controller, which is used in new or existing JCI system integrations. Pow-R-Command PRC100 Panelboard Standard Features Time-of-Day scheduling Each breaker may be individually time scheduled Holiday scheduling Astronomical scheduling Memory loss protection Real-time clock Hardware diagnostics Power failure recovery Brownout recovery Alarms and alarm log Local programming port Network communications port Breaker bypass On/Off and restore buttons Lights-off warning Load priority management Plug-and-play installation Data logging 12 dry contact switch inputs Pow-R-Command PRC100 Panelboard Network Should more than one panelboard be required for a facility, Pow-R-Command panelboards can be networked to form a system. This allows each panelboard to communicate with each other and to a central computer over a shielded twisted pair network cable. Pow-R-Command PRC100 Panelboard Optional Features: The Pow-R-Command PRC100 panelboard may be ordered with an optional factory-installed Expansion Chassis in addition to the factory-installed Universal System Controller. The optional Expansion Chassis houses up to two PRC100 Application Specific Controllers (ASC), which may be field installed. The addition of the optional Expansion Chassis and Application Specific Controllers to the standard PRC100 panelboard will extend the functionality of the PRC100 panelboard beyond time-of-day power

switching. PRC100 Application Specic Controllers Eatons Pow-R-Command Application Specific Controllers (ASCs) are designed to expand the PRC100 panelboard system beyond time-of-day power switching requirements. The controllers may be plugged into the PRC100EC panelboard and the PRC100SCC Control Cabinet.

Pow-R-Command 25 (PRC25)
Eatons PRC25 Panelboard replaces contactors and relay panels in lighting control and other load switching systems. It is the most basic and cost-effective way to remotely control loads. The PRC25 is ideal for any building that requires a fixed lighting control scheme with a low installed cost. Examples may include small commercial buildings, tenant spaces, and other light commercial facilities. Pow-R-Command 100 Universal System Controller (PRC100 USC) The heart of the PRC100 panelboard is the Universal System Controller. Integral to the panelboard, this controller provides the PRC100 panelboard with distributed intelligence to control solenoid operated circuit breakers. The controller has the ability to communicate with other panelboard mounted controllers using a shielded twisted pair network cable. To further support system integrations, the PRC100 is also available in two additional native protocol versions that are installed in the PRC100 panelboard. The PRC100MOD is a native Modbus protocol controller that can be integrated easily into an existing or new Modbus system. Also available is the PRCJCI, a

PRC100SCC Control Cabinet with Application Specic Controllers

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Pow-R-Command 100 (PRC100)


Eatons PRC100 panelboard system offers the broadest range of energy control in the industry using standalone PRC100 panelboards or a network of PRC100 panelboards. The PRC100 system is ideal for large, medium and small facilities with lighting control systems that require frequent changes, networkable panelboards, remote access, or all of the above. There are applicationspecific controllers available such as the native Johnson Controls Metasys (JCI) and the native Modbus controllers. Examples may include stadiums, auditoriums and theatres, office buildings, large retailers and schools.

Switch Override Controller (PRC100SOC) The Switch Override Controller provides the ability to connect and monitor up to 48 dry contact closures from wall switches, occupancy sensors, photocells, building automation system relay contacts or any remotely mounted device with a dry contact relay. Input connections to the controller are self powered with 28 Vac and may be individually custom programmed to operate differently. It is possible to program any connected input to control any breaker or group of breakers in the panelboard or system. Inputs have adjustable priorities and are capable of being individually time schedule enabled for different days of the week.

Pow-R-Command 50 (PRC50)
The PRC50 panelboard is a PRC100 panelboard with additional programming capability added that provides the ability to group up to 42

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

449

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
450

Panelboards and Lighting Control


Pow-R-Command

Telephone Override Controller (PRC100TOC) The Telephone Override Controller provides a voice prompted method for On/Off override control of lighting. The telephone override controller is connected the same as an extension telephone. Simply plug it into a local analog telephone extension wall jack. The telephone override controller allows voice prompted control of lighting circuits for up to 1000 individual users. It is possible to program any of the 1000 users to override any breaker, or group of breakers in the panelboard, or system on or off during scheduled or non-scheduled hours, using any touch-tone telephone. Remote Access Controller (PRC100RAC) Allows programming and monitoring of the Pow-RCommand system from a remote location using a personal computer with a modem. The RAC is ideal for multi-location systems, such as campus and chain stores. Only one RAC is required per system to accomplish this task. The system can be designed to allow various levels of access. All programming and monitoring functions are available from the central location.

PRC100 Network Interface Box (PRC100NIB) The Network Interface Box allows the central computer to be located more than 25 feet (7.6m) from the closest Pow-R-Command panelboard. The Network Interface Box comes complete with serial interface cable and power cord. PRC100 Control Cabinet The PRC100 Control Cabinet incorporates a power supply and the Universal System Controller from the PRC100 panelboard into a cabinet that may house up to three ASCs. The PRC100 Control Cabinet is ideal for retrofit applications when the existing panelboards may be reused or new construction applications where two or more panelboards requiring switched loads are located within the same electrical closet. The PRC100 Control Cabinet will control up to 48 remotely mounted circuit breakers using preterminated pigtail cables.

PRC100 Setup Software (PRC100LOS) Windows-based setup software is required for programming the PRC100 panelboard and Application Specific Controllers. PRC100 System Support Application Engineering support is available from the Pow-R-Command Applications Engineering Group located in the Sumter, SC, plant. PRC100 Field Technical Support Programming, Startup, Training and Field Service are available from a professional team of factory trained engineers. Startup services are recommended to ensure peak system performance. Online Support Available to those customers who choose Remote Access Controllers. Factory technicians can help diagnose systems, set up or change programs and troubleshoot online.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10

Product Selection Guide


Pow-R-Command Selection Guide

Controller Mandatory Eaton startup and integration required Inputs Switch Universal (switch or analog) Optional switch input expander Total inputs Outputs Outputs digital (maximum controllable zones) Analog Universal I/O module Telephone override Data logging Remote access Power supply for external devices Maximum number of loads (breaker/relay) Number of expansion panels Manual override

PRC25 No

PRC50 No

PRC100 Yes

PRC750 No

PRC1000 Yes

PRC2000 Yes

PRC2000B No

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

6 0 0 6

8 0 0 8

4 8 48 64

8 8 0 16

8 8 48 64

8 8 48 64

8 8 48 64

6 0 No No No No N/A 42 0 Yes

0 0 No No No No No 42 0 Yes

4 4 Yes Yes Yes Yes Yes 42 0 Yes

16 0 No No No No Yes 168 7 Yes

75 4 Yes Yes Yes Yes Yes 168 7 Yes

75 4 Yes Yes Yes Yes Yes 168 7 Yes

75 4 Yes Yes Yes Yes Yes 168 7 Yes

Notes Startup and Integration by Eaton is not mandatory when utilizing the PRC2000B with BACnet protocol. Each rail drives 21 breakers. Rails can be distributed individually over a total of eight panels (max. SLAN wire-length of 150 ft).

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

451

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Controller Outputs (continued) Dimming

Panelboards and Lighting Control


Pow-R-Command

Pow-R-Command Selection Guide, continued


PRC25 PRC50 PRC100 PRC750 PRC1000 PRC2000 PRC2000B

No 0 No Yes No No N/A N/A N/A No N/A No No No No No No No Yes No N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Yes N/A Yes Yes N/A N/A No No Yes

No 0 No Yes No No N/A N/A N/A No N/A No No No No No Yes No Yes Yes 10 yrs 10 yrs No N/A N/A N/A N/A N/A N/A N/A No No No Yes N/A Yes Yes Yes 9.6k 1 No No Yes

Yes 160 Yes Yes Yes Yes 75 50 30 Yes 24 No Yes No Yes Yes Yes No Yes Yes 10 yrs 10 yrs No Yes No Yes Yes No Yes Yes Yes No No Yes Yes Yes Yes Yes 9.6k 120 Yes No Yes

No 0 No Yes Yes Yes 75 50 30 Yes 24 No No No No No Yes Yes Yes Yes 10 yrs 10 yrs Yes No No No No No No No No N/A N/A Yes Yes Yes Yes Yes 9.6k 1 Yes No Yes

Yes 160 Yes Yes Yes Yes 75/250 50 30/16 Yes 24 No Yes No Yes Yes Yes Option Yes Yes 10 yrs 10 yrs Yes No No No Yes No Yes Yes Yes N/A N/A Yes Yes Yes Yes Yes 9.6k 1800 Yes No Yes

Yes 160 Yes Yes Yes Yes 75/250 50 30/16 Yes 24 No Yes Yes Yes Yes Yes Option Yes Yes 10 yrs 10 yrs Yes No No No Yes No Yes Yes Yes Yes N/A Yes Yes Yes Yes Yes 9.6k 1800 Yes No Yes

Yes 160 Yes Yes Yes Yes 75/250 50 30/16 Yes 24 No Yes Yes Yes Yes Yes Option Yes Yes 10 yrs 10 yrs Yes N/A N/A N/A Yes N/A N/A Yes Yes Yes Yes Yes Yes Yes Yes Yes 9.6k 1800 Yes No Yes

Maximum number of dimming ballasts Daylight harvesting (using dimming ballasts) Daylight switching (on/off circuit switching) Time clock Time schedules Scheduling zones On/off periods per schedule Holidays Blink notice Maximum override time (hrs) RS-232 port RS-485 port Ethernet port Ethernet via external gateway Input/output matrix across controllers Input/output matrix within controller Local LCD/LED display Local LED status indicators Non-volatile program memory Battery backup for program memory Clock memory backup Flash rmware memory Protocols Modbus ASCII/RTU Modbus TCP Johnson Controls N2 BACnet LonWorks SOAP/XML OPC Browser Access TCP/IP external device Built-in Web Server TCP/IP BACnet IP server Standards UL 916 energy management equipment California Title 24 NEC 110-10 UL 67 panelboards CSA C22.2 #29 panelboards Baud rate Maximum controllers/network Password protected Mounting Three-pole breaker housing External bracket mount available

Notes 250 additional schedules with optional Network Interface Box NIB. 16 additional holidays with optional Network Interface Box NIB.

452

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
Page 447 451 454 457 460 463 467 470 473

Pow-R-Command 4000 Wireless Controller

Contents
Description Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Eaton Green Solution

10 10 10 10 10 10 10 10 10 10 10 10

Pow-R-Command 4000 (PRC4000)


Product Description
The PRC4000 wireless controller is designed to act as the coordinator of the wireless lighting network; All configuration and control can be done through a standard Web browser instead of learning a new software platform. In addition, the PRC4000 is networkable with existing Pow-R-Command lighting control products over the RS-485 network to expand system capabilities. The PRC4000 also comes equipped with analog and digital inputs/outputs to accommodate an extended array of input devices, switching and dimming needs. The PRC4000 wirelessly communicates to the PRCWIOM and the PRC Wireless Switch using the IEEE802.15.4 standard. Components Embedded Web server Integrated I/O PRC Wireless I/O Module PRC Wireless Switch The PRC4000 wireless controller offers industryleading wireless technology. Not only does it have a builtin radio to communicate wirelessly directly with each I/O module and wireless switch, but it also offers many advanced features to help coordinate your lighting network. The PRC4000 has a built-in battery-backed time clock. In addition to its advanced time-scheduling feature set, the PRC4000 also offers astronomical time scheduling that dynamically adjusts to your geographic location and time of year. With any automated system, data logging and alarm notifications are essential. To meet this need, the PRC4000 offers an integrated internal data and alarm notification system. This gives you access to valuable information that you would need to quickly see the status of your lighting system. PRC Wireless Devices PRC Wireless I/O Module (PRCWIOM) The PRCWIOM is used to segment the system and connect external inputs and loads to the system remotely. It allows local connectivity of low voltage switches, photo sensors, occupancy sensors, 010 Vdc dimming ballasts, and other auxiliary devices. The I/O module also adds discrete on/off load control through an onboard relay for loads up to 120/277V, 20A. Running control wires from each device in the facility back to the electrical room is no longer required. The configuration and programming is stored in the internal memory of the PRC Wireless I/O module and the PRC Wireless Switch. This allows for distributed intelligence that adds reliability to an already robust lighting control network. Pow-R-Command line of lighting controllers through a Pow-R-Command Wireless Switch Interface (PRCWSI) unit. Each PRCWS switch is completely customizable and can be programmed to meet the needs of the customers lighting control strategy. The PRCWS configuration is stored directly in the integrated memory of the switch, which adds to the reliability of the device. In addition to the wireless network communication capabilities, the PRCWS has built-in input and output that are capable of connecting a photo sensor, occupancy sensor, and dimmable ballasts to achieve a fully integrated zone lighting control from one device. The wireless switch network can have up to 99 switches per controller. PRC Wireless Switch Interface (PRCWSI) The PRCWSI is a wireless gateway device that passes the wireless data of the PRC Wireless Switch to the PRC Digital Switch network of the PRC1000 or PRC2000 Controller. This two-way communication transfers commands from the switch as well as feedback from the controller.

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

PRC Wireless Switch Interface

PRC Wireless Switch (PRCWS) The PRC Wireless Switch is a state-of-the-art, microprocessor-based, low voltage wireless communication device that is based on the 802.15.4 wireless standard. The switch is used for local control and has the ability to communicate directly to the PRC4000 and to the standard

PRC Wireless I/O Module

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

453

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
454

Panelboards and Lighting Control


Pow-R-Command

Pow-R-Command 2000 Panelboard

Contents
Description Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard Technical Data and Specications . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Eaton Green Solution

Page 447 451 453 455 456 478 457 460 463 467 470 473

Pow-R-Command 2000 Panelboard


Product Description
Eatons Pow-R-Command 2000 is a microprocessor-based programmable lighting control system with an embedded Web server for robust control. The PRC2000 can be used as a standalone panelboard or networked as a system. An upgrade can be purchased to integrate the unit within BACnet native control networks.

