DGA - Method in the Past and for the Future

Ivanka Atanasova-Hhlein

Siemens AG

Page 2

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

1970 1973 1975 1995


Page 3

Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced ratios for fault gases with similar solubility. Halstead developed the theoretical thermodynamic theory. The ratios are temperature dependent. With increasing the hotspot the amount of gases increases in the order: methane-ethane-ethylene. The evaluation scheme of the modern Gas-in-Oil Analysis is developed by Rogers, Mueller, Schliesing, Soldner (MSS).

Development of In-Line Monitoring


Siemens AG Energy Sector

May 2012

Ivanka Atanasova-Hhlein

Different phenomena in oil take place like: dielectric thermal dynamic chemical ! Gas-in-Oil Analysis (DGA = Dissolved Gas Analysis)
Page 4 May 2012 Ivanka Atanasova-Hhlein Siemens AG Energy Sector

Change/Ageing

The measurement of dissolved gases allow the knowledge on

! ! !

Type Complexity Seriousness

of event
Page 5 May 2012 Ivanka Atanasova-Hhlein Siemens AG Energy Sector

Sampling

Page 6

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Sampling Container

! Perfectly cleaned & Dried ! Free from dust & moisture ! Airtight ! Glass or Metal cans, syringes

Page 7

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

! Protect sample from direct light ! Avoid moisture & dust contamination ! Use the sampling containers exclusively for transformer oil sampling

Page 8

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

1 Handwheel 2 Sealing cap 3 Safety chain 4 Polyamid gasket 5 Nut 6 Drain valve 7 Hose and screw connector 8 Sampling bottle 9 Overflow vessel

Page 9

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Page 10

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Required information concerning oil sample(example)


Requested analysis:
Colour Appearance Neutralisationvalue Breakdownvoltage Water content Loss factor at50Hz Interfacial tension PCB-content Furananalysis (DGA) Gas-in-oil-analysis ISO 2049 IEC 60422 IEC 62021-1 IEC 60156 IEC 60814 IEC 60247 ISO 6295 EN 12766-2 IEC 61198 IEC 60567

Please fill in the following data:


Manufacturer: Customer: Location: Year ofmanufacture: Type: Power: Rating: Sampletaken from: Tank: conservator OLTC Bushing Others: Reason for sampletaking: Dateofoperationfault: Dateofrepair : Dateofoil treatment/reclaiming Routinecheckup: Further informations andprevious history: Oil samplevalve Top Transformer OLTC tank FTNR (ManufacturingNo.): WNR (Order No.): SampleNo.: Datesampletaken.: Typeofoil Quantity ofoil: Oiltemperaturein thesampletaken: Oil drainagedevice A 22/31/40DIN 42551 Middle OLTC Others Bottom Bushing

Sampletaker: Date Lab information: Consecutiveno.: Datesamplereceived: Datesampleanalysed: Typeofsamplecontainer: Nameinblock letters Company/Department specialfeatures: Phone

Page 11

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Extraction of Gases from the Oil

Page 12

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

DGA. Toepler Pump

Page 13

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

DGA. Partial Degassing

Page 14

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

DGA. Headspace at Ambient Temperature

Page 15

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

DGA. Headspace at 70C

Page 16

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Gaschromatographic Analysis

Page 17

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Gaschromatographic Analysis

Sample injection

Detector

Carrier Gas

Detector gas

Page 18

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Failures which can be identified by DGA

! Partial discharges ! Electrical discharges ! Charcoal coating of contacts ! Accelerated cellulosic degradation ! Local overheating ! Untightness of OLTC tank ! Catalytic reactions of materials ! Additional information from BHR gas
Siemens AG Energy Sector

Page 19

May 2012

Ivanka Atanasova-Hhlein

Failures which can not be identified by DGA

! Incipient Failures ! Long lasting temperatures < 150 C

Page 20

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Interpretation Schemes

Page 21

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Duvals Triangle

Page 22

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Patterns
Electrical Discharges Thermal Problem Partial Discharges

Page 23

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

MSS Scheme
Ratio ranges [C2H2] [C2H6] 0 1 1 2 2 0 2 2 1 1 0 0 1 1 0 Ratio numbers [H2] [C2H4] [C2H4] [CH4] [C2H6] [C3H6] 0 0 0 0 0 1 1 1 2 2 1 3 3 1 3 Number sequences 0 0 0 1 1 2/3 2 1 2/3 3 0 n.i. 3 0 n.i. 0 0 1 0 1 2 0 1 2/3 1 1 2 3 1 2

