Uses Permitted for Metallic Wireways: 1. For exposed work. 2. In concealed spaces as permitted in NEC section 376.10. 3. In hazardous (classified) locations as permitted by NEC articles 501, 502, and 504. 4. As extension through walls if the length passing through a wal is unbroken and access to conductors can be maine Uses NOT Permitted for Metallic Wireways: 1. Where subject to severe physical damage. 2. Where subject to severe corrosive environments.
Size of Conductors
Table 1 shows maximum conductor size based on bending space, (UL Standard 870, Table 7.1) Table 1 Wireway size 4"x4" 6"x6" 8"x8" Cross Section (in2) 16 36 64 Max. Cable Size 4/O 500 900
1. Sum of the cross-sectional area of all conductors contained in the wireway at any cross section shall not exceed 20% o interior cross-sectional area of the wireway. See Table 2 for allowable conductor cross-sectional areas. 2. Wireways containing (30) current conductors or less are not subject to adjustment factors. 3. Wireway exceeding (30) current carrying conductors shall be subject to adjustment factors as defined in NEC Article 3 Table 2 Wireway size 4"x4" 6"x6" 8"x8" Allowable Cable Area (in2) 3.2 7.2 12.8
Supports
Horizontal supports shall be supported at each end and at intervals not exceeding 10 feet. Vertical supports shall be supported at intervals not exceeding 15 feet and shall not have more than (1) joint between su
al Electrical Code)
splice or tap.
Directions
1)
2) 3) 4)
Wireway systems allow multiple cond is a function of the cross-sectional of the largest conductor. This tool calculates the recommended Enter the cable diameter and number then leve inputs B & C blank Also input the largest conductor type
10
4"x4"
Note: if more than 30 current-carrying conductors are present at any cross section, cable derating may be required (see NEC 362-5)
ems allow multiple conductors sizes within a wireway. The size of wireway required n of the cross-sectional area of the cables but is also limited by the cable bending requirements est conductor. lates the recommended wireway size and allows up to 3 different cable diameter inputs. e diameter and number of cables in the yellow cells. If only one cable size is being used nputs B & C blank largest conductor type in this section.
<-