Features

LCD display and keypad Memory loss protection Power failure/brownout recovery Astronomical real-time clock Control software Time scheduling Holiday scheduling Input to output switch matrix Messages/alarms Daylight optimization Switch Override Controller (SOC) Telephone Override Controller (TOC)

Components Embedded Web server Intelligent power switching equipment LCD programming display and keypad Application Specic Controllers (ASCs) Software and support Integration components

208Y/120V and 480Y/277V, single-phase and threephase. The panelboard utilizes both branch mounted standard breakers through 100A, and controllable thermal-magnetic breakers that are controlled by the PRC2000 System Controller. The PRC2000 controllers provide the ability to directly operate up to eight breaker control buses that are installed in the PRC2000 panelboard and the various PRCEP panelboards with one or two breaker control bus installed in each. Such a capability allows a single controller to directly operate up to 168 GHQRSP and BABRSP controllable circuit breakers, with individual control and status feedback of each controllable breaker. The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants by blinking lights, memory loss protection, power failure/brownout protection, hardware diagnostics, a real-time clock and 16 dry contact switch inputs.

Equipment within the PRC2000 system may be networked. Up to 120 panelboards may be networked over a shielded twisted pair network cable without the need for a personal computer in the system. To better support retrofit applications, the PRC2000 is offered in an external cabinet and the Breaker Control Bus is offered in retrofit kits. BACnet Protocol The PRC2000 unit can also be used for integration within BACnet native control networks. BACnet is a communications protocol widely used in building automation and controls and adds even more flexibility to the control system.

Standards and Certications


The Pow-R-Command 2000 Panelboard is listed UL 67 for panelboards and UL 916 for energy management equipment.

Intelligent Power Switching Equipment PRC2000 Panelboards PRC2000 panelboards are offered from 100225A in main lug and main configurations. Available voltages are 120/240V,

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10 10

Technical Data and Specications


System Congurations PRC2000 Network Architecture Containing an embedded webserver, each PRC2000 system is programmed with a unique IP address for communication via any standard Internet browser. Web access is standard with the PRC2000. Eight 21-circuit control buses configured as needed throughout PRL1A and PRL2A panels. The PRC2000B directly interfaces to a BACnet Client Workstation. Breaker Control Buses (BCB) Every Pow-R-Command Expansion Panelboard can be configured with the left and/ or right breaker control buses installed. When using PRC EP Panel with one BCB, the remote-controlled breakers are placed on the side with the control bus. Standard and controlled breakers can be distributed anywhere in the panel as needed.

PRC2000 Breaker Control Busses

PRC EP 1 BCB 5th Floor Sub LAN 4 Conductor Cable PRC EP 1 BCB 4th Floor Sub LAN 4 Conductor Cable PRC EP 2 BCBs 3rd Floor Sub LAN 4 Conductor Cable PRC EP 2 BCBs 2nd Floor Sub LAN 4 Conductor Cable PRC 2000 2 BCBs Ground Each Pow-R-Command 2000 Typical for 8 Breaker Control Busses Each with 21 Breakers Customer Ethernet LAN

PRC EP 2 BCBs

10 10 10 10 10 10 10 10 10 10 10
PC with Internet Browser

PRC EP 2 BCBs

PRC EP 2 BCBs

PRC 2000 2 BCBs

10 10
Remote Access Thru VPN

10 10 10 10 10 10

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

455

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
456
ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Controller

Panelboards and Lighting Control


Pow-R-Command

Panel Layout
PRC2000 Layout
14 in.18 Ckt. Chassis Includes PRC2000 Controller
ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42

PRC2000 Panel Layout Instructions 1. Select PRC2000 Panelboard Chassis from layout on left. a. Determine required mains (lugs or breaker) b. Select appropriate main lug c. Select appropriate main device d. Select appropriate branch breakers 2. Layout panel as shown on left. Total in. determine box height shown in on left. (When total in. units exceeds the number shown, use next size box size.

Layout Example 1. Panel Description: a. PRC2000, threephase four-wire, 208Y/120 Vac, interrupting rating of 10 kAIC symmetrical: 225A main lugs only at bottom, surface mounted and the following branch breakers b. 3620A, single-pole BABRSP c. 620A, single-pole BABRSP spaces 2. Layout information from layout on left. a. PRC2000 with 42circuit Interior 26 inches b. 225A main lugs Section 4 inches c. Total panelboard height 30 inches 3. From table below:

20 in.30 Ckt. Chassis Includes PRC2000 Controller 26 in.42 Ckt. Chassis Includes PRC2000 Controller

Main Lug Section

2 in.100 Amp MLO 4 in.225 Amp MLO 6 in. 400 Amp MLO 8 in.100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD 9 in. 225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 22 in.400 Ampere Frame DK, KD, HKD, KDC

Vertically Mounted

Panel height: 30 inches 20 inches wide x 5.75 inches deep Box height: 48 inches Box catalog number: YS2048 or EZB2048R Trim catalog number: LT2048S or EZT2048S

Approximate Dimensions in Inches (mm) Box Selection


Maximum Panel Height Box Height, Catalog Number YS Box LT Trim EZ Box EZ Trim

20-Inch Wide x 5.75-Inch Deep Boxes 022.00 23.0028.00 29.0034.00 35.0046.00 47.0058.00 36.00 (914.4) 42.00 (1066.8) 48.00 (1219.2) 60.00 (1524.0) 72.00 (1828.8) YS2036 YS2042 YS2048 YS2060 YS2072 LT2036S or F LT2042S or F LT2048S or F LT2060S or F LT2072S or F EZB2036R EZB2042R EZB2048R EZB2060R EZB2072R EZT2036S or F EZT2042S or F EZT2048S or F EZT2060S or F EZT2072S or F

Cabinets Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20.00 inches (508.0 mm) wide x 5.75 inches (146.1 mm) deep.
Note: Width of enclosure will be 28.00 inches (711.2 mm) minimum.

Top and Bottom Gutters 6.38 inches (162.1 mm). Minimum Side Gutters 4.00-inch (101.6 mm) minimum on 20.00-inch (508.0 mm) wide box size.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
Page 447 451 453 454 458 459 478 460 463 467 470 473

Pow-R-Command 1000 Panelboard

Contents
Description Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard Technical Data and Specications . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Eaton Green Solution

10 10 10 10 10 10 10 10 10 10 10 10

Pow-R-Command 1000 Panelboard


Product Description
Eatons Pow-R-Command 1000 is a microprocessor-based programmable lighting control system. The PRC1000 can be used as a standalone panelboard or networked as a system.

Features

LCD display and keypad Memory loss protection Power failure/brownout recovery Astronomical real-time clock Control software Time scheduling Holiday scheduling Input to output switch matrix Messages/alarms Daylight optimization Switch Override Controller (SOC) Telephone Override Controller (TOC)

Intelligent Power Switching Equipment PRC1000 Panelboards PRC1000 panelboards are offered from 100225A in main lug and main breaker configurations. Available voltages are 120/240V, 208Y/ 120V and 480Y/277V, singlephase and three-phase. The panelboard utilizes both branch mounted standard breakers through 100A, and controllable thermal-magnetic breakers that are controlled by the PRC1000 System Controller. The PRC1000 controllers provide the ability to directly operate up to eight breaker control buses. To better support retrofit applications, the PRC1000 is offered in an external cabinet and the Breaker Control Bus is offered in retrofit kits. Such a capability allows a single controller to directly operate up to 168 GHQRSP and BABRSP controllable circuit breakers, with individual control and status feedback of each controllable breaker.

The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants by blinking lights, memory loss protection, power failure/brownout protection, hardware diagnostics, a real-time clock and 16 dry contact switch inputs. Equipment within the PRC1000 system may be networked. Up to 120 panelboards may be networked over a shielded twisted pair network cable without the need for a personal computer in the system that are installed in the PRC1000 panelboard and the various PRCEP panelboards with one or two breaker control bus installed in each.

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Components Intelligent power switching equipment LCD programming display and keypad Application Specic Controllers (ASCs) Software and support Integration components

Standards and Certications


The PRC1000 panelboard is listed UL 67 for panelboards and UL 916 for energy management equipment.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

457

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
2nd Floor 3rd Floor 4th Floor PRC EP 1 BCB 5th Floor PRC EP 1 BCB

Panelboards and Lighting Control


Pow-R-Command

Technical Data and Specications


System Congurations PRC1000 Application Customizable extension panels allow for combinations of both regular and remote controllable breakers for individualized solutions as shown in this riser diagram. Eatons PRC1000 Controller can support up to eight PRC1000 Breaker Control Buses Breaker Control Buses contained within four standard panelboards or split between a maximum of eight. When connected to the buildings Internet, all master and expansion panels can be controlled.

PRC EP 2 BCBs Sub LAN 4 Conductor Cable PRC EP 2 BCBs Sub LAN 4 Conductor Cable

PRC EP 2 BCBs Sub LAN 4 Conductor Cable PRC EP 2 BCBs Sub LAN 4 Conductor Cable PRC 1000 2 BCBs Ground Network Interface

PRC EP 2 BCBs

PRC 1000 2 BCBs

10 10 10 10 10 10 10 10 10 10 10 10
458

RS-485

PC with Software

Remote Access Thru Modem

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
EZ Box EZ Trim

Panel Layout
PRC1000 Layout
14 in. - 18 Ckt. Chassis Includes PRC1000 Controller
ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42

Controller ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41

PRC1000 Panel Layout Instructions 1. Select PRC1000 Panelboard Chassis from layout on left. a. Determine required mains (lugs or breaker) b. Select appropriate main lug c. Select appropriate main device d. Select appropriate branch breakers 2. Layout panel as shown on left. Total in. determine box height shown on left. (When total in. units exceeds the number shown, use next size box size.

Layout Example 1. Panel Description: a. PRC1000, threephase four-wire, 208Y/120 Vac, interrupting rating of 10 kAIC symmetrical: 225A main lugs only at bottom, surface mounted and the following branch breakers b. 3620A, single-pole BABRSP c. 620A, single-pole BABRSP spaces 2. Layout information from layout on left. a. PRC1000 with 42-circuit Interior 26 inches b. 225A main lugs section 4 inches c. Total panelboard height 30 inches 3. From table below:

20 in. - 30 Ckt. Chassis Includes PRC1000 Controller 26 in. - 42 Ckt. Chassis Includes PRC1000 Controller

Main Lug Section

2 in.100 Amp MLO 4 in.225 Amp MLO 6 in. 400 Amp MLO 8 in.100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD 9 in. 225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 22 in.400 Ampere Frame DK, KD, HKD, KDC

Vertically Mounted

Panel height: 30 inches 20 inches wide x 5.75 inches deep Box height: 48 inches Box catalog number: YS2048 or EZB2048R Trim catalog number: LT2048S or EZT2048S

Approximate Dimensions in Inches (mm) Box Selection


Maximum Panel Height Box Height, Catalog Number YS Box LT Trim

10 10 10 10 10 10 10 10 10 10

20-Inch Wide x 5.75-Inch Deep Boxes 022.00 23.0028.00 29.0034.00 35.0046.00 47.0058.00 36.00 (914.4) YS2036 LT2036S or F LT2042S or F LT2048S or F LT2060S or F LT2072S or F EZB2036R EZB2042R EZB2048R EZB2060R EZB2072R EZT2036S or F EZT2042S or F EZT2048S or F EZT2060S or F EZT2072S or F

42.00 (1066.8) YS2042 48.00 (1219.2) YS2048 60.00 (1524.0) YS2060 72.00 (1828.8) YS2072

Cabinets Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20.00 inches (508.0 mm) wide x 5.75 inches (146.1 mm) deep.
Note: Width of enclosure will be 28.00 inches (711.2 mm) minimum.

Top and Bottom Gutters 6.38 inches (162.1 mm). Minimum Side Gutters 4.00-inch (101.6 mm) minimum on 20.00-inch (508.0 mm) wide box size.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

459

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
460

Panelboards and Lighting Control


Pow-R-Command

Pow-R-Command 750 Panelboard

Contents
Description Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard Technical Data and Specications . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Eaton Green Solution

Page 447 451 453 454 457 461 462 478 463 467 470 473

Pow-R-Command 750 Panelboard


Product Description
Eatons Pow-R-Command 750 is a microprocessorbased programmable lighting control system. The PRC750 can be used as a standalone panel, or the user has the option to connect up to three expansion panels, creating its own standalone subnetwork.

Features

LCD display and keypad Memory loss protection Power failure/brownout recovery Astronomical real-time clock Control software Time scheduling Holiday scheduling Input to output switch matrix Messages/alarms Daylight optimization Switch Override Controller (SOC) Telephone Override Controller (TOC)

Intelligent Power Switching Equipment PRC750 Panelboards PRC750 panelboards are offered from 100225A in main lug and main breaker configurations. Available voltages are 120/240V, 208Y/ 120V and 480Y/277V, singlephase and three-phase. The panelboard utilizes both branch mounted standard breakers through 100A, and controllable thermal-magnetic breakers that are controlled by the PRC750 system controller. The PRC750 controllers provide the ability to directly operate up to eight breaker control buses. To better support retrofit applications, the PRC750 is offered in an external cabinet and the Breaker Control Bus is offered in retrofit kits. Such a capability allows a single controller to directly operate up to 168 GHQRSP and BABRSP controllable circuit breakers, with individual control and status feedback of each controllable breaker.

The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants by blinking lights, memory loss protection, power failure/brownout protection, hardware diagnostics, a real-time clock and 16 dry contact switch inputs that are installed in the PRC750 panelboard and the various PRCEP panelboards with one or two breaker control bus installed in each.

Standards and Certications


The PRC750 panelboard is listed UL 67 for panelboards and UL 916 for energy management equipment.

Components Intelligent power switching equipment LCD programming display and keypad Integration components

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10

Technical Data and Specications


Designed for standalone applications, Eatons PRC750 is a premier microprocessorbased lighting control system that can be used to control all of the lighting in your industrial facilities, high-rise office buildings and airports. A single PRC750 panel can be connected to a maximum of eight Breaker Control Buses (BCB) in any combination within panelboards for the ability to control up to a total of 168 Smart Breakers. The PRC750 also boasts load override, holiday scheduling, memory loss protection, astronomical time clocks and scheduling, 16 switch inputs, and alarm and message log features.