<0.3 0.3 to < 1.0 1.0 to < 3.0 3.0 to < 10.0 ! 10.0 Diagnosis Normal ageing of insultans Discharge of high energy Discharge of low energy Partial discharge with high energy Partial discharge with low energy Local overheating up to 300 C Local overheating from 300 C to 1000 C Local overheating over 1000 C Local overheating and discharge Local overheating and partial discharge
n.i. = not indicative

[CO2] [CO] 1 1 1 0 2 0 1 1 0 0 2 2 2 2 2
Siemens AG Energy Sector

Page 24

May 2012

Ivanka Atanasova-Hhlein

IEC Scheme

Page 25

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

In case of quotient information it must be clear, that quotients are only representative, if following values of the fault gases (in ppm) are exceeded: C2 H 2 H2 " [CXHY] x=1;2;3 CO CO2 !1 ! 15 ! 50 ! 80 ! 200

Page 26

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

DGA Example thermal Problem MSS-Code


Fault gas Hydrogen Methane Ethane Ethylene Acetylene Propane Propylene Carbon monoxide Carbon dioxide Oxygen Nitrogen
Page 27

00120
ppm H2 CH4 C2H6 C2H4 C2H2 C3H8 C3H6 CO CO2 O2 N2
May 2012

1967 8008 2013 8323 57 401 4824 253 1903 18222 61662
Ivanka Atanasova-Hhlein Siemens AG Energy Sector

MSS-Code
Fault gas Hydrogen Methane Ethane Ethylene Acetylene Propane Propylene Carbon monoxide Carbon dioxide Oxygen Nitrogen
Page 28

00120
ppm H2 CH4 C2H6 C2H4 C2H2 C3H8 C3H6 CO CO2 O2 N2
May 2012

Manufacturing year 1970 360 MVA Carbon deposits on PLTC Contacts

537 1041 295 1726 25 83 1012 1047 6158 11805 58084


Ivanka Atanasova-Hhlein Siemens AG Energy Sector

Gas-in-Oil Analysis Turn-to-Turn Fa MSS-Code


Fault gas Hydrogen Methane Ethane Ethylene Acetylene Propane Propylene Carbon monoxide Carbon dioxide Oxygen Nitrogen
Page 29

21121
ppm H2 CH4 C2H6 C2H4 C2H2 C3H8 C3H6 CO CO2 O2 N2
May 2012

4973 1758 243 2813 8236 58 1320 1196 2431 6743 44120
Ivanka Atanasova-Hhlein Siemens AG Energy Sector

DGA Thermal Problem with Partial Discharges MSS-Code


Fault gas Hydrogen Methane Ethane Ethylene Acetylene Carbon monoxide Carbon dioxide H2 CH4 C2H6 C2H4 C2H2 CO CO2

00101
ppm 1060 2481 703 2187 4 450 995

Manufacturing year 1991 234 MVA, 330 kV Defective welding joint

Page 30

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

DGA Catalytical Effects MSS-Code


Fault gas Hydrogen Methane Ethane Ethylene Acetylene Propane Propylene Carbon monoxide Carbon dioxide Oxygen Nitrogen
Page 31

?3??0
ppm H2 CH4 C2H6 C2H4 C2H2 C3H8 C3H6 CO CO2 O2 N2
May 2012

Manufacturing year 1977 Closed type Color 0,5 / Acidity 0,01

488 1 <1 <1 <1 <1 <1 67 222 5180 23700


Ivanka Atanasova-Hhlein Siemens AG Energy Sector

DGA Untight OLTC MSS-Code


Fault gas Hydrogen Methane Ethane Ethylene Acetylene Propane Propylene Carbon monoxide Carbon dioxide Oxygen Nitrogen
Page 32

22122
ppm H2 CH4 C2H6 C2H4 C2H2 C3H8 C3H6 CO CO2 O2 N2
May 2012

128 25 5 81 288 5 50 143 1920 24600 52000


Ivanka Atanasova-Hhlein Siemens AG Energy Sector

DGA Diagnostic Importance in Service

Ratios

Gas increase rates

Absolute Values

Trend

Page 33

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Absolute Values

IEC 60599 (VDE 0370-7)


C2H2 All transformers H2 50 " 150 2 " 20 60 " 280
Ivanka Atanasova-Hhlein Siemens AG Energy Sector

CH4 30 " 130

C2H4 60 " 280

C2H6 20 " 90

CO 400 " 600

CO2 2800 " 14000

No OLTC

Communicating OLTC

Page 34

May 2012

Ratios

a) Eliminates the effect of the oil volume b) Eliminates some effects of sampling c) Especially interesting is the ratio formation for fault gases which exhibit similar solubilities, but their development is temperature dependent e. g. the thermodynamic considerations of Halstead.