PRC750 Standalone System Architecture

PRC EP 1 BCB 5th Floor Sub LAN 4 Conductor Cable PRC EP 1 BCB 4th Floor Sub LAN 4 Conductor Cable PRC EP 2 BCBs 3rd Floor Sub LAN 4 Conductor Cable PRC EP 2 BCBs 2nd Floor Sub LAN 4 Conductor Cable PRC 750 2 BCBs Ground Programming via Local LCD Display No Start-Up Required by Factory

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

461

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
462
ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Controller

Panelboards and Lighting Control


Pow-R-Command

Panel Layout
PRC750 Layout
14 in. - 18 Ckt. Chassis Includes PRC750 Controller
ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42

PRC750 Panel Layout Instructions 1. Select PRC750 Panelboard Chassis from layout on left. a. Determine required mains (lugs or breaker) b. Select appropriate main lug c. Select appropriate main device d. Select appropriate branch breakers 2. Layout panel as shown on left. Total in. determine box height shown on left. (When total in. units exceeds the number shown, use next size box size.

Layout Example 1. Panel description: a. PRC750, three-phase four-wire, 208Y/120 Vac, interrupting rating of 10 kAIC symmetrical: 225A main lugs only at bottom, surface mounted and the following branch breakers b. 3620A, single-pole BABRSP c. 620A, single-pole BABRSP spaces 2. Layout information from layout on left. a. PRC750 with 42-circuit Interior 26 inches b. 225A main lugs section 4 inches c. Total panelboard height 30 inches 3. From table below:

20 in. - 30 Ckt. Chassis Includes PRC750 Controller 26 in. - 42 Ckt. Chassis Includes PRC750 Controller

Main Lug Section

2 in.100 Amp MLO 4 in.225 Amp MLO 6 in.400 Amp MLO 8 in.100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD 9 in.225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 22 in.400 Ampere Frame DK, KD, HKD, KDC

Vertically Mounted

Panel height: 30 inches 20 inches wide x 5.75 inches deep Box height: 48 inches Box catalog number: YS2048 or EZB2048R Trim catalog number: LT2048S or EZT2048S

Approximate Dimensions in Inches (mm) Box Selection


Maximum Panel Height Box Height, Catalog Number YS Box LT Trim EZ Box EZ Trim

20-Inch Wide x 5.75-Inch Deep Boxes 022.00 23.0028.00 29.0034.00 35.0046.00 47.0058.00 36.00 (914.4) YS2036 LT2036S or F LT2042S or F LT2048S or F LT2060S or F LT2072S or F EZB2036R EZB2042R EZB2048R EZB2060R EZB2072R EZT2036S or F EZT2042S or F EZT2048S or F EZT2060S or F EZT2072S or F

42.00 (1066.8) YS2042 48.00 (1219.2) YS2048 60.00 (1524.0) YS2060 72.00 (1828.8) YS2072

Cabinets Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20.00 inches (508.0 mm) wide x 5.75 inches (146.1 mm) deep.
Note: Width of enclosure will be 28.00 inches (711.2 mm) minimum.

Top and Bottom Gutters 6.38 inches (162.1 mm). Minimum Side Gutters 4.00-inch (101.6 mm) minimum on 20.00-inch (508.0 mm) wide box size.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
Page 447 451 453 454 457 460 464 466 478 467 470 473

PRC100 Panelboard

Contents
Description Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Eaton Green Solution

10 10 10 10 10 10 10 10 10 10 10

PRC100 Panelboard
Product Description
Eatons Pow-R-Command is designed to meet the needs for microprocessor-based programmable lighting control. Used as a standalone panelboard or networked as a system, the Pow-R-Command PRC100 offers the broadest range of energy control in the industry. The PRC100 panelboard system is ideal for large, medium and small building applications. The Pow-R-Command panelboard mounts the same as traditional panelboards. Power and branch wiring is also the same. It can be applied to distribution systems rated single-phase three-wire and three-phase four-wire 120V, 120/240V, 208Y/120V and 480Y/277 Vac. See Page 447 for additional information. Branch Breakers Refer to Page 465.

Standards and Certications


10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

UL 67 Panelboards UL 50 Enclosures UL 916 Energy Management Equipment National Electrical Code Federal Specication W-P-115C FCC Emissions Standards: Part 15, Subject J for Class A Application IBC and UBC Seismic Qualied Equipment is available

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

463

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
464

Panelboards and Lighting Control


Pow-R-Command

Product Selection
PRC100 Panelboard
Ampere Rating Interrupting Rating (kA Symmetrical) Device 240V 480Y/277V Type

Type PRC100

Main Integral Fuse DisconnectSeries Rated Combinations


Ampere Rating 100 MLO MLO MLO 200 65 65 Interrupting Rating (kA Symmetrical) 240V 480Y/277V 100 100 Device Type T Fuse Disconnect T Fuse Disconnect Approved Branch Devices GHB, GHBS, EHD, FDB, FD GHB, GHBS, EHD, FDB, FD

Main Lug Only 100 250 400

Main Breaker 100 100 100 100 100 100 100 225 225 225 225 225 225 225 225 250 250 250 400 400 400 400 400 18 18 65 100 200 200 200 22 42 65 100 200 65 100 200 65 100 200 65 65 100 200 200 14 14 35 65 100 150 200 35 65 100 35 65 100 35 65 100 100 EHD FDB FD HFD FDC FCL FB-P EDB EDS ED EDH EDC FD HFD FDC JD HJD JDC DK KD HKD KDC LCL

Notes The short-circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short-circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short-circuit rating of the lowest rated main or branch device. Top feed only. Requires 6.50-inch (165.1 mm) deep box. The short-circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included.

Includes Smart Chassis (system controller integral to the panelboard chassis).


Lighting optimization software and startup support must be included with each systemsee Page 475.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10

BABRP Remote Control Circuit Breaker

Branch Circuit Breakers480Y/277V Maximum


Ampere Rating Interrupting Rating (kA Symmetrical) 240V 480V Breaker Type

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Remote Controllable Branch Circuit Breakers 1530 1530 1520 1530 10 10 65 65 14 14 BABRP BABRSP GHQRSP GHBS

Conventional Branch Circuit BreakersNot Controllable GHBS Remote Control Circuit Breaker 1560 1560 70 70 80100 80100 1550 1550 1520 1520 1520 2560 70100 1560 70100 1560 70100 110150 1560 70100 110225 1560 70100 110225 1560 70100 110225 100225 100225 100225 100225 100225 10 10 10 10 10 10 10 10 10 65 65 65 65 18 18 18 18 18 65 65 65 100 100 100 200 200 200 22 42 65 100 200 14 14 14 14 14 14 14 14 14 35 35 35 65 65 65 100 100 100 BAB BAB-H BAB BAB-H BAB BAB-H QBGF QBGFEP QBCAF GHQ GHB GHB GHB EHD EHD FDB FDB FDB FD FD FD HFD HFD HFD FDC FDC FDC EDB EDS ED EDH EDC

Notes Single-pole breaker rated 120 Vac. two-pole breaker rated 120/240 Vac. Single-pole breakers are rated 277 Vac maximum. Two- and three-pole breakers are rated 480Y/277 Vac maximum. For use on 480Y/277 Vac maximum.50A devices are available as two-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Maximum lug size, 4/0 AWG Al/Cu in 20-inch (508.0 mm) wide box. 300 kcmil lug available in 28-inch (711.2 mm) wide box.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

465

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Neutral Section Main Lug Section
ckt 1 3 5 7 9 11 13 15 17 Pow-R-Command Smart Chassis and 18 Pole Spaces

Panelboards and Lighting Control


Pow-R-Command

Panel Layout
PRC100 Layout
1-Pole 2-Pole 1-Pole 2-Pole 2-Pole 3-Pole 2X 3X 1-Pole 2-Pole 3-Pole 1X 2X 3X EHD FDB FD HFD FDC

Layout Instructions 1. Select: a. Smart Chassis from layout on left.


Note: Smart chassis is always located at the bottom of the panelboard chassis immediately below the bottom breaker.

EDB, EDS, ED, EDH EDC EDB, EDS, ED, EDH EDC BABRP BABRSP BAB GHBS GHQRSP GHB

b. Required mains (lugs, breaker or fuse pullout). c. Appropriate neutral. d. Branch breakers and additional chassis space, as needed. 2. Layout panel as shown on left, using appropriate X units. Total X units determine box height shown in table below. (When total X units exceeds the number shown, use next size box size.

Layout Example 1. Panel description: a. Pow-R-Command, three-phase, four-wire 480Y/277 Vac, interrupting rating of 14 kAIC symmetrical, 250A main lugs only at bottom, surface mounted and the following branch breakers: b. 3620A, single-pole GHBS. c. 620A, single-pole GHBS spaces. 2. Layout information from layout on left: a. Smart Chassis . = 13X b. 24-circuit add-on chassis . . . . . . = 10X c. 250A neutral . . = 5X d. 250A main lugs only . . . . . = 5X e. Total panelboard height . . . . . . . = 33X 3. From table below: 33X height (use 40X box). Box catalog number. . . . . . . YS2072 Trim catalog number. . . . . . LT2072S OR Box catalog number. . . . . EZB2072R Trim catalog number. . . . . EZT2072S

5X 12 Poles 10X 24 Poles

ckt 2 4 6 8 10 12 14 16 18

13X Smart Chassis includes spaces for 18 Poles GHBS, GHQRSP, GHB, BABRP, BABRSP, BAB Smart Chassis is always located at the bottom of the panelboard chassis immediately below all GHBS/GHB or BABR/ BABRS/BAB breakers.

5X 8X 2X 5X 8X

100250 A 400 A 100 A 250 A 400 A

Approximate Dimensions in Inches (mm) Box Tabulation


X Units Box Height YS Box Catalog Number LT Trim Catalog Number EZ Box Catalog Number EZ Trim Catalog Number

Main Device Horizontally Mounted Main Device Vertically Mounted

See branch mounted EHD, FD, FDB, HFD, FDC, EDB, EDS, ED, EDH, EDC above 7XEHD, FDB, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC 7X100 A Class T fusible pullout 9X200 A Class T fusible pullout 9XFB-P 14XJD, HJD, JDC 15XDK, KD, HKD, KDC

100400A 23X 31X 40X 53X 48.00 (1219.2) 60.00 (1524.0) 72.00 (1828.8) 90.00 (2286.0) YS2048 YS2060 YS2072 YS2090 LT2048S or F LT2060S or F LT2072S or F LT2090S or F EZB2048R EZB2060R EZB2072R EZB2090R EZT2048S or F EZT2060S or F EZT2072S or F EZT2090S or F

Notes All F-Frame branch breakers must be mounted above (top) of all controllable breakers on the chassis. EDB, EDS, ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order. All add-on branch spaces must be adjacent to smart chassis poles. GHBS, GHQRSP and GHB breakers cannot be mixed on same chassis with BABRP, BABRSP and BAB breakers. Top-mounted mainonly.

Cabinets Fronts are code-gauge steel, ANSI-61 light gray painted finish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5.75 inches (146.1 mm). Standard width is 20.00-inch (508.0 mm) 100400A.

Top and Bottom Gutters 5.50 inches (139.7 mm) minimum. Side Gutters 4.00 inches (101.6 mm) minimum.

466

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
Page 447 451 453 454 457 460 463 468 469 478 470 473

PRC100EC Panelboard

Contents
Description Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Eaton Green Solution

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

PRC100EC Panelboard
Product Description
Eatons Pow-R-Command PRC100 panelboard may be ordered with an optional factory-installed Expansion Chassis in addition to the factory-installed Universal System Controller. The optional Expansion Chassis houses up to two PRC100 Application Specific Controllers (ASC) that may be field installed. The addition of the optional Expansion Chassis and Application Specific Controllers to the standard PRC100 panelboard will extend the functionality of the PRC100 panelboard beyond time-of-day power switching. Branch Breakers Refer to Page 465 Application Specic Controllers (ASC)

Select up to two ASCs per panel from Page 475

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

467

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
468

Panelboards and Lighting Control


Pow-R-Command

Product Selection
PRC100EC Panelboard
Ampere Rating Interrupting Rating (kA Symmetrical) Device 240V 480Y/277V Type

Type PRC100EC

Main Integral Fuse DisconnectSeries Rated Combinations


Ampere Rating 100 Interrupting Rating (kA Symmetrical) 240V 480Y/277V 100 65 100 65 Device Type T Fuse Disconnect T Fuse Disconnect Approved Branch Devices GHB, GHBS, EHD, FDB, FD GHB, GHBS, EHD, FDB, FD

Main Lug Only 100 250 400 MLO MLO MLO

200

Main Breaker 100 100 100 100 100 100 100 225 225 225 225 225 225 225 225 250 250 250 400 400 400 400 18 18 65 100 200 200 200 22 42 65 100 200 65 100 200 65 100 200 65 65 100 200 14 14 35 65 100 150 200 35 65 100 35 65 100 35 65 100 EHD FDB FD HFD FDC FCL FB-P EDB EDS ED EDH EDC FD HFD FDC JD HJD JDC DK KD HKD KDC

Notes The short-circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short-circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short-circuit rating of the lowest rated main or branch device. Top feed only. The short-circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included.

Includes Smart Chassis (system controller integral to the panelboard chassis).


Lighting optimization software and startup support must be included with each systemsee Page 475.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Panel Layout
Pow-R-Command PRC100EC Layout
1-Pole 2-Pole 1-Pole 2-Pole 2-Pole 3-Pole 2X 3X 1-Pole 2-Pole 3-Pole 1X 2X 3X EHD FDB FD HFD FDC EDB, EDS, ED, EDH EDC EDB, EDS, ED, EDH, EDC BABRP BABRSP BAB GHQRSP GHBS GHB

Instructions 1. Select: (from layout on left) a. Smart Chassis with Expansion Chassis.
Note: Smart chassis is always located at the bottom of the panelboard chassis immediately below the bottom breaker.

5X 12 Poles 10X 24 Poles


ckt 1 3 5 7 9 11 13 15 17 Pow-R-Command Smart Chassis and 18 Pole Spaces ckt 2 4 6 8 10 12 14 16 18

b. Required mains (lugs, breaker or fuse pullout). c. Appropriate neutral. d. Branch breakers and additional chassis space, as needed. 2. Layout panel as shown on left, using appropriate X units. Total X units determine box height shown on left. (When total X units exceeds the number shown, use next size box size.)