Page 35

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Thermodynamcal considerations of Halstead

Page 36

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Gas Increase Rates information on seriousness of failure

C2H2 All 0,01 transformers

H2 0,36

CH4 0,33

C2H4 C2H6 0,40 0,25

CO 2,9

CO2 27

! 90% gas increase source: Cigre TF11 in ppm/day


Gas increase rates are temperature and volume dependent

Page 37

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Trend Analysis
Development of the Fault Gases After Two Months of On-Line Monitoring
600 100 90 80 70 60

ppm H 2, CO,CH 4, C2 H4, C2 H6, top oil (C)

500

400

Carbon Dioxide Hydrogen Methane Carbon Monoxide Ethane Ethylene top oil temp C

ppm CO 2

300

50 40

200 30 20 100 10 0 1.7.08 11.7.08 21.7.08 31.7.08 10.8.08 20.8.08 30.8.08 Sa m pling da te 0 9.9.08

Page 38

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Trend Analysis

40

35 5 30

25

Ratio C 2H 4/C 2H 6, CH 4 /H2

top oil (C)

Top

20

C2H

CH

15 2 10 1
35 5 30

40

0
25

0 11.7.08
Top oil Temperature (C) C2H4/C2H6 CH4/H2

Ratio C 2H 4/C 2H 6, CH 4 /H2

1.7.08

21.7.08

31.7.08

10.8.08

20.8.08

30.8.08

9.9.08

top oil (C)

Sa m pling da te

20

15 2 10

! Trendanalysis is important not only with absolute values, but also with the ratios.
1 5 0 0 1.7.08 11.7.08 21.7.08 31.7.08 10.8.08 20.8.08 30.8.08 9.9.08 Sa m pling da te

Page 39

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

On-Line Monitoring

# Early failure recognition # Diagnosis is only possible with the sofisticated types where IEC ratios can be built Cigre TF 15 DGA did a comparison between On-Line monitoring systems and Off-Line analyses. The brochure is on the way. Evaluated are: " Precision " Longterm stability " Repeatability In case of " Routine concentrations, d.h. 5 * Detection Limit " Low Concentrations, d. h. 2-5*Detection Limit
Page 40 May 2012 Ivanka Atanasova-Hhlein Siemens AG Energy Sector

Recommendation of Cigre A2.27 for On-LineMonitoring

# Necessary in case a problem has been identified # Often, however, difficult to maintain # Interfaces can lead to problems # Able to deliver important information in a short time # Does not automatically lead to higher reliability

Page 41

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

What can be measured on-line:

! Temperature ! Current, Voltage ! OLTC ! Oil level ! Gas-in-l Analysis ! Humidity in oil ! Bushings ! Acoustic Signals ! Magnetic Circuit ! Coolers
Page 42 May 2012 Ivanka Atanasova-Hhlein Siemens AG Energy Sector

More Data does not mean automatically more Information Data Explosion1) (Total Exabytes)
200 150 100 50 0 2002
1) Exa = 1016 = 10 Mil of Billions

2003
May 2012

2004

2005

2006

2007
Siemens AG Energy Sector

Page 43

Ivanka Atanasova-Hhlein

Transformer Failure Rate

$ Failure rate

Failure at Comissioning

Failure because of aging

Constant failure rate

Aging / years %
Siemens AG Energy Sector

Page 44

May 2012

Ivanka Atanasova-Hhlein

Future Developments

# Further development of the On-Line analysis with decision criteria # Gas-in-oil analysis in OLTC # Gas-in-oil analysis in alternative insulation fluids and high temperature insulating materials

Page 45

May 2012

Ivanka Atanasova-Hhlein

Siemens AG Energy Sector

Thank you for your attention!