Layout Example 1. Panel description: a. Pow-R-Command, three-phase, four-wire 480Y/277 Vac, interrupting rating of 14 kAIC symmetrical, 250A main lugs only at bottom, surface mounted and the following branch breakers: b. 3620A, single-pole GHBS. c. 620A, single-pole GHBS spaces. 2. Layout information from layout on left: a. Smart Chassis with EC . . . . . . = 20X b. 24-circuit add-on chassis . . . . . . = 10X c. 250A neutral . . = 5X d. 250A main lugs only . . . . . = 5X e. Total panelboard height . . . . . . . = 40X 3. From table below: (40X box) Box catalog number . . . . . . . YS2072 Trim catalog number . . . . . . LT2072S OR Box catalog number . . . . . EZB2072R Trim catalog number . . . . . EZT2072S

20X Smart Chassis includes spaces for 18 Poles GHBS, GHQRSP, GHB, BABRP, BABRSP, BAB

Expansion Chassis Accepts 1 Application Specific Controller

Smart Chassis is always located at the bottom of the panelboard chassis immediately below all GHBS/GHB or BABR/ BABRS/BAB breakers.

Neutral Section Main Lug Section

5X 8X 2X 5X 8X

100250 A 400 A 100 A 250 A 400 A

Approximate Dimensions in Inches (mm) Box Tabulation


X Units Box Height YS Box Catalog Number LT Trim Catalog Number EZ Box Catalog Number EZ Trim Catalog Number

Main Device Horizontally Mounted Main Devices Vertically Mounted

See branch mounted EHD, FD, FDB, HFD, FDC, EDB, EDS, ED, EDH, EDC above 7XEHD, FDB, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC 7X100 A Class T fusible pullout 9X200 A Class T fusible pullout 9XFB-P 14XJD, HJD, JDC 15XDK, KD, HKD, KDC

100400A 23X 31X 40X 53X 48.00 (1219.2) 60.00 (1524.0) 72.00 (1828.8) 90.00 (2286.0) YS2048 YS2060 YS2072 YS2090 LT2048S or F LT2060S or F LT2072S or F LT2090S or F EZB2048R EZB2060R EZB2072R EZB2090R EZT2048S or F EZT2060S or F EZT2072S or F EZT2090S or F

Notes All F-Frame branch breakers must be mounted above (top) of all controllable breakers on the chassis. EDB, EDS, ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order. All add-on branch spaces must be adjacent to smart chassis poles. GHBS, GHQRSP and GHB breakers cannot be mixed on same chassis with BABRP, BABRSP and BAB breakers. Top mounted mainonly.

Cabinets Fronts are code-gauge steel, ANSI-61 light gray painted finish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5.75 inches (146.1 mm). Standard width is 20.00-inch (508.0 mm) 100400 amperes.

Top and Bottom Gutters 5.50 inches (139.7 mm) minimum. Side Gutters 4.00 inches (101.6 mm) minimum.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

469

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
470 PRC50 Panelboard

Panelboards and Lighting Control


Pow-R-Command

Contents
Description Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Eaton Green Solution

Page 447 451 453 454 457 460 463 467 471 478 473

PRC50 Panelboard
Product Description
Eatons PRC50 panelboard is similar to a PRC100 panelboard with additional programming capability added that provides the ability to group up to 42 remotely operated circuit breakers into eight individual zones. Each zone is designed to be switched by a dry contact from an external time clock, switch or interposing relay. The PRC50 programming board included with the controller allows the breakers to be grouped locally without the need of special equipment or software. The groupings can be easily changed without the need of any field rewiring. The grouping configurations are made using simple pushbutton inputs. Service 120/240 Vac single-phase three-wire, 208Y/120 Vac three-phase four-wire 240/120 Vac three-phase four-wire, 480Y/277 Vac three-phase four-wire

Zone Conguration Eight Zones of Event Driven Control Simple two key eld programming Matrix wiring allows breakers to be assigned to multiple zones Eight integrated digital override inputs No analog inputs

Branch Breakers Refer to Page 472

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Product Selection
PRC50 Panelboard
Ampere Rating Interrupting Rating (kA Symmetrical) Device 240V 480Y/277V Type

Type PRC100

Main Integral Fuse DisconnectSeries Rated Combinations


Ampere Rating 100 MLO MLO MLO 200 65 65 Interrupting Rating (kA Symmetrical) 240V 480Y/277V 100 100 Device Type T Fuse Disconnect T Fuse Disconnect Approved Branch Devices GHB, GHBS, EHD, FDB, FD GHB, GHBS, EHD, FDB, FD

Main Lug Only 100 250 400

Main Breaker 100 100 100 100 100 100 100 225 225 225 225 225 225 225 225 250 250 250 400 400 400 400 400 18 18 65 100 200 200 200 22 42 65 100 200 65 100 200 65 100 200 65 65 100 200 200 14 14 35 65 100 150 200 35 65 100 35 65 100 35 65 100 100 EHD FDB FD HFD FDC FCL FB-P EDB EDS ED EDH EDC FD HFD FDC JD HJD JDC DK KD HKD KDC LCL

Notes The short-circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short-circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short-circuit rating of the lowest rated main or branch device. Top feed only. Requires 6.50-inch (165.1 mm) deep box. The short-circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included. Includes Pow-R-Command Universal System Controller integral to the panelboard chassis (Smart Chassis) and the PRC50 Programming Board. Lighting optimization software and start-up support are not required.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

471

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
472 GHBS Remote Control Circuit Breaker BABRP Remote Control Circuit Breaker

Panelboards and Lighting Control


Pow-R-Command

Branch Circuit Breakers480Y/277 Volt Maximum


Ampere Rating Interrupting Rating (kA Symmetrical) 240 Volt 480 Volt Breaker Type

Remote Controllable Branch Circuit Breakers 1530 1530 1520 1530 10 10 65 65 14 14 BABRP BABRSP GHQRSP GHBS

Conventional Branch Circuit BreakersNot Controllable 1560 1560 70 70 80100 80100 1550 1550 1520 1520 1520 2560 70100 1560 70100 1560 70100 110150 1560 70100 110225 1560 70100 110225 1560 70100 110225 100225 100225 100225 100225 100225 10 10 10 10 10 10 10 10 10 65 65 65 65 18 18 18 18 18 65 65 65 100 100 100 200 200 200 22 42 65 100 200 14 14 14 14 14 14 14 14 14 35 35 35 65 65 65 100 100 100 BAB BAB-H BAB BAB-H BAB BAB-H QBGF QBGFEP QBCAF GHQ GHB GHB GHB EHD EHD FDB FDB FDB FD FD FD HFD HFD HFD FDC FDC FDC EDB EDS ED EDH EDC

Notes Single-pole breaker rated 120 Vac. Two-pole breaker rated 120/240 Vac. Single-pole breakers are rated 277 Vac maximum. Two- and three-pole breakers are rated 480Y/277 Vac maximum. 50A devices are available as two-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. For use on 480Y/277 Vac maximum. Maximum lug size, 4/0 AWG Al/Cu in 20-inch (508.0 mm) wide box. 300 kcmil lug available in 28-inch (711.2 mm) wide box.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
Page 447 451 453 454 457 460 463 467 470 474 478

PRC25 Panelboard

Contents
Description Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10 10 10 10 10 10 10 10 10 10 10 10

PRC25 Panelboard
Product Description
The PRC25 panelboard is designed to meet the needs for control of lighting and small branch circuits. Used as a standalone panelboard controlled by a time clock or wall switch, the PRC25 offers a solution for replacement of contactor and relay-based lighting control schemes. It can be applied to distribution systems rated:

to group individual breakers into zones that may be switched on/off by a dry contact from a time clock, photocell, wall switch or building automation system. Branch Breakers Refer to Page 478.

Branch BreakersPRC25
Ampere Rating 1520 1520 2560 70100 1530 1520 1560 1520 Provision Interrupting Rating (kA Symmetrical) 480Y/277 Vac 14 14 14 14 25 14 14 14 Breaker Type GHQ GHB GHB GHB HGHB GHQRSP GHBGFEP GHBHID

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

Standards and Certications


Single-phase three-wire and three-phase four-wire 120/240, 208Y/120 and 480Y/277 Vac

UL 67, UL 50 Federal Specication W-P-115c Refer to Page 463 for additional information

The heart of the PRC25 panel is the Zoning Board integral to the panelboard. This controller provides the ability

Product Selection
Branch Circuit BreakersPRC25
Ampere Rating 1560 70 80100 1550 1550 1520 1560 1530 1530 1530 Provision Interrupting Rating (kA Symmetrical) 240 Vac 10 10 10 10 10 10 10 10 10 10 Breaker Type BAB BAB BAB QBGF QBGFEP QBCAF BAB-D BAB-C BABRP BABRSP

Notes Single-pole breakers are rated 120 Vac maximum. 50 ampere devices are available as two-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. HID (High Intensity Discharge) rated breaker. Switching neutral breaker. Single-pole device requires two-pole space; two-pole device requires three-pole space. Solenoid operated breaker.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

473

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Vertically Mounted Deadfront Cover Main Lug Section

Panelboards and Lighting Control


Pow-R-Command

Panel Layout
PRC25 Layout
Note: Controlled circuits must be grouped in maximum of 6 Zones. All circuits within a zone must be together on the same side of the panelboard.
ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 PRC25 Class II Chassis ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42

Instructions 1. Select PRC25 Panelboard Chassis from layout on left. a. Determine required mains (lugs or breaker) b. Select appropriate main lug c. Select appropriate main device d. Select appropriate branch breakers 2. Layout panel as shown on left. Total inches determine box height shown on left. (When total inch units exceed the number shown, use next size box size.)

Layout Example 1. Panel Description: a. PRC25, three-phase four-wire, 208Y/120 Vac, interrupting rating of 10 kAIC symmetrical: 225A main lugs only at bottom, surface mounted and the following branch breakers b. 3620A, single-pole BABRP c. 620A, single-pole BABRP spaces 2. Layout information from layout on left. a. PRC25 with 42-circuit Interior 31 inches b. 225A main lugs Section 4 inches c. Total panelboard height 35 inches 3. From table below:

31 in. - Includes Class II Chassis and spaces for 42 poles

Note: PRC25 Chassis may be located at the Top or Bottom of the panelboard immediately above or below the breakers.

2 in. for Deadfront Cover Supports 2 in.100 Amp MLO 4 in.225 Amp MLO 21 in.400 Amp MLO 8 in.100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD 9 in.225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 24 in.JD, HJD, JDC 24 in.DK, KD, HKD, KDC

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
474

Panel height: 20 inches wide x 5.75 inches deep Box height: 35 inches 60 inches Box catalog number: YS2060 or EZB2060R Trim catalog number: LT2060S or EZT2060S

Approximate Dimensions in Inches (mm) Box Tabulation


X Units Box Height YS Box Catalog Number LT Trim Catalog Number EZ Box Catalog Number EZ Trim Catalog Number

20-Inch Wide x 5.75-Inch Deep Boxes 33.00 (838.2) 35.00 (889.0) 38.00 (965.2) 48.00 (1219.2) 60.00 (1524.0) 60.00 (1524.0) YS2048 YS2060 YS2060 YS2060 YS2060 YS2072 LT2048S or F LT2060S or F LT2060S or F LT2060S or F LT2060S or F LT2072S or F EZB2048R EZB2060R EZB2060R EZB2060R EZB2060R EZB2072R EZT2048S or F EZT2060S or F EZT2060S or F EZT2060S or F EZT2060S or F EZT2072S or F

40.00 (1016.0) 60.00 (1524.0) 44.00 (1117.6) 60.00 (1524.0) 55.00 (1397.0) 72.00 (1828.8)

Cabinets Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20.00 inches (508.0 mm) wide x 5.75 inches (146.1 mm) deep.

Top and Bottom Gutters 6.38 inches (162.1 mm). Minimum Side Gutters 4.00-inch (101.6 mm) minimum on 20.00-inch (508.0 mm) wide box size.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

PRC Catalog Numbers


Description Catalog Number Control CabinetWith Power Supply, System Controller and Space for Up to Three ASCs Control cabinetsurface mount Control cabinetush mount GHBS pigtail cable8 feet (2.4m) GHBS pigtail cable16 feet (4.9m) GHBS pigtail cable24 feet (7.3m) GHBS pigtail cable32 feet (9.8m) Controllers 208V PRC2000 ControllerLCD display 480V PRC2000 ControllerLCD display 240V PRC2000 ControllerLCD display 208V PRC2000 Controller 480V PRC2000 Controller 240V PRC2000 Controller 208V PRC1000 ControllerLCD display 480V PRC1000 ControllerLCD display 240V PRC1000 ControllerLCD display 208V PRC1000 Controller 480V PRC1000 Controller 240V PRC1000 Controller 208V PRC750 ControllerLCD display 480V PRC750 ControllerLCD display 240V PRC2000 ControllerLCD display External Controller 120V PRC2000 External ControllerLCD display 120V PRC2000 External Controller 277V PRC2000 External ControllerLCD display 277V PRC2000 External Controller 120V PRC1000 External ControllerLCD display 120V PRC1000 External Controller 277V PRC1000 External ControllerLCD display 277V PRC1000 External Controller 120V PRC750 External ControllerLCD display 277V PRC750 External ControllerLCD display Note All catalog numbers are non-standard items. PRC2000ECD-120 PRC2000EC-120 PRC2000ECD-277 PRC2000EC-277 PRC1000ECD-120 PRC1000EC-120 PRC1000ECD-277 PRC1000EC-277 PRC750ECD-120 PRC750ECD-277 PRC2000D-208 PRC2000D-480 PRC2000D-240 PRC2000-208 PRC2000-480 PRC2000-240 PRC1000D-208 PRC1000D-480 PRC1000D-240 PRC1000-208 PRC1000-480 PRC1000-240 PRC750D-208 PRC750D-480 PRC750D-240 PRC100CCS PRC100CCF PRL100ECP PRC100ECP-16 PRC100ECP-24 PRC100ECP-32

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

475

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
476 Description

Panelboards and Lighting Control


Pow-R-Command

PRC Catalog Numbers, continued


Catalog Number Advanced Control Devices PRC Digital Network Switch 2-button (Black) PRC Digital Network Switch 2-button (White) PRC Digital Network Switch 2-button (Almond) PRC Digital Network Switch 4-button (Black) PRC Digital Network Switch 4-button (White) PRC Digital Network Switch 4-button (Almond) PRC Digital Network Switch 6-button (Black) PRC Digital Network Switch 6-button (White) PRC Digital Network Switch 6-button (Almond) PRC Digital Switch Network Power Injector PRC Digital Switch Network Splitter PRC 2-button Momentary Low Voltage Switch (Black) PRC 2-button Momentary Low Voltage Switch (White) PRC 2-button Momentary Low Voltage Switch (Almond) PRC 4-button Momentary Low Voltage Switch (Black) PRC 4-button Momentary Low Voltage Switch (White) PRC 4-button Momentary Low Voltage Switch (Almond) PRC 6-button Momentary Low Voltage Switch (Black) PRC 6-button Momentary Low Voltage Switch (White) PRC 6-button Momentary Low Voltage Switch (Almond) Wireless Control Devices PRC4000 Wireless Small Building Controller PRC4000 Wireless Extended Range Small Building Controller PRC Wireless I/O Module Assembly PRC Wireless Switch Interface PRC Wireless Network Switch 2-button (Black) PRC Wireless Network Switch 2-button (White) PRC Wireless Network Switch 2-button (Almond) PRC Wireless Network Switch 4-button (Black) PRC Wireless Network Switch 4-button (White) PRC Wireless Network Switch 4-button (Almond) PRC Wireless Network Switch 6-button (Black) PRC Wireless Network Switch 6-button (White) PRC Wireless Network Switch 6-button (Almond) PRC25 6-zone PRC25 Maintained to Momentary Controller 4-zone PRC25 Maintained to Momentary Controller Note All catalog numbers are non-standard items. PRC25-6 PRC25-4 PRC4000-W PRC4000-WX PRCWIOM PRCWSI PRCWS2B PRCWS2W PRCWS2A PRCWS4B PRCWS4W PRCWS4A PRCWS6B PRCWS6W PRCWS6A PRCDS2B PRCDS2W PRCDS2A PRCDS4B PRCDS4W PRCDS4A PRCDS6B PRCDS6W PRCDS6A PRCDSNPI PRCDSNSP PRCLS2B PRCLS2W PRCLS2A PRCLS4B PRCLS4W PRCLS4A PRCLS6B PRCLS6W PRCLS6A

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

PRC Catalog Numbers, continued


Description Optional Equipment LCD Display unit for PRC1000/2000 Breaker Control Bus21-circuitRetrot Kit Breaker Control Bus15-circuitRetrot Kit Breaker Control Bus 9-circuitRetrot Kit Breaker Control Bus21-circuit Breaker Control Bus15-circuit Breaker Control Bus9-circuit 24 Volt AC Power supply Application Specic Controllers (ASC) Switch override controller Telephone override controller PRC100 universal system controller PRC50 programming board Native Modbus controller JCI Metasys controller Computers and Peripherals Network interface box Ethernet terminal server Smart programming cable (serial) Modbus programming cable (serial) Laptop computer Central operators station Data logging printer Data fax modem56K Software Lighting optimization software Web server software with hardware server key Building graphics software with PC hardware key Custom graphics screens programming Technical Support Startup, training and/or programming rst day of trip (includes expenses) Additional consecutive days of same trip Additional users guide Notes All catalog numbers are non-standard items. One software package required per system. One day required per system (up to six panels). Required to start up six panels per day after the rst day. One users guide included with each system at no charge. PRC100SUT1 PRC100SUT2 PRC100UG PRC100SLO PRC100SWS PRC100SBG PRC100SCG PRC100NIB PRC100ENS PRCSMARTCABLE MPC-S PRC100LTC PRC100COS PRC100DLP PRC100DFM PRC100SOC PRC100TOC PRC100USC PRC50SPB PRC100MOD PCR100JCI PRCLCD PRCBCB-21R PRCBCB-15R PRCBCB-9R PRCBCB-21 PRCBCB-15 PRCBCB-9 PRCPS24 Catalog Number

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

477

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
4. Nameplate, Engraved

Panelboards and Lighting Control


Pow-R-Command

Modications
1. Special Cabinet (Box) Construction Modication 1
Modication Type 1 Enclosure 28-inch (711.2 mm) wide in place of standard 20-inch (508.0 mm) wide Type 2 Enclosure (Drip-proof with gasketed trim) Type 3R Enclosure (20-inch (508 mm) wide) (28-inch (711.2 mm) wide) Type 12 Enclosure (20-inch (508 mm) wide) (28-inch (711.2 mm) wide)

8. Trim and Door Modications Special Fronts and Doors Modication 8


Description Door-in-door, one door over interior and one which exposes gutter (LT Trim) Common LT trim for two section panels with boxes bolted together Standard ush lock with quarter turn fasteners at top and bottom of trim door (standard on doors 48-inch (1219.2 mm) high and over) (LT Trim)

9. Special HingesLT Trim Piano hinges in lieu of standard hinges. Modication 9


Description Add for each panel door

2. Complete Assembly Complete assembly of panelboard box, interior and trim prior to shipment when required. Modication 2
Description Add per panel

10. Special Locks Modication 10


Description LT Type Trim Yale 511S with rosette Yale 4651S (LL803 Key) Master keyingabove locks or standard lockper panelboard Tee handle and 3-point catch National metal lock with standard keying National metal lock with GE75 keyway EZ Trim Standard lock, keyed GE75 Standard lock, keyed to Corbin TEU-1 Standard lock, keyed to Corbin Cat 60 Standard lock, keyed to Corbin WEM1

3. Concealed Trim ClampsLT Trim Modication 3


Description Add per panel

10 10 10 10 10 10 10 10 10 10 10 10 10 10

Modication 4
Type Mastic back and installed by purchaser, per nameplate Fixed to panel trim with two screws or rivets, per nameplate

5. Directory FrameMetal Modication 5


Frame Type Metal frame, plastic cover

11. Conduit Covers Fabricated sheet metal to cover open conduits above and/or below standard NEMA Type 1 box. Modication 11
Cover Type Conduit enclosing shield (open back) Conduit enclosure (solid back)

6. Permanent Circuit Numbers 12. Increased Dimensions Modication 6


Description To provide permanently attached Micarta circuit numbers

Modication 12
Description Increased End Gutters

7. Tamperproof ScrewsLT Trim Modication 7


Description Tamperproof screws for trims, in lieu of standard screws

4-inch (101.6 mm) top or bottom 7-inch (177.8 mm) top or bottom 12-inch (304.8 mm) top or bottom Increased Side Gutters 4-inch (101.6 mm) left or right 7-inch (177.8 mm) left or right 12-inch (304.8 mm) left or right

478

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Panelboards and Lighting Control


Pow-R-Command

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
479

13. Painting and Special Coatings Standard boxes are code-gauge galvanized sheet steel. Standard trims are code-gauge sheet steel with a rust inhibiting phosphatized coating and finished with ANSI-61. Modication 13
Description Painted boxes (ANSI-61) Painted trims or boxes (other than ANSI-61)

16. Bus Density Main bus ampere rating is determined by UL listed temperature test. For 750 ampere per square inch aluminum or 1000 ampere per square inch copper, make price addition as follows: Modication 16
Amperes Per Square Inch Aluminum750A 250A Maximum 400A Maximum

14. Copper Main Bus Modication 14


Main Bus Ratings Amperes 100 225250 400

Copper1000A 250A Maximum 400A Maximum

Note: Modication 14Applies to 310 and 310+ Trip Units.

17. Neutral Rated 200% Modication 17

14a. Silver-Plated Copper Main Bus For silver-plated copper panelboard main bus and/or connectors, add as follows: Modication 14a
Main Bus Ratings Amperes 100250 400

Main Bus Rating Amperes 100 225 250 400

Neutral Rating Amperes 225 450 500 800

Box Height Addition 0 0 3X 3X

Note: Prices and dimensions based on mechanical lugs. For compression or copper lugs, refer to Eaton.

14b. Tin-Plated Copper Main Bus For tin-plated copper panelboard main bus and/or connectors, add as follows: Modication 14b
Main Bus Ratings Amperes 100250 400

18. Increased Panel Main Bus Rating Modication 18


Ampere Rating Change 100250 250400 400600

15. Ground Bar Modication 15


Aluminum Terminal Bar for Aluminum or Copper Cable Standard Insulated/ Isolated Copper Terminal Bar for Copper Cable Only Standard Insulated/ Isolated

19. Compression Main LugsType Burndy Range Taking Al/Cu Compression Terminations For other terminal types, refer to Eaton. Modication 19
Wire Range by Panel Type Main Ampere PRL1a and PRL2a PRL3E 100 125 225 250 400 600 800 1200 (1) #11/0 or (1) 2/0300 kcmil (1) #42/0 or (1) 2/0 300 kcmil PRL3a (1) #42/0 or (1) 2/0300 kcmil PRL4

(1) 2/0300 kcmil or (1) 4/0500 kcmil

(1) 2/0 350 kcmil or (1) 2/0350 kcmil or (2) 500750 kcmil (1) 4/0500 kcmil (1)4/0500 kcmil

(2) 4/0300 kcmil or (2) 4/0300 kcmil or (2) 4/0300 kcmil or (2) 500750 kcmil (2) 500750 kcmil (2) 500750 kcmil (2) 500750 kcmil (2) 2/0500 kcmil or (2) 2/0500 kcmil or (2) 500750 kcmil (2) 500750 kcmil (2) 500750 kcmil (3) 500750 kcmil (4) #2600 kcmil or (4) 500750 kcmil

Note Insulated/isolated ground bar includes a standard ground bar.

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

10.6
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
480

Panelboards and Lighting Control


Pow-R-Command

20. Copper Lugs Optional copper mechanical main lugs only. (Includes main incoming neutral lug.) Modication 20
Main Amperes 100 225250 400 Wire Range and Number of Lugs Per Phase (1) #141/0 (1) #6250 kcmil (2) #1/0600 kcmil

25. Circuit Breaker Handle Lockoff Devices Modication 25


Breaker Type Non-Padlockable GHB, EHD, FDB, FD, ED, EDH, EDC, BAB Padlockable EHD, FDB, FD, HFD, FDC, ED, EDH, EDC, GHB, BAB

21. Sub-Feed LugsPRC100 and PRC50 Only Mechanical Al/Cu lugs. Compression or copper lugs requires additional price adder from Modication 19 or Modication 20 as appropriate. Available on main lug panels only. Modication 21
Main Amperes 100250 Box Height Addition 1X

26. Copper Wire Only Terminals for Molded Case Circuit Breakers (To replace standard Al/Cu terminals) Modication 26
Frame F J K Max. Breaker Ampere Rating 225 250 225 350 400 Terminal Material Copper Stainless Steel Copper Copper Copper Wire Range #44/0 #4350 (1)#3350 (1)250500 (2)3/0250

22. Through-Feed Lugs Mechanical Al/Cu lugs. Compression or copper lugs requires additional price adder from Modication 19 or Modication 20 as appropriate. Modication 22
Main Amperes 100 250 400 Box Height Addition 2X 5X 8X

27. Touchup Paint Modication 27


Description 12 oz. Spray Can. ANSI-61 Light Gray Indoor Case lot of 1212 oz. spray cans. ANSI-61 light gray indoor Single style Note BAB breakers with shunt trips require one additional pole space, i.e., three-pole breaker with shunt trip requires four-pole space.

23. Service Entrance To provide a Service Entrance label as detailed under the Service Entrance Equipment in application considerations. Only panelboards meeting these requirements can be labeled as such. The requirement for a Service Entrance Label must be noted on order entry. Includes neutral disconnect link and Service Entrance Equipment Label. (Ground bar not included see Modication 15.) Modication 23
Device Add per panel

24. Shunt Trip for Main or Branch Circuit Breaker For tripping circuit breaker from a remote point. Voltage and frequency must be specified. Wiring to terminal blocks is not included. Standard leads extend 18 inches (457.2 mm) out of breaker. Circuit breakers with factory-installed 120, 240 or 480 Vac shunt trips are available with UL listing as shown in table below. Modication 24
Device GHB (three-pole only) All other circuit breakers

Volume 2Commercial Distribution CA08100003EDecember 2010

www.eaton.com

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Index

A
ability, 2-3, 7-8, 11, 14-15, 24, 27 above, 3, 20, 23, 28, 32 AC, 31 ac, 27 Accepts, 23 Access, 4, 9, 12 access, 1, 3-5, 7, 9 accessories, 3 AccessTCP, 6 accommodate, 7 accomplish, 4 achieve, 2, 7 across, 6 act, 7 Add, 32, 34 add, 20, 23, 33 added, 3, 24 adder, 34 Addition, 33-34 addition, 2-3, 7, 21, 33 Additional, 31 additional, 2-3, 6, 17, 20, 23-24, 27, 34 address, 9 adds, 2, 7-8 adjacent, 1, 20, 23 adjustable, 3 adjusts, 7 Advanced, 2, 30 advanced, 2, 7 after, 31

aid, 3 airports, 2, 15 Al, 19, 26, 33-34 alarm, 2-3, 7, 15 Alarms, 3 alarms, 8, 11, 14 All, 4, 7, 20, 23, 28-31, 34 all, 1-3, 12, 15, 20, 23 allow, 1-2, 4, 12 allowing, 1 Allows, 4 allows, 1, 3-4, 7-8, 11, 14, 24 Almond, 2, 30 almost, 1 already, 7 Also, 3 also, 2-3, 7-8, 11, 14-15, 17 Although, 1 Aluminum, 33 aluminum, 33 always, 20, 23 Amp, 10, 13, 16, 28 Ampere, 10, 13, 16, 18-19, 22, 25-28, 33-34 ampere, 27, 33 Amperes, 33-34 amperes, 23 An, 1, 7-8, 11, 14, 17, 21, 24 an, 1-4, 7-9, 11, 14, 18, 21-22, 24-25 Analog, 5 analog, 4-5, 7, 24 and, 1-34 ANSI, 10, 13, 16, 20, 23, 28, 33-34 any, 3-4, 7, 9, 15, 24 anywhere, 9

Index

Application, 3-4, 8, 11-12, 17, 21, 23, 31 application, 3, 34 Applications, 1, 4 applications, 1-4, 8, 11, 14-15, 17 applied, 1, 17, 27 Applies, 33 Appropriate, 20, 23 appropriate, 10, 13, 16, 20, 23, 28, 34 Approved, 18, 22, 25 approved, 18, 22, 25 Approximate, 10, 13, 16, 20, 23, 28 APRC, 30 Arc, 19, 26-27 Architecture, 9, 15 are, 1-4, 7-11, 13-14, 16, 19-20, 23-31, 33-34 around, 2 array, 7 art, 2, 7 Article, 1 as, 1-4, 7-14, 16-20, 22-23, 25-28, 33-34 ASC, 3, 21, 31 ASCII, 6 ASCs, 3-4, 8, 11, 21, 29 assembled, 18, 22, 25 Assembly, 30, 32 assembly, 18, 22, 25, 32 assigned, 24 assistance, 2 associated, 2 Astronomical, 3, 8, 11, 14 astronomical, 2, 7, 15 at, 1-34 attached, 32 auditoriums, 3 automated, 2, 7 Automation, 2 automation, 1, 3, 8, 27 auxiliary, 7 Available, 4, 8, 11, 14, 34 available, 1-4, 6, 17, 19, 26-27, 34 AWG, 19, 26

B
BAB, 19-20, 23, 26-27, 34 BABR, 20, 23 BABRP, 19-20, 23, 26-28 BABRS, 20, 23

BABRSP, 8, 10-11, 13-14, 16, 19-20, 23, 26-27 back, 1-2, 7, 32 backed, 7 backup, 6 BACnet, 2, 5-6, 8-9 ballasts, 2, 6-7 Bar, 33 bar, 33-34 BAS, 1 based, 1-2, 4, 7-8, 11, 14-15, 17-18, 22, 25, 27, 33 Basic, 2 basic, 3 basis, 2 Battery, 6 battery, 7 Baud, 6 BCB, 3, 9, 12, 15 BCBs, 3, 9, 12, 15 be, 1-5, 7-18, 20-25, 27-28, 34 Because, 2 Being, 2 being, 2-3 below, 10, 13, 16, 20, 23, 28, 32, 34 better, 8, 11, 14 between, 2, 12 beyond, 3, 21 Black, 2, 30 Blink, 6 blinking, 8, 11, 14 blocks, 34 Board, 25, 27 board, 3, 24, 31 boasts, 2, 15 bolted, 32 Both, 2 both, 2-3, 8, 11-12, 14 Bottom, 10, 13, 16, 20, 23, 28 bottom, 10, 13, 16, 20, 23, 28, 32 bottomcation, 32 Box, 4, 6, 10, 13, 16, 20, 23, 28, 32-34 box, 1, 10, 13, 16, 18-20, 23, 25-26, 28, 31-32 Boxes, 10, 13, 16, 20, 23, 28 boxes, 32-33 bracket, 6 Branch, 17-27, 34 branch, 1-2, 8, 10-11, 13-14, 16-18, 20, 22-23, 25, 27-28 Breaker, 2-3, 8-9, 11-12, 14-15, 18-19, 22, 25-27, 31, 34 breaker, 2-6, 8-11, 13-14, 16, 18-20, 22-23, 25-28, 34 Breakers, 2, 9, 15, 17, 19, 21, 24, 26-27, 34 breakers, 1-5, 8-14, 16, 19-20, 23-24, 26-28, 34 broadest, 3, 17 Brownout, 3 brownout, 8, 11, 14

Index

Browser, 6, 9 browser, 7, 9 Building, 2, 30-31 building, 1, 3, 8, 12, 17, 27 buildings, 1-3, 15 Built, 6 built, 2, 7 Burndy, 33 Bus, 3, 8, 11, 14, 31, 33 bus, 8-9, 11, 14, 33 Buses, 9, 12, 15 buses, 8-9, 11, 14 Busses, 9 but, 3, 7 button, 2, 30 buttons, 3 by, 1-3, 5, 8, 11, 14-15, 24, 27, 32-33 bypass, 3

C
CA, 1-34 Cabinet, 3-4, 29, 32 cabinet, 4, 8, 11, 14, 29 Cabinets, 10, 13, 16, 20, 23, 28 Cable, 9, 12, 15, 33 cable, 2-4, 8, 11, 29, 31 cables, 1-2, 4 California, 6 call, 1-34 campus, 4 Can, 34 can, 1-5, 7-9, 11-12, 14-15, 17, 24, 27, 34 cannot, 20, 23 cans, 34 capabilities, 2, 7 capability, 3, 8, 11, 14, 24 Capable, 2 capable, 3, 7 carry, 1 Case, 34 cases, 1-2 CAT, 2 Cat, 32 Catalog, 10, 13, 16, 20, 23, 28-31 catalog, 10, 13, 16, 20, 23, 28-31 CatalogMain, 20 catchModification, 32

cation, 32-33 CCF, 29 CCS, 29 cells, 1 Central, 31 central, 3-4 Certifications, 11, 14, 17, 27 Certificationsholiday, 8 chain, 4 Change, 33 change, 2, 4 changed, 2-3, 24 changes, 1-3 charge, 31 Chassis, 3, 10, 13, 16, 18, 20-23, 25, 28 chassis, 18, 20, 22-23, 25 Choices, 1 choose, 4 Circuit, 1, 19, 26-27, 32, 34 circuit, 1-4, 6, 8-11, 13-14, 16, 18-20, 22-28, 31-32, 34 circuits, 4, 27-28 Ckt, 10, 13, 16 ckt, 10, 13, 16, 20, 23, 28 Clamps, 32 Class, 17, 20, 23, 28 Client, 9 Clock, 6 clock, 2-3, 6-8, 11, 14, 24, 27 clocks, 1-2, 15 close, 1 closest, 4 closet, 4 closing, 1 closures, 3 coating, 33 Coatings, 33 Code, 1, 17 code, 10, 13, 16, 20, 23, 28, 33 colors, 2 com, 1-34 combination, 15 Combinations, 18, 22, 25 combinations, 12 comes, 4, 7 Command, 1-34 commands, 7 Commercial, 1-34 commercial, 3 Common, 32 common, 2 communicate, 2-3, 7 communicates, 7 communication, 2, 7, 9

Index

communications, 1, 3, 8 compatibility, 3 Complete, 32 complete, 4 completely, 2, 7 complex, 2 complexity, 1 component, 2 Components, 7-8, 11, 14 components, 1-2, 8, 11, 14 Compression, 33-34 compression, 33 computer, 3-4, 8, 11, 31 Computers, 31 Concealed, 32 concern, 1 conditions, 1 Conductor, 9, 12, 15 Conduit, 32 conduit, 2 conduits, 32 Configuration, 24 configuration, 2, 7 Configurations, 9, 12 configurations, 2-3, 8, 11, 14, 24 configured, 3, 9 conjunction, 3 connect, 3, 7, 14 connected, 2-4, 12, 15 connecting, 7 connection, 2 connections, 3 connectivity, 7 connectors, 33 consecutive, 31 Considerations, 1-2 considerations, 34 consist, 2 consists, 1 Construction, 32 construction, 4 contact, 1-3, 8, 11, 14, 24, 27 Contactor, 1 contactor, 1-2, 27 contactors, 1-3 contacts, 3 contained, 12 Containing, 9 contains, 2 Contents, 1, 7-8, 11, 14, 17, 21, 24, 27 continued, 6, 30-31 Control, 1-34 control, 1-4, 7-9, 11, 14-15, 17, 27

Controllable, 19, 26 controllable, 1-3, 5, 8, 11-12, 14, 20, 23 Controlled, 28 controlled, 2, 8-9, 11-12, 14, 27 Controller, 2-8, 10-14, 16, 21, 23, 25, 29-30 controller, 1-4, 6-8, 11, 14, 18, 22, 24, 27, 31 Controllers, 3-4, 8, 11, 21, 29, 31 controllers, 1-3, 6-8, 11, 14 Controls, 3, 6 controls, 8 Conventional, 19, 26 coordinate, 7 coordinator, 7 Copper, 33-34 copper, 33-34 Corbin, 32 cord, 4 COS, 31 cost, 2-3 Cover, 28, 32 cover, 32 Covers, 32 creating, 14 Cu, 19, 26, 33-34 current, 1 Custom, 31 custom, 3 Customer, 9 customer, 2, 7 customers, 1, 4 Customizable, 12 customizable, 2, 7 cutting, 2

D
Data, 3, 5, 8-9, 11-12, 14-15, 31 data, 7 Day, 3 day, 3, 21, 31 Daylight, 6, 8, 11, 14 days, 3, 31 Deadfront, 28 December, 1-34 dedicated, 2 Deep, 10, 13, 16, 28 deep, 10, 13, 16, 18, 25, 28 Delivery, 1-34

Index

Density, 33 Depending, 1 depth, 20, 23 Description, 1, 7-8, 10-11, 13-14, 17, 21, 24, 27-34 description, 16, 20, 23 Design, 1 design, 1 Designed, 2, 15 designed, 1, 3-4, 7, 17, 24, 27 detailed, 34 Determine, 10, 13, 16, 28 determine, 10, 13, 16, 20, 23, 28 determined, 33 Device, 18, 20, 22-23, 25, 34 device, 2-3, 6-7, 10, 13, 16, 18, 22, 25, 27-28 Devices, 2, 7, 23, 25, 30 devices, 1-2, 5, 7, 18-19, 22, 25-27 DevicesMain, 18, 22 DevicesOptional, 34 DFM, 31 diagnose, 4 diagnostics, 2, 8, 11, 14 diagnosticsany, 3 diagram, 12 different, 3 differently, 3 difficult, 2 Digital, 2, 7, 30 digital, 2, 5, 7, 24 Dimensions, 10, 13, 16, 20, 23, 28, 32 dimensions, 33 dimmable, 2, 7 Dimming, 6 dimming, 6-7 directly, 1-2, 7-9, 11, 14 Directory, 32 Discharge, 27 Disconnect, 18, 22, 25 disconnect, 34 discrete, 7 Display, 15, 31 display, 2, 6, 8, 11, 14, 29 distributed, 1-3, 5, 7, 9 Distribution, 1-34 distribution, 1, 17, 27 DK, 10, 13, 16, 18, 20, 22-23, 25, 28 DLP, 31 does, 2, 7 done, 2, 7 Door, 32 door, 32 Doors, 32 doors, 32

downtime, 1-2 Drip, 32 Driven, 24 drives, 5 dry, 2-3, 8, 11, 14, 24, 27 DSN, 2 dual, 1 due, 2 during, 1, 4 dynamically, 7

E
Each, 2-3, 5, 7, 9, 24 each, 2-3, 7-9, 11, 14, 18, 22, 31-32 easily, 3, 24 easy, 2 Eaton, 1-3, 5, 7-8, 11-12, 14-15, 17, 21, 24, 33 eaton, 1-34 EC, 1, 3, 7-8, 11, 14, 17, 21-24, 27, 29 ECD, 29 ECP, 29 ED, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 EDB, 10, 13, 16, 18-20, 22-23, 25-26, 28 EDC, 18-20, 22-23, 25-26, 34 edge, 2 EDH, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 EDS, 10, 13, 16, 18-20, 22-23, 25-26, 28 effective, 3 EHD, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 Eight, 9, 24 eight, 3, 5, 8, 11-12, 14-15, 24 either, 20, 23 Electrical, 1, 17 electrical, 1, 4, 7 elephone, 5 eliminate, 1 eliminated, 2 Embedded, 7-8 embedded, 2, 8-9 Emissions, 17 employs, 1 enabled, 3 enclosing, 32 Enclosure, 32 enclosure, 10, 13, 16, 32 Enclosures, 17 End, 32

Index

Energy, 17 energy, 2-3, 6, 8, 11, 14, 17 Engineering, 4 engineers, 4 Engraved, 32 ENS, 31 ensure, 4 entire, 2 Entrance, 34 EntranceTo, 34 entry, 34 EP, 9, 12, 15 Equipment, 8, 11, 14, 17, 31, 34 equipment, 1, 3, 6, 8, 11, 14, 19, 24, 26-27 equipped, 7 ertically, 16 essential, 7 Ethernet, 6, 9, 31 even, 8 Event, 24 event, 2, 8, 11, 14 Every, 9 every, 2 Example, 13, 20, 23, 28 ExampleInstructions, 10, 16 Examples, 3 exceed, 28 exceeds, 10, 13, 16, 20, 23 existing, 1, 3-4, 7 expand, 3, 7 expander, 5 Expansion, 3, 9, 21, 23 expansion, 2, 5, 12, 14 expenses, 31 exposes, 32 extend, 3, 21, 34 Extended, 30 extended, 7 extension, 4, 12 extensive, 1 External, 6, 29 external, 3, 5-8, 11, 14, 24 EZ, 10, 13, 16, 20, 23, 28, 32 EZB, 10, 13, 16, 20, 23, 28 EZT, 10, 13, 16, 20, 23, 28

F
Fabricated, 32 facilities, 2-3, 15 facility, 2-3, 7 Factory, 4, 15 factory, 2-4, 21, 34 fails, 2 Failure, 2 failure, 2-3, 8, 11, 14 Family, 1 family, 1 fasteners, 32 fault, 19, 26-27 fax, 31 FB, 18, 20, 22-23, 25 FCC, 17 FCL, 18, 22, 25 FD, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 FDB, 18-20, 22-23, 25-26, 34 FDC, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 feature, 7 Features, 3, 8, 11, 14 features, 2, 7, 15 Federal, 17, 27 Feed, 34 feed, 1, 18, 22, 25 feedback, 2, 7-8, 11, 14 feet, 4, 29 Field, 4 field, 1, 3, 21, 24 finish, 10, 13, 16, 20, 23, 28 finished, 33 firmware, 6 first, 31 Fixed, 32 fixed, 3 Flash, 6 Flexibility, 1-2 flexibility, 1-2, 8 Floor, 9, 12, 15 flush, 29, 32 following, 10, 13, 16, 20, 23, 28 follows, 33 For, 1-34 for, 1-9, 11-12, 14-15, 17, 19-20, 23, 26-29, 31-34 form, 3 four, 1, 10, 12-13, 16-17, 20, 23-24, 27-28, 34 Frame, 10, 13, 16, 20, 23, 28, 32, 34 frame, 32

Index

free, 2 freeing, 1 frequency, 34 frequent, 3 From, 10, 13, 16, 20, 23, 28 from, 1-4, 7-8, 10-11, 13-14, 16, 20-21, 23-24, 27-28, 34 Fronts, 20, 23, 32 ft, 5 full, 3 fully, 2, 7, 18, 22, 25 function, 1 functionality, 3, 21 functions, 2, 4 further, 3 Fuse, 18, 22, 25 fuse, 20, 23 Fuses, 18, 22, 25 fusible, 20, 23 fusing, 1

groups, 1 Guide, 1, 5-8, 11, 14, 17, 21, 24, 27 guide, 31 gutter, 32 Gutters, 10, 13, 16, 20, 23, 28, 32 GuttersTamperproof, 32 GuttersTrims, 28

H
Handle, 34 handle, 32 hard, 2 Hardware, 3 hardware, 2, 8, 11, 14, 31 harvesting, 6 has, 2-3, 7, 14 have, 1-3, 7 heart, 3, 27 Height, 10, 13, 16, 20, 23, 28, 33-34 height, 10, 13, 16, 20, 23, 28 help, 4, 7 HFD, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 HGHB, 27 HID, 27 High, 27 high, 1-2, 15, 32 Hinges, 32 hinges, 32 HJD, 18, 20, 22-23, 25, 28 HKD, 10, 13, 16, 18, 20, 22-23, 25, 28 Holiday, 3, 8, 11, 14 holiday, 2, 11, 14-15 Holidays, 6 holidays, 6 Horizontally, 23 hours, 4 house, 4 houses, 3, 21 housing, 6 hrs, 6

G
galvanized, 10, 13, 16, 20, 23, 28, 33 gasketed, 32 gateway, 6-7 gauge, 10, 13, 16, 20, 23, 28, 33 GE, 32 geographic, 7 GFCI, 19, 26-27 GFP, 19, 26-27 GHB, 18-20, 22-23, 25-27, 34 GHBGFEP, 27 GHBHID, 27 GHBS, 18-20, 22-23, 25-26, 29 GHQ, 19, 26-27 GHQRSP, 8, 11, 14, 19-20, 23, 26-27 gives, 2, 7 graphics, 31 Gray, 34 gray, 10, 13, 16, 20, 23, 28, 34 Green, 1, 7-8, 11, 14, 17, 21, 24 Ground, 9, 12, 15, 33-34 ground, 33 Group, 4 group, 3-4, 24, 27 grouped, 3, 24, 28 grouping, 3, 24 groupings, 3, 24

Index

I
IBC, 17 ideal, 3-4, 17 IEEE, 7 If, 2 II, 28 illuminated, 2 Immediate, 1-34 immediately, 20, 23, 28 In, 1-2, 7 in, 1-4, 6-17, 19-21, 23, 26, 28, 32, 34 Inch, 10, 13, 16, 28, 33 inch, 10, 13, 16, 18-20, 23, 25-26, 28, 32-33 Inches, 10, 13, 16, 20, 23, 28 inches, 10, 13, 16, 20, 23, 28, 34 inchesertically, 28 include, 3 included, 3, 18, 22, 24-25, 31, 34 Includes, 10, 13, 16, 18, 22, 25, 28, 34 includes, 2, 8, 11, 14, 20, 23, 31, 33 including, 2 incoming, 34 incorporate, 2 incorporates, 1-2, 4 Increased, 32-33 increased, 2 indicators, 6 individual, 2-4, 8, 11, 14, 24, 27 individualized, 12 individually, 3, 5 Indoor, 34 indoor, 34 industrial, 2, 15 industry, 2-3, 7, 17 inexpensive, 1 information, 7, 10, 13, 16-17, 20, 23, 27-28 inhibiting, 33 Injector, 30 Input, 1, 3, 6, 8, 11, 14 input, 3, 5, 7 Inputs, 3, 5 inputs, 1-3, 5, 7-8, 11, 14-15, 24 install, 2 Installation, 2 installation, 2-3 installations, 1 installed, 1, 3, 8-9, 11, 14, 21, 32, 34 installing, 2 instead, 7

Instructions, 13, 20, 23, 28 Insulated, 33 Integral, 3, 18, 22, 25 integral, 18, 22, 25, 27 integrate, 8 Integrated, 7 integrated, 2-3, 7, 24 Integration, 5, 8, 11, 14 integration, 5, 8 integrations, 3 intelligence, 1-3, 7 Intelligent, 8, 11, 14 Intensity, 27 interaction, 2 Interface, 4, 6-7, 12, 30 interface, 2, 4, 31 interfaced, 1 interfaces, 9 Interior, 10, 13, 16, 28 interior, 1, 32 internal, 7 Internet, 1, 9, 12 Interposing, 3 interposing, 24 Interrupting, 18-19, 22, 25-27 interrupting, 10, 13, 16, 20, 23, 28 into, 1-4, 24, 27 IP, 2, 6, 9 is, 1-5, 7-11, 13-18, 20, 22-25, 27-28, 33-34 Isolated, 33 isolated, 33 It, 2-4, 7, 17, 27 it, 2, 4, 7 items, 29-31 its, 2, 7, 14

J
jack, 4 JCI, 3, 31 JD, 18, 20, 22-23, 25, 28 JDC, 18, 20, 22-23, 25, 28 Johnson, 3, 6

Index

K
kA, 18-19, 22, 25-27 kAIC, 10, 13, 16, 20, 23, 28 kcmil, 19, 26, 33-34 KD, 10, 13, 16, 18, 20, 22-23, 25, 28 KDC, 10, 13, 16, 18, 20, 22-23, 25, 28 Key, 32 key, 24, 31 keyed, 32 keying, 32 keypad, 2, 8, 11, 14 keyway, 32 Kit, 31 kits, 8, 11, 14 KMParts, 1-34 knockout, 10, 13, 16, 28 knockouts, 20, 23

L
Label, 34 label, 34 labeled, 34 Labor, 2 labor, 2 LAN, 1, 9, 12, 15 Laptop, 31 large, 3, 17 Layout, 8, 10-11, 13-14, 16-17, 20-21, 23, 27-28 layout, 3, 10, 13, 16, 20, 23, 28 LCD, 2, 6, 8, 11, 14-15, 29, 31 LCL, 18, 25 leading, 7 leads, 34 learning, 7 LED, 2, 6 left, 3, 9-10, 13, 16, 20, 23, 28, 32 length, 5 levels, 1, 4 lieu, 32 life, 2 Light, 34 light, 3, 10, 13, 16, 20, 23, 28, 34 Lighting, 1-34 lighting, 1-4, 7-8, 11, 14-15, 17, 27

Lights, 3 lights, 2, 8, 11, 14 limited, 1 line, 3, 7 link, 34 listed, 8, 11, 14, 18, 22, 25, 33 listing, 34 LL, 32 Load, 3 load, 1-3, 7-8, 11, 14-15, 20, 23 loads, 3-5, 7 Local, 3, 6, 15 local, 2, 4, 7 locally, 3, 24 located, 1, 4, 20, 23, 28 location, 2, 4, 7 lock, 32 Lockoff, 34 Locks, 32 locks, 32 log, 2-3, 15 logging, 3, 5, 7, 31 longer, 7 LonWorks, 6 LOS, 4 loss, 2-3, 8, 11, 14-15 lot, 34 Low, 2, 30 low, 2-3, 7 lower, 2 lowest, 18, 22, 25 LT, 10, 13, 16, 20, 23, 28, 32 LTC, 31 Lug, 10, 13, 16, 18, 20, 22-23, 25, 28 lug, 8, 10-11, 13-14, 16, 19, 26, 28, 34 Lugs, 33-34 lugs, 10, 13, 16, 20, 23, 28, 33-34

M
mA, 19, 26-27 made, 3, 24 magnetic, 2, 8, 11, 14 Main, 10, 13, 16, 18, 20, 22-23, 25, 28, 33-34 main, 8, 10-11, 13-14, 16, 18, 20, 22-23, 25, 28, 33-34 mains, 10, 13, 16, 20, 23, 28 Maintained, 30 major, 1-2

Index

make, 1, 33 makes, 1 Management, 17 management, 2-3, 6, 8, 11, 14 Mandatory, 5 mandatory, 5 Manual, 5 manually, 2 many, 2, 7 Master, 32 master, 12 Mastic, 32 Material, 34 Matrix, 24 matrix, 6, 8, 11, 14 Max, 34 max, 5 Maximum, 5-6, 10, 13, 16, 19, 26, 33 maximum, 2, 5, 12, 15, 19, 26-28 MaximumCircuit, 26 may, 1-4, 8, 11, 18, 20-23, 25, 27-28 Mechanical, 34 mechanical, 2, 33-34 medium, 3, 17 meet, 1-2, 7, 17, 27 meeting, 1, 34 Memory, 3, 8, 11, 14 memory, 2, 6-8, 11, 14-15 message, 2, 15 Messages, 8, 11, 14 Metal, 32 metal, 32 Metasys, 3, 31 method, 4 methods, 1-2 Micarta, 32 microprocessor, 1-2, 7-8, 11, 14-15, 17 microprocessortemporary, 2 minimal, 1 Minimum, 10, 13, 16, 28 minimum, 10, 13, 16, 20, 23, 28 mixed, 20, 23 MLO, 10, 13, 16, 18, 22, 25, 28 mm, 10, 13, 16, 18-20, 23, 25-26, 28, 32, 34 MOD, 3, 31 Modbus, 3, 6, 31 model, 1 Modem, 12 modem, 4, 31 Modes, 2 Modifi, 32-33 Modification, 32-34 modification, 2

Modifications, 8, 11, 14, 17, 21, 24, 27, 32 Module, 2, 7, 30 module, 5, 7 Molded, 34 Momentary, 30 momentary, 2 monitor, 3 monitoring, 4 more, 1, 3-4, 8 most, 1, 3 mount, 6, 29 Mounted, 10, 13, 16, 20, 23, 28 mounted, 1-4, 8, 10-11, 13-14, 16, 20, 23, 28 Mounting, 6 mounting, 1 mounts, 17 MPC, 31 much, 2 multi, 4 multiple, 24 multitude, 2 must, 18, 20, 22-23, 28, 34

N
Nameplate, 32 nameplate, 32 National, 1, 17, 32 Native, 31 native, 3, 8 nd, 9, 12, 15 NEC, 1, 6 necessary, 2 need, 2-3, 7-8, 11, 24 needed, 9, 20, 23 needs, 1-2, 7, 17, 27 NEMA, 32 Network, 2-4, 6, 9, 12, 30-31 network, 2-3, 6-8, 11 networkable, 2-3, 7 networked, 1-3, 8, 11, 17 networks, 8 Neutral, 20, 23, 33 neutral, 20, 23, 27, 34 new, 1-4, 7 next, 10, 13, 16, 20, 23, 28 NIB, 4, 6, 31 No, 5-6, 15, 24

Index

no, 2, 7, 31 Non, 6, 34 non, 4, 29-31 Not, 7, 19, 26 not, 1-2, 5, 18, 22, 25, 34 Note, 10, 13, 16, 20, 23, 28-30, 33-34 noted, 34 Notes, 5-6, 18-20, 22-23, 25-27, 31 notice, 6 notification, 7 notifications, 7 Number, 5, 10, 13, 16, 20, 23, 28-31, 34 number, 5-6, 10, 13, 16, 20, 23, 28 Numbers, 29-32 numbers, 29-32

O
occupancy, 2-3, 7 of, 1-8, 10-18, 20-25, 27-28, 31-32, 34 Off, 3-4 off, 1-4, 6-8, 11, 14, 27 offer, 1 offered, 2, 8, 11, 14 offers, 3, 7, 17, 27 office, 2-3, 15 Often, 2 often, 1-2 On, 3-4, 6 on, 1-4, 6-7, 9-10, 13, 16, 19-20, 23, 26-28, 32-34 onboard, 2, 7 One, 31 one, 2-4, 7-9, 11, 14, 32, 34 Online, 4 online, 4 Only, 4, 18, 22, 25, 33-34 only, 7, 10, 13, 16, 18-20, 22-23, 25-28, 34 OPC, 6 open, 32 opening, 1 operate, 2-3, 8, 11, 14 operated, 3, 24, 27 operation, 2 Operational, 2 operator, 31 optimal, 2 optimization, 8, 11, 14, 18, 22, 25, 31 Option, 6

option, 14 Optional, 3, 5, 31 optional, 2-3, 6, 21 OR, 23 or, 1-34 order, 20, 23, 34 ordered, 3, 21 other, 3, 7, 33-34 out, 34 output, 6-8, 11, 14 Outputs, 5-6 outputs, 2, 7 over, 1-3, 5, 7-8, 11, 32 overcurrent, 1 overload, 1 Override, 3-4, 8, 11, 14 override, 2, 4-6, 8, 11, 14-15, 24, 31 Overview, 1, 7-8, 11, 14, 17, 21, 24, 27 own, 14 oz, 34

P
package, 31 Padlockable, 34 PadlockableMain, 34 Page, 1, 7-8, 11, 14, 17-18, 21-22, 24, 27 page, 2 Paintadditional, 34 Painted, 33 painted, 10, 13, 16, 20, 23, 28 Painting, 33 pair, 3, 8, 11 Panel, 8-11, 13-14, 16-17, 20-21, 23, 27-28, 33 panel, 1, 9-10, 13-16, 20-21, 23, 27-28, 32, 34 Panelboard, 1, 3, 7-11, 13-14, 16-18, 21-22, 24-25, 27-28 panelboard, 1-4, 8, 10-11, 13-14, 16-18, 20-25, 27-28, 32-33 Panelboards, 1-34 panelboards, 1-4, 6, 8, 11-12, 14-15, 17, 34 PanelboardTechnical, 14 panels, 1, 3, 5, 9, 12, 14, 31-32, 34 Part, 17 passes, 7 Password, 6 password, 1 past, 1 PC, 9, 12, 31

Index

PCR, 31 peak, 4 Per, 33-34 per, 1, 4, 6-7, 21, 31-34 perform, 1-2 performance, 4 periods, 6 Peripherals, 31 Permanent, 32 permanently, 32 personal, 4, 8, 11 personnel, 19, 26-27 Phase, 34 phase, 1, 8, 10-11, 13-14, 16-17, 20, 23-24, 27-28 phosphatized, 33 photo, 1-2, 7 photocell, 27 photocells, 3 Piano, 32 pigtail, 4, 29 place, 32 placed, 9 plant, 4 plastic, 32 Plated, 33 plated, 33 platform, 7 play, 3 Plug, 3 plug, 4 plugged, 3 point, 32, 34 Pole, 20, 23 pole, 6, 10, 13, 16, 19-20, 23, 26-28, 34 Poles, 20, 23 poles, 20, 23, 28 port, 3, 6 possible, 3-4 Pow, 1-34 Power, 2-3, 5, 8, 11, 14, 17, 29-31 power, 1-4, 8, 11, 14, 21 powered, 3 PRC, 1-18, 20-25, 27-31, 34 PRCBCB, 31 PRCDS, 2, 30 PRCDSNPI, 30 PRCDSNSP, 30 PRCEP, 1, 3, 8, 11-12, 14 PRCJCI, 3 PRCLCD, 31 PRCLS, 2, 30 PRCPS, 31 PRCSMARTCABLE, 31

PRCWIOM, 2, 7, 30 PRCWS, 2, 7, 30 PRCWSI, 7, 30 pre, 4 premier, 2, 15 prewired, 2 price, 33-34 Prices, 33 printer, 31 prior, 32 priorities, 3 priority, 3 PRL, 9, 29, 33 Product, 1, 5, 7-8, 11, 14, 17-18, 21-22, 24-25, 27 products, 7 professional, 4 program, 3-4, 6 programmable, 2, 8, 11, 14, 17 programmed, 2-3, 7, 9 Programming, 4, 15, 25 programming, 2-4, 7-8, 11, 14, 24, 31 programs, 4 prompted, 4 proof, 32 protected, 1, 6 Protection, 1 protection, 1-3, 8, 11, 14-15, 19, 26-27 Protocol, 8 protocol, 2-3, 5, 8 provide, 1, 8, 11, 14, 32, 34 provided, 2 provides, 2-4, 24, 27 Provision, 27 pullout, 20, 23 purchased, 8 purchaser, 32 pushbutton, 3, 24

Q
QBCAF, 19, 26-27 QBGF, 19, 26-27 QBGFEP, 19, 26-27 Qualified, 17 quarter, 32 quickly, 7

Index

R
RAC, 4 radio, 7 rail, 5 Rails, 5 Range, 30, 33-34 range, 3, 17 rate, 6 Rated, 18, 22, 25, 33 rated, 1, 17-19, 22, 25-27 Rating, 18-19, 22, 25-27, 33-34 rating, 1, 10, 13, 16, 18, 20, 22-23, 25, 28, 33 RatingAmpere, 18, 22 Ratings, 33 ratings, 1-3 rd, 9, 12, 15 re, 1 Real, 3 real, 2, 8, 11, 14 recommended, 4 recovery, 3, 8, 11, 14 reduction, 3 Refer, 17, 21, 24, 27 refer, 33 regular, 12 relay, 1-3, 5, 7, 24, 27 relays, 1-2 reliability, 2, 7 Remote, 4-5, 9, 12, 19, 26 remote, 1, 3-4, 9, 12, 34 remotely, 3-4, 7, 24 replace, 34 replacement, 27 replaces, 3 require, 1-3, 34 Required, 15, 20, 23, 31 required, 1, 3-5, 7, 10, 13, 16, 25, 28, 31-32 requirement, 34 requirements, 1, 3, 34 Requires, 18, 25 requires, 1-3, 27, 34 requiring, 4 response, 1 restore, 3 retailers, 3 Retrofit, 1, 31 retrofit, 2, 4, 8, 11, 14 Retrofitting, 1 reused, 4

rewiring, 1-3, 24 right, 3, 9, 20, 23, 32 rise, 2, 15 riser, 12 rivets, 32 robust, 2, 7-8 room, 7 rooms, 1 rosette, 32 RS, 6-7, 12 RTU, 6 rules, 3 Running, 7 rust, 33

S
same, 1, 3-4, 17-18, 20, 22-23, 25, 28, 31 SBG, 31 SC, 4 SCC, 3 SCG, 31 schedule, 3, 6 scheduled, 3-4 schedules, 2, 6, 8, 11, 14 Scheduling, 6 scheduling, 2-3, 7-8, 11, 14-15 schedulingBACnet, 8 scheme, 2-3 schemes, 2, 27 schools, 3 screens, 31 Screws, 32 screws, 32 seamless, 2 Section, 10, 13, 16, 20, 23, 28 section, 13, 16, 32 See, 17, 20, 23 see, 7, 18, 22, 34 segment, 7 Seismic, 17 Select, 10, 13, 16, 20-21, 23, 28 Selection, 1, 5-8, 10-11, 13-14, 16-18, 21-22, 24-25, 27 selection, 2 self, 3 sensor, 7 sensors, 2-3, 7 serial, 4, 31

Index

Series, 18, 22, 25 series, 18, 22, 25 Server, 6 server, 2, 6-8, 31 Service, 4, 24, 34 services, 4 set, 4, 7 Setup, 4 setup, 4 sheet, 32-33 shield, 32 shielded, 3, 8, 11 shipment, 32 Shor, 1 short, 1, 18, 22, 25 shot, 2, 8, 11, 14 Should, 3 shown, 10, 12-13, 16, 18, 20, 22-23, 25, 28, 34 Shunt, 34 shunt, 34 Side, 10, 13, 16, 20, 23, 28, 32 side, 9, 28 sides, 3 signal, 1 Silver, 33 silver, 33 similar, 24 Simple, 24 simple, 1-3, 24 Simplicity, 2 simplifying, 1 Simply, 4 Single, 19, 26-27, 34 single, 1-2, 8, 10-11, 13-17, 20, 23-24, 28 site, 2 six, 1-2, 31 size, 10, 13, 16, 19-20, 23, 26, 28 sizes, 1 sizing, 3 SLAN, 5 slave, 3 SLO, 31 Small, 30 small, 3, 17, 27 Smart, 2, 15, 18, 20, 22-23, 25, 31 smart, 20, 23 SOAP, 6 SOC, 3, 8, 11, 14, 31 Software, 4, 8, 11-12, 31 software, 2-4, 7-8, 11, 14, 18, 22, 24-25, 31 Solenoid, 27 solenoid, 3 solid, 32

Solution, 1, 7-8, 11, 14, 17, 21, 24 solution, 3, 27 solutions, 12 some, 1, 3 sophisticated, 1 SOR, 20 Space, 1, 29 space, 1, 20, 23, 27, 34 Spaces, 20, 23 spaces, 3, 10, 13, 20, 23, 28 spaceson, 16 SPB, 31 Special, 32-33 special, 3, 24 Specific, 3-4, 8, 11, 21, 23, 31 specific, 3 Specification, 17, 27 Specifications, 8-9, 11-12, 14-15 specified, 34 Specify, 20, 23 specifying, 1 split, 12 Splitter, 30 Spray, 34 spray, 34 Square, 33 square, 33 stadiums, 3 Stainless, 34 Standalone, 15 standalone, 2-3, 8, 11, 14-15, 17, 27 Standard, 3, 9-10, 13, 16, 20, 23, 28, 32-34 standard, 1-3, 7-9, 11-12, 14, 21, 29-34 Standards, 6, 8, 11, 14, 17, 27 Start, 15 start, 25, 31 Startup, 2, 4-5, 31 startup, 1-2, 5, 18, 22 state, 2, 7 station, 31 status, 2, 6-8, 11, 14 Steel, 34 steel, 10, 13, 16, 20, 23, 28, 33 stored, 2, 7 stores, 4 straightforward, 2 strategy, 2, 7 style, 34 Sub, 9, 12, 15, 34 Subject, 17 subjected, 1 subnetwork, 14 Such, 8, 11, 14

Index

such, 3-4, 34 Sumter, 4 Supply, 29 supply, 2, 4-5, 31 Support, 1-34 support, 3-4, 8, 11-12, 14, 18, 22, 25 Supports, 28 Supportswitched, 4 Supportthe, 4 surface, 10, 13, 16, 20, 23, 28-29 SUT, 31 Switch, 2-3, 5, 7-8, 11, 14, 30-31 switch, 2-3, 5, 7-8, 11, 14-15, 24, 27 switched, 2-3, 24, 27 Switches, 2 switches, 1-3, 7 Switching, 8, 11, 14, 27 switching, 2-3, 6-8, 11, 14, 21 SWS, 31 Symmetrical, 18-19, 22, 25-27 symmetrical, 10, 13, 16, 20, 23, 28 System, 2-4, 8-9, 11-12, 14-15, 21, 25, 29 system, 1-4, 7-9, 11, 14-15, 17-18, 22, 27, 31 systems, 1, 3-4, 17, 27

T
table, 10, 13, 16, 20, 23, 28, 34 Tabulation, 23, 28 TabulationHorizontally, 20 tailored, 2 Taking, 33 Tamperproof, 32 task, 4 tasks, 2 TCP, 6 team, 4 Tech, 1-34 Technical, 4, 8-9, 11-12, 15, 31 technicians, 4 technology, 2, 7 Tee, 32 Telephone, 4, 8, 11, 14, 31 telephone, 4 temperature, 33 tenant, 3 tenants, 2, 8, 11, 14 Terminal, 33-34

terminal, 31, 33-34 Terminals, 34 terminals, 34 terminated, 1, 4 Terminations, 33 test, 33 TEU, 32 th, 9, 12, 15 than, 3-4, 33 that, 1-4, 7-8, 11, 14-15, 18, 21-22, 24-25, 27 The, 1-4, 7-9, 11, 14-15, 17-18, 21-22, 24-25, 27, 34 the, 1-5, 7-18, 20-25, 27-28, 31, 34 theatres, 3 them, 1-2 There, 2-3 there, 2-3 thermal, 2, 8, 11, 14 These, 1 these, 1, 34 They, 1-2 This, 2-3, 7, 27 this, 3-4, 7, 12 those, 1, 4 Three, 6, 29 three, 1-2, 4, 8, 10-11, 13-14, 16-17, 19-20, 23-24, 26-28, 34 Through, 34 through, 2, 7-8, 11, 14 throughout, 2, 9 Thru, 9, 12 Time, 3, 6, 8, 11, 14 time, 1-3, 6-8, 11, 14-15, 21, 24, 27 Tin, 33 tin, 33 Title, 6 To, 3, 7-8, 11, 14, 32, 34 to, 1-4, 7-9, 11-12, 14-15, 17-18, 20-25, 27, 29-34 TOC, 4, 8, 11, 14, 31 Today, 1 together, 28, 32 tone, 4 Top, 10, 13, 16, 18, 20, 22-23, 25, 28 top, 20, 23, 32 Total, 5, 10, 13, 16, 20, 23, 28 total, 2, 5, 10, 13, 15-16, 20, 23, 28 touch, 4 Touchup, 34 Traditional, 1 traditional, 1-2, 17 trained, 4 Training, 4 training, 31 transfers, 7

Index

Trim, 10, 13, 16, 20, 23, 28, 32 trim, 32 Trims, 10, 13, 16 trims, 32-33 Trip, 33-34 trip, 31, 34 tripping, 34 trips, 34 trouble, 2 troubleshoot, 4 turn, 1, 32 twisted, 3, 8, 11 Two, 19, 26 two, 3-4, 7-8, 11, 14, 19, 21, 24, 26-27, 32 Type, 18-19, 22, 25-27, 32-34 types, 33 Typeype, 32 Typical, 9 typically, 1

utilizing, 5

V
Vac, 1, 3, 10, 13, 16-17, 19-20, 23-24, 26-28, 34 valuable, 1, 7 various, 3-4, 8, 11, 14 varying, 1 Vdc, 7 version, 1 versions, 3 Vertically, 10, 13, 20, 23 very, 2 via, 6, 9, 15 voice, 4 volatile, 6 Volt, 26, 31 Voltage, 2, 30, 34 voltage, 2, 7 voltages, 8, 11, 14 Volume, 1-34 VPN, 9

U
UBC, 17 UG, 31 UL, 6, 8, 11, 14, 17, 27, 33-34 under, 34 unique, 9 unit, 7-8, 31 Units, 20, 23, 28, 33 units, 3, 10, 13, 16, 20, 23, 28 Universal, 3-5, 21, 25 universal, 2, 31 until, 2 unwanted, 1 Up, 8, 11, 15, 29 up, 1-4, 7-8, 11-12, 14-15, 21, 24-25, 31 upgrade, 8 upon, 18, 22, 25 upstream, 1, 18, 22, 25 USC, 3, 31 use, 10, 13, 16, 19-20, 23, 26, 28 Used, 17, 27 used, 2-3, 7-8, 11, 14-15 user, 14, 31 users, 4 using, 2-4, 6-7, 9, 20, 23-24 utilized, 2 utilizes, 2, 8, 11, 14

W
wall, 1, 3-4, 27 warning, 2-3, 8, 11, 14 way, 3, 7 Web, 2, 6-9, 31 web, 1 webserver, 9 week, 3 well, 2, 7 WEM, 32 were, 1 When, 9-10, 12-13, 16, 20, 23, 28 when, 4-5, 32 where, 4 which, 1-3, 7, 32 White, 2, 30 who, 4 Wide, 10, 13, 16, 28 wide, 10, 13, 16, 19, 26, 28, 32 widely, 8

Index

Width, 10, 13, 16 width, 1, 20, 23 will, 3-4, 10, 13, 16, 21 Windows, 4 Wire, 33-34 wire, 1-2, 5, 10, 13, 16-17, 20, 23-24, 27-28 Wireless, 2, 7, 30 wireless, 1-2, 7 wirelessly, 7 wires, 7 Wiring, 34 wiring, 1, 17, 24 With, 2, 7, 29 with, 1-14, 16, 18, 20-25, 28, 31-34 within, 1-2, 4, 6, 8, 11-12, 15, 28 without, 3, 8, 10-11, 13, 16, 20, 23-24, 28 work, 3 Workstation, 9 would, 7 WPRC, 30 www, 1-34 WX, 30

Z
Zone, 24 zone, 2-3, 7, 24, 28, 30 Zones, 24, 28 zones, 1, 3, 5-6, 24, 27 Zoning, 27

X
Xckt, 20 XML, 6

Y
Yale, 32 year, 7 Yes, 5-6 YesCSA, 6 YesEthernet, 6 YesProtocols, 6 YesTime, 6 you, 7 your, 2, 7, 15 yrs, 6 YS, 10, 13, 16, 20, 23, 28

You might